IMAX XTRA EL 1090kW • Simple control interface with large backlit display • Volt free contacts • 0-10V BMS operation standard • Robust aluminium silicon alloy heat exchanger • Suitable for single or multiple installations • Up to 109.8% part load at 30% output • NOx <40mg/kWh • Natural Gas • Building Regulation Part L2 compliant FEATURES & BENEFITS BOILER DIM A DIM B DIM C 1090 1674 1567 1685 The following minimum clearances must be maintained for operation and servicing: The Imax Xtra EL range of condensing boilers is available in 10 models with outputs from 320 to 1240kW. Suitable for floor standing applications in either single or multiple installations. All dimensions in mm A B DIMENSIONS & CLEARANCES TOP: 700mm RIGHT SIDE: 700mm FRONT: 700mm LEFT SIDE: 700mm REAR: 1000mmFrom back of boiler C

IMAX XTRA EL - Ideal Boilers IE · Boiler Clearances mm Front: 700 Left Side: 700 Right Side: 700 Top: 700 Rear: 1000 Seasonal Efficiency (Building Regs L2) % 96.9 Min/Max Gas pressure

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: IMAX XTRA EL - Ideal Boilers IE · Boiler Clearances mm Front: 700 Left Side: 700 Right Side: 700 Top: 700 Rear: 1000 Seasonal Efficiency (Building Regs L2) % 96.9 Min/Max Gas pressure

IMAX XTRA EL1090kW

•Simplecontrolinterfacewithlargebacklitdisplay

•Voltfreecontacts

•0-10VBMSoperationstandard

•Robustaluminiumsiliconalloyheatexchanger

•Suitableforsingleormultipleinstallations

•Upto109.8%partloadat30%output

•NOx<40mg/kWh

•NaturalGas

•BuildingRegulationPartL2compliant

FEATURES & BENEFITS

BOILER DIM A DIM B DIM C

1090 1674 1567 1685

Thefollowingminimumclearancesmustbemaintainedforoperationandservicing:

TheImaxXtraELrangeofcondensingboilersisavailablein10modelswithoutputsfrom320to1240kW.Suitableforfloorstandingapplicationsineithersingleormultipleinstallations.

All dimensions in mm

A

B

C

DIMENSIONS & CLEARANCES

TOP:700mm

RIGHT SIDE:700mm

FRONT:700mm

LEFT SIDE: 700mm

REAR: 1000mm†

†Frombackofboiler

A

B

C

Page 2: IMAX XTRA EL - Ideal Boilers IE · Boiler Clearances mm Front: 700 Left Side: 700 Right Side: 700 Top: 700 Rear: 1000 Seasonal Efficiency (Building Regs L2) % 96.9 Min/Max Gas pressure

TECHNICAL SPECIFICATIONSIMAX XTRA EL 1090kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE

*2yearwarrantysubjecttoTermsandConditions.2yearspartsandlabourwarrantyavailablesubjecttobeingcommissionedbyIdealBoilers.

DryWeight KG 1066

BoilerDimensions mm 1567(H)x1674(W)x1685(D)

BoilerClearances mm Front:700LeftSide:700RightSide:700Top:700Rear:1000

SeasonalEfficiency(BuildingRegsL2) % 96.9

Min/MaxGaspressure(NatGas) mbar 15-20

Fuel (TypeG20) NaturalGas

FuelConsumption(NatGas) m³/h 109.8

FlameProtection Ionisation

Ignition Spark

BoilerOutput(Mean70°C) kW 201.4-1017.2

BoilerOutput(Mean40°C) kW 226-1105.4

BoilerInput(Grosscv) kW 1152

GasInletSize 2xG2”

NOxRating/emissionsat0%O2

mg/kWh Class6(38.7)

HydraulicResistance(11°C∆T) mbar 320

HydraulicResistance(20°C∆T) mbar 97.65

NominalFlowRate(11°C∆T) l/s 23.7

NominalFlowRate(20°C∆T) l/s 13

MinFlowRate(20°C∆T)(MAXMOD) l/s 2.6

MinFlowTemperature °C 30

MaxFlowTemperature °C 90

MinWorkingPressure bar 1

MaxWorkingPressure bar 6

MaxStaticHeadOfWater metres 61

CondensateConnection mm 21.5x2

HighLimitSetPoint °C 100flow,100return105H/Ex

Flow&ReturnSize 2xG3”

WaterContent litres 130.6

FlueSize mm 350

FlueGasVolume m³/h 1609.4

Min-MaxFlueGasTemperature80/60 °C 50-63

MaxFlueResistance Pa 100

ElectricalSupply 230/240V50Hz1Ph

Current(MaxNoPump) amp 2x2.71

PowerConsumption watt 1250

ModulatingInput V/dc 0-10V

FuseRating amp 2x7

ControlsVoltage V 24or240

InsulationClassIP IP20

On/Off0-10VDC Yes

OpenTherm Yes

HighLimitProtection Yes

LowWaterProtection Yes

VoltFreeCommonAlarm Yes

BoilerRunIndication Yes

ModulatingSequencerKit,includingDHWTankKit,PlantRoomSensorKit,6ZoneExpansionKit

Yes

ProgrammableRoomThermostatKits Yes

OutsideSensorKit Yes

DHWTankSensorKit Yes

SafetyInterlockKit Yes

BACNetGatewayKit Yes

LONWorksGatewayKit Yes

MODBusGatewayKit Yes

RemoteAccessKit Yes

SealedSystemServicesFlowManifoldKit Yes

InletAirFilterKit Yes

CondensatePumpKit Yes

RoomSealedAirDuctKit Yes

HeaderKit(flow/return) Yes

HeaderKit(gas) Yes

HeaderKit(air) Yes

GENERAL FLUE/AIR INLET

ELECTRICAL

CONTROL OPERATION

OPTIONAL EXTRAS

BURNER PRE MIX

HYDRAULICS

Page 3: IMAX XTRA EL - Ideal Boilers IE · Boiler Clearances mm Front: 700 Left Side: 700 Right Side: 700 Top: 700 Rear: 1000 Seasonal Efficiency (Building Regs L2) % 96.9 Min/Max Gas pressure

SUGGESTED ENGINEERING SPECIFICATIONIMAX XTRA EL 1090kW

Pleasenotethattheaboveinformationiscorrectattimeofpublication.IdealCommercialHeatingLimitedhasapolicyofcontinuousdevelopmentandthereforereservestherighttoalterspecificationswithoutpriornotification. 211328

OVERVIEW

Theboilersmustbefullyautomaticallycontrolled,floorstanding,fanned,super-efficientcondensingappliancesutilisinganaluminiumsiliconalloyheatexchangerandbesuitableforconnectiontofullypumpedopenventedorsealedwatersystems.

CONTROLS

ThecondensingboilersmusthaveconnectivityforallcommontypesofBMSintegrationincluding0-10v,voltfreeandOpenThermconnections.AdditionalmodulesmaybeusedforBACnet,LONWorksandMODBusgateways.WherenoBMSispresentamodulatingsequencermustbeavailable.

Theboilermustbefullymodulatingwitha5:1turndownratioandincludecontrolfeaturesenablingsetpointadjustment,heatingcircuitcontrolofoneconstanttemperatureandoneDHWcircuitor2constanttemperaturecircuits,andsafetylockoutparametersincludingfaultdiagnosisforbothboilerandexternalcomponentssuchassensorsorpumps.

Boilercapabilitiesmustinclude,withtheuseofexternalcomponents,frostprotection,weatherorroomcompensationandsystempumpcontrol.

FLUE

ThecondensingboilersmustbesuitableforusewitharoomsealedflueoropenflueapplicationsincludingC13,C33andB23classifications.Theflueoutletandairinletmustbesituatedattherearoftheboiler.

HYDRAULIC

Thecondensingboilermustbesuitableforconnectiontofullypumpedopenventedorsealedwatersystems.Allhydraulicconnectionsincludingflowreturnandcondensatedrainmustbelocatedontherearoftheboiler.Hydraulicconnectionsmustbeuniformacrosstheoutputsavailableintherangetoensureeaseofinstallationandmaintenance.

Theboilermusthaveamaximumoperatingpressureof6barandbesuitableforheatingandindirecthotwatersystems.

DIMENSIONS

Thecondensingboilermustfitwithinmaximumpermittedfloorspaceof1.41m²(320–620kWmodels)or2.82m²(715–1240kWmodels).

MOUNTING / POSITIONING

Thecondensingboilerswillbefloorstanding.

EFFICIENCY

Thecondensingboilersarecapableofhighseasonalefficiencieswithaminimumrequirementof96.8%andlowNOxemissionsnogreaterthan38.7mg/kWH.

APPROVALS

TheboilersmustbetestedandcertifiedbyBSItoEN15502forusewithNaturalGas.

BoilersarecertifiedtomeettherequirementsoftheECGasApplianceDirective,BoilerEfficiencyDirective,EMCandLowVoltageDirective.

ThemanufacturermustbeISO9001accredited.

SPECIFICATION

Theboilerwillbecapableofflowratesforcommonsystemsusing11°Cto20°Ctemperaturedifferentials.

SOURCING

ThecondensingboilermustbemanufacturedorfinallyassembledintheUnitedKingdom.

WARRANTY

Theboilermustbeavailablewitha2yearwarranty.