HVAC BOQ -R0

Embed Size (px)

Citation preview

  • 7/27/2019 HVAC BOQ -R0

    1/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    DATE : 06.09.2013

    Sl No Description Unit Qty Rate Amount

    Note: The contractor should read the specifications thoroughly and quote the price foreach item. The BOQ should read in conjuction with specification, drawing & equipment

    schedule.

    NOTE : Quoted price shall be inclusive of Supply, sea freight, insurance, packing and

    forwarding charges etc., as applicable

    COOLING TOWER

    1.00Supply, Installation, testing and commissioning of CTI approved MULTI CELL INDUCED

    DRAFT CROSS FLOW COOLING TOWERS for airconditioning system. Each tower shall be

    complete with basin, casing, distribution system, filling, louvers, ladder, fan, Motor and

    other complete accessories as described in the technical specifications. Motor shall be

    suitable for 41510% volts, 50 cycles and 3 phase power supply. Tower shall be designed

    with high efficiency drift eliminators to meet current environmental standards and

    guidelines for microbial control. Each tower cell must be installed with individual cold

    water basins and water discharge sumps to facilitate maintenance without causing

    disruption to the other cells in operation. Tower for airconditioning system shall be

    selected on the basis of following parameters Refer Equipment schedule & Technical

    Specification for details

    Make : Marley /BAC / Advance

    a Cooling Tower 825 USGPM Nos 2Ambient WB Temperature : 82F

    Cooling capacity : 275TR

    Leaving water leaving temperature : 87 F

    Entering water entering temperature : 97 F

    I TOTAL VALUE FOR COOLING TOWER

    II CENTRIFUGAL PUMPS

    PRIMARY CHILLED WATER PUMPS

    1.00 Supply, installation, testing & commissioning of Centrifugal monobloc type pumpset motor

    shall be suitable for 415 + 10% volts, 50 cycles/second, 3-phase power supply. The quoted

    price shall include cost of thermal insulation and cladding . The unit complete should be

    suitable for outdoor installation at the roof of the building. Refer Equipment schedule &

    Technical Specification for details

    Make : ITT BELL & GOSSETT, GRUNDFOS, Armstrong

    1.10 Primary Chilled Water pumps Nos 4

    660 USGPM

    Head in Ft - 40

    SECONDARY CHILLED WATER PUMPS

    2.00 Supply, instal lation, testing & commissioning of End Suction Back pul l out Centri fugal

    chilled water pumpsets suitable for VFD. Factory mounted on a common base with electric

    motor for recirculation of water for the central air conditioning system. All pumps shall be

    aligned properly as required and complete with mechanical seal. The pump motor shall be

    suitable for 415 + 10% volts, 50 cycles/second, 3-phase power supply. The quoted price

    PROJECT: OZONE GALLERIA MALL @ RANCHI

    BILL OF QUANTITIES FOR HVAC LOW SIDE WORKS

    Revision-R0

  • 7/27/2019 HVAC BOQ -R0

    2/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    660 USGPM - 17 KW

    Head in Ft - 90

    2.11 Supply, installation, testing & commissioning ofVFD, VFD controller, microprocessor panel

    necessary cabling, two sets of sensors, required enclosure, with By Pass control, including

    cabling and cable Termination etc.

    lot 1

    CONDENSER CHILLED WATER PUMPS

    3.00 Supply, installation, testing & commissioning of End Suction Back pull out type pumpset

    motor shall be suitable for 415 + 10% volts, 50 cycles/second, 3-phase power supply. The

    quoted price shall include cost of thermal insulation and cladding . The unit complete

    should be suitable for outdoor installation at the roof of the building. Refer Equipment

    schedule & Technical Specification for details

    Make : ITT BELL & GOSSETT, GRUNDFOS, Armstrong

    3.10 Condenser Chilled Water pumps Nos 3825 USGPM -

    Head in Ft - 40

    II TOTAL VALUE FOR CENTRIFUGAL PUMPS

    III AIR HANDLING UNITS

    1.00 Supply, installation, testing & commissioning of Double skin construction draw thru type

    Horizontal Floor mounted / CEILING SUSPENDED AIR HANDLING UNITS with 25 mm thick

    Sandwitched PUF insulation as per specification & as indicated in the Equipment Schedule.Each complete with DIDW FORWARD Curved Centrifugal Fan, Pre filter of 10 micron, 6

    row deep water coil of copper tube & aluminium fins construction with blue Hydraufillic

    coating for chilled water coil, coil size shall be selected for a maximum face velocity of 500

    feet/minute. and squirrel cage induction motor, centrifugal fan belt drive and vibration

    isolators, Limit switches,Emergency Light , Guard for inspection door. Motor shall be

    suitable for 41510% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD

    operation. Note: AHU shall be supplied with one set of pre commissioning filters. Refer

    Equipment schedule & Technicla Specification for details

    Make : Caryaire / VTS / Zeco / Edgetech

    1.01 LGF-AHU-01 - 35 TR/ Nos 1

    1.02 LGF-AHU-02 - 30 TR Nos 1

    1.03 LGF-CSU-01 - 30 TR Nos 1

    1.04 LGF-CSU-02 - 30 TR Nos 1

    1.05 LGF-CSU-03 - 30 TR Nos 1

    1.06 LGF-CSU-04 - 30 TR Nos 1

    1.07 LGF-CSU-05 - 30 TR Nos 1

    1.08 LGF-CSU-06 - 30 TR Nos 1

    1.09 LGF-CSU-07 - 10 TR Nos 1

    1.10 LGF-CSU-08 - 30 TR Nos 1

    1.11 GF-AHU-01 - 30 TR Nos 1

    1.12 GF-AHU-02 - 28 TR Nos 1

    1.13 GF-CSU-01 - 17 TR Nos 1

    1.14 GF-CSU-02 - 4.0 TR Nos 1

    1.15 GF-CSU-03 - 3.0 TR Nos 1

    1.16 GF-CSU-04 - 5.0 TR Nos 1

  • 7/27/2019 HVAC BOQ -R0

    3/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    1.27 GF-CSU-15 - 5.0 TR Nos 1

    1.28 GF-CSU-16 - 25 TR Nos 1

    1.29 1F-AHU-01 - 27 TR Nos 1

    1.30 1F-AHU-02 - 27 TR Nos 1

    1.31 1F-CSU-01 - 16 TR Nos 1

    1.32 1F-CSU-02 - 2.0 TR Nos 11.33 1F-CSU-03 - 3.0 TR Nos 1

    1.34 1F-CSU-04 - 3.0 TR Nos 1

    1.35 1F-CSU-05 - 5.0 TR Nos 1

    1.36 1F-CSU-06 - 4.0 TR Nos 1

    1.37 1F-CSU-07 - 4.0 TR Nos 1

    1.38 1F-CSU-08 - 5.0 TR Nos 1

    1.39 1F-CSU-09 - 21 TR Nos 1

    1.40 1F-CSU-10 - 4.0TR Nos 1

    1.41 1F-CSU-11 - 4.0TR Nos 1

    1.42 1F-CSU-12 - 4.0TR Nos 11.43 1F-CSU-13 - 4.0TR Nos 1

    1.44 1F-CSU-14 - 12TR Nos 1

    1.45 1F-CSU-15 - 4.0TR Nos 1

    1.46 1F-CSU-16 - 4.0TR Nos 1

    1.47 1F-CSU-17 - 5.0TR Nos 1

    1.48 1F-CSU-18 - 3.0TR Nos 1

    1.49 1F-CSU-19 - 3.0TR Nos 1

    1.50 1F-CSU-20 - 3.0TR Nos 1

    1.51 1F-CSU-21 - 3.0TR Nos 1

    1.52 1F-CSU-22 - 21TR Nos 11.53 2F-AHU-01 - 28 TR Nos 1

    1.54 2F-AHU-02 - 27 TR Nos 1

    1.55 2F-CSU-01 - 16TR Nos 1

    1.56 2F-CSU-02 - 2.0TR Nos 1

    1.57 2F-CSU-03 - 2.0TR Nos 1

    1.58 2F-CSU-04 - 3.0TR Nos 1

    1.59 2F-CSU-05 - 3.0TR Nos 1

    1.60 2F-CSU-06 - 4.0TR Nos 1

    1.61 2F-CSU-07 - 4.0TR Nos 1

    1.62 2F-CSU-08 - 4.0TR Nos 1

    1.63 2F-CSU-09 - 4.0TR Nos 1

    1.64 2F-CSU-10 - 22TR Nos 1

    1.65 2F-CSU-11 - 4.0TR Nos 1

    1.66 2F-CSU-12 - 2.0TR Nos 1

    1.67 2F-CSU-13 - 3.0TR Nos 1

    1.68 2F-CSU-14 - 12TR Nos 1

    1.69 2F-CSU-15 - 4.0TR Nos 1

    1.70 2F-CSU-16 - 4.0TR Nos 1

    1.71 2F-CSU-17 - 5.0TR Nos 1

    1.72 2F-CSU-18 - 3.0TR Nos 1

    1.73 2F-CSU-19 - 3.0TR Nos 1

    1.74 2F-CSU-20 - 3.0TR Nos 1

    1.75 2F-CSU-21 - 3.0TR Nos 1

    1.76 2F-CSU-22 - 22TR Nos 1

    1.77 3F-AHU-01 - 26 TR Nos 1

    1.78 3F-AHU-02 - 22 TR Nos 1

    1.79 3F-CSU-01- 3.0TR Nos 1

  • 7/27/2019 HVAC BOQ -R0

    4/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    1.90 3F-CSU-12- 4.0TR Nos 1

    1.91 3F-CSU-13- 4.0TR Nos 1

    1.92 3F-CSU-14- 4.0TR Nos 1

    1.93 3F-CSU-15- 4.0TR Nos 1

    1.94 3F-CSU-16- 8.0TR Nos 1

    1.95 3F-CSU-17- 17TR Nos 11.96 3F-CSU-18- 3.0TR Nos 1

    1.97 4F-AHU-01 - 18 TR Nos 1

    1.98 4F-AHU-02 - 18 TR Nos 1

    1.99 4F-CSU-01- 22TR Nos 1

    2.00 4F-CSU-02- 20TR Nos 1

    2.01 4F-CSU-03- 9.0TR Nos 1

    2.02 4F-CSU-04- 20TR Nos 1

    2.03 5F-AHU-01 - 17 TR Nos 1

    2.04 5F-AHU-02 - 24 TR Nos 1

    2.05 5F-AHU-03 - 16 TR Nos 12.06 5F-AHU-04 - 20 TR Nos 1

    III TOTAL VALUE FOR AIR HANDLING UNITS

    IV CENTRIFUGAL FANS FOR VENTILATION

    PRESSURIZATION FANS

    1

    Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction

    draw thru type , Floor Mounted type Fresh Air Handling Units with 50 mm thick , Intake

    Plenum, suitable for Outdoor installation of below mentioned capacities( Fan & Filtersection only ) as per specification and as indicated in the drawing. Each complete TEFC

    squirrel cage induction motor, Each complete with DIDW forward Curved aerofoil blade

    Centrifugal Fan, belt drive and vibration isolators, Limit switches, Emergency Light, Motor

    shall be suitable for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be

    suitable for 41510% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD

    operation. The unit shall be suitable for outdoor installation.

    Make : Kruger / Nicotra

    a LIFT WELL PRESSURIZATION

    b TE-LWP -01,02,03 & 04 Nos 7

    5000 CFM TSP - 75MM WG

    e STAIRCASE PRESSURIZATION.

    f TE-SP-01 & 02 Nos 3

    12000 CFM TSP - 75MM WG

    g PUMP ROOM FRESH AIR UNIT ( CEILING SUPSENDED TYPE)

    LB-FAU-01 Nos 1

    2000 CFM TSP - 75MM WG

  • 7/27/2019 HVAC BOQ -R0

    5/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    SEWAGE TREATMENT PLANT VENTILATION FAN

    2

    Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction

    draw thru type , Floor Mounted type Exhaust Units with 50 mm thick , Intake Plenum,

    suitable for Outdoor installation of below mentioned capacities( Fan & Filter section only )

    as per specification and as indicated in the drawing. Each complete TEFC squirrel cage

    induction motor, Each complete with DIDW forward Curved aerofoil blade Centrifugal Fan,belt drive and vibration isolators, Limit switches, Emergency Light, Motor shall be suitable

    for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be suitable for

    41510% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD operation.

    The unit shall be suitable for outdoor installation.

    TF - EAU - 01 Nos 1

    8000 CFM TSP - 65MM WG

    PUMP ROOM VENTILATION FAN

    3

    Supply, Installation, Testing and Commissioning of cabinet type Double Skin construction

    draw thru type , Suspeneded type Exhaust Units with 50 mm thick , Intake Plenum,

    suitable for Outdoor installation of below mentioned capacities( Fan & Filter section only )

    as per specification and as indicated in the drawing. Each complete TEFC squirrel cage

    induction motor, Each complete with DIDW forward Curved aerofoil blade Centrifugal Fan,

    belt drive and vibration isolators, Limit switches, Emergency Light, Motor shall be suitable

    for and 415 +/- 10% Volts, 50Hz, 3 phase AC supply and Motor shall be suitable for

    41510% volts, 50 cycles/second, 3 phase AC supply and also suitable for VFD operation.

    The unit shall be suitable for outdoor installation.

    LB - EAU - 01 Nos 1

    2000 CFM TSP - 75MM WG

    IV TOTAL VALUE FOR CENTRIFUGAL FANS

    V PIPING WORKS

    PIPING

    1.00 Supply, installation, testing & commissioning ofMS class C pipes for chilled water cut to

    required lengths and installed with all welded joints, providing and fixing in position with

    the necessary fittings like elbows, tees and reducers, sockets for probe meter: Supports,

    Support hangers with vibration isolation arrangement as per specification, drawings /

    details.

    Make : Jindal /Tata

    1.01 350 mm dia Rmt 100

    0.01 300 mm dia Rmt

    0.02 250 mm dia Rmt 300

    0.03 200 mm dia Rmt 100

    0.04 150 mm dia Rmt 30

    0.05 125 mm dia Rmt 30

    0.06 100 mm dia Rmt 25

    0.07 80 mm dia Rmt 600

    0.08 65 mm dia Rmt 600

    0.09 50 mm dia Rmt 780

    0.10 40 mm dia Rmt 100

  • 7/27/2019 HVAC BOQ -R0

    6/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    2.04 150 mm dia Nos R.O

    2.05 125 mm dia Nos R.O

    2.06 100 mm dia Nos 2

    2.07 80 mm dia Nos 90

    2.08 65 mm dia Nos 11

    2.09 50 mm dia Nos 1242.10 40 mm dia Nos R.O

    2.11 32 mm dia Nos R.O

    2.12 25 mm dia Nos R.O

    BALL VALVES

    3.00 Supply, installation, testing & commissioning ofBall valve with PN 10 rating and matching

    flanges (For details refer Technical specfication).

    Make : Audco /Advance /Shakthi

    3.01 40 mm dia Nos 25

    3.02 32 mm dia Nos 253.03 25 mm dia Nos 305

    BALL VALVES WITH STRAINER

    4.00 Supply, installation, testing & commissioning ofBall valve with stainer with PN 10 rating

    and matching flanges (For details refer Technical specfication).

    Make : Audco /Advance /Shakthi

    4.01 40 mm dia Nos R.O

    4.02 32 mm dia Nos R.O

    4.03 25 mm dia Nos R.O

    GATE VALVE

    5.00 Supply, installation, testing & commissioning ofGate Valves with matching flanges with

    PN 10 rating (For details refer Technical specfication).

    Make : Audco /Advance /Shakthi

    5.01 50 mm dia Nos R.O

    5.02 32 mm dia Nos R.O

    5.03 25 mm dia Nos R.O

    AUTOMATIC BALANCING VALVE

    6.00 Supply, installation, testing & commissioning ofAutomatic Balancing Valve with matching

    flanges with PN 10 rating (For details refer Technical specfication).

    Make : TA/ Flowcon / frese /Danfoss

    6.01 250 mm dia Nos 2

    6.02 200 mm dia Nos 8

    6.03 150 mm dia Nos R.O

    6.04 125 mm dia Nos R.O

    6.05 100 mm dia Nos R.O

    6.06 80 mm dia Nos 10

    6.07 65 mm dia Nos 1

    6.08 50 mm dia Nos 24

    6.09 40 mm dia Nos 5

    6.10 32 mm dia Nos 5

    6.11 25 mm dia Nos 61

  • 7/27/2019 HVAC BOQ -R0

    7/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    2 - WAY VALVE

    7.00 Supply, installation, testing & commissioning of2-way balancing Valve with matching

    flanges with PN 10 rating (For details refer Technical specfication). The valve should be

    above provide position feed back status.

    Make : TA/ Flowcon / frese /Danfoss

    7.01 250 mm dia Nos R.O7.02 200 mm dia Nos R.O

    7.03 150 mm dia Nos R.O

    7.04 125 mm dia Nos R.O

    7.05 100 mm dia Nos R.O

    7.06 80 mm dia Nos 10

    7.07 65 mm dia Nos 1

    7.08 50 mm dia Nos 24

    7.09 40 mm dia Nos 5

    7.10 32 mm dia Nos 5

    7.11 25 mm dia Nos 61

    PUMP SUCTION GUIDE

    8.00 Supply, installation, testing & commissioning of Pump suction guide with stainer &

    matching flanges with PN 10 rating (For details Technical specfication).

    Make : Sant / Emerald

    8.01 200 mm dia Nos 11

    8.02 150 mm dia Nos R.O

    Y - STRAINER

    9.00 Supply, installation, testing & commissioning ofY Strainers with matching flanges with PN10 rating (For details refer Technical specfication) .

    Make : Sant / Emerald

    9.01 200 mm dia Nos R.O

    9.02 150 mm dia Nos R.O

    9.03 125 mm dia Nos R.O

    9.04 100 mm dia Nos R.O

    9.05 80 mm dia Nos 10

    9.06 65 mm dia Nos 1

    9.07 50 mm dia Nos 24

    9.08 40 mm dia Nos 59.09 32 mm dia Nos 5

    9.10 25 mm dia Nos 61

    DUAL PLATE CHECK VALVE

    10.00 Supply, installation, testing & commissioning ofDual Plate Check Valve with matching

    flanges with PN 10 rating (For details refer Technical specfication).

    Make : Audco /Advance /Shakthi

    10.01 250 mm dia Nos R.O

    10.02 200 mm dia Nos 3

    10.03 150 mm dia Nos 810.04 125 mm dia Nos R.O

    10.05 100 mm dia Nos R.O

    MOTORISED ON/OFF VALVE

    11.00 Supply, installation, testing & commissioning ofMotorised on/off valve with PN 10 rating

    (For details refer Technical specfication).

    Make : Audco /Advance /Shakthi

  • 7/27/2019 HVAC BOQ -R0

    8/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    DIAL TYPE THERMOMETER

    12.00 Supply, installation, testing & commissioning ofDial type thermometer (For details refer

    Technical specfication).Nos 212

    Make : H GURU / Warry

    PRESSURE GAUGE

    13.00 Supply, installation, testing & commissioning ofPressure gauge (For details refer Technical

    specfication).Nos 250

    Make : H GURU / Warry

    FLEXIBLE CONNECTIONS

    14.00 Supply, installation, testing & commissioning of Flexible connections of suitable pressure

    rating to be installed at CHILLERS, AHU's & Pumpsets inlets & outlets andat pipes crossing

    building expansion joints with suitable Flanges (For details refer Technical specfication).

    Make : UP Twiga / Arma Flex

    14.01 200 mm dia Nos 38

    14.02 150 mm dia Nos R.O

    14.03 125 mm dia Nos R.O

    14.04 100 mm dia Nos R.O

    14.05 80 mm dia Nos 20

    14.06 65 mm dia Nos 2

    14.07 50 mm dia Nos 56

    14.08 40 mm dia Nos 10

    14.09 32 mm dia Nos 10

    14.10 25 mm dia Nos 122

  • 7/27/2019 HVAC BOQ -R0

    9/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    EXPANSION TANK

    15.00 Supply, installation, testing & commissioning of Closed loop expansion tank asper

    standards & requirements.The tank shall be made of mild steel and has a synthetic rubber

    membrane. Nitrogen gas or compressed air is filled in space between the membrane and

    the wall of the tank. The tank should be supplied complete with pumps(1W+1S), isolating

    valve, check valve, drain valve & pressure gauge. Before connecting the tank to watersystem, the gas pressure should be checked through the charging valve and adjusted

    according to the requirements. The quoted price shall be inclusive of structural support for

    the tank. Capacity of tank is 300 lts.

    Nos 1

    Make : Anergy / ITT Industries / Grundfos

    DRAIN VALVE

    16 Drain Valve 25 mm dia Nos. 50

    Make : RB / Belimo

    AIR SEPARATOR

    17 AIR SEPERATOR300 Dia as per the schematic diagram Nos. 1

    Make : Anergy / ITT Industries

    CHEMICAL DOSING POT

    18 Supply, installation, testing & commissioning of Chemical dosing pot along with valves to

    be installed at Chillers water inlet line, as per Specifications.Nos 1

    Make : Ion Exchange / PMI Process

    AUTO AIR VENT

    19 Supply, installation testing & commissioning ofAuto Air vents Nos 20

    Make : Anergy

    TEST POINT

    20 Test points For taking pressure & temperature measurements in Chiller's. Nos. 12

    Make : H GURU / Warry

    21 DRAIN PIPING

    Supply,installation, testing & commissioning of followig sizes insulated GI drain pipes Class

    'B' from Ahu drain pans to nearest floor drain dnd from CHW pump glands to the nearest

    drain complete with interconnection,flanges,elbows,tees,nuts,U-trap etc.the insulation

    should be similar to chilled water piping insulation

    21.01 80mm dia Rmt R.O

    21.02 65mm dia Rmt R.O

    21.03 50mm dia Rmt 100

    21.04 40mm dia Rmt 100

    21.05 25mm dia Rmt 50

    V TOTAL VALUE FOR PIPING SYSTEM

  • 7/27/2019 HVAC BOQ -R0

    10/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    VI AIR DISTRIBUTION SYSTEM

    1.00 Supply, Fabrication, installation and testing of sheet metal ducts (FACTORY FABRICATED

    DUCTS) in accordance with the approved shop drawings complete with all accessories like

    vanes, flanges, suspension rods , anchor bolts, GI bolts & nuts, canvas connections , duct

    dampers & splitter dampers etc.,and as required by the specifications. All size duct shouldbe with ductmate joints. No C & Ss clip joints should be used

    Make : Sail / Jindal / TATA

    1.01 24 gauge galvanised sheet steel Sqm 2600

    1.02 22 gauge galvanised sheet steel Sqm 400

    1.03 20 gauge galvanised sheet steel Sqm 150

    1.04 18 gauge galvanised sheet steel Sqm R.O

    2.00 Supply, installation, testing and balancing ofGSS Volume Control Dampers with operating

    handle for Supply air duct branches in accordance with the approved shop drawings andspecifications. Sqm 16

    Make : Air Master / KC Industries / Caryaire

    3.00 Supply installation testing and commissioning ofFire damper complete with standard

    accessories and 600 mm sleeve as per specifications. (Only Damper price of total Cross-

    sectional Area)

    Sqm 9

    Make : Air Master / Caryaire / RaviStar with UL Listing

    4.00 Supply installation testing and commissioning of Fire/Smoke damper suitable for

    motorized actuators, sensors, controls & all accessories as per specification - Torque 5 NM Nos

    Make : Belimo / Siemens

    EXHUAST VALES FOR TOILETS

    5.00 Supply, installation,testing & balancing of Exhaust Valves for Toilet Exhaust as per

    specifications & approved shop drawings for the following sizes.

    Make : Air Master / Caryaire

    5.01 150 Dia Nos R.O

    5.02 200 Dia Nos R.O

    5.03 100 Dia Nos R.O

    6.00 Supply, installation, testing and balancing of powder coated Extruded Aluminium supply air

    Diffusers with removable core , Aluminium opposed blade volume control dampers in

    accordance with the approved shop drawings and specifications to fit in the tile size of 600

    x 600. The neck size shall be of following sizes

    Make : Air Master / Caryaire

    6.01 450 x 450 Nos R.O

    6.02 375 x 375 Nos 10

    6.03 300 x 300 Nos 10

    6.04 225 x 225 Nos R.O

  • 7/27/2019 HVAC BOQ -R0

    11/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    7.00 Supply, installation, testing and balancing of powder coated Extruded Aluminium Return

    air diffusers with removable core, in accordance with the approved shop drawings and

    specifications to fit in the tile size of 600 x 600 . The neck size shall be of following sizes

    Make : Air Master / Caryaire

    7.01 450 x 450 Nos R.O7.02 375 x 375 Nos 20

    8.00 Supply, installation, testing & commissioning ofspill boxes made of 22G G.I with round

    neck necessary threaded rods for supporting & anchor fasten the of following sizes.

    Make : RolaStar / Zeco

    8.01 600 x 600 X 350 Nos R.O

    8.02 150 x 150 X 250 Nos 370

    8.03 400 x 400 X 350 Nos R.O

    9.00 Supply, installation, testing & commissioning ofSpigot & Butterfly Dampers of the

    following sizes

    Make : Air Master / KC Industries / Caryaire

    9.01 300 mm dia Nos R.O

    9.02 250 mm dia Nos R.O

    9.03 100 mm dia Nos 370

    10.00 Supply, Fabrication, installation and testing of the insulated flexible ducting , complete

    with connecting rings, duct supports etc as per standards and specification

    Make : Asiana pack / caryaire / interlock

    10.01 250 dia Rm R.O

    10.02 200 dia Rm R.O

    10.03 150 dia Rm 550

    11.00 Supply & installation , testing and balancing ofAl. Powder coated Continuous grillswithnecessary flanges for supply & return air of the following sizes.

    Make: Airmaster / Caryaire / Rolastar / Dynacraft

    11.01 100 mm wide continous grille Sqm RO

    11.02 150 mm wide continous grille Sqm 10

    11.03 200 mm wide continous grille Sqm RO

    11.04 350 mm wide (STP Ventilation) grille Sqm RO

    11.05 200 mm wide (PUMP ROOM Ventilation) Sqm RO

    11.06 500 mm wide continous grille Sqm RO

    11.07 300 mm wide continous grille Sqm RO

    11.08 Aluminium. collar damper Sqm RO

    FA LOUVER

    12.00 Supply, & installation of powder coated Al. Louver for fresh air , filter, etc as per the sizes

    indicated in the drawing.Sqm 6

    Make : Air Master / Caryaire

    13.00 Supply, installation and laying of INSULATION FOR FRESH AIR DUCTS with 50MM thick EPS

    and Sand Cement plasterSqm RO

    VI TOTAL VALUE FOR AIR DISTRIBUTION SYSTEM

  • 7/27/2019 HVAC BOQ -R0

    12/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    VII INSULATION

    NITRILE RUBBER INSULATION - Chilled Water Pipes

    1.00 Supply, installation and testing ofTF Quality Class 'O' Nitrile rubber of preformed pipe

    section ( Thicknes as below ) for all pipes with factory laminated aluminum foil facing,,

    'fittings, valves, unions, etc as per specifications. The exposed pipes on terrace shall bewith FRP lining and quoted with uv protective paints .

    The insulation should meet the green building norms.

    Make : Lloyds / Beardsell

    1.01 350 mm dia Rmt 100

    1.02 300 mm dia Rmt 300

    1.03 250 mm dia Rmt 100

    1.04 200 mm dia Rmt 30

    1.05 150 mm dia Rmt 30

    1.06 125 mm diaRmt 251.07 100 mm dia Rmt 600

    1.08 80 mm dia Rmt 600

    1.09 65 mm dia Rmt 780

    1.10 50 mm dia Rmt 100

    1.11 40 mm dia Rmt 100

    1.12 32 mm dia Rmt 450

    1.13 25 mm dia

    ACCOUSTIC INSULATION

    2.00 Supply, installation and testing of TF Quality Acoustic lining for supply and return air ducts

    with 25 mm thick rigid fibre glass of 48Kg/Cum density covered with factory laminated RP

    Tissue and finished with with 26G Perforated Aluminium sheet as per the specifications

    and as detailed in the drawings. (For details refer Technical specfication).

    Sqm 300

    Make : UP Twiga / Owens corning / Kimmco

    AHU/MECHANICAL PLANT ROOM

    3.00 Supply and instal lation of acoustic l ining on walls the AHU/mechanical plant room with

    50 mm thick TF quality fibre glass and 48 Kg/Cum density with GI frame grid and covered

    with 22G perforated GI sheet as per the approved shop drawings & specifications. (For

    details Technical specfication).

    Sqm 2800

    Make : KC Industries / Eqvt

    NITRILE RUBBER - Ducts

    4.00 Supply & Installat ion of13 mm thick TF quality Class 'O' Elastometric nitrile rubber for

    duct insulation. The quoted price inclusive of adhesives fixtures etc., Sqm R.O

    Make : ArmaFlex / K - Flex

    UNDER DECK INSULATION

    5.00 Supply and installation of Duct Thermal insulation on ducts with 19mm thick Class-O,

    Elestomeric Nitrile rubber insulation. The quoted price shall include 2" wide self adhesive

    black cotton tape, adhesive etc.,

    Sqm. 4250

    Make : Beardsell / coolite / Indian packaging services / Styrene

    VII TOTAL VALUE FOR INSULATION

  • 7/27/2019 HVAC BOQ -R0

    13/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    VIII ELECTRICAL WORKS RELATED TO HVAC

    1 POWER WIRING

    Supply, installation, testing & laying of 1.1 KV grade XLPE insulated, Cu conductor

    armoured and PVC sheathed cables.Make : KEI / POLYLAB / HAVELLS / SBEE

    1.01 4C x 16 sqmm - YRY Rmt 100

    1.02 4C x 10 sqmm - YRY Rmt 150

    1.03 4C x 6 sqmm - YRY Rmt 75

    1.04 3C x 6 sqmm - YRY Rmt 150

    1.05 3C x 4 sqmm - YRY Rmt 150

    2 CONTROL WIRING

    Make : KEI / POLYLAB / HAVELLS / SBEE

    2.01 2C x 1.5 Sq.mm YRY (Cu) cable Rmt RO

    2.02 3C x 1.5 Sq.mm YRY (Cu) cable Rmt 500

    2.03 4C x 1.5 Sq.mm YRY (Cu) cable Rmt RO

    3Control cabling of 3C x 1.0 Sqmm between each pump to remote push button to be

    suitably laid in 1' PVC conduit.Rmt 9

    4 Supply, installation & Laying of G.I. Cable Tray of following width

    4.1 150 mm wide Rmt 250

    4.2 250 mm wide Rmt 500

    5 EARTHING

    Earthing conductor

    5.01 25 * 3 GI Flat Rmt 1000

    5.02 8 SWG GI wire Rmt 500

    6

    Supply, installation, testing of Electrical starter panel for Air Handling Units with necessary

    DOL / Start Delta starters, Indicating lamps,ammeter,Voltmeter,necessary controls,

    cabling, etc as per specification. The price should include end termination (copper).Thestarter shall be able to connect to BMS

    6.01 1.1 KW Nos 63

    6.02 1.5 KW Nos RO

    6.03 2.2 KW Nos RO

    6.04 3.3 KW Nos 25

    6.05 5.5 KW Nos 16

    6.06 7.5 KW Nos RO

    6.07 9.3 KW Nos RO

    6.08 11 KW Nos RO

    6.09 15 KW Nos RO

    6.10 18.5 KW Nos RO

    6.11 20 KW Nos RO

    7Supply, installation, testing ofElectrical starter panel for Pumps with necessary DOL /

    Start Delta starters, Indicating lamps,necessary controls, cabling, etc as per specification.

  • 7/27/2019 HVAC BOQ -R0

    14/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    9

    Supply, laying, testing & commissioning of copper power cable from converer box to

    chillers . (Refer Electrical SLD for cable Details) The price should include end termination

    (copper).

    Set 4

    10 Supply, installation, testing & commissioning ofRemote lockable push button starter forVentilation fans, HRW and pumps The price should include end termination (copper).

    Nos 21

    11 End terminations Nos 20

    VIII TOTAL VALUE FOR ELECTRICAL WORKS RELATED TO HVAC

    IX BASEMENT VENTILATION WORKS

    Supply, Installation, Testing, Commissioning & Handing over of the following for Basement

    of Natural fresh air for upper basement and independent Forced exhaust air for both the

    basements.

    The complete system along with the procurement & installation shall be sourced from

    main manufacturer with a written system guarantee & final handing over & acceptance

    clearance test

    FRESH AIR FAN FOR UPPER BASEMENT

    1

    Supply, installation testing & commissioning of high tempearture rated direct driven Smoke

    Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH opearation (For lower

    basement) - Fresh air. Each fan shall be complete with mounting legs, Ceiling Suspension

    Rod, Anchor Fastners & Spring Isolators, inlet screen, flexible connection at outlet, inlet

    silencer and rated 180C for 2 hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3

    phase AC supply.

    Make : Flaktwoods / System Air / Green Heck / Humidin

    a 25000 CFM, Static Pressure :25mmWC, Motor: 9.3 KW Nos 4

    FRESH AIR FAN FOR LOWER BASEMENT

    2

    Supply, installation testing & commissioning of high tempearture rated direct driven Smoke

    Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH opearation (For lower

    basement) - Fresh air. Each fan shall be complete with mounting legs, Ceiling Suspension

    Rod, Anchor Fastners & Spring Isolators, inlet screen, flexible connection at outlet, inlet

    silencer and rated 180C for 2 hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3

    phase AC supply.

    Make : Flaktwoods / System Air / Green Heck / Humidin

    a 25000 CFM, Static Pressure :25mm , Motor: 5.6 KW Nos 5

    EXHAUST AIR FAN WITH VFD FOR UPPER BASEMENT

    3

    Supply, installation testing & commissioning of high tempearture rated direct driven Smoke

    Spill Axial fan with VFD, for demand controlled ventialtion for 8 ACH/16 ACH opearation

    (For Upper basement) - Exhaust Air. Each fan shall be complete with mounting legs, outlet

    screen, flexible connection at inlet or outlet and rated 180C for 2 hours Class-H Motor

    suitable for 415+10% volts, 50 cycles , 3 phase AC supply.

    Make : Flaktwoods / System Air / Green Heck / Humidin

    a 30000 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 4

    EXHAUST AIR FAN WITH CONSTANT SPEED FOR UPPER BASEMENT

    Supply, installation testing & commissioning of high tempearture rated Axial fan with

    constant speed star delta starters non return damper Each fan shall be complete with

  • 7/27/2019 HVAC BOQ -R0

    15/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    EXHAUST AIR FAN WITH VFD FOR LOWER BASEMENT

    5

    Supply, installation testing & commissioning of high tempearture rated direct driven Smoke

    Spill Axial fan with VFD, for demand controlled ventialtion for 10 ACH opearation (For

    lower basement) - Exhaust Air. Each fan shall be complete with mounting legs, outlet

    screen, flexible connection at inlet or outlet and rated 180C for 2 hours Class-H Motor

    suitable for 415+10% volts, 50 cycles , 3 phase AC supply.

    Make : Flaktwoods / System Air / Green Heck / Humidin

    a 48750 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 2

    EXHAUST AIR FAN WITH CONSTANT SPEED FOR LOWER BASEMENT

    6

    Supply, installation testing & commissioning of high tempearture rated Axial fan with

    constant speed star delta starters,non return damper,Each fan shall be complete with

    mounting legs, outlet screen, flexible connection at inlet or outlet and rated 180C for 2

    hours Class-H Motor suitable for 415+10% volts, 50 cycles , 3 phase AC supply.

    Make : Flaktwoods / System Air / Green Heck / Humidin

    a 48750 CFM, Static Pressure :25mmWC, Motor: 11.0 KW Nos 2

    JET FAN

    3 JET FAN

    Installation of jet fans

    QTY OF JET FAN SHALL BE FREEZED AFTER CFD ANALYSIS.

    Make : Flaktwoods / System Air / Green Heck / Humidin

    a Lower Basement Nos 14

    b Upper Basement Nos 13

    CFD ANALYSIS

    4Computational Fluid Dynamics analysis report should include submittal of 3 sets of Color

    printed report document and the location of Jet fans.Lot 2

    CO SENSORS

    5Supply, Installation, Testing & Commissioning of CO Sensors (Location of the CO Sensor

    should be as per CFD Analysis)Nos 14

    Make : Grey Stone / Honey Well

    PLC PANEL FOR UPPER BASEMENT

    6

    Floor mounted free standing compartmentalized fire rated Electrical MCC Panel as per IS

    standards 8623 with Protection Class of IP 42 and Fault level of 25kA. The panel made out

    of 14 SWG CRCA sheet finished with Siemens Grey painting. The Panel consists of suitable

    dual Incomer (One incomer from Common area panel and another incomer from Fire

    emergency panel), Feeders and Starters for 24 nos. of Jet fans of 1.1 KW each (0.14KW for

    low speed / 1.1KW for High speed) and 4 nos of dual speed Axial fans of 7.5/15 KW with

    Danfoss VFD & 5 nos. of Axial fans of 11 KW each with star delta starters, with 5 nos. spare

    feeders, MCCB, Metering panel, top cable entry, aluminum bus bar and custom built

    microprocessor logic controller with necessary control wiring etc. Each feeder shall have

    TPN MCB, two starters and indication lamps, toggle switch for two speed operations andElectrical interlock for two speed functions. It should control of JET fans for demand

    ventilation with a logic. Vendor should submit SLD and GA drawings for consultants

    approval.

    LOGIC CONTROL microprocessor logic PANEL to perform the logical operation of Speed

    change in fans from Low to high speed based on the CO Level

    in the basement. The control is envisaged for JET Vent fans and AXIAL fans. ALL these fans

    should also be SWITCHED on in full speed incase of Receipt of FIRE SIGNAL The Logical

    Sets 1

  • 7/27/2019 HVAC BOQ -R0

    16/17

    Project:-OZONE GALLERIA @ RANCHI HVAC LOW SIDE BOQ

    Sl No Description Unit Qty Rate Amount

    7

    Floor mounted free standing compartmentalized fire rated Electrical MCC Panel as per IS

    standards 8623 with Protection Class of IP 42 and Fault level of 25kA. The panel made out

    of 14 SWG CRCA sheet finished with Siemens Grey painting. The Panel consists of suitable

    dual Incomer (One incomer from Common area panel and another incomer from Fire

    emergency panel), Feeders and Starters for 7 nos. of Jet fans of 1.1 KW each (0.14KW for

    low speed / 1.1KW for High speed) and 2 nos of Axial fans of 9.5 KW with Danfoss VFD & 1

    no. of Axial fans of 7.5 KW with star delta starters, with 5 nos. spare feeders, MCCB,

    Metering panel, top cable entry, aluminum bus bar and custom built microprocessor logic

    controller with necessary control wiring etc. Each feeder shall have TPN MCB, two starters

    and indication lamps, toggle switch for two speed operations and Electrical interlock for

    two speed functions. It should control of JET fans for demand ventilation with a logic.

    Vendor should submit SLD and GA drawings for consultants approval.

    LOGIC CONTROL microprocessor logic PANEL to perform the logical operation of Speed

    change in fans from Low to high speed based on the CO Level

    in the basement. The control is envisaged for JET Vent fans and AXIAL fans. ALL these fans

    should also be SWITCHED on in full speed incase of Receipt of FIRE SIGNAL. The Logical

    Operationof Pollution mode and FIRE mode is desired from the control panel\. This shall also include

    all the

    necessary cabling & control wiring for all the fans.

    Sets 1

    Make : ABB / Schneider

    POWER CABLING

    Supply and Laying of Following Size fire rated FRLS aluminium/copper cables with

    necessary supports. The cables shall be pvc sheathed or armoured cables with including

    standard cu lugs with terminating

    Make : KEI / POLYLAB / HAVELLS / SBEE

    a3 C X 1.5 Sq.mm FRLS Armoured Copper Cable 2 runs for high & Low speed (from Car Park

    Ventilation Panel to Jet Vent Fans)Rmt 600

    b4 C X 25 Sq.mm FRLS Armoured Aluminium Cable (from Car Park Ventilation Panel to

    Extract Fans)Rmt 450

    c2C X 1 Sq.mm FRLS Copper cable unarmoured in 19 mm PVC conduit (from PLC Panel to CO

    Sensor )Rmt 500

    8

    Providing & Install cable terminations for the below cables including double compression

    type chrome plated brass glands and lugs(crimping type), gland earthing, PVC taping as

    required and all accessories complete.

    a 3 C X 1.5 Sq.mm FRLS Armoured Copper Cable (from Jetfan to electrical panel) Set 50

    b4 C X 25 Sq.mm FRLS Armoured Aluminium Cable (from Emergency extract fan to electrical

    panel)Set 20

    c2C X 1 Sq.mm FRLS Copper cable unarmoured in 19 mm PVC conduit (from CO Sensor to

    PLC Panel)Set 30

    9Supply of Sheet steel Ladder Type cable tray of 450 mm width with necessary supports for

    extract fans

    a 450 mm wide Rmt RO

    b 300 mm wide Rmt 350

    10Supply,Installation of Earthing wire for, Extract Fans, Supply Fans, Electrical Panel (25 x 3

    mm width G.I)Rmt 300

    11 Supply,Installation of Earthing Wire for Jet Vent fans - 8SWG Rmt 510

  • 7/27/2019 HVAC BOQ -R0

    17/17

    Project:-OZONE GALLERIA @ RANCHI Summary

    Sl No Description Total Amount (in Rs)

    I TOTAL VALUE FOR COOLING TOWER

    II TOTAL VALUE FOR CENTRIFUGAL PUMPS

    III TOTAL VALUE FOR AIR HANDLING UNIT & HRW

    IV TOTAL VALUE FOR CENTRIFUGAL FANS

    V TOTAL VALUE FOR PIPING SYSTEM

    VI TOTAL VALUE FOR AIR DISTRIBUTION WORKS

    VII TOTAL VALUE FOR INSULATION

    VIII TOTAL VALUE FOR ELECTRICAL WORKS RELATED TO HVAC

    IX TOTAL VALUE FOR BASEMENT VENTILATION

    GRAND TOTAL

    PROJECT: OZONE GALLERIA MALL @ RANCHI

    SUMMARY SHEET FOR HVAC LOWSIDE WORKS

    Architects: BENTEL ASSOCIATES Page 1 of 1 Consultants :- Entask Consultancy services Pvt Ltd.