Feedwater Heater Drain Cooler Vent Valve Leakage

Eric Fulton

NPPD - Cooper Nuclear Station

January 2017

Started as small SJAE flow and temperature spikes

Then it got worse:

SJAE flow oscillations ~45 scfm

SJAE temperature oscillations up to 30°F

Condenser pressure oscillations ~0.15”Hg

Hotwell level oscillations 1-2”

Symptoms

\\cnspi \P.N085.V.CNS

51.881

CFM

\\cnspi \P.T106.V.CNS

105.88

DEGF

\\cnspi \P.T012.V.CNS

2.8231

HGAB

\\cnspi \P.F011.V.CNS

7.0446

FT

\\cnspi \P.F041.V.CNS

186.85

DEGF

SJAE B AIR FLOW SJ-EJTR B 1ST STAGE SUCT CONDENSER 1B ABS PRESS CONDENSR HOTWEL 1B LEVEL STM JETAIREJECT 1B DRAIN

23:00 22:00 21:00 20:00 19:00 18:00 17:00 16:00 15:00 14:00 10:00 9:00 8:00 7:00 6:00 5:00 4:00 3:00 2:00 1:00

7/3/2015 12:00:00 AMSJAE-B AR Temps

0

10

20

30

40

50

60

70

80

90

100

0

300

0

4

0

10

0

200

SJAE flow and temperature spiking began on July 3.

\\cnspi \P.N085.V.CNS

81.543

CFM

\\cnspi \P.T106.V.CNS

86.257

DEGF

\\cnspi \P.T012.V.CNS

2.4773

HGAB

\\cnspi \P.F011.V.CNS

7.0955

FT

\\cnspi \P.F041.V.CNS

188.87

DEGF

SJAE B AIR FLOW SJ-EJTR B 1ST STAGE SUCT CONDENSER 1B ABS PRESS CONDENSR HOTWEL 1B LEVEL STM JETAIREJECT 1B DRAIN

23:00 22:00 21:00 20:00 19:00 18:00 17:00 16:00 15:00 14:00 10:00 9:00 8:00 7:00 6:00 5:00 4:00 3:00 2:00 1:00

8/22/2015 12:00:00 AMSJAE-B AR Temps

0

10

20

30

40

50

60

70

80

90

100

0

300

0

4

0

10

0

200

By August 22, it had degraded to this!

Feedwater heater drain cooler vents return to main condenser through SJAE intercondenser loop seal drain

Vents are normally closed, only opened for a few minutes during startup

Not a problem unless the valves leak by!

Investigation

Feedwater HeaterDrain CoolerVents (open duringstartup only)

Feedwater HeaterDrain CoolerVents (open duringstartup only)

Main Condenser

From FWHDrain CoolerVentsSJAE Drain

Closed this normally open valve to isolate drain cooler vents from SJAE

\\cnspi \P.N085.V.CNS

51.011

CFM

\\cnspi \P.T106.V.CNS

106.63

DEGF

\\cnspi \P.T012.V.CNS

2.5113

HGAB

\\cnspi \P.F011.V.CNS

6.9943

FT

\\cnspi \P.F041.V.CNS

185.89

DEGF

SJAE B AIR FLOW SJ-EJTR B 1ST STAGE SUCT CONDENSER 1B ABS PRESS CONDENSR HOTWEL 1B LEVEL STM JETAIREJECT 1B DRAIN

23:00 22:00 21:00 20:00 19:00 18:00 17:00 16:00 15:00 14:00 10:00 9:00 8:00 7:00 6:00 5:00 4:00 3:00 2:00 1:00

8/23/2015 12:00:00 AMSJAE-B AR Temps

0

10

20

30

40

50

60

70

80

90

100

0

300

0

4

0

10

0

200

Examined all drain cooler vent valves during next refueling outage

Installed temperature elements on piping downstream of each valve for periodic temperature monitoring

Corrective Actions

We didn’t pay much attention to these valves until this issue occurred

Your vents probably don’t connect to SJAE’s

Leakage costs $$$

There are better valve designs

Conclusion

Recommended