Heater disconnection warning machine
Forest Co., Ltd.
FAL-21-3 < for three-phase >
FAL-21-1 < for single phase >
<RoHS>Goods for RoHS made the DIN rail installation possible.
NEW
FAL-20-1
FAL-20-3
Specification
Meter power supply AC100V/200V
Load current 5A(C.T external when 5A is exceeded)
Load voltage 0~100V/0~200V
Range of load setting 1~5A
Range of warning setting 3~50%
Power supply frequency 50/60Hz
Set accuracy ±3%
Warning setting accuracy 5A~3A ±3% 3A~1A ±5%
Detection method Load current and load voltage
Alarm output Relay point of contact 1c(ratings 200V 0.1A resistance load)
Category temperature range 0~50℃
Operating humidity limits 90%RH or less(No do be dewy. )
Installation method Installation type plug-in type in board
Insulation resistance 500VDC 20MΩ or more between each I/O terminals
Withstand voltage 1500VAC 1 minute between each I/O terminals
Weight 680g
Specification
Meter power supply AC200V/220V
Load current Three-phase circuit 5A(Please put external C.T. )
Load voltage 0~200V
Range of load setting 1~5A
Range of warning setting 3~50%
Power supply frequency 50/60Hz
Set accuracy ±3%
Warning setting accuracy 5A~3A ±3% 3A~1A ±5%
Detection method Load current and load voltage
Alarm output Relay point of contact 1c(ratings 200V 0.1A resistance load)
Category temperature range 0~50℃
Operating humidity limits 90%RH or less(No do be dewy. )
Installation method Installation type plug-in type in board
Insulation resistance 500VDC 20MΩ or more between each I/O terminals
Withstand voltage 1500VAC 1 minute between each I/O terminals
Weight 760g
・Phase control, ON-OFF control, and 0 crossing control, etc.
It is possible to use it regardless of the shape of waves.
・One heater disconnection perception in parallel heater
・The detection point can be arbitrarily set with the dial scale.
・The indicator lamp lights when it reaches the detection point,
and the output signal. It does.
350g
430g
FAL-20-1外部結線例
AC100V 0.5kW
AC200V 1.0kW
ブザー等
サイリスター
電力調整器
100V
200V
AC100V
or
AC200V
67
1
負荷
100V
200V
5
4
3
2
8
9
10
11
以下の場合
FAL-20-1 Example of external connecting wires
In the following cases
Thyristor
Electric power
adjustment machine
Buzzer etc.
Load
FAL-20-3外部結線例
ブザー等
サイリスタ
電力調整器
11
9
10
200VCT3
CT2
CT1
負荷
8
7 6
5
4
3
2
1
T
S
R
FAL-20-3 Example of external connecting wires
Thyristor
Electric power
adjustment machine
Load
Buzzer etc.
Externals dimensional drawing
FAL-21-1 Example of external connecting wires
FAL-21-3 Example of external connecting wires
AC100V 0.5kWAC200V 1.0kW
ブザー等
サイリスター電力調整器
100V
200V
AC100V orAC200V
67
1
負荷
100V
200V
5
4
3
2
8
9
10
11
以上の場合
Buzzer etc.
In case of the above-mentioned
Thyristor
Electric power
adjustment machine
Load
FAL-21-3は( )内の寸法になります。
周囲の温度上昇を防ぐために図のように間隔をあけて取り付けるようにして下さい。
55 or more
180 o
r m
ore
M4 or Φ4.5
FAL21-3 becomes a size in ( ).
It leaves space as stated above to prevent a surrounding rise in heat and installation
(mm)
10.04001A L
Forest Co., Ltd.
Business line
Automatic temperature control meter
Various temperature detection edges
Direct-current ampere-hour meter
Direct-current ampere-hour meter by microcomputer control
Thyristor power controller
Heater disconnection alarm
In addition, electronic application apparatus
Since this product is not manufactured for the applications stipulated in the Export Trade Caution Control Ordinance, it cannot be used for the purpose of weapons of mass destruction.
in using The final application and final customer must be checked so that it will not be used for weapons of mass destruction (military application, military equipment). Due attention must also be paid to the re-sale so that it will not be illegally exported.
homepage http://www.forest-ele.co.jp/
Head Office Shimouma 4-14-15,Setagaya-ku, Tokyo 154-0002, Japan Telephone : +81 3 3421 5141 Fax : +81 3 3421 5145
Yamanashi Fuji Plant Shibokusa, Oshino-mura, Minami-Tsuru, Yamanashi 401-0511, Japan Telephone : +81 555 84 2503 Fax : +81 555 84 3157
Recommended