Signaling Line Circuit
2Leaders in Life. Safety. Technology.
Section # 1
Review of style 4,
6 & 7 SLC loops.
3Leaders in Life. Safety. Technology.
Quick-Reference Chart
Style
IDC / In NAC / Out SLC / NFN
Class B B
DClass A
Y
Z
4
6, 7
IDC = Initiating Device Circuits
NAC = Notification Appliance Circuits
4Leaders in Life. Safety. Technology.
FACP
M M M
M M M
M M M
NFPA Style 4 SLC
Branch Line Resistor from End of Line to FACP
Shall Not Over 50 ohms per Branch
Twisted Unshielded Pair 12 to 18 AWG
SLC Distance
12 AWG 3810 M 16 AWG 1828 M
14 AWG 2895.6 M 18 AWG 1127 M
5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG)
5Leaders in Life. Safety. Technology.
Isolator Application - Style 4 Riser
Max 25 standard devices between Isolators
6Leaders in Life. Safety. Technology.
M M
M
M
MM
M
M
M
FACP
NFPA Style 6 SLC
Loop Resistor from End of Line to FACP
Shall Not Over 50 ohms
5000 ft ( 1500 M) for Shield Twisted Pair Cable
(12 to 18 AWG)
Twisted Unshielded Pair 12 to 18 AWG
SLC Distance
12 AWG 3810 M 16 AWG 1828 M
14 AWG 2895.6 M 18 AWG 1127 M
7Leaders in Life. Safety. Technology.
Isolator Application - Style 6
Max 25 standard devices between Isolators
8Leaders in Life. Safety. Technology.
M M
M
M
MM
M
M
M
FACP
Style 6 with Isolators
9Leaders in Life. Safety. Technology.
Isolator Application - Style 7
• SLC address capacity of loop is reduced by 2
addresses for every isolator device in excess of 200.
10Leaders in Life. Safety. Technology.
SLC Installation
SLC Loop Connections and Wiring
11Leaders in Life. Safety. Technology.
(+) SLC Channel A
no connection
(-) SLC Channel A
NFS-320 / 640 / 3030 / NFS2-640 / NFS2-3030
Floating Shield
12Leaders in Life. Safety. Technology.
Notifier System Basics – Types of Cables
13Leaders in Life. Safety. Technology.
LED Operation
CLIP Mode FlashScan Mode
Control Panel
Device Standby Activated Standby Activated
Onyx Panels
Monitor Module
Control Module
Detector
Blink Red
Blink Green
Blink Red
Steady Red
Steady Green
Steady Red
Blink Green
Blink Green
Blink Green
Steady Red
Steady Green
Steady Red
FDM-1 Blink Red Steady Red Blink Red Steady Red
14Leaders in Life. Safety. Technology.
Section # 2
Data Format and
Loop Capacity
15Leaders in Life. Safety. Technology.
How many devices per SLC?
A
B
CLIP 99 DET/99 MOD
D
E
FLASHSCAN 159 DET/159 MOD
16Leaders in Life. Safety. Technology.
Section # 3
Detectors
17Leaders in Life. Safety. Technology.
Detectors
FSI 851 Ionization Detector
FSP851 Photoelectric Detector
FSP 851T Photo detector w/(135oF) Fixed Heat
FST 851 Fixed Heat detector (135oF)
FST 851R Fixed and Rate-of-rise (15oF/minute)
FAPT 851 Acclimate™ Photo/Heat detector
DNR/FSP 851 Duct Detector/ Photo, Low Flow
FSB200 Beam detector w/Test Function
FSL 751 Laser detector ( VIEW)
FSC 851 COPTIR Multi Sensor
18Leaders in Life. Safety. Technology.
Detectors
Rotary Address Switches
Address = 33
19Leaders in Life. Safety. Technology.
Section # 3.1
Bases
20Leaders in Life. Safety. Technology.
Flash Scan Detector Bases
B501(A) Standard European flangeless mounting base Dia 4.0”
B210LP(A) Flangeless mounting base Dia 6.0”
B200S Sounder base,,
85dBA internal horn.
B224RB Detector base, relay.
B224BI Detector base, Isolator
21Leaders in Life. Safety. Technology.
B501 or B210LP Flangeless mounting base
22Leaders in Life. Safety. Technology.
B200S Sounder base
23Leaders in Life. Safety. Technology.
B224RB Detector base, relay
24Leaders in Life. Safety. Technology.
B224BI Detector base, Isolator
25Leaders in Life. Safety. Technology.
Section # 4
Modules
26Leaders in Life. Safety. Technology.
8
9 0
1
2
3
4
7
6
5
ADDRESSLOOP
8 9
01
2
3
4
5
67
ONES
8 910
11
12
13
14150
1
2
3
4
5
67
TENS
Monitor Modules and Control Modules
Monitor conventional alarm initiating device Circuits
FMM-1 Open Contact Class A or Class B
FMM-101 Open Contact Class B only
FDM-1 Dual Address Open Contact Class B only
FZM-1 Conventional Detectors Class A or B
FCM-1 Bell output circuit
FRM-1 Relay volt-free
NBG-12LX Addressable Manual Station
FMM-4-20mA 4-20mA Input Module
FTM-1 Telephone Module
0
10
11
12
1314 15 ADDRESS
LOOP
12
3
4
TENS ONES
6789
5
0 12
3
4
6789
5
27Leaders in Life. Safety. Technology.
XP10-M
10 Class B Initiating Device Circuits
Uses 10 addresses
5 Class A IDC’s
Uses 5 addresses
Use for tamper & flow switches, 4 wire detectors,
pull stations
28Leaders in Life. Safety. Technology.
XP6-MA
2-wire smoke detector circuits
6 Class B conventional detector circuits
3 Class A conventional detector circuits
Compatible with Honeywell & SSD detectors
Also with Cerberus,Kidde-Fenwal,Hochicki, & Simplex
Great for retrofit applications
29Leaders in Life. Safety. Technology.
FZM-1 Interface Modules
FZM-1 Class A or B IDC, for zone of 2-wire smoke detectors or
heat detectors
30Leaders in Life. Safety. Technology.
FMM-1 Monitor Modules
FMM-1 Class A or B IDC, for dry-contact input devices or zone of
four-wire smoke detectors
31Leaders in Life. Safety. Technology.
FMM-101 Miniature Monitor Modules
FMM-101 Class B IDC, for dry-contact input devices or zone of
four-wire smoke detectors
32Leaders in Life. Safety. Technology.
FDM-1 Interface Module
FZM-1 Class B IDC, for Heat Conventional Detector or Manual Pull Station
33Leaders in Life. Safety. Technology.
FMM-4-20
4-20mA Analog Input Module
34Leaders in Life. Safety. Technology.
Strategy
Focus on new applications
FMM-4-20mA Gas Detection Monitoring and Control
Pressure Monitoring in Pharmaceutical / Industrial
Air Pressurization in Staircase / Fan Controls
Temperature Monitoring in Data Centre or Critical
Process
UV Flame
Sensor
Gas Sensor
NFS2-3030
35Leaders in Life. Safety. Technology.
FMM 4-20mA Module – Available Now
Process
Area
Smoke, exit points, pull stations, etc.
Gas DetectorsFlame Detectors
Safe
Area
Horns & Strobes
37Leaders in Life. Safety. Technology.
Flash Control Modules
Control Module
FCM-1 Class A or B NAC, Speaker or Telephone
38Leaders in Life. Safety. Technology.
XP6-C
6 Class B Notification Appliance Circuits
Uses 6 addresses
3 Class A NAC’s
Uses 3 addresses
Ratings:
63 watts @ 70.7 VAC per circuit
37.5 watts @ 25 VAC per circuit
3 amps @ 30 VDC per circuit
39Leaders in Life. Safety. Technology.
FRM - 1 Class A or B NAC, for dry-contact output Dual Form-C
operation (DPDT) such as fans, dampers, control equipment, etc.
FRM - 1 Relay Modules
40Leaders in Life. Safety. Technology.
XP6-R
6 Form-C relays
3A @ 30 VDC
0.9A @ 125 VAC
General purpose switching
41Leaders in Life. Safety. Technology.
FTM-1 FlashScanTelephone Module
SLC Loop
FFT-7
Tele
ph
on
e
FTM - 1 Class A or B, used to connect a remote firefighter
telephone to a centralized telephone console
42Leaders in Life. Safety. Technology.
Pull Stations
Dual Action
Key lock/reset
NBG-12LX
Addressable
Field replaceable, plug-in monitor module
Leaders in Life. Safety. Technology.Leaders in Life. Safety. Technology.
Thank You