View
1
Download
0
Category
Preview:
Citation preview
MyDro 150, 850
The Next Generation of Wireless Real-Time Alarm, Monitoring, and Remote-ControlAll of the functionality of the legacy series (M110 and M800) with an onboard interactive display and enhanced electronics
MyDro 150 and 850 RTUsEasy to InstallEach remote terminal unit (RTU) includes all necessary hardware for a standard installation, such as a cellular radio, enclosure, backup battery, transformer, antenna with cable, and mounting hardware. Purpose-built RTUs simplify and speed installation. There is no programming required, and RTUs are self-enrolling.
Reliable Wireless CommunicationsRTUs operate on current generation cellular radios for dependable data transmissions. Mission maintains direct relationships with the largest cellular carriers in the U.S. and Canada to ensure the best service possible. There are no radios to license or cellular contracts to set up.
Real-Time Alarms Delivered To All DevicesReal-time alarms are delivered via phone call, text message, email, fax, page, and even to an existing HMI software through an OPC data link. Each alarm is logged with a time stamp for tracking and reporting. The alarm call-out schedule is easy, flexible, and intuitive to set up.
Managed Service–The Complete PackageThe Mission system includes all cellular data service, data storage, alarm call-outs, reports, and on-call, 24-7-365 technical support. The highly reliable turnkey system offers more features at a lower cost than an in-house setup. No engineering or programming is required, and there are no networks to maintain.
View data and reports using the secure 123SCADA web portal, accessible from any web-enabled device. The 123SCADA user interface is designed to mimic industry-standard HMI SCADA and also includes a legacy user mode. Tabular and graphical reports can be used for compliance reporting and comparative studies. System enhancements are available immediately and included at no cost.
M150 RTUsReal-Time Alarms with Hourly SummariesM150 RTUs summarize pump runtimes and pump starts hourly. All alarm data is reported in real-time. Analog data and RTU status are reported hourly. Simultaneous pump runtimes can be reported when two pumps run.
M850 RTUsReal-Time Alarms and Streaming DataM850 RTUs report pump starts and stops in real-time. Analog values are reported every two minutes or on a five percent change. Volumetric flow calculations can utilize this information along with sump volume (as determined by an analog level sensor or fixed entries) to calculate hourly volumetric flow rates.
Remote-ControlExpand system operations with optional remote-control for off-site wells, tanks, gates, chlorine dosers, variable frequency drives, and more. Optional automatic remote control interfaces include the Tank and Well Control Package, Digital Interconnect, and Analog Interconnect.
Was
tew
ater
Sewage lift station, industrial water quality (WQ) alarming, lift station generator alarming
Master pump station monitoring and remote-control, critical process monitoring, open channel flow monitoring, sewer station power monitoring, reuse water monitoring and control
Wat
er
Pump station alarming, reservoir level alarming, remote valve alarming, chlorine (Cl) residual WQ alarming, pressure reducing valve station alarming
Pump station monitoring, tank and multiple well control, remote valve monitoring and control, Cl residual WQ alarming, flow or pressure monitoring
Oth
er
Gate status alarming, rainfall monitoring
Septic offload and billing, custody transfer and billing, canal level monitoring and gate control, I&I flow, level data logging
LCD Touch Screen• Displays current status• Supports local configuration
Radio• Cellular radios support LTE, 4G, 3G, and 2G
for both GSM (AT&T and partners) and CDMA (Verizon and partners)
• No radio licenses or site path studies required
Expandable• Up to 16 digital inputs, 6 analog inputs, 2 pulse
inputs, and 2 analog outputs, simultaneously• Onboard digital inputs configurable for wire fault
supervision or strap on current sensing switch for easier pump run indication
• RS485 for digital, analog, and pulse expansion
Enhanced• 12 or 24 VDC auxiliary output for battery-backed
analog instrument loop power• Over-the-air upgradeable firmware
MyDro 150 MyDro 850
Technical Specifications
Outdoor NEMA 4X enclosure:13.25” w x 13.75” h x 6.25” d
With sun shieldWeight: 8 lbs
NEMA 1 enclosure:11.375” w x 11.25” h x 3.5” dUse indoors, wall mounting
Weight: 3 lbs
FlatPak NEMA 1 enclosure:10.5” w x 7.75” h x 1.5” dUse inside MCC cabinet
Weight: 2 lbs
Dat
a
Alarm Data Real-time Real-time
Pump State Summarized hourly Real-time
Analog Reporting Current value reported hourly Every 2 minutes or on 5% change
Device Health Built-in inputs reported hourly
Inpu
t/Out
put
Digital Inputs 8 onboard, dry digital inputs with selectable wire fault supervision or direct attach current sensing switch; Expandable to 16 with PN OP653
3 configurable for pump run summary reporting; Simultaneous runtimes reported when 2 pumps are monitored
8 configurable for pump run; Pump states reported in real-time. Simultaneous pump runtime reporting supported for up to 7 pumps
Analog Inputs 2 onboard, 4–20 mA isolated or 0–5 VDC; 4 alarm set points each; Expandable to 6 with PN OP465
Relay Outputs 3 remotely controllable, form C, dry contact relay outputs; 5 A at 30VDC, 120 VAC, SPDT, N/O, or N/C
RS485 Support for specified expansion modules
Pulse Inputs 2 channels with pulse input expansion module (PN OP464)
15-minute reporting 2-minute reporting
Analog Output 2 channels (4–20 mA or 0–5 V) with PN OP461
Electronic Key Reader Key reader for site activity tracking and service mode
Built-in Inputs AC voltage, battery voltage, board temp, and signal strength; Optional second key reader
Elec
tric
al
AC Power Supervised 120 VAC to 12 VAC, 1.2 A, UL-recognized class II/class III transformer
Backup Power 12 V, 5 Ah battery standard with enhanced charging system
Up to 50 hours Up to 18 hours
Auxiliary Auxiliary output selectable 12 VDC or 24 VDC for battery-backed analog instrument loop powering; 250 mA max
Removable Terminals Included: Amphenol PN 20020008-G061B01LF (6 pin for power), 20020004-D081B01LF (D08, D04, D03 for I/O)
Power Consumption 4.2 W
Oth
er
Enclosures FlatPak (PN M153), NEMA 1 (PN M151), NEMA 4X (PN M152), Large NEMA 4X (PN M152L)
FlatPak (PN M853), NEMA 1 (PN M851), NEMA 4X (PN M852),Large NEMA 4X (PN M852L)
Environment Operating temperature -20–75°C, non-condensing
Cellular Radio Radios make live, continuous, encrypted TCP socket connections; Payload is end-to-end acknowledged; Penta band (850, 900, 1700, 1900, 2100 mHz); AT&T and partners: LTE, HSPA+, 3G; Verizon and partners: LTE, EVDO, 1XRTT
Antenna Omnidirectional antenna with 11' cable, SMA termination, universal mounting bracket
Options Optional SCADA integration OPC link (PN SW586) to client/server HMI, Tank and Well Control Package (see Accessory Catalog for details)
Service Requires Service Packages for the unit and optional expansion boards (see Accessory Catalog for details)
Warranty One-year manufacturing and material warranty
MyDro 150 MyDro 850
(877) 993-1911 • sales@123mc.com • 123mc.com M150/M850-0119
12 VAC in
12 VDC battery
Auxiliary out(0, 12, or 24 VDC)
Mini USB(for factory use)
Expansion module(s)
Analog channelsignal selector
Analog channel(1, 2)
Digital inputs(1–4) (5–8)
Relays(1–3)
Max 5 A at 30 VDC, 5A at 120 VAC
Antenna connection(SMA-F)
Key reader
Secondary SIM holder
Radio module(built-in SIM)
Ethernet
SD card
Touch LCDACBattery
Sounder
Removable mini fuses:
Channel 1 Channel 2
Recommended