Merlin GerinMedium Voltage Distribution
Fluair 100 / 200withdrawable factory-built assemblies
3 to 17.5 kV
Building a New Electric World
2 Schneider Electric
Fluair 100/200: 3 to 17.5 kV
The Fluair range:a reliable installation 2
Circuit breaker compartment 3
Withdrawable circuit-breakers≤ 17.5 kV and technical features 4
RI operating mechanism andauxiliary diagram 6
Cable connection compartment 8
Measuring transformers 9
Busbar compartment 10
Control compartment 11
Switchboard monitoring & control 12
Panel selection ( 630 to 3150 A ) 14
Characteristics and dimensions 15
General contents
3Schneider Electric
Fluair 100 Fluair 200
short-circuitpower(MVA)
breaking capacityIsc (kA rms)
rated voltage7.2 17.5
31.5
14.5
20
0 3 12Ua (kV)
1000
750
500
350250
40
Fluair 100/200: 3 to 17.5 kVThe Fluair range: a reliable installation
The Fluair rangeThe Fluair range comprises a series of homogeneous, compatible, factory-builtpanels, designed for use in MV installations rated from 3 to 17.5 kV.
Since the switchgear units are of a withdrawable design and can be used with aremote control system, the range is ideally suited for all types of applications andinstallations which call for:■ continuity of service;■ easy commissioning;■ quick assembly;■ user and system safety;■ flexibility in operation;■ easy extension;■ low maintenance costs.
Inside the range, the Fluair 100/200 is used to build single or double busbar 3 to17.5 kV distribution switchboards encountered in:■ electrical power-generating stations (feeds to station auxiliaries),■ primary substations in the public distribution sector,■ in MV process installations,■ in distribution and final distribution substations in the industrial or tertiary sector.
Metal-clad substationsThe Fluair panels are made up of factory-built metal enclosures of the metal-cladtype in accordance with IEC international standards. These panels comprise 4 fullyself-contained compartments:■ a switchgear compartment,■ a cable connection compartment,■ a busbar compartment,■ a control gear compartment.All the metal frames are permanently connected together electrically.
Degree of protectionIP 3X or IP 5X to IEC 529 (a higher level of protection can be provided on request).
Surface treatmentAll the metal surfaces in the panels are treated against corrosion:■ the outside panels are protected by galvanisation and with an epoxy polyestercoating standard colour RAL 1011 or RAL 7030, and have been put throughthe surface tests laid down in standards IEC 68-2-11.■ the internal partitions are protected against corrosion by galvanisation, withchrome passivation.
N.B. For other ratings please consult us.
InterlocksOperating safety is enhanced by a series of interlocksdesigned to:■ prevent incorrect operation,■ prevent direct access to current-carrying parts,■ restrict access to the network control equipment.
Withdrawable circuit-breaker unitsThe Fluair range of panels are fitted with withdrawableSF6 circuit-breaker units.
The circuit-breaker and its operating mechanism,mounted on a slide-out truck make for fully-visibleisolation and simple, 100% interchangeability.This technology provides the users with the bestguarantee of continuity of service for their installations.
Rigorous testingThe Fluair panels have successfully undergone thetype approval tests set down in the IEC internationalstandards, including:■ dielectric tests,■ temperature-rise tests,■ mechanical endurance tests,■ short time withstand current and peak withstandcurrent tests.
In addition to these standardised tests, therequirements for other types of installation can alsobe met. For example:■ resistance to humid conditions,■ resistance to internal arcing (in accrodance toIEC international standards).
Fluair 100/200 cubicle
4 Schneider Electric
Fixed portionThe fixed portion is equipped with all the devicesnecessary for the withdrawable unit to be connectedand disconnected in total safety:
■ bushing, electrical insulating and containing built-infixed contacts,■ sliding metallic shutters, can be fitted withpadlocks, and which automatically blank off the fixedcontacts; the shutters can be manually operated toinject a signal to search for faults on cables,■ bolted-on panels, which can be removed at thefront in order to access the busbar set and the currenttransformer’s secondary,■ an arrangement, to maintain the continuity to earthwhile the unit is being pulled out or inserted,■ an insertion disabling interlock which can bepadlocked (padlock not supplied), automaticallypreventing the insertion of the withdrawable unit if theearthing switch is closed,■ safety interlock to prevent closure ofthe earthing switch if the unit is in the “in service”position,■ a multi-contact connector, used to connect auxiliarycircuits.
Fixed portion for circuit-breaker.
Fluair 100/200: 3 to 17.5 kVCircuit-breaker compartment
Options for fixed portionThe following optional auxiliaries and accessories are available for the fixed portion:
■ 5 or 12 change over contacts, used to signal the “ inserted ” or “ withdrawn ”positions,■ “ voltage on ” indicator lamps,■ an earthing switch: the position of this switch’s flags is clearly visible fromthe front and indicated from the rear of the panel (see also cable connectioncompartment),■ padlocks: 4 padlocks can be fitted for the earthing switch and 2 for thecircuit-breaker (withdrawn position),■ a foolproofing interlock, which only allows withdrawable units appropriate tothe panel to be inserted into the panel,■ a front door, the addition of which creates extra space, which can then takethe withdrawable unit in the “ isolated ” door closed position, giving the IP5Xdegree of protection (steps are taken to maintain alignment of front panels).
Circuit-breaker panel
The circuit-breaker compartment is totally enclosed by metal walls. It houses awithdrawable unit which can take up 3 positions:
■ “ in service ” : unit latched in the plugged-in position,■ “ isolated ” : unit latched in unplugged or test position, with fully visible isolationachieved by disconnection of the moving portion from the fixed portion and closing ofthe shutters,■ “ withdrawn ” : unit outside the panel.
5Schneider Electric
Fluair 100/200: 3 to 17.5 kVWithdrawable circuit-breakers ≤ 17.5 kV
SF6, the switchgear gasFluair circuit-breakers use sulphur hexafluoride (SF6) for isolation and breaking.The active parts are housed in an insulating enclosure of the sealed pressuresystem type, in compliance with IEC 56.
The devices used to equip the Fluair range of functional units have outstandingfeatures:
■ long service life,■ maintenance-free active parts,■ high electrical endurance,■ very low switching surges,■ operating safety,■ insensitivity to the environment,■ breaking capacity and dielectric strength maintained at atmospheric pressure,■ low filling pressure.
Circuit-breaker rangeCircuit-breaker ranges are used in 7.2 to 17.5 kV cubicles. Breaker operation isbased on SF6 technology.
The circuit-breaker is of the sealed pressure system type. The gas-tight enclosure isfilled with SF6 at a low gauge pressure of 0.15 MPa (1.5 bar).
A pressure switch with a NO contact for continuous monitoring of the SF6. Lowpressure filling guarantees reliable gas-tightness.
Circuit-breaker ranges are actuated by RI type spring stored energy operatingmechanisms.
Self-expansion interrupting principle for LF circuit-breaker rangeThe operating principle combines the rotating arc technique with the effect of thermalexpansion.
The contacts are housed inside a chamber which provides the volume for expansion.
Circuit-breaker closed (fig. 1)
Main contacts open (fig. 2)The main contacts open and the current is transferred to the arcing contacts.
Arcing period (fig. 3)The arcing contacts separate. The arc is cooled by rotation, caused by a magneticfield created by the coil when the current is low. The over-pressure of thermal originproduced by the arc in the expansion chamber extinguishes the arc by forcing it intothe hollow contact.
Circuit-breaker open (fig. 4)
Fig. 4Fig. 2Fig. 1 Fig. 3
6 Schneider Electric
Fluair 100/200: 3 to 17.5 kVWithdrawable circuit-breakers ≤ 17.5 kVTechnical features
LF1, LF2 circuit-breakers
IEC 56 LF1 LF2
rated voltage kV, 50/60 Hz 7.2 12 7.2 12 17.5
insulation level kV rms 50 Hz - 1 mn 20 28 20 28 38
kV, impulse 1.2/50 µs 60 75 60 75 95
rated current A 630 ■ ■ ■ ■ ■ ■ ■
1250 ■ ■ ■ ■ ■ ■ ■
1600 ■ ■ ■
breaking capacity Isc kA, rms 25 31.5 25 31.5 50 40 31.5
making capacity kA, peak 63 79 63 79 125 100 79
permissible short time withstand current kA, rms, 3 s 25 31.5 25 31.5 50 40 31.5
capacitor breaking capacity A 440 440 440 440 440
rated switching sequence O-3 mn - CO-3 mn - CO ■ ■ ■ ■ ■
O-0.3 s - CO-15 s - CO ■ ■ ■ ■ ■
O-0.3 s - CO-3 mn - CO ■ ■ ■ ■ ■
operating times ms opening 48 48 48 48 48
breaking 70 70 70 70 70
closing 65 65 65 65 65
LF3 circuit-breaker
IEC 56 LF3
rated voltage kV, 50/60 Hz 7.2 12 17.5
insulation level kV, rms 50 Hz - 1 mn 20 28 38
kV, impact 1.2/50 µs 60 75 95
rated current (Ia) A 1250 ■
2500 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
3150 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
breaking capacity Isc kA, rms 25 31.5 40 50 25 31.5 40 50 25 31.5
making capacity kA, peak 63 79 100 125 63 79 100 125 63 79
permissible short time withstand current kA, rms, 3 s 25 31.5 40 50 25 31.5 40 50 25 31.5
capacitor breaking A 440 440 440capacity
rated switching sequence O-3 mn - CO-3 mn - CO ■ ■ ■
O-0.3 s - CO-15 s - CO ■ ■ ■
O-0.3 s - CO-3 mn - CO ■ ■ ■
operating times ms opening 48 48 48
breaking 70 70 70
closing 65 65 65
7Schneider Electric
rated current 10 A
breaking capacity AC 10 A with 220V ( p.f. ≥ 0.3 )
DC 1.5 A with 110 or 220V ( L / R ≤ 0.01 s )
(1) mitop: very low power consuming release used as option with Sepam 100 LA, back-upprotection supplied by CT secondaries only.
A RI electrical operating mechanism includes:■ a spring system that stores the energy needed to close and open the breaker,■ a manual spring charging system,■ an electrical motor spring charging device that automatically recharges themechanism as soon as the contacts close (time ≤ 5 s),■ two mechanical push buttons on the front panel for opening and closing,■ an electrical closing system including:❐ a closing release for remote control and an anti-pumping relay.■ an electrical “opening” release system featuring one or more releases of thefollowing types:❐ shunt,❐ undervoltage,❐ low power-consuming mitop (1),■ operation counter,■ an optional “ operating mechanism charged ” indication contact,■ an end-of-charging contact,■ a black and white mechanical “ open closed ” position indicator,■ a multi-pin connector for isolating auxiliary circuits in the “ disconnected ” position.
Auxiliary contactsThe RI operating mechanism is equipped with a block of 14 auxiliary contacts,including:■ 1 changeover contact for the electrical operating mechanism,■ 1 changeover contact for indication,■ 1 contact for the shunt release.
The number of available contacts depends on the composition of the operatingmechanism and the options chosen, (see the table below).
(2) consumption pick-up/hold.
Fluair 100/200: 3 to 17.5 kVRI operating mechanism
RI operating mechanismLF range circuit breakers are actuated by an RIoperating mechanism that ensures switching deviceclosing and opening speed that is independent of theoperator.
Circuit breakers equipped with an RI electricaloperating mechanism can perform remote controlfunctions and implement reclosing cycles.
RI operating mechanism characteristicstype of auxiliaries spring closing opening release contacts available
charging release shunt under- Mitopmotor simple double voltage C/O O/C changeover
supply voltage AC (V) 50 Hz 48 - 110 - 125 - 220
DC (V) 24 - 30 - 48 - 60 - 110 - 125 - 220
consumption AC (VA) 380 300 300 450 400/90 (2)
DC (W) 380 180 100 150 100/10 (2)
7
possible combinations = + + + + +of auxiliaries ■ 1 ■ 1 ■ 1 ■ 1 6 6 1
and quantities or ■ 1 ■ 1 ■ 1 6 6 1
or ■ 1 ■ 1 ■ 1 6 6 1
or ■ 1 ■ 1 6 7
or ■ 1 ■ 1 ■ 1 ■ 1 6 6 1
or ■ 1 ■ 1 ■ 1 6 6 1
or ■ 1 ■ 1 ■ 1 6 7 1
or ■ 1 ■ 1 ■ 1 6 7 1
or ■ 1 ■ 1 ■ 1 ■ 1 6 5 1
or ■ 1 ■ 1 ■ 1 ■ 1 4 5 1
or ■ 1 ■ 1 ■ 1 ■ 1 6 5 1
8 Schneider Electric
J: circuit-breaker.
KN: anti-pumping relay.
M: spring charging motor.
M1-M2: end-of-chargingcontacts.
M3: operating mechanismcharged indication.
QF: circuit-breaker auxiliarycontacts.
SD: transient fault tripindication contact (Mitop).
SE: held tripping contact.
Sm1: closing push button(outside).
Sm2: opening push buttonfor shunt trip release(outside).
Sm3: opening push buttonfor undervoltage release(outside).Sn: closing disable contact(outside).
SP: pressure-switch contact.
YF: closing release.
Y01-Y02: shunt openingreleases.
YM: undervoltage openingrelease.
Mitop: mitop openingrelease (CT current release).
Sm2
Sm3
Sm1
Sn
M3
KN
Y01
YM
M2
SE
YF
JM1
M
QF
Mitop
Y02
SPSD
Fluair 100/200: 3 to 17.5 kVRI operating mechanismAuxiliary diagram
Auxiliary diagram
Fluair cubicle IP 5XFluair cubicle IP 3X
The Fluairswitchgear is
available in IP 3Xor IP 5X
(on request)
9Schneider Electric
The cable connection compartment, which is accessedfrom the rear of the panel, is entirely enclosed by metalwalls.
This compartment contains:
■ gland plates, fitted out to receive single-core orthree-core dry-insulated cables with synthetic cableterminations,
■ non-magnetic cable supports to prevent externalcable damage due to eddy currents,
■ panels earth wire which interconnects, externally,the metal frames of the different panels so that theycan be earthed,
■ measuring transformers (see facing page).
Cable connection is made simple by the clearance leftbetween the floor and gland plates and the largeamount of space left free within the compartment.
Circuit-breaker panel
Fluair 100/200: 3 to 17.5 kVCable connection compartment
Cable connection compartment of a circuit-breaker panel
OptionsThe following optional accessories are available:
■ 3 voltage capacitive dividers, incorporated into the insulators which support theterminal plates, and connected to 3 “ neon ” indicators mounted on the front plate,to indicate whether the cables are live or dead,
■ an earthing switch, used to earth and short-circuit the cable ends before work isperformed on the cable connection compartment, this switch comprises:
❐ a fast-acting closing mechanism, independent of the operator,❐ an interlock which will not allow it to be operated until the circuit-breaker contactorhas been withdrawn,❐ the positively driven flag, mounted on the front plate, the switch position isclearly visible from the front and rear of the panel,
■ two contacts to indicate the “ closed ” position (1 contact) and the “ open ”position (1 contact) of the earthing switch,
■ the equipment required for connection of single or three-core cables insulatedwith impregnated paper (contact us for details),
■ earthing switch with making capacity is not supplied as standard. It is available onrequest.
10 Schneider Electric
The active components of the dry-insulationmeasuring transformers (current and voltagetransformers) are sealed in an insulating resin.
They supply power to the “ current ” and “ voltage ”circuits of the measurement and/or protectiondevices.
These compact transformers have very goodelectrical and mechanical characteristics.
Current transformersCurrent transformers are accomodated inside cableconnection compartment and come in 3 types .
■ conventional type, with 1, 2 or 35 A secondary windings (1 A as an option).
■ air core current sensor (CSP), non-saturating, withlinear response and broad dynamic range.
■ core balance type (CSH), provides more sensitiveprotection by direct measurement of earth fault current.
Measuring transformers in a circuit-breaker panel, showing optionalfunctional voltage transformer with fuse
Fluair 100/200: 3 to 17.5 kVMeasuring transformers
Optional functional voltage transformer with fuse
Standard fixed type voltage transformer (fuse optional)
Voltage transformersAs a standard, voltage transformers are of the fixedtype (fixed fuse can be supplied as an option).
Functional voltage transformers can be supplied as anoption. They are protected by a built-in fuse, and canbe operated simultaneously from the rear of the panelwithout interruption to the busbar.
When the functional voltage transformers are in theisolated position, the replacement of a fuse can beperformed using a padlockable shutter.
11Schneider Electric
Circuit-breaker panel single-busbar
The busbar compartmentforms a distributiontrunking enclosed bymetal partition walls.The system of busbars isthus totally safe, since nomoving parts are insidethe compartment.
Busbar compartment
Fluair 100/200: 3 to 17.5 kVBusbar compartment
Double-busbar panelsCircuit-breaker double-busbar panels are used whentwo separate power supply circuits are used to ensurecontinuity of service.
Each busbar system is housed in an independentcompartment. The two compartments contain bareplate copper busbars, bolted onto the supports(insulated bars optional).
In the “ incoming ” or “ outgoing ” panels, the circuit-breaker is connected to 2 branching isolators whichconnect it to either one or other of the 2 busbar sets.The isolators can be operated mechanically using alever located on the rear panel.
The branching isolators can be interlockedmechanically by a key system.
As an option, each isolator can be fitted with:
■ electrical control,■ an electrical interlock system.
Circuit-breaker panel double-busbar
Single-busbar panelsIn single-busbar panels, this compartment containsbare plate copper busbars bolted onto the supports(insulated bars optional).
12 Schneider Electric
The control compartment which is located at thefront of the Fluair panel, is also separated from theother compartments by metal partition walls.
This compartment contains all the protection andcontrol units required to perform protection,automation and measurement functions.
Control compartment of a circuit-breaker panel
Fluair 100/200: 3 to 17.5 kVControl compartment
Sepam rangeSepam replaces measuring instruments such asammeters, voltmeters, watt meters, power meters, etc.It displays alarm and operating messages inassociation with the protection functions and controllogic, which eliminates the need for indicator lamps.
The front panel includes:■ light-up alphanumeric display that is simple andlegible from several meters away.
■ keys used to select the measurements to bedisplayed and acknowledge messages. As a securitymeasure, these keys do not provide access to theprotection settings.
■ a dedicated door providing access to:❐ the outlet for connection of the TSM 2001 pocketsetting terminal,❐ the housing for the cartridge that contains thedifferent application programs needed for Sepamoperation.
Settings and operationA TSM 2001 pocket terminal is used to set Sepam parameters and makeadjustments.
The pocket terminal, equipped with a keyboard and a display unit with four 20-character lines, has an operating system that comprises user-friendly menus.
The terminal may also be used to look up maintenance information such as faultcurrent value, number of breaker operations, sum of breaking kA, etc…
As a security measure, access to Sepam parameters is protected by a password.
MER
LING
ERINM
ERLIN
GERIN
MER
LING
ERIN
MERLINGERIN
sepam 1000
I1=
162A
I2=
161A
I3=
163A
THD= 2
%reset
I on
SF6
ext
Io >> 51n
Io > 51n
I > 51
Trip
on
0 off
clear
Sepam 2000
Sepam 1000
Circuit monitor Power meter
13Schneider Electric
User-friendly, dependableoperator interfaceThe “ Monitoring & control Software ” operator interfaceis designed to be used by electricians. Theergonomics is intuitive, making the package easy tounderstand and use on a daily basis.
In addition, the operator interface offers a field ofaction that is defined for each operator according topasswords assigned by the installation securitymanager.
ArchitectureThe user terminal consists of a compatible personalcomputer. It is directly connected to the Sepamprotection units via a standard communication bus.
The control station may easily be connected to ahigher level monitoring and control system viaEthernet.
Monitoring & controlsoftwareThe “ Monitoring & control software ”product is a software package designed tocontrol and monitor Fluair switchboards.
The use of “Monitoring & control software”improves quality of service:■ efficiency in daily use and operationsthanks to a user-friendly user interface,■ continuity of service by fastintervention provided by remote control ofthe Fluair switchboard,■ understanding and analysisof events and loads.
Modular designThe software unit capacity and functionality may be scaled in accordance with thesize of the switchboard.
This also provides the option of starting with a small set of monitoring and controlequipment, and then completing it later on, by adding a substation or electricalnetwork monitoring and control system.
Basic functionsThe main functions are:
■ installation display by chained mimic diagrams (animated single-line diagram,device position, energized parts, current faults…),■ real time access to Sepam protection unit measurements (display ofmeasurements, remote control, protection curves and settings…),■ alarm management (tracking, diagnosis…),■ data analysis (measurements, monitoring curves, data logging…),■ power consumption analysis.
Fluair 100/200: 3 to 17.5 kVSwitchboard monitoring and control
Disturbance recording
Supervisory control system
14 Schneider Electric
PowerLogic systemThe PowerLogic system integrates all the intelligent components of the electricalnetwork, using standard communications and powerful software. This gives you thetools you need to manage the cost and quality of power.
PowerLogic software provides you the tools ...■ standard software - configure it yourself in minutes,
■ many standard displays and reports available instantly,
■ create your own custom displays, drawings and reports,
■ harmonics analysis and voltage disturbance monitoring.
Flexible communications deliver the information ...■ ethernet networking based on open TCP / IP protocol - transparent access viayour intranet or the Internet,
■ scaleable system architecture lets you start small and add devices and upgradeyour system as you want.
Schneider ensures your complete satisfaction■ engineering services available for on-site start-up assistance, training, andtechnical support,
■ broad range of components can be installed on existing equipment by anymanufacturer,
■ field-upgradeable products and periodic software upgrades ensure the system willcontinue to meet new or changing needs.
Harmonic analysis is availableany time you need it, withsimultaneous capture ofcurrent and voltage waveforms,plus summary information.
With a record of each voltagesag, you can diagnoseproblems and prevent futuredowntime.
Fluair 100/200: 3 to 17.5 kVSwitchboard monitoring and control
15Schneider Electric
The incoming panelsupplies power to andprotects the switchboard.The outgoing panelsupplies power to andprotects an outgoingcircuit and/or take-offs(motors, transformers,etc.).
These panels are fittedout according to the ratedcurrent and degree ofprotection:■ standard type panel forIP3X,■ panel with front doorfor IP5X (consult us).
The coupling panel isdesigned to connect 2half busbar sets to:■ provide continuity ofsupply when a powersource is switched off,■ connect severalsources in parallel.
These panels, alwaysassociated withbusrisers, are also fittedout to suit the ratedcurrent:■ standard type panel forIP3X,■ panel with front doorfor IP5X (consult us).
Fluair 100/200: 3 to 17.5 kVPanel selection (630 to 3150 A)
The incoming panelsupplies power to andprotects the switchboard.The outgoing panelsupplies power to andprotects an outgoingcircuit and/or take-offs(motors, transformers,etc.).
These panels are fittedout according to the ratedcurrent and degree ofprotection:■ standard type panel forIP3X,■ panel with front doorfor IP5X (consult us).
■ optional isolatablefused potentialtransformer
Double busbar panels
Circuit-breaker incoming and outgoing panels
Single busbar panels
Circuit-breaker incoming and outgoing panels
Standard panel With front door (option)
Circuit-breaker coupling (with busriser)
Buscoupler panel Busriser panel
16 Schneider Electric
Auxiliary circuitsThe auxiliary conductors can be led out to theoutside via:■ the ground, underneath each panel or at the end ofthe switchboard.■ overhead, at the rear of each panel.
(1) The circuit-breaker panels are designed to be fitted withsingle-core (max outside diameter 60 mm) or three-core (maxoutside diameter 95 mm) dry-insulated power cables.
Cables insulated with impregnated paper can also be used,(please consult us for details).
(2) “ Isolated ” position.
(3) “ withdrawn ” position.
(4) all dimensions are given for indication only. Exactdimensions depend on configurations, (please consult us fordetails).
Fluair 100/200: 3 to 17.5 kVCharacteristics and dimensions
≥ 500
H
800
≥ 500
1110
D
260(2) 817(3)
1400
360
1476
351
2190
1945
1455
0
551
150
650
0
2000
2100
N.B.: for other ratings, please consult us
rated rated dry cablevoltage current quantity (1)
(kV) (A) D 1-core 3-core7.2 630/1250/1600 1945 2 2
2190 4 42500/3150 2190 5 3
12 630/1250/1600 1945 2 22190 4 4
2500/3150 2190 5 317.5 630/1250/1600 1945 2 2
2190 4 42500/3150 2190 5 3
Connection capacity (per phase)
panel type rated current approximateweight
(A) (kg)circuit- ≤ 1600 600breaker 3150 720panelbusriser ≤ 1600 380
3150 430
Approximate weight
panel type rated current dimensions(A) (mm)
H W (4) D (4)
incoming ≤ 1600 2100 650 1945or outgoing 2100 650 2190
3150 2100 900 19452100 900 2190
coupling ≤ 1600 2100 650 14553150 2100 900 1700
busriser ≤ 1600 2100 650 14553150 2100 900 1700
Dimensions
17Schneider Electric