Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Integrating and Automating

Local-Area with Wide-Area Data

For Better Root-Cause Analytics

Dr. Greg Zweigle

Schweitzer Engineering Laboratories, Inc.

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

What Is an Event Report

Substation 1

Substation 2

Prefault Data Post-Fault Data

• Currents

• Voltages

• Digitals

Fault DataIED

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

What Is a Synchrophasor

A B

Vref

Va(A)

Va(B)IRIG-B

Magnitude

and Angle

Magnitude

and Angle

IRIG-B

GPS Clock

IED / PMU

GPS Clock

IED / PMU

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Correlation of Time-Stamped Data Types

1

2

1

2

PMU

Event

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Hawaii Electric Light Company (HELCO)

Map data ©2016 Google

50% Renewable Power

Regularly Integrated

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Collection Architecture Implemented at HELCO

Control Center

Substation

Event Report Data

Synchrophasor Data

WAN

Central PDC

Synchrophasor Archive

Event Report Collection

and Archive

Protective

Relays

Switch

PDC

Communications

Processor

Web

Client

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Defense-in-Depth Security Approach

Substation Perimeter

Serial Encryption,

User Access Proxy

Switch

WAN

Zone 0

Zone 1

Zone 2

Zone 3

Protective

Relays

Communications Processor

or PDC

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Challenges With Islanded Systems

PMU Frequency

59.647 Hz

60.014 Hz

60.564 Hz

12:40:00 AM 12:53:20 AM 1:10:00 AM

Copyright © HELCO 2017

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Frequency Deviation

PMU Frequency

59.647 Hz

60.014 Hz

60.564 Hz

12:40:00 AM 12:53:20 AM 1:10:00 AM

IED 1

IED 2

IED 3

Copyright © HELCO 2017

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

59.647 Hz

60.014 Hz

60.564 Hz

12:40:00 AM 12:53:20 AM 1:10:00 AM

IED 1

IED 2

IED 3

Synchrophasors

IED Event Reports

Data Correlation for Added Context

Copyright © HELCO 2017

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

59.647 Hz

60.014 Hz

60.564 Hz

12:40:00 AM 12:53:20 AM 1:10:00 AM

IED 1

IED 2

IED 3

Event Summary Data for Operations

IED Event

Report Summary

Copyright © HELCO 2017

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Event Reports for Detailed Analysis

Copyright © HELCO 2017

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

San Diego Gas and Electric

• 103 PMUs Installed

• Leveraged existing protection relays

• > 99.9% Availability

• < 100ms average latency

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Event Report Integration Architecture

Substation

PDC

Local

Archive

Relay

Data

Center

Operations

PDC SynchroWAVe

Archive

Engineering

Web-client Web-client

Event Report Archive

Collect

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Complete 230kV & 500kV Coverage

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Detected Oscillation - Generator

Voltage Magnitude

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Detected Oscillation

Voltage Magnitude

Frequency

df/dt

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

TL #1TL #2TL #3 TL #4TL #5TL #6…

Synchrophasor Data

Relay Event Reports

Correlate Relay Event Data

Voltage Magnitude

Frequency

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Line Trip

Relay Event Report

Correlate Relay Event Data

Voltage MagnitudeFrequency

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Event Summary for Operations

TL #1 – SEL-311L

Event Summary

TL #1TL #2TL #3 TL #4TL #5TL #6TL #7

Voltage MagnitudeFrequency

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

TL #1 – SEL-311L

Integrated Event Analysis

Relay Oscillography

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Too Much Data for Human Analysis

1 GB Per Hour

25 GB Per Day

8 TB Per Year

100 PMUs

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Solution – Automatically Detect Disturbances

Previous 1 Hour

Fre

quency

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Notify Operations of Disturbances

Alert Threshold

Z-R

atio

Detection Threshold

0

30

50

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Determine Disturbance Type With Oscillation Energy

Oscillation Energy Band BPA Energy Band Key

0.01–0.15 Hz Generator, HVDC, or SVC

0.15–1.0 Hz Local plant controls

1.0–5.0 Hz Inter-area oscillations

5.0–14.0 Hz Local plant controls or AGC

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Example Disturbance Results

22Disturbances

11Unique

91%Local

Disturbance Type

13Line

7Oscillation

1Generator Trip

1Load Trip

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Blue Ridge Electric Cooperative (BREC)

MRO

NPCC

SPP

RFC

SERC

FRCC

South Carolina

Anderson

County

Greenville

County

Spartanburg

County

Pickens

County

Oconee

County

Image source: NERC

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Automatic Collection Adds Insight

31

370

630

Trip Pickup Event Report

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Automatic Collection Simplifies The Analysis Process

Event Report

Database

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Analytics For Distribution Fault

Location

BREC Oakway Feeder

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Faults Per SubstationThree Month Period

150

125

100

75

50

25

0

Faults

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Location Number of Faults

X Circuit 1 52

X Circuit 2 48

X Circuit 3 37

Month Number of Faults

January 78

February 38

March 21

Faults Per Feeder at Substation X

Faults Per Month at Substation X

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Breakdown of Faults at Substation XJanuary 2016

30

25

20

15

10

5

0

35

Faults

40

45

50

4 5 6 11 12 17 19 22 23 24 26 27January

Copyright © Schweitzer Engineering Laboratories, Inc. 2017

Questions?