Irreversible Flow from Turbine Exit to Condenser
P M V Subbarao Professor
Mechanical Engineering DepartmentI I T Delhi
Irreversibilities due to Closed Cycle Policy …..
The Last Stage of LP Turbine
First Stage of A Turbine : Governing Stage
• A governing stage is the first stage in a turbine with nozzle steam distribution.
• The principal design feature of a governing stage is that its degree of partiality changes with variations of flow rate through the turbine.
• The nozzles of a governing stages are combined into groups, each of them being supplied with steam from a separate governing valve.
• A governing stage is separated by a spacious chamber from the subsequent non-controlled stages.
• Governing stages may be of a single-row or two-row type.• Single row impulse governing stage is employed for an enthalpy
drop of 80-120 kJ/kg.• Two row governing stages are used when enthalpy drop is high,
100 – 250 kJ/kg.
Governing Stage
Selection of Enthalpy Drop & Type of Governing stage
• The enthalpy drop & type of governing stages are selected by considering the probable effect of the governing stage on the design and efficiency of the turbine.
• Higher the number of governing stages, lower will be the number of other stages.
• A high enthalpy drop in governing stage ensures a lower temperature of steam in its chamber and permits application of less expensive materials.
• In high capacity steam turbines, a single-row governing stages are preferred, since the advantages of elevated enthalpy drop are justified economically.
• The efficiency of governing stages,
in
inVustageg T
p
mk
0002.083.0/,
in
inVustagesg T
p
mk
0002.08.0/2,
Steam Path in Non-Controlled Stages
• Estimate approximate mass flow rate of steam by assuming an overall turbine internal efficiency of 0.85.
• Calculate flow through the condenser, using optimum of number of FWHs. (Using Cycle Calculations).
• Calculate Modified Efficiency of Low volume and intermediate volume stages.
• For a group of stages between two successive FWHs.
Z
h
m
lgroupiso
steam
avgrouplistages
,12sin
12000
6001
5.0925.0
groupegroupiav ..
•Average density is calculated as
• The efficiency of groups of very high volume stages:
• While designing the steam path, it is essential to consider the pressure losses in the following:
• Pressure loss in reheater: 0.1 prh.
• Pressure loss in connecting pipes between turbine cylinders:0.2ppipe.
groupiso
evgroupisogegigroup
hv h
hhxx
10000
4001
28.01870.0 ,,
Internal Reheating due to Irreversibilities
3
4s
4IIs
4IIIs
4Is
4Vs
4IVs
4Ia
4IIa
4IIIa
4IVa
4Va
4VIs
4VIa
T
s
Governing group
Group 1
Group 2
Group 3
Group 4
Group 5
Macro available enthalpy:
Micro available enthalpy:
shh 43
...444443
sasas IIIIIIIII hhhhhh
Macro available enthalpy:
Micro available enthalpy:
shh 43
N
Ijsas jjI hhhh 14443
Reheat Factor:
N
Ijsas
sh
jjI hhhh
hhR
14443
43
Internal Reheating due to Irreversibilities : HP
3
4s
4IIs
4IIIs
4Is
4Vs
4IVs
4Ia
4IIa
4IIIa
4IVa
4Va
4VIs
4VIa
T
s
Governing stage
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
22.33 MPa,3379.0
15.74 MPa,3303.0 k J/kg
13.77 MPa, 3269.0 k J/kg
12.12 MPa, 3236.5.0 k J/kg
10.56 MPa, 3203.8 k J/kg
9.2 MPa, 3171.0 k J/kg
7.94 MPa, 3140.4 k J/kg
4VIIa
6.9 MPa, 3104.9 k J/kg
4VIIIa
5.17 MPa, 3036.7 k J/kg
4IXa
5.95 MPa, 3070.9 k J/kg
Pho=5 %
Pho=19.5%
Pho=21%
Pho=22%
Pho=23.5%
Pho=25%
Pho=30%
Pho=32%
Stage 6
Stage 7
Stage 8
Pho=35%
0
2
4
6
8
10
12
14
Stages
Loss
(kJ/
kg)
Cumulative loss
Cumulative Losses for All Stages : 500 MW
Definition of Efficiency
• Relative blade efficiency is calculated as:
• Internal Relative Efficiency is calculated as:
dropEnthalpy Effective
loss Blade Moving & Nozzle-dropEntalpy Effectiverel
dropEnthalpy Effective
loss profile - loss leakage-losses Blade Moving & Nozzle-dropEntalpy Effectiveint, rel
Blade Efficiency & Internal Relative Efficiency: 800 MW
LP Turbine Exhaust System • In a condensing steam turbine, the low-pressure exhaust hood,
consisting of a diffuser and a collector or volute!, connects the last stage turbine and the condenser.
• The function of the hood is to transfer the turbine leaving kinetic energy to potential energy while guiding the flow from the turbine exit plane to the condenser.
• Most of exhaust hoods discharge towards the downward condenser. • Flow inside the hood therefore must turn about 90 deg from the
axial direction to the radial direction before exhausting into the condenser.
• The 90-deg turning results in vortical flow in the upper half part of the collector and also high losses.
• The exhaust hood is one of the few steam turbine components that has the considerable aerodynamic losses.
• It is a challenge for engineers to operate a hood with high pressure recovery and low total pressure loss in a compact axial length.
Exhaust Hood
Exhaust Diffuser For L P Turbine
Steam Turbine Exhaust Size Selection
• The steam leaving the last stage of a condensing steam turbine can carry considerably useful power to the condenser as kinetic energy.
• The turbine performance analysis needs to identify an exhaust area for a particular load that provides a balance between exhaust loss and capital investment in turbine equipment.
Path Lines in Exhaust Hood
Exhaust Losses
• Exhaust losses are losses which occur between last stage of turbine and condenser.
• Exhaust losses made up of four components:• Actual leaving losses• Gross hood loss• Annulus restriction loss• Turn up loss
Residual velocity loss
• Steam leaving the last stage of the turbine has certain velocity, which represent the amount of kinetic energy that cannot be imparted to the turbine shaft and thus it is wasted
Exhaust end loss
1. Exhaust end loss occur between the last stage of low pressure turbine and condenser inlet.
2. Exhaust loss depends on the absolute steam velocity.
Turbine Exhaust end loss = Expansion-line -end point - Used energy at end point.
Turn-up loss
Total Exhaust Loss
Gross hood loss
Actual leaving loss
Annulus restriction loss
Annulus Velocity (m/s)
Exh
aust
Los
s, k
J/kg
of
dry
flow
0 120 150 180 240 300 360
10
20
30
40
50Annulus velocity (m/s)
Condenser flow rate
Annulus area
Percentage of Moisture at the Expansion line end point
Typical exhaust loss curve showing distribution of component loss
SP.Volume
an
steamexan A
xvmV
3600
01.01.
Optimal Design of Exhaust Hood
Performance Analysis of Power Plant Condensers
P M V SubbaraoProfessor
Mechanical Engineering DepartmentI I T Delhi
A Device Which makes Power Plant A True Cycle..A Device Which set the limit on minimum cycle
pressure…..
T-S Diagram : Rankine Cycle with FWHs.
?,, exitcondincond pp
inCWT ,outCWT ,
?TTD
exhaustturbinep ,
hoodp
A Device to Convert Dead Steam into Live Water
Water ready to take Rebirth
Dead Steam
Steam Condenser
• Steam condenser is a closed space into which steam exits the turbine and is forced to give up its latent heat of vaporization.
• It is a necessary component of a steam power plant because of two reasons.• It converts dead steam into live feed water.• It lowers the cost of supply of cleaning and treating of working fluid.• It is far easier to pump a liquid than a steam.• It increases the efficiency of the cycle by allowing the plant to operate on largest
possible temperature difference between source and sink.• The steam’s latent heat of condensation is passed to the water flowing through the
tubes of condenser.• After steam condenses, the saturated water continues to transfer heat to cooling
water as it falls to the bottom of the condenser called, hotwell.• The difference between saturation temperature corresponding to condenser
vaccum and temperature of condensate in hotwell is called condensate depression.
Two-Pass Surface Condenser
Layouts of A Condenser
Layouts of A Condenser
An Integral Steam Turbine and Condenser System