View
522
Download
34
Category
Preview:
Citation preview
7/27/2019 HVAC BOQ -R0
1/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
DATE : 06.09.2013
Sl No Description Unit Qty Rate Amount
Note: The contractor should read the specifications thoroughly and quote the price foreach item. The BOQ should read in conjuction with specification, drawing & equipment
schedule.
NOTE : Quoted price shall be inclusive of Supply, sea freight, insurance, packing and
forwarding charges etc., as applicable
COOLING TOWER
1.00Supply, Installation, testing and commissioning of CTI approved MULTI CELL INDUCED
DRAFT CROSS FLOW COOLING TOWERS for airconditioning system. Each tower shall be
complete with basin, casing, distribution system, filling, louvers, ladder, fan, Motor and
other complete accessories as described in the technical specifications. Motor shall be
suitable for 41510% volts, 50 cycles and 3 phase power supply. Tower shall be designed
with high efficiency drift eliminators to meet current environmental standards and
guidelines for microbial control. Each tower cell must be installed with individual cold
water basins and water discharge sumps to facilitate maintenance without causing
disruption to the other cells in operation. Tower for airconditioning system shall be
selected on the basis of following parameters Refer Equipment schedule & Technical
Specification for details
Make : Marley /BAC / Advance
a Cooling Tower 825 USGPM Nos 2Ambient WB Temperature : 82F
Cooling capacity : 275TR
Leaving water leaving temperature : 87 F
Entering water entering temperature : 97 F
I TOTAL VALUE FOR COOLING TOWER
II CENTRIFUGAL PUMPS
PRIMARY CHILLED WATER PUMPS
1.00 Supply, installation, testing & commissioning of Centrifugal monobloc type pumpset motor
shall be suitable for 415 + 10% volts, 50 cycles/second, 3-phase power supply. The quoted
price shall include cost of thermal insulation and cladding . The unit complete should be
suitable for outdoor installation at the roof of the building. Refer Equipment schedule &
Technical Specification for details
Make : ITT BELL & GOSSETT, GRUNDFOS, Armstrong
1.10 Primary Chilled Water pumps Nos 4
660 USGPM
Head in Ft - 40
SECONDARY CHILLED WATER PUMPS
2.00 Supply, instal lation, testing & commissioning of End Suction Back pul l out Centri fugal
chilled water pumpsets suitable for VFD. Factory mounted on a common base with electric
motor for recirculation of water for the central air conditioning system. All pumps shall be
aligned properly as required and complete with mechanical seal. The pump motor shall be
suitable for 415 + 10% volts, 50 cycles/second, 3-phase power supply. The quoted price
PROJECT: OZONE GALLERIA MALL @ RANCHI
BILL OF QUANTITIES FOR HVAC LOW SIDE WORKS
Revision-R0
7/27/2019 HVAC BOQ -R0
2/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
660 USGPM - 17 KW
Head in Ft - 90
2.11 Supply, installation, testing & commissioning ofVFD, VFD controller, microprocessor panel
necessary cabling, two sets of sensors, required enclosure, with By Pass control, including
cabling and cable Termination etc.
lot 1
CONDENSER CHILLED WATER PUMPS
3.00 Supply, installation, testing & commissioning of End Suction Back pull out type pumpset
motor shall be suitable for 415 + 10% volts, 50 cycles/second, 3-phase power supply. The
quoted price shall include cost of thermal insulation and cladding . The unit complete
should be suitable for outdoor installation at the roof of the building. Refer Equipment
schedule & Technical Specification for details
Make : ITT BELL & GOSSETT, GRUNDFOS, Armstrong
3.10 Condenser Chilled Water pumps Nos 3825 USGPM -
Head in Ft - 40
II TOTAL VALUE FOR CENTRIFUGAL PUMPS
III AIR HANDLING UNITS
1.00 Supply, installation, testing & commissioning of Double skin construction draw thru type
Horizontal Floor mounted / CEILING SUSPENDED AIR HANDLING UNITS with 25 mm thick
Sandwitched PUF insulation as per specification & as indicated in the Equipment Schedule.Each complete with DIDW FORWARD Curved Centrifugal Fan, Pre filter of 10 micron, 6
row deep water coil of copper tube & aluminium fins construction with blue Hydraufillic
coating for chilled water coil, coil size shall be selected for a maximum face velocity of 500
feet/minute. and squirrel cage induction motor, centrifugal fan belt drive and vibration
isolators, Limit switches,Emergency Light , Guard for inspection door. Motor shall be
suitable for 41510% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD
operation. Note: AHU shall be supplied with one set of pre commissioning filters. Refer
Equipment schedule & Technicla Specification for details
Make : Caryaire / VTS / Zeco / Edgetech
1.01 LGF-AHU-01 - 35 TR/ Nos 1
1.02 LGF-AHU-02 - 30 TR Nos 1
1.03 LGF-CSU-01 - 30 TR Nos 1
1.04 LGF-CSU-02 - 30 TR Nos 1
1.05 LGF-CSU-03 - 30 TR Nos 1
1.06 LGF-CSU-04 - 30 TR Nos 1
1.07 LGF-CSU-05 - 30 TR Nos 1
1.08 LGF-CSU-06 - 30 TR Nos 1
1.09 LGF-CSU-07 - 10 TR Nos 1
1.10 LGF-CSU-08 - 30 TR Nos 1
1.11 GF-AHU-01 - 30 TR Nos 1
1.12 GF-AHU-02 - 28 TR Nos 1
1.13 GF-CSU-01 - 17 TR Nos 1
1.14 GF-CSU-02 - 4.0 TR Nos 1
1.15 GF-CSU-03 - 3.0 TR Nos 1
1.16 GF-CSU-04 - 5.0 TR Nos 1
7/27/2019 HVAC BOQ -R0
3/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
1.27 GF-CSU-15 - 5.0 TR Nos 1
1.28 GF-CSU-16 - 25 TR Nos 1
1.29 1F-AHU-01 - 27 TR Nos 1
1.30 1F-AHU-02 - 27 TR Nos 1
1.31 1F-CSU-01 - 16 TR Nos 1
1.32 1F-CSU-02 - 2.0 TR Nos 11.33 1F-CSU-03 - 3.0 TR Nos 1
1.34 1F-CSU-04 - 3.0 TR Nos 1
1.35 1F-CSU-05 - 5.0 TR Nos 1
1.36 1F-CSU-06 - 4.0 TR Nos 1
1.37 1F-CSU-07 - 4.0 TR Nos 1
1.38 1F-CSU-08 - 5.0 TR Nos 1
1.39 1F-CSU-09 - 21 TR Nos 1
1.40 1F-CSU-10 - 4.0TR Nos 1
1.41 1F-CSU-11 - 4.0TR Nos 1
1.42 1F-CSU-12 - 4.0TR Nos 11.43 1F-CSU-13 - 4.0TR Nos 1
1.44 1F-CSU-14 - 12TR Nos 1
1.45 1F-CSU-15 - 4.0TR Nos 1
1.46 1F-CSU-16 - 4.0TR Nos 1
1.47 1F-CSU-17 - 5.0TR Nos 1
1.48 1F-CSU-18 - 3.0TR Nos 1
1.49 1F-CSU-19 - 3.0TR Nos 1
1.50 1F-CSU-20 - 3.0TR Nos 1
1.51 1F-CSU-21 - 3.0TR Nos 1
1.52 1F-CSU-22 - 21TR Nos 11.53 2F-AHU-01 - 28 TR Nos 1
1.54 2F-AHU-02 - 27 TR Nos 1
1.55 2F-CSU-01 - 16TR Nos 1
1.56 2F-CSU-02 - 2.0TR Nos 1
1.57 2F-CSU-03 - 2.0TR Nos 1
1.58 2F-CSU-04 - 3.0TR Nos 1
1.59 2F-CSU-05 - 3.0TR Nos 1
1.60 2F-CSU-06 - 4.0TR Nos 1
1.61 2F-CSU-07 - 4.0TR Nos 1
1.62 2F-CSU-08 - 4.0TR Nos 1
1.63 2F-CSU-09 - 4.0TR Nos 1
1.64 2F-CSU-10 - 22TR Nos 1
1.65 2F-CSU-11 - 4.0TR Nos 1
1.66 2F-CSU-12 - 2.0TR Nos 1
1.67 2F-CSU-13 - 3.0TR Nos 1
1.68 2F-CSU-14 - 12TR Nos 1
1.69 2F-CSU-15 - 4.0TR Nos 1
1.70 2F-CSU-16 - 4.0TR Nos 1
1.71 2F-CSU-17 - 5.0TR Nos 1
1.72 2F-CSU-18 - 3.0TR Nos 1
1.73 2F-CSU-19 - 3.0TR Nos 1
1.74 2F-CSU-20 - 3.0TR Nos 1
1.75 2F-CSU-21 - 3.0TR Nos 1
1.76 2F-CSU-22 - 22TR Nos 1
1.77 3F-AHU-01 - 26 TR Nos 1
1.78 3F-AHU-02 - 22 TR Nos 1
1.79 3F-CSU-01- 3.0TR Nos 1
7/27/2019 HVAC BOQ -R0
4/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
1.90 3F-CSU-12- 4.0TR Nos 1
1.91 3F-CSU-13- 4.0TR Nos 1
1.92 3F-CSU-14- 4.0TR Nos 1
1.93 3F-CSU-15- 4.0TR Nos 1
1.94 3F-CSU-16- 8.0TR Nos 1
1.95 3F-CSU-17- 17TR Nos 11.96 3F-CSU-18- 3.0TR Nos 1
1.97 4F-AHU-01 - 18 TR Nos 1
1.98 4F-AHU-02 - 18 TR Nos 1
1.99 4F-CSU-01- 22TR Nos 1
2.00 4F-CSU-02- 20TR Nos 1
2.01 4F-CSU-03- 9.0TR Nos 1
2.02 4F-CSU-04- 20TR Nos 1
2.03 5F-AHU-01 - 17 TR Nos 1
2.04 5F-AHU-02 - 24 TR Nos 1
2.05 5F-AHU-03 - 16 TR Nos 12.06 5F-AHU-04 - 20 TR Nos 1
III TOTAL VALUE FOR AIR HANDLING UNITS
IV CENTRIFUGAL FANS FOR VENTILATION
PRESSURIZATION FANS
1
Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction
draw thru type , Floor Mounted type Fresh Air Handling Units with 50 mm thick , Intake
Plenum, suitable for Outdoor installation of below mentioned capacities( Fan & Filtersection only ) as per specification and as indicated in the drawing. Each complete TEFC
squirrel cage induction motor, Each complete with DIDW forward Curved aerofoil blade
Centrifugal Fan, belt drive and vibration isolators, Limit switches, Emergency Light, Motor
shall be suitable for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be
suitable for 41510% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD
operation. The unit shall be suitable for outdoor installation.
Make : Kruger / Nicotra
a LIFT WELL PRESSURIZATION
b TE-LWP -01,02,03 & 04 Nos 7
5000 CFM TSP - 75MM WG
e STAIRCASE PRESSURIZATION.
f TE-SP-01 & 02 Nos 3
12000 CFM TSP - 75MM WG
g PUMP ROOM FRESH AIR UNIT ( CEILING SUPSENDED TYPE)
LB-FAU-01 Nos 1
2000 CFM TSP - 75MM WG
7/27/2019 HVAC BOQ -R0
5/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
SEWAGE TREATMENT PLANT VENTILATION FAN
2
Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction
draw thru type , Floor Mounted type Exhaust Units with 50 mm thick , Intake Plenum,
suitable for Outdoor installation of below mentioned capacities( Fan & Filter section only )
as per specification and as indicated in the drawing. Each complete TEFC squirrel cage
induction motor, Each complete with DIDW forward Curved aerofoil blade Centrifugal Fan,belt drive and vibration isolators, Limit switches, Emergency Light, Motor shall be suitable
for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be suitable for
41510% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD operation.
The unit shall be suitable for outdoor installation.
TF - EAU - 01 Nos 1
8000 CFM TSP - 65MM WG
PUMP ROOM VENTILATION FAN
3
Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction
draw thru type , Suspeneded type Exhaust Units with 50 mm thick , Intake Plenum,
suitable for Outdoor installation of below mentioned capacities( Fan & Filter section only )
as per specification and as indicated in the drawing. Each complete TEFC squirrel cage
induction motor, Each complete with DIDW forward Curved aerofoil blade Centrifugal Fan,
belt drive and vibration isolators, Limit switches, Emergency Light, Motor shall be suitable
for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be suitable for
41510% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD operation.
The unit shall be suitable for outdoor installation.
LB - EAU - 01 Nos 1
2000 CFM TSP - 75MM WG
IV TOTAL VALUE FOR CENTRIFUGAL FANS
V PIPING WORKS
PIPING
1.00 Supply, installation, testing & commissioning ofMS class C pipes for chilled water cut to
required lengths and installed with all welded joints, providing and fixing in position with
the necessary fittings like elbows, tees and reducers, sockets for probe meter: Supports,
Support hangers with vibration isolation arrangement as per specification, drawings /
details.
Make : Jindal /Tata
1.01 350 mm dia Rmt 100
0.01 300 mm dia Rmt
0.02 250 mm dia Rmt 300
0.03 200 mm dia Rmt 100
0.04 150 mm dia Rmt 30
0.05 125 mm dia Rmt 30
0.06 100 mm dia Rmt 25
0.07 80 mm dia Rmt 600
0.08 65 mm dia Rmt 600
0.09 50 mm dia Rmt 780
0.10 40 mm dia Rmt 100
7/27/2019 HVAC BOQ -R0
6/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
2.04 150 mm dia Nos R.O
2.05 125 mm dia Nos R.O
2.06 100 mm dia Nos 2
2.07 80 mm dia Nos 90
2.08 65 mm dia Nos 11
2.09 50 mm dia Nos 1242.10 40 mm dia Nos R.O
2.11 32 mm dia Nos R.O
2.12 25 mm dia Nos R.O
BALL VALVES
3.00 Supply, installation, testing & commissioning ofBall valve with PN 10 rating and matching
flanges (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
3.01 40 mm dia Nos 25
3.02 32 mm dia Nos 253.03 25 mm dia Nos 305
BALL VALVES WITH STRAINER
4.00 Supply, installation, testing & commissioning ofBall valve with stainer with PN 10 rating
and matching flanges (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
4.01 40 mm dia Nos R.O
4.02 32 mm dia Nos R.O
4.03 25 mm dia Nos R.O
GATE VALVE
5.00 Supply, installation, testing & commissioning ofGate Valves with matching flanges with
PN 10 rating (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
5.01 50 mm dia Nos R.O
5.02 32 mm dia Nos R.O
5.03 25 mm dia Nos R.O
AUTOMATIC BALANCING VALVE
6.00 Supply, installation, testing & commissioning ofAutomatic Balancing Valve with matching
flanges with PN 10 rating (For details refer Technical specfication).
Make : TA/ Flowcon / frese /Danfoss
6.01 250 mm dia Nos 2
6.02 200 mm dia Nos 8
6.03 150 mm dia Nos R.O
6.04 125 mm dia Nos R.O
6.05 100 mm dia Nos R.O
6.06 80 mm dia Nos 10
6.07 65 mm dia Nos 1
6.08 50 mm dia Nos 24
6.09 40 mm dia Nos 5
6.10 32 mm dia Nos 5
6.11 25 mm dia Nos 61
7/27/2019 HVAC BOQ -R0
7/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
2 - WAY VALVE
7.00 Supply, installation, testing & commissioning of2-way balancing Valve with matching
flanges with PN 10 rating (For details refer Technical specfication). The valve should be
above provide position feed back status.
Make : TA/ Flowcon / frese /Danfoss
7.01 250 mm dia Nos R.O7.02 200 mm dia Nos R.O
7.03 150 mm dia Nos R.O
7.04 125 mm dia Nos R.O
7.05 100 mm dia Nos R.O
7.06 80 mm dia Nos 10
7.07 65 mm dia Nos 1
7.08 50 mm dia Nos 24
7.09 40 mm dia Nos 5
7.10 32 mm dia Nos 5
7.11 25 mm dia Nos 61
PUMP SUCTION GUIDE
8.00 Supply, installation, testing & commissioning of Pump suction guide with stainer &
matching flanges with PN 10 rating (For details Technical specfication).
Make : Sant / Emerald
8.01 200 mm dia Nos 11
8.02 150 mm dia Nos R.O
Y - STRAINER
9.00 Supply, installation, testing & commissioning ofY Strainers with matching flanges with PN10 rating (For details refer Technical specfication) .
Make : Sant / Emerald
9.01 200 mm dia Nos R.O
9.02 150 mm dia Nos R.O
9.03 125 mm dia Nos R.O
9.04 100 mm dia Nos R.O
9.05 80 mm dia Nos 10
9.06 65 mm dia Nos 1
9.07 50 mm dia Nos 24
9.08 40 mm dia Nos 59.09 32 mm dia Nos 5
9.10 25 mm dia Nos 61
DUAL PLATE CHECK VALVE
10.00 Supply, installation, testing & commissioning ofDual Plate Check Valve with matching
flanges with PN 10 rating (For details refer Technical specfication).
Make : Audco /Advance /Shakthi
10.01 250 mm dia Nos R.O
10.02 200 mm dia Nos 3
10.03 150 mm dia Nos 810.04 125 mm dia Nos R.O
10.05 100 mm dia Nos R.O
MOTORISED ON/OFF VALVE
11.00 Supply, installation, testing & commissioning ofMotorised on/off valve with PN 10 rating
(For details refer Technical specfication).
Make : Audco /Advance /Shakthi
7/27/2019 HVAC BOQ -R0
8/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
DIAL TYPE THERMOMETER
12.00 Supply, installation, testing & commissioning ofDial type thermometer (For details refer
Technical specfication).Nos 212
Make : H GURU / Warry
PRESSURE GAUGE
13.00 Supply, installation, testing & commissioning ofPressure gauge (For details refer Technical
specfication).Nos 250
Make : H GURU / Warry
FLEXIBLE CONNECTIONS
14.00 Supply, installation, testing & commissioning of Flexible connections of suitable pressure
rating to be installed at CHILLERS, AHU's & Pumpsets inlets & outlets andat pipes crossing
building expansion joints with suitable Flanges (For details refer Technical specfication).
Make : UP Twiga / Arma Flex
14.01 200 mm dia Nos 38
14.02 150 mm dia Nos R.O
14.03 125 mm dia Nos R.O
14.04 100 mm dia Nos R.O
14.05 80 mm dia Nos 20
14.06 65 mm dia Nos 2
14.07 50 mm dia Nos 56
14.08 40 mm dia Nos 10
14.09 32 mm dia Nos 10
14.10 25 mm dia Nos 122
7/27/2019 HVAC BOQ -R0
9/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
EXPANSION TANK
15.00 Supply, installation, testing & commissioning of Closed loop expansion tank asper
standards & requirements.The tank shall be made of mild steel and has a synthetic rubber
membrane. Nitrogen gas or compressed air is filled in space between the membrane and
the wall of the tank. The tank should be supplied complete with pumps(1W+1S), isolating
valve, check valve, drain valve & pressure gauge. Before connecting the tank to watersystem, the gas pressure should be checked through the charging valve and adjusted
according to the requirements. The quoted price shall be inclusive of structural support for
the tank. Capacity of tank is 300 lts.
Nos 1
Make : Anergy / ITT Industries / Grundfos
DRAIN VALVE
16 Drain Valve 25 mm dia Nos. 50
Make : RB / Belimo
AIR SEPARATOR
17 AIR SEPERATOR300 Dia as per the schematic diagram Nos. 1
Make : Anergy / ITT Industries
CHEMICAL DOSING POT
18 Supply, installation, testing & commissioning of Chemical dosing pot along with valves to
be installed at Chillers water inlet line, as per Specifications.Nos 1
Make : Ion Exchange / PMI Process
AUTO AIR VENT
19 Supply, installation testing & commissioning ofAuto Air vents Nos 20
Make : Anergy
TEST POINT
20 Test points For taking pressure & temperature measurements in Chiller's. Nos. 12
Make : H GURU / Warry
21 DRAIN PIPING
Supply,installation, testing & commissioning of followig sizes insulated GI drain pipes Class
'B' from Ahu drain pans to nearest floor drain dnd from CHW pump glands to the nearest
drain complete with interconnection,flanges,elbows,tees,nuts,U-trap etc.the insulation
should be similar to chilled water piping insulation
21.01 80mm dia Rmt R.O
21.02 65mm dia Rmt R.O
21.03 50mm dia Rmt 100
21.04 40mm dia Rmt 100
21.05 25mm dia Rmt 50
V TOTAL VALUE FOR PIPING SYSTEM
7/27/2019 HVAC BOQ -R0
10/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
VI AIR DISTRIBUTION SYSTEM
1.00 Supply, Fabrication, installation and testing of sheet metal ducts (FACTORY FABRICATED
DUCTS) in accordance with the approved shop drawings complete with all accessories like
vanes, flanges, suspension rods , anchor bolts, GI bolts & nuts, canvas connections , duct
dampers & splitter dampers etc.,and as required by the specifications. All size duct shouldbe with ductmate joints. No C & Ss clip joints should be used
Make : Sail / Jindal / TATA
1.01 24 gauge galvanised sheet steel Sqm 2600
1.02 22 gauge galvanised sheet steel Sqm 400
1.03 20 gauge galvanised sheet steel Sqm 150
1.04 18 gauge galvanised sheet steel Sqm R.O
2.00 Supply, installation, testing and balancing ofGSS Volume Control Dampers with operating
handle for Supply air duct branches in accordance with the approved shop drawings andspecifications. Sqm 16
Make : Air Master / KC Industries / Caryaire
3.00 Supply installation testing and commissioning ofFire damper complete with standard
accessories and 600 mm sleeve as per specifications. (Only Damper price of total Cross-
sectional Area)
Sqm 9
Make : Air Master / Caryaire / RaviStar with UL Listing
4.00 Supply installation testing and commissioning of Fire/Smoke damper suitable for
motorized actuators, sensors, controls & all accessories as per specification - Torque 5 NM Nos
Make : Belimo / Siemens
EXHUAST VALES FOR TOILETS
5.00 Supply, installation,testing & balancing of Exhaust Valves for Toilet Exhaust as per
specifications & approved shop drawings for the following sizes.
Make : Air Master / Caryaire
5.01 150 Dia Nos R.O
5.02 200 Dia Nos R.O
5.03 100 Dia Nos R.O
6.00 Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air
Diffusers with removable core , Aluminium opposed blade volume control dampers in
accordance with the approved shop drawings and specifications to fit in the tile size of 600
x 600. The neck size shall be of following sizes
Make : Air Master / Caryaire
6.01 450 x 450 Nos R.O
6.02 375 x 375 Nos 10
6.03 300 x 300 Nos 10
6.04 225 x 225 Nos R.O
7/27/2019 HVAC BOQ -R0
11/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
7.00 Supply, installation, testing and balancing of powder coated Extruded Aluminium Return
air diffusers with removable core, in accordance with the approved shop drawings and
specifications to fit in the tile size of 600 x 600 . The neck size shall be of following sizes
Make : Air Master / Caryaire
7.01 450 x 450 Nos R.O7.02 375 x 375 Nos 20
8.00 Supply, installation, testing & commissioning ofspill boxes made of 22G G.I with round
neck necessary threaded rods for supporting & anchor fasten the of following sizes.
Make : RolaStar / Zeco
8.01 600 x 600 X 350 Nos R.O
8.02 150 x 150 X 250 Nos 370
8.03 400 x 400 X 350 Nos R.O
9.00 Supply, installation, testing & commissioning ofSpigot & Butterfly Dampers of the
following sizes
Make : Air Master / KC Industries / Caryaire
9.01 300 mm dia Nos R.O
9.02 250 mm dia Nos R.O
9.03 100 mm dia Nos 370
10.00 Supply, Fabrication, installation and testing of the insulated flexible ducting , complete
with connecting rings, duct supports etc as per standards and specification
Make : Asiana pack / caryaire / interlock
10.01 250 dia Rm R.O
10.02 200 dia Rm R.O
10.03 150 dia Rm 550
11.00 Supply & installation , testing and balancing ofAl. Powder coated Continuous grillswithnecessary flanges for supply & return air of the following sizes.
Make: Airmaster / Caryaire / Rolastar / Dynacraft
11.01 100 mm wide continous grille Sqm RO
11.02 150 mm wide continous grille Sqm 10
11.03 200 mm wide continous grille Sqm RO
11.04 350 mm wide (STP Ventilation) grille Sqm RO
11.05 200 mm wide (PUMP ROOM Ventilation) Sqm RO
11.06 500 mm wide continous grille Sqm RO
11.07 300 mm wide continous grille Sqm RO
11.08 Aluminium. collar damper Sqm RO
FA LOUVER
12.00 Supply, & installation of powder coated Al. Louver for fresh air , filter, etc as per the sizes
indicated in the drawing.Sqm 6
Make : Air Master / Caryaire
13.00 Supply, installation and laying of INSULATION FOR FRESH AIR DUCTS with 50MM thick EPS
and Sand Cement plasterSqm RO
VI TOTAL VALUE FOR AIR DISTRIBUTION SYSTEM
7/27/2019 HVAC BOQ -R0
12/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
VII INSULATION
NITRILE RUBBER INSULATION - Chilled Water Pipes
1.00 Supply, installation and testing ofTF Quality Class 'O' Nitrile rubber of preformed pipe
section ( Thicknes as below ) for all pipes with factory laminated aluminum foil facing,,
'fittings, valves, unions, etc as per specifications. The exposed pipes on terrace shall bewith FRP lining and quoted with uv protective paints .
The insulation should meet the green building norms.
Make : Lloyds / Beardsell
1.01 350 mm dia Rmt 100
1.02 300 mm dia Rmt 300
1.03 250 mm dia Rmt 100
1.04 200 mm dia Rmt 30
1.05 150 mm dia Rmt 30
1.06 125 mm diaRmt 251.07 100 mm dia Rmt 600
1.08 80 mm dia Rmt 600
1.09 65 mm dia Rmt 780
1.10 50 mm dia Rmt 100
1.11 40 mm dia Rmt 100
1.12 32 mm dia Rmt 450
1.13 25 mm dia
ACCOUSTIC INSULATION
2.00 Supply, installation and testing of TF Quality Acoustic lining for supply and return air ducts
with 25 mm thick rigid fibre glass of 48Kg/Cum density covered with factory laminated RP
Tissue and finished with with 26G Perforated Aluminium sheet as per the specifications
and as detailed in the drawings. (For details refer Technical specfication).
Sqm 300
Make : UP Twiga / Owens corning / Kimmco
AHU/MECHANICAL PLANT ROOM
3.00 Supply and instal lation of acoustic l ining on walls the AHU/mechanical plant room with
50 mm thick TF quality fibre glass and 48 Kg/Cum density with GI frame grid and covered
with 22G perforated GI sheet as per the approved shop drawings & specifications. (For
details Technical specfication).
Sqm 2800
Make : KC Industries / Eqvt
NITRILE RUBBER - Ducts
4.00 Supply & Installat ion of13 mm thick TF quality Class 'O' Elastometric nitrile rubber for
duct insulation. The quoted price inclusive of adhesives fixtures etc., Sqm R.O
Make : ArmaFlex / K - Flex
UNDER DECK INSULATION
5.00 Supply and installation of Duct Thermal insulation on ducts with 19mm thick Class-O,
Elestomeric Nitrile rubber insulation. The quoted price shall include 2" wide self adhesive
black cotton tape, adhesive etc.,
Sqm. 4250
Make : Beardsell / coolite / Indian packaging services / Styrene
VII TOTAL VALUE FOR INSULATION
7/27/2019 HVAC BOQ -R0
13/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
VIII ELECTRICAL WORKS RELATED TO HVAC
1 POWER WIRING
Supply, installation, testing & laying of 1.1 KV grade XLPE insulated, Cu conductor
armoured and PVC sheathed cables.Make : KEI / POLYLAB / HAVELLS / SBEE
1.01 4C x 16 sqmm - YRY Rmt 100
1.02 4C x 10 sqmm - YRY Rmt 150
1.03 4C x 6 sqmm - YRY Rmt 75
1.04 3C x 6 sqmm - YRY Rmt 150
1.05 3C x 4 sqmm - YRY Rmt 150
2 CONTROL WIRING
Make : KEI / POLYLAB / HAVELLS / SBEE
2.01 2C x 1.5 Sq.mm YRY (Cu) cable Rmt RO
2.02 3C x 1.5 Sq.mm YRY (Cu) cable Rmt 500
2.03 4C x 1.5 Sq.mm YRY (Cu) cable Rmt RO
3Control cabling of 3C x 1.0 Sqmm between each pump to remote push button to be
suitably laid in 1' PVC conduit.Rmt 9
4 Supply, installation & Laying of G.I. Cable Tray of following width
4.1 150 mm wide Rmt 250
4.2 250 mm wide Rmt 500
5 EARTHING
Earthing conductor
5.01 25 * 3 GI Flat Rmt 1000
5.02 8 SWG GI wire Rmt 500
6
Supply, installation, testing of Electrical starter panel for Air Handling Units with necessary
DOL / Start Delta starters, Indicating lamps,ammeter,Voltmeter,necessary controls,
cabling, etc as per specification. The price should include end termination (copper).Thestarter shall be able to connect to BMS
6.01 1.1 KW Nos 63
6.02 1.5 KW Nos RO
6.03 2.2 KW Nos RO
6.04 3.3 KW Nos 25
6.05 5.5 KW Nos 16
6.06 7.5 KW Nos RO
6.07 9.3 KW Nos RO
6.08 11 KW Nos RO
6.09 15 KW Nos RO
6.10 18.5 KW Nos RO
6.11 20 KW Nos RO
7Supply, installation, testing ofElectrical starter panel for Pumps with necessary DOL /
Start Delta starters, Indicating lamps,necessary controls, cabling, etc as per specification.
7/27/2019 HVAC BOQ -R0
14/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
9
Supply, laying, testing & commissioning of copper power cable from converer box to
chillers . (Refer Electrical SLD for cable Details) The price should include end termination
(copper).
Set 4
10 Supply, installation, testing & commissioning ofRemote lockable push button starter forVentilation fans, HRW and pumps The price should include end termination (copper).
Nos 21
11 End terminations Nos 20
VIII TOTAL VALUE FOR ELECTRICAL WORKS RELATED TO HVAC
IX BASEMENT VENTILATION WORKS
Supply, Installation, Testing, Commissioning & Handing over of the following for Basement
of Natural fresh air for upper basement and independent Forced exhaust air for both the
basements.
The complete system along with the procurement & installation shall be sourced from
main manufacturer with a written system guarantee & final handing over & acceptance
clearance test
FRESH AIR FAN FOR UPPER BASEMENT
1
Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH opearation (For lower
basement) - Fresh air. Each fan shall be complete with mounting legs, Ceiling Suspension
Rod, Anchor Fastners & Spring Isolators, inlet screen, flexible connection at outlet, inlet
silencer and rated 180C for 2 hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3
phase AC supply.
Make : Flaktwoods / System Air / Green Heck / Humidin
a 25000 CFM, Static Pressure :25mmWC, Motor: 9.3 KW Nos 4
FRESH AIR FAN FOR LOWER BASEMENT
2
Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH opearation (For lower
basement) - Fresh air. Each fan shall be complete with mounting legs, Ceiling Suspension
Rod, Anchor Fastners & Spring Isolators, inlet screen, flexible connection at outlet, inlet
silencer and rated 180C for 2 hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3
phase AC supply.
Make : Flaktwoods / System Air / Green Heck / Humidin
a 25000 CFM, Static Pressure :25mm , Motor: 5.6 KW Nos 5
EXHAUST AIR FAN WITH VFD FOR UPPER BASEMENT
3
Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH/16 ACH opearation
(For Upper basement) - Exhaust Air. Each fan shall be complete with mounting legs, outlet
screen, flexible connection at inlet or outlet and rated 180C for 2 hours Class-H Motor
suitable for 415+10% volts, 50 cycles , 3 phase AC supply.
Make : Flaktwoods / System Air / Green Heck / Humidin
a 30000 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 4
EXHAUST AIR FAN WITH CONSTANT SPEED FOR UPPER BASEMENT
Supply, installation testing & commissioning of high tempearture rated Axial fan with
constant speed star delta starters non return damper Each fan shall be complete with
7/27/2019 HVAC BOQ -R0
15/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
EXHAUST AIR FAN WITH VFD FOR LOWER BASEMENT
5
Supply, installation testing & commissioning of high tempearture rated direct driven Smoke
Spill Axial fan with VFD, for demand controlled ventialtion for 10 ACH opearation (For
lower basement) - Exhaust Air. Each fan shall be complete with mounting legs, outlet
screen, flexible connection at inlet or outlet and rated 180C for 2 hours Class-H Motor
suitable for 415+10% volts, 50 cycles , 3 phase AC supply.
Make : Flaktwoods / System Air / Green Heck / Humidin
a 48750 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 2
EXHAUST AIR FAN WITH CONSTANT SPEED FOR LOWER BASEMENT
6
Supply, installation testing & commissioning of high tempearture rated Axial fan with
constant speed star delta starters,non return damper,Each fan shall be complete with
mounting legs, outlet screen, flexible connection at inlet or outlet and rated 180C for 2
hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3 phase AC supply.
Make : Flaktwoods / System Air / Green Heck / Humidin
a 48750 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 2
JET FAN
3 JET FAN
Installation of jet fans
QTY OF JET FAN SHALL BE FREEZED AFTER CFD ANALYSIS.
Make : Flaktwoods / System Air / Green Heck / Humidin
a Lower Basement Nos 14
b Upper Basement Nos 13
CFD ANALYSIS
4Computational Fluid Dynamics analysis report should include submittal of 3 sets of Color
printed report document and the location of Jet fans.Lot 2
CO SENSORS
5Supply, Installation, Testing & Commissioning of CO Sensors (Location of the CO Sensor
should be as per CFD Analysis)Nos 14
Make : Grey Stone / Honey Well
PLC PANEL FOR UPPER BASEMENT
6
Floor mounted free standing compartmentalized fire rated Electrical MCC Panel as per IS
standards 8623 with Protection Class of IP 42 and Fault level of 25kA. The panel made out
of 14 SWG CRCA sheet finished with Siemens Grey painting. The Panel consists of suitable
dual Incomer (One incomer from Common area panel and another incomer from Fire
emergency panel), Feeders and Starters for 24 nos. of Jet fans of 1.1 KW each (0.14KW for
low speed / 1.1KW for High speed) and 4 nos of dual speed Axial fans of 7.5/15 KW with
Danfoss VFD & 5 nos. of Axial fans of 11 KW each with star delta starters, with 5 nos. spare
feeders, MCCB, Metering panel, top cable entry, aluminum bus bar and custom built
microprocessor logic controller with necessary control wiring etc. Each feeder shall have
TPN MCB, two starters and indication lamps, toggle switch for two speed operations andElectrical interlock for two speed functions. It should control of JET fans for demand
ventilation with a logic. Vendor should submit SLD and GA drawings for consultants
approval.
LOGIC CONTROL microprocessor logic PANEL to perform the logical operation of Speed
change in fans from Low to high speed based on the CO Level
in the basement. The control is envisaged for JET Vent fans and AXIAL fans. ALL these fans
should also be SWITCHED on in full speed incase of Receipt of FIRE SIGNAL The Logical
Sets 1
7/27/2019 HVAC BOQ -R0
16/17
Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ
Sl No Description Unit Qty Rate Amount
7
Floor mounted free standing compartmentalized fire rated Electrical MCC Panel as per IS
standards 8623 with Protection Class of IP 42 and Fault level of 25kA. The panel made out
of 14 SWG CRCA sheet finished with Siemens Grey painting. The Panel consists of suitable
dual Incomer (One incomer from Common area panel and another incomer from Fire
emergency panel), Feeders and Starters for 7 nos. of Jet fans of 1.1 KW each (0.14KW for
low speed / 1.1KW for High speed) and 2 nos of Axial fans of 9.5 KW with Danfoss VFD & 1
no. of Axial fans of 7.5 KW with star delta starters, with 5 nos. spare feeders, MCCB,
Metering panel, top cable entry, aluminum bus bar and custom built microprocessor logic
controller with necessary control wiring etc. Each feeder shall have TPN MCB, two starters
and indication lamps, toggle switch for two speed operations and Electrical interlock for
two speed functions. It should control of JET fans for demand ventilation with a logic.
Vendor should submit SLD and GA drawings for consultants approval.
LOGIC CONTROL microprocessor logic PANEL to perform the logical operation of Speed
change in fans from Low to high speed based on the CO Level
in the basement. The control is envisaged for JET Vent fans and AXIAL fans. ALL these fans
should also be SWITCHED on in full speed incase of Receipt of FIRE SIGNAL. The Logical
Operationof Pollution mode and FIRE mode is desired from the control panel\. This shall also include
all the
necessary cabling & control wiring for all the fans.
Sets 1
Make : ABB / Schneider
POWER CABLING
Supply and Laying of Following Size fire rated FRLS aluminium/copper cables with
necessary supports. The cables shall be pvc sheathed or armoured cables with including
standard cu lugs with terminating
Make : KEI / POLYLAB / HAVELLS / SBEE
a3 C X 1.5 Sq.mm FRLS Armoured Copper Cable 2 runs for high & Low speed (from Car Park
Ventilation Panel to Jet Vent Fans)Rmt 600
b4 C X 25 Sq.mm FRLS Armoured Aluminium Cable (from Car Park Ventilation Panel to
Extract Fans)Rmt 450
c2C X 1 Sq.mm FRLS Copper cable unarmoured in 19 mm PVC conduit (from PLC Panel to CO
Sensor )Rmt 500
8
Providing & Install cable terminations for the below cables including double compression
type chrome plated brass glands and lugs(crimping type), gland earthing, PVC taping as
required and all accessories complete.
a 3 C X 1.5 Sq.mm FRLS Armoured Copper Cable (from Jetfan to electrical panel) Set 50
b4 C X 25 Sq.mm FRLS Armoured Aluminium Cable (from Emergency extract fan to electrical
panel)Set 20
c2C X 1 Sq.mm FRLS Copper cable unarmoured in 19 mm PVC conduit (from CO Sensor to
PLC Panel)Set 30
9Supply of Sheet steel Ladder Type cable tray of 450 mm width with necessary supports for
extract fans
a 450 mm wide Rmt RO
b 300 mm wide Rmt 350
10Supply,Installation of Earthing wire for, Extract Fans, Supply Fans, Electrical Panel (25 x 3
mm width G.I)Rmt 300
11 Supply,Installation of Earthing Wire for Jet Vent fans - 8SWG Rmt 510
7/27/2019 HVAC BOQ -R0
17/17
Project:-OZONE GALLERIA @ RANCHI Summary
Sl No Description Total Amount (in Rs)
I TOTAL VALUE FOR COOLING TOWER
II TOTAL VALUE FOR CENTRIFUGAL PUMPS
III TOTAL VALUE FOR AIR HANDLING UNIT & HRW
IV TOTAL VALUE FOR CENTRIFUGAL FANS
V TOTAL VALUE FOR PIPING SYSTEM
VI TOTAL VALUE FOR AIR DISTRIBUTION WORKS
VII TOTAL VALUE FOR INSULATION
VIII TOTAL VALUE FOR ELECTRICAL WORKS RELATED TO HVAC
IX TOTAL VALUE FOR BASEMENT VENTILATION
GRAND TOTAL
PROJECT: OZONE GALLERIA MALL @ RANCHI
SUMMARY SHEET FOR HVAC LOWSIDE WORKS
Architects: BENTEL ASSOCIATES Page 1 of 1 Consultants :- Entask Consultancy services Pvt Ltd.