IMAX XTRA EL - Ideal Boilers IE · Boiler Clearances mm Front: 700 Left Side: 700 Right Side: 700...

Preview:

Citation preview

IMAX XTRA EL1090kW

•Simplecontrolinterfacewithlargebacklitdisplay

•Voltfreecontacts

•0-10VBMSoperationstandard

•Robustaluminiumsiliconalloyheatexchanger

•Suitableforsingleormultipleinstallations

•Upto109.8%partloadat30%output

•NOx<40mg/kWh

•NaturalGas

•BuildingRegulationPartL2compliant

FEATURES & BENEFITS

BOILER DIM A DIM B DIM C

1090 1674 1567 1685

Thefollowingminimumclearancesmustbemaintainedforoperationandservicing:

TheImaxXtraELrangeofcondensingboilersisavailablein10modelswithoutputsfrom320to1240kW.Suitableforfloorstandingapplicationsineithersingleormultipleinstallations.

All dimensions in mm

A

B

C

DIMENSIONS & CLEARANCES

TOP:700mm

RIGHT SIDE:700mm

FRONT:700mm

LEFT SIDE: 700mm

REAR: 1000mm†

†Frombackofboiler

A

B

C

TECHNICAL SPECIFICATIONSIMAX XTRA EL 1090kW

W: IDEALCOMMERCIALBOILERS.COM E: commercial@idealboilers.comT: 0844 5436060

GET A QUOTE

*2yearwarrantysubjecttoTermsandConditions.2yearspartsandlabourwarrantyavailablesubjecttobeingcommissionedbyIdealBoilers.

DryWeight KG 1066

BoilerDimensions mm 1567(H)x1674(W)x1685(D)

BoilerClearances mm Front:700LeftSide:700RightSide:700Top:700Rear:1000

SeasonalEfficiency(BuildingRegsL2) % 96.9

Min/MaxGaspressure(NatGas) mbar 15-20

Fuel (TypeG20) NaturalGas

FuelConsumption(NatGas) m³/h 109.8

FlameProtection Ionisation

Ignition Spark

BoilerOutput(Mean70°C) kW 201.4-1017.2

BoilerOutput(Mean40°C) kW 226-1105.4

BoilerInput(Grosscv) kW 1152

GasInletSize 2xG2”

NOxRating/emissionsat0%O2

mg/kWh Class6(38.7)

HydraulicResistance(11°C∆T) mbar 320

HydraulicResistance(20°C∆T) mbar 97.65

NominalFlowRate(11°C∆T) l/s 23.7

NominalFlowRate(20°C∆T) l/s 13

MinFlowRate(20°C∆T)(MAXMOD) l/s 2.6

MinFlowTemperature °C 30

MaxFlowTemperature °C 90

MinWorkingPressure bar 1

MaxWorkingPressure bar 6

MaxStaticHeadOfWater metres 61

CondensateConnection mm 21.5x2

HighLimitSetPoint °C 100flow,100return105H/Ex

Flow&ReturnSize 2xG3”

WaterContent litres 130.6

FlueSize mm 350

FlueGasVolume m³/h 1609.4

Min-MaxFlueGasTemperature80/60 °C 50-63

MaxFlueResistance Pa 100

ElectricalSupply 230/240V50Hz1Ph

Current(MaxNoPump) amp 2x2.71

PowerConsumption watt 1250

ModulatingInput V/dc 0-10V

FuseRating amp 2x7

ControlsVoltage V 24or240

InsulationClassIP IP20

On/Off0-10VDC Yes

OpenTherm Yes

HighLimitProtection Yes

LowWaterProtection Yes

VoltFreeCommonAlarm Yes

BoilerRunIndication Yes

ModulatingSequencerKit,includingDHWTankKit,PlantRoomSensorKit,6ZoneExpansionKit

Yes

ProgrammableRoomThermostatKits Yes

OutsideSensorKit Yes

DHWTankSensorKit Yes

SafetyInterlockKit Yes

BACNetGatewayKit Yes

LONWorksGatewayKit Yes

MODBusGatewayKit Yes

RemoteAccessKit Yes

SealedSystemServicesFlowManifoldKit Yes

InletAirFilterKit Yes

CondensatePumpKit Yes

RoomSealedAirDuctKit Yes

HeaderKit(flow/return) Yes

HeaderKit(gas) Yes

HeaderKit(air) Yes

GENERAL FLUE/AIR INLET

ELECTRICAL

CONTROL OPERATION

OPTIONAL EXTRAS

BURNER PRE MIX

HYDRAULICS

SUGGESTED ENGINEERING SPECIFICATIONIMAX XTRA EL 1090kW

Pleasenotethattheaboveinformationiscorrectattimeofpublication.IdealCommercialHeatingLimitedhasapolicyofcontinuousdevelopmentandthereforereservestherighttoalterspecificationswithoutpriornotification. 211328

OVERVIEW

Theboilersmustbefullyautomaticallycontrolled,floorstanding,fanned,super-efficientcondensingappliancesutilisinganaluminiumsiliconalloyheatexchangerandbesuitableforconnectiontofullypumpedopenventedorsealedwatersystems.

CONTROLS

ThecondensingboilersmusthaveconnectivityforallcommontypesofBMSintegrationincluding0-10v,voltfreeandOpenThermconnections.AdditionalmodulesmaybeusedforBACnet,LONWorksandMODBusgateways.WherenoBMSispresentamodulatingsequencermustbeavailable.

Theboilermustbefullymodulatingwitha5:1turndownratioandincludecontrolfeaturesenablingsetpointadjustment,heatingcircuitcontrolofoneconstanttemperatureandoneDHWcircuitor2constanttemperaturecircuits,andsafetylockoutparametersincludingfaultdiagnosisforbothboilerandexternalcomponentssuchassensorsorpumps.

Boilercapabilitiesmustinclude,withtheuseofexternalcomponents,frostprotection,weatherorroomcompensationandsystempumpcontrol.

FLUE

ThecondensingboilersmustbesuitableforusewitharoomsealedflueoropenflueapplicationsincludingC13,C33andB23classifications.Theflueoutletandairinletmustbesituatedattherearoftheboiler.

HYDRAULIC

Thecondensingboilermustbesuitableforconnectiontofullypumpedopenventedorsealedwatersystems.Allhydraulicconnectionsincludingflowreturnandcondensatedrainmustbelocatedontherearoftheboiler.Hydraulicconnectionsmustbeuniformacrosstheoutputsavailableintherangetoensureeaseofinstallationandmaintenance.

Theboilermusthaveamaximumoperatingpressureof6barandbesuitableforheatingandindirecthotwatersystems.

DIMENSIONS

Thecondensingboilermustfitwithinmaximumpermittedfloorspaceof1.41m²(320–620kWmodels)or2.82m²(715–1240kWmodels).

MOUNTING / POSITIONING

Thecondensingboilerswillbefloorstanding.

EFFICIENCY

Thecondensingboilersarecapableofhighseasonalefficiencieswithaminimumrequirementof96.8%andlowNOxemissionsnogreaterthan38.7mg/kWH.

APPROVALS

TheboilersmustbetestedandcertifiedbyBSItoEN15502forusewithNaturalGas.

BoilersarecertifiedtomeettherequirementsoftheECGasApplianceDirective,BoilerEfficiencyDirective,EMCandLowVoltageDirective.

ThemanufacturermustbeISO9001accredited.

SPECIFICATION

Theboilerwillbecapableofflowratesforcommonsystemsusing11°Cto20°Ctemperaturedifferentials.

SOURCING

ThecondensingboilermustbemanufacturedorfinallyassembledintheUnitedKingdom.

WARRANTY

Theboilermustbeavailablewitha2yearwarranty.

Recommended