Page 1: RCCB-RCBO Safetrip

GE Power Controls

Safe-trip RCCB - RCBO

Page 2: RCCB-RCBO Safetrip

Safe-trip RCCB - RCBO

2

GE Power Controls, a global leader in Electrical Control &

Protection equipment offers Safe-trip RCCBs and RCBOs

for reliable Protection of human beings and Installations from:

Shock Hazards Electrical Fire

- RCCB : residual current operated circuit breakers without integral

overcurrent protection.

- RCBO : residual current operated breakers with integral

overcurrent protection.

GeneralElectricity if used without proper caution can be lethal. Leakage

currents, arising due to faulty Wiring or damaged insulation flow to

earth through an alternate path. Any direct or indirect contact with

the leakage current can be lead to fatal accidents. Consistent

leakage currents of about 300 - 500 mA heat up the current path

(material in-appropriate to actually carry current) and are capable of

causing sparks that ignites fire.

Direct Contact Indirect Contact

RCCB

Operational Principal

Safe-trip RCCBs and RCBOs are current operated devices and are

independent of line voltage conditions. This means that they provide

protection even when there is voltage dip or the neutral conductor is

interrupted.

In a healthy system the vector sum of all currents in phase and

neutral is equal to zero. The device senses imbalance or residual

currents in the system and disconnects unhealthy circuit.

The supply conductors that is phase and neutral are passed through

a torroidal current transformer. In an unhealthy circuit a residual

current flows in the system which is fed to a highly sensitive

electromagnetic relay connected to secondary winding. On receipt of

signal the electromagnetic relay mechanically actuates the tripping

mechanism thereby instantaneously isolating the defective circuit.

The tripping time is < 40 ms as per IEC 1008.

As per Indian Electricity Rules - 61a, 71(1), 73(1), usage ofRCCB, in all installation 5KW and above; in all luminoustubesigns & X-Ray installations, is mandatory.

Page 3: RCCB-RCBO Safetrip

Safe-trip RCCB - RCBO

3

Features

Compact Size:

The RCCBs and RCBOs are sized in 2 & 4 module configurations;saving space in Distribution board.

Disconnector Function:It incorporates neutral advance mechanism for safe interruption andcan be used as a isolator.

Anti Welding Contacts:The contact tips are made of silver Graphite which has highconductivity and anti welding properties. This ensures reliableoperation of the devices under fault conditions as contacts do notweld under fault conditions.

Terminal Design:

- Dual TerminalsDouble function terminal allow simultaneous termination of busbar& conductors.

- Touch Proof TerminalsThe terminals are touch proof to ensure maximum operator safety.

- Terminal SizeThe terminals can accommodate conductors up to 25mm2

facilitating ease of wiring.

Resistance against Unwanted Tripping:A special filter circuit is incorporated to avoid nuisance tripping dueto impulse voltage.

Positive Contact Indication:The Red and Green making on the operating knob indicates the ON& OFF position in 2P RCCB & RCBO. In 4 module the same isindicated through flag in the window provided above the operatingknob.

Testing Function:A test knob (T) is provided on the device to check the electrical &mechanical effectiveness. The RCCB/RCBO should be electricallyconnected in the circuit when the test knob is operated, the deviceshould trip instantaneously. It is recommended that the test knobshould be operated periodically (at least once a month).

No Ageing Effect:No deviation in the characteristics shall occur over long periods ofusage.

Duraton of current flowms

mA

a

1 2 3

bc1 c2 c3

Threshold = 30 mA Current flowing through the body

100005000

20001000

500

20010050

2010

0.1 0.2 0.5 1 10 20 50 100200 50010002000 5000100002 5

4

Effect of AC Current (50Hz) on human body as perIEC 60479-1

Zone 1 : Usually no reaction effect.

Zone 2 : Usually no pathophisiologically dangerous effect.

Zone 3 : Usually no danger of fibrillation.

Zone 4 : Fibrillation possible (C1-C2 - upto 5%, C2-C3 upto 50% andbeyond C3>50%)

Wiring Precautions• The neutral conductor on the load end should not be connected

to earth.

• In case of 3P 3 wire system appropriate care should be taken offor wiring as shown in the diagram.

• Earth loop impedance specified on the unit label not to exceedmaximum permissible touch voltage of 50/25V AC (Daily/Dampconditions).

RCBO

Page 4: RCCB-RCBO Safetrip

Safe-trip RCCB - RCBO

Dimensions (mm)RCCO 2-pole RCCB 4-pole RCBO

Products ReferenceRCCB Type AC2 module version (Un - 240 V~)

30mA304/022031-180304/024031-180304/026031-180

100mA304/022101-180304/024101-180304/026101-180

300mA304/022301-180304/024301-180304/026301-180

In25A40A63A

RCCO Type ACCharacteristic C, 2 module

30mA305/206033-180305/210033-180305/216033-180305/220033-180305/225033-180305/232033-180305/240033-180

300mA305/206033-180305/210303-180305/216303-180305/220303-180305/225303-180305/232303-180305/240303-180

In6A10A16A20A25A32A40A

4 module version (Un - 240/415 V)SGE8124025SGE8124040SGE8124063

SGE8134025SGE8134040SGE8134063

SGE8144025SGE8144040SGE8144063

25A40A63A

Note:Available on request* RCCB 2P, 16A/higher 10mA, and all above ratings with 500mA* RCCB rated for 80A & 100A with 30/100/300/500mA sensitivity in 4 module.* Type A series RCCB & RCBO for non sinusoidal leakage current (with

DC components)* RCCB 10mA, 4A to 20A, 2 module* 4 Pole RCBO upto 63A 30/300mA

Technical details of RCCB and RCBOParticulars RCCB RCBO (ELMCB)Standards IS 12640, IEC 1008 & BS EN 61008 IEC 1009Residual operating current I∆n 30, 100, 300mA 6, 10, 16, 25, 32, 40

Configuration 2 Pole, 4 Pole 2 Pole / 4 Pole*

Frequency 50/60Hz 50/60HzRated Voltage 230/415V 230V

Size (Width) 2/4 module 2 module

Short Circuit Capacity (Inc) 10000A 10000AResistance against unwanted Tripping 8/20 µsec 250A (VDE 0664.1) 8/20, µsec 250A (VDE 0664.1)

0.5, µsec100 kHz 200A (EN 61008) 0.5, µsec 100 kHz 200A (EN 61008)

Terminal Capacity 25mm2 25mm2

Optional Accessories Display contacts Auxiliary contactsMotor driver for remote closing Shunt Trip (Right only) Motor Driver

Operating temperature range -25° to +55°C -25° to +55°CService life 20000 Operations As per IEC 1009

Tripping Characteristic:In case Earth Leakage current (RCCB Part) Type AC (Sinusoidal current) Type AC (Sinusoidal current)In case Overload & Short-circuit (MCB Part) Type C (5-10 In)

Mounting arrangement Snap fix on 35mm Din Channel Snap fix on 35mm Din Channel

GE Power ControlsH.O.GE Power Controls India Private Limited1106/6, Balaji ComplexA.M. Industrial EstateGuruvebhavipalya, Hosur RoadBangalore-560 068Ph : +91 (080) 572 5140, 41, 42Fax : +91 (080) 572 4947

(for 2 module version)

NORTH

4, Community Centre,Panchsheel Park,New Delhi-110017Tel.: 011-6497807-10Fax : 011-6497812/13

SOUTH

Temple Towers,6th Floor, 476, Anna Salai,Nandanam,Chennai - 600035Tel.: 044-4329179/80, 4353776/769Fax : 044-4337325

EAST

Berger House,4th Floor, 129, Park Street,Calcutta - 700017Tel.: 033-2292156/2161007Fax : 033-2292918

WEST

Mahalakshmi Engg. Estate,Block No. 571,3rd Floor, Lady Jamsaedji,Ist Cross Road, Mahim,Mumbai - 400016Tel.: 022-4448570 Fax : 022-4442921

725344

4592

2 4 6 N

1 3 5 N

DIN RAIL FOR MOUNTING36

64.550

90 45

67

90

3667

44 6

45

58