GE Power Controls
Safe-trip RCCB - RCBO
Safe-trip RCCB - RCBO
2
GE Power Controls, a global leader in Electrical Control &
Protection equipment offers Safe-trip RCCBs and RCBOs
for reliable Protection of human beings and Installations from:
Shock Hazards Electrical Fire
- RCCB : residual current operated circuit breakers without integral
overcurrent protection.
- RCBO : residual current operated breakers with integral
overcurrent protection.
GeneralElectricity if used without proper caution can be lethal. Leakage
currents, arising due to faulty Wiring or damaged insulation flow to
earth through an alternate path. Any direct or indirect contact with
the leakage current can be lead to fatal accidents. Consistent
leakage currents of about 300 - 500 mA heat up the current path
(material in-appropriate to actually carry current) and are capable of
causing sparks that ignites fire.
Direct Contact Indirect Contact
RCCB
Operational Principal
Safe-trip RCCBs and RCBOs are current operated devices and are
independent of line voltage conditions. This means that they provide
protection even when there is voltage dip or the neutral conductor is
interrupted.
In a healthy system the vector sum of all currents in phase and
neutral is equal to zero. The device senses imbalance or residual
currents in the system and disconnects unhealthy circuit.
The supply conductors that is phase and neutral are passed through
a torroidal current transformer. In an unhealthy circuit a residual
current flows in the system which is fed to a highly sensitive
electromagnetic relay connected to secondary winding. On receipt of
signal the electromagnetic relay mechanically actuates the tripping
mechanism thereby instantaneously isolating the defective circuit.
The tripping time is < 40 ms as per IEC 1008.
As per Indian Electricity Rules - 61a, 71(1), 73(1), usage ofRCCB, in all installation 5KW and above; in all luminoustubesigns & X-Ray installations, is mandatory.
Safe-trip RCCB - RCBO
3
Features
Compact Size:
The RCCBs and RCBOs are sized in 2 & 4 module configurations;saving space in Distribution board.
Disconnector Function:It incorporates neutral advance mechanism for safe interruption andcan be used as a isolator.
Anti Welding Contacts:The contact tips are made of silver Graphite which has highconductivity and anti welding properties. This ensures reliableoperation of the devices under fault conditions as contacts do notweld under fault conditions.
Terminal Design:
- Dual TerminalsDouble function terminal allow simultaneous termination of busbar& conductors.
- Touch Proof TerminalsThe terminals are touch proof to ensure maximum operator safety.
- Terminal SizeThe terminals can accommodate conductors up to 25mm2
facilitating ease of wiring.
Resistance against Unwanted Tripping:A special filter circuit is incorporated to avoid nuisance tripping dueto impulse voltage.
Positive Contact Indication:The Red and Green making on the operating knob indicates the ON& OFF position in 2P RCCB & RCBO. In 4 module the same isindicated through flag in the window provided above the operatingknob.
Testing Function:A test knob (T) is provided on the device to check the electrical &mechanical effectiveness. The RCCB/RCBO should be electricallyconnected in the circuit when the test knob is operated, the deviceshould trip instantaneously. It is recommended that the test knobshould be operated periodically (at least once a month).
No Ageing Effect:No deviation in the characteristics shall occur over long periods ofusage.
Duraton of current flowms
mA
a
1 2 3
bc1 c2 c3
Threshold = 30 mA Current flowing through the body
100005000
20001000
500
20010050
2010
0.1 0.2 0.5 1 10 20 50 100200 50010002000 5000100002 5
4
Effect of AC Current (50Hz) on human body as perIEC 60479-1
Zone 1 : Usually no reaction effect.
Zone 2 : Usually no pathophisiologically dangerous effect.
Zone 3 : Usually no danger of fibrillation.
Zone 4 : Fibrillation possible (C1-C2 - upto 5%, C2-C3 upto 50% andbeyond C3>50%)
Wiring Precautions• The neutral conductor on the load end should not be connected
to earth.
• In case of 3P 3 wire system appropriate care should be taken offor wiring as shown in the diagram.
• Earth loop impedance specified on the unit label not to exceedmaximum permissible touch voltage of 50/25V AC (Daily/Dampconditions).
RCBO
Safe-trip RCCB - RCBO
Dimensions (mm)RCCO 2-pole RCCB 4-pole RCBO
Products ReferenceRCCB Type AC2 module version (Un - 240 V~)
30mA304/022031-180304/024031-180304/026031-180
100mA304/022101-180304/024101-180304/026101-180
300mA304/022301-180304/024301-180304/026301-180
In25A40A63A
RCCO Type ACCharacteristic C, 2 module
30mA305/206033-180305/210033-180305/216033-180305/220033-180305/225033-180305/232033-180305/240033-180
300mA305/206033-180305/210303-180305/216303-180305/220303-180305/225303-180305/232303-180305/240303-180
In6A10A16A20A25A32A40A
4 module version (Un - 240/415 V)SGE8124025SGE8124040SGE8124063
SGE8134025SGE8134040SGE8134063
SGE8144025SGE8144040SGE8144063
25A40A63A
Note:Available on request* RCCB 2P, 16A/higher 10mA, and all above ratings with 500mA* RCCB rated for 80A & 100A with 30/100/300/500mA sensitivity in 4 module.* Type A series RCCB & RCBO for non sinusoidal leakage current (with
DC components)* RCCB 10mA, 4A to 20A, 2 module* 4 Pole RCBO upto 63A 30/300mA
Technical details of RCCB and RCBOParticulars RCCB RCBO (ELMCB)Standards IS 12640, IEC 1008 & BS EN 61008 IEC 1009Residual operating current I∆n 30, 100, 300mA 6, 10, 16, 25, 32, 40
Configuration 2 Pole, 4 Pole 2 Pole / 4 Pole*
Frequency 50/60Hz 50/60HzRated Voltage 230/415V 230V
Size (Width) 2/4 module 2 module
Short Circuit Capacity (Inc) 10000A 10000AResistance against unwanted Tripping 8/20 µsec 250A (VDE 0664.1) 8/20, µsec 250A (VDE 0664.1)
0.5, µsec100 kHz 200A (EN 61008) 0.5, µsec 100 kHz 200A (EN 61008)
Terminal Capacity 25mm2 25mm2
Optional Accessories Display contacts Auxiliary contactsMotor driver for remote closing Shunt Trip (Right only) Motor Driver
Operating temperature range -25° to +55°C -25° to +55°CService life 20000 Operations As per IEC 1009
Tripping Characteristic:In case Earth Leakage current (RCCB Part) Type AC (Sinusoidal current) Type AC (Sinusoidal current)In case Overload & Short-circuit (MCB Part) Type C (5-10 In)
Mounting arrangement Snap fix on 35mm Din Channel Snap fix on 35mm Din Channel
GE Power ControlsH.O.GE Power Controls India Private Limited1106/6, Balaji ComplexA.M. Industrial EstateGuruvebhavipalya, Hosur RoadBangalore-560 068Ph : +91 (080) 572 5140, 41, 42Fax : +91 (080) 572 4947
(for 2 module version)
NORTH
4, Community Centre,Panchsheel Park,New Delhi-110017Tel.: 011-6497807-10Fax : 011-6497812/13
SOUTH
Temple Towers,6th Floor, 476, Anna Salai,Nandanam,Chennai - 600035Tel.: 044-4329179/80, 4353776/769Fax : 044-4337325
EAST
Berger House,4th Floor, 129, Park Street,Calcutta - 700017Tel.: 033-2292156/2161007Fax : 033-2292918
WEST
Mahalakshmi Engg. Estate,Block No. 571,3rd Floor, Lady Jamsaedji,Ist Cross Road, Mahim,Mumbai - 400016Tel.: 022-4448570 Fax : 022-4442921
725344
4592
2 4 6 N
1 3 5 N
DIN RAIL FOR MOUNTING36
64.550
90 45
67
90
3667
44 6
45
58
Recommended