Merlin Gerin Medium Voltage Distribution Fluair 100 / 200 withdrawable factory-built assemblies 3 to 17.5 kV Building a New Electric World

F200

Embed Size (px)

Citation preview

Page 1: F200

Merlin GerinMedium Voltage Distribution

Fluair 100 / 200withdrawable factory-built assemblies

3 to 17.5 kV

Building a New Electric World

Page 2: F200

2 Schneider Electric

Fluair 100/200: 3 to 17.5 kV

The Fluair range:a reliable installation 2

Circuit breaker compartment 3

Withdrawable circuit-breakers≤ 17.5 kV and technical features 4

RI operating mechanism andauxiliary diagram 6

Cable connection compartment 8

Measuring transformers 9

Busbar compartment 10

Control compartment 11

Switchboard monitoring & control 12

Panel selection ( 630 to 3150 A ) 14

Characteristics and dimensions 15

General contents

Page 3: F200

3Schneider Electric

Fluair 100 Fluair 200

short-circuitpower(MVA)

breaking capacityIsc (kA rms)

rated voltage7.2 17.5

31.5

14.5

20

0 3 12Ua (kV)

1000

750

500

350250

40

Fluair 100/200: 3 to 17.5 kVThe Fluair range: a reliable installation

The Fluair rangeThe Fluair range comprises a series of homogeneous, compatible, factory-builtpanels, designed for use in MV installations rated from 3 to 17.5 kV.

Since the switchgear units are of a withdrawable design and can be used with aremote control system, the range is ideally suited for all types of applications andinstallations which call for:■ continuity of service;■ easy commissioning;■ quick assembly;■ user and system safety;■ flexibility in operation;■ easy extension;■ low maintenance costs.

Inside the range, the Fluair 100/200 is used to build single or double busbar 3 to17.5 kV distribution switchboards encountered in:■ electrical power-generating stations (feeds to station auxiliaries),■ primary substations in the public distribution sector,■ in MV process installations,■ in distribution and final distribution substations in the industrial or tertiary sector.

Metal-clad substationsThe Fluair panels are made up of factory-built metal enclosures of the metal-cladtype in accordance with IEC international standards. These panels comprise 4 fullyself-contained compartments:■ a switchgear compartment,■ a cable connection compartment,■ a busbar compartment,■ a control gear compartment.All the metal frames are permanently connected together electrically.

Degree of protectionIP 3X or IP 5X to IEC 529 (a higher level of protection can be provided on request).

Surface treatmentAll the metal surfaces in the panels are treated against corrosion:■ the outside panels are protected by galvanisation and with an epoxy polyestercoating standard colour RAL 1011 or RAL 7030, and have been put throughthe surface tests laid down in standards IEC 68-2-11.■ the internal partitions are protected against corrosion by galvanisation, withchrome passivation.

N.B. For other ratings please consult us.

InterlocksOperating safety is enhanced by a series of interlocksdesigned to:■ prevent incorrect operation,■ prevent direct access to current-carrying parts,■ restrict access to the network control equipment.

Withdrawable circuit-breaker unitsThe Fluair range of panels are fitted with withdrawableSF6 circuit-breaker units.

The circuit-breaker and its operating mechanism,mounted on a slide-out truck make for fully-visibleisolation and simple, 100% interchangeability.This technology provides the users with the bestguarantee of continuity of service for their installations.

Rigorous testingThe Fluair panels have successfully undergone thetype approval tests set down in the IEC internationalstandards, including:■ dielectric tests,■ temperature-rise tests,■ mechanical endurance tests,■ short time withstand current and peak withstandcurrent tests.

In addition to these standardised tests, therequirements for other types of installation can alsobe met. For example:■ resistance to humid conditions,■ resistance to internal arcing (in accrodance toIEC international standards).

Fluair 100/200 cubicle

Page 4: F200

4 Schneider Electric

Fixed portionThe fixed portion is equipped with all the devicesnecessary for the withdrawable unit to be connectedand disconnected in total safety:

■ bushing, electrical insulating and containing built-infixed contacts,■ sliding metallic shutters, can be fitted withpadlocks, and which automatically blank off the fixedcontacts; the shutters can be manually operated toinject a signal to search for faults on cables,■ bolted-on panels, which can be removed at thefront in order to access the busbar set and the currenttransformer’s secondary,■ an arrangement, to maintain the continuity to earthwhile the unit is being pulled out or inserted,■ an insertion disabling interlock which can bepadlocked (padlock not supplied), automaticallypreventing the insertion of the withdrawable unit if theearthing switch is closed,■ safety interlock to prevent closure ofthe earthing switch if the unit is in the “in service”position,■ a multi-contact connector, used to connect auxiliarycircuits.

Fixed portion for circuit-breaker.

Fluair 100/200: 3 to 17.5 kVCircuit-breaker compartment

Options for fixed portionThe following optional auxiliaries and accessories are available for the fixed portion:

■ 5 or 12 change over contacts, used to signal the “ inserted ” or “ withdrawn ”positions,■ “ voltage on ” indicator lamps,■ an earthing switch: the position of this switch’s flags is clearly visible fromthe front and indicated from the rear of the panel (see also cable connectioncompartment),■ padlocks: 4 padlocks can be fitted for the earthing switch and 2 for thecircuit-breaker (withdrawn position),■ a foolproofing interlock, which only allows withdrawable units appropriate tothe panel to be inserted into the panel,■ a front door, the addition of which creates extra space, which can then takethe withdrawable unit in the “ isolated ” door closed position, giving the IP5Xdegree of protection (steps are taken to maintain alignment of front panels).

Circuit-breaker panel

The circuit-breaker compartment is totally enclosed by metal walls. It houses awithdrawable unit which can take up 3 positions:

■ “ in service ” : unit latched in the plugged-in position,■ “ isolated ” : unit latched in unplugged or test position, with fully visible isolationachieved by disconnection of the moving portion from the fixed portion and closing ofthe shutters,■ “ withdrawn ” : unit outside the panel.

Page 5: F200

5Schneider Electric

Fluair 100/200: 3 to 17.5 kVWithdrawable circuit-breakers ≤ 17.5 kV

SF6, the switchgear gasFluair circuit-breakers use sulphur hexafluoride (SF6) for isolation and breaking.The active parts are housed in an insulating enclosure of the sealed pressuresystem type, in compliance with IEC 56.

The devices used to equip the Fluair range of functional units have outstandingfeatures:

■ long service life,■ maintenance-free active parts,■ high electrical endurance,■ very low switching surges,■ operating safety,■ insensitivity to the environment,■ breaking capacity and dielectric strength maintained at atmospheric pressure,■ low filling pressure.

Circuit-breaker rangeCircuit-breaker ranges are used in 7.2 to 17.5 kV cubicles. Breaker operation isbased on SF6 technology.

The circuit-breaker is of the sealed pressure system type. The gas-tight enclosure isfilled with SF6 at a low gauge pressure of 0.15 MPa (1.5 bar).

A pressure switch with a NO contact for continuous monitoring of the SF6. Lowpressure filling guarantees reliable gas-tightness.

Circuit-breaker ranges are actuated by RI type spring stored energy operatingmechanisms.

Self-expansion interrupting principle for LF circuit-breaker rangeThe operating principle combines the rotating arc technique with the effect of thermalexpansion.

The contacts are housed inside a chamber which provides the volume for expansion.

Circuit-breaker closed (fig. 1)

Main contacts open (fig. 2)The main contacts open and the current is transferred to the arcing contacts.

Arcing period (fig. 3)The arcing contacts separate. The arc is cooled by rotation, caused by a magneticfield created by the coil when the current is low. The over-pressure of thermal originproduced by the arc in the expansion chamber extinguishes the arc by forcing it intothe hollow contact.

Circuit-breaker open (fig. 4)

Fig. 4Fig. 2Fig. 1 Fig. 3

Page 6: F200

6 Schneider Electric

Fluair 100/200: 3 to 17.5 kVWithdrawable circuit-breakers ≤ 17.5 kVTechnical features

LF1, LF2 circuit-breakers

IEC 56 LF1 LF2

rated voltage kV, 50/60 Hz 7.2 12 7.2 12 17.5

insulation level kV rms 50 Hz - 1 mn 20 28 20 28 38

kV, impulse 1.2/50 µs 60 75 60 75 95

rated current A 630 ■ ■ ■ ■ ■ ■ ■

1250 ■ ■ ■ ■ ■ ■ ■

1600 ■ ■ ■

breaking capacity Isc kA, rms 25 31.5 25 31.5 50 40 31.5

making capacity kA, peak 63 79 63 79 125 100 79

permissible short time withstand current kA, rms, 3 s 25 31.5 25 31.5 50 40 31.5

capacitor breaking capacity A 440 440 440 440 440

rated switching sequence O-3 mn - CO-3 mn - CO ■ ■ ■ ■ ■

O-0.3 s - CO-15 s - CO ■ ■ ■ ■ ■

O-0.3 s - CO-3 mn - CO ■ ■ ■ ■ ■

operating times ms opening 48 48 48 48 48

breaking 70 70 70 70 70

closing 65 65 65 65 65

LF3 circuit-breaker

IEC 56 LF3

rated voltage kV, 50/60 Hz 7.2 12 17.5

insulation level kV, rms 50 Hz - 1 mn 20 28 38

kV, impact 1.2/50 µs 60 75 95

rated current (Ia) A 1250 ■

2500 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

3150 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

breaking capacity Isc kA, rms 25 31.5 40 50 25 31.5 40 50 25 31.5

making capacity kA, peak 63 79 100 125 63 79 100 125 63 79

permissible short time withstand current kA, rms, 3 s 25 31.5 40 50 25 31.5 40 50 25 31.5

capacitor breaking A 440 440 440capacity

rated switching sequence O-3 mn - CO-3 mn - CO ■ ■ ■

O-0.3 s - CO-15 s - CO ■ ■ ■

O-0.3 s - CO-3 mn - CO ■ ■ ■

operating times ms opening 48 48 48

breaking 70 70 70

closing 65 65 65

Page 7: F200

7Schneider Electric

rated current 10 A

breaking capacity AC 10 A with 220V ( p.f. ≥ 0.3 )

DC 1.5 A with 110 or 220V ( L / R ≤ 0.01 s )

(1) mitop: very low power consuming release used as option with Sepam 100 LA, back-upprotection supplied by CT secondaries only.

A RI electrical operating mechanism includes:■ a spring system that stores the energy needed to close and open the breaker,■ a manual spring charging system,■ an electrical motor spring charging device that automatically recharges themechanism as soon as the contacts close (time ≤ 5 s),■ two mechanical push buttons on the front panel for opening and closing,■ an electrical closing system including:❐ a closing release for remote control and an anti-pumping relay.■ an electrical “opening” release system featuring one or more releases of thefollowing types:❐ shunt,❐ undervoltage,❐ low power-consuming mitop (1),■ operation counter,■ an optional “ operating mechanism charged ” indication contact,■ an end-of-charging contact,■ a black and white mechanical “ open closed ” position indicator,■ a multi-pin connector for isolating auxiliary circuits in the “ disconnected ” position.

Auxiliary contactsThe RI operating mechanism is equipped with a block of 14 auxiliary contacts,including:■ 1 changeover contact for the electrical operating mechanism,■ 1 changeover contact for indication,■ 1 contact for the shunt release.

The number of available contacts depends on the composition of the operatingmechanism and the options chosen, (see the table below).

(2) consumption pick-up/hold.

Fluair 100/200: 3 to 17.5 kVRI operating mechanism

RI operating mechanismLF range circuit breakers are actuated by an RIoperating mechanism that ensures switching deviceclosing and opening speed that is independent of theoperator.

Circuit breakers equipped with an RI electricaloperating mechanism can perform remote controlfunctions and implement reclosing cycles.

RI operating mechanism characteristicstype of auxiliaries spring closing opening release contacts available

charging release shunt under- Mitopmotor simple double voltage C/O O/C changeover

supply voltage AC (V) 50 Hz 48 - 110 - 125 - 220

DC (V) 24 - 30 - 48 - 60 - 110 - 125 - 220

consumption AC (VA) 380 300 300 450 400/90 (2)

DC (W) 380 180 100 150 100/10 (2)

7

possible combinations = + + + + +of auxiliaries ■ 1 ■ 1 ■ 1 ■ 1 6 6 1

and quantities or ■ 1 ■ 1 ■ 1 6 6 1

or ■ 1 ■ 1 ■ 1 6 6 1

or ■ 1 ■ 1 6 7

or ■ 1 ■ 1 ■ 1 ■ 1 6 6 1

or ■ 1 ■ 1 ■ 1 6 6 1

or ■ 1 ■ 1 ■ 1 6 7 1

or ■ 1 ■ 1 ■ 1 6 7 1

or ■ 1 ■ 1 ■ 1 ■ 1 6 5 1

or ■ 1 ■ 1 ■ 1 ■ 1 4 5 1

or ■ 1 ■ 1 ■ 1 ■ 1 6 5 1

Page 8: F200

8 Schneider Electric

J: circuit-breaker.

KN: anti-pumping relay.

M: spring charging motor.

M1-M2: end-of-chargingcontacts.

M3: operating mechanismcharged indication.

QF: circuit-breaker auxiliarycontacts.

SD: transient fault tripindication contact (Mitop).

SE: held tripping contact.

Sm1: closing push button(outside).

Sm2: opening push buttonfor shunt trip release(outside).

Sm3: opening push buttonfor undervoltage release(outside).Sn: closing disable contact(outside).

SP: pressure-switch contact.

YF: closing release.

Y01-Y02: shunt openingreleases.

YM: undervoltage openingrelease.

Mitop: mitop openingrelease (CT current release).

Sm2

Sm3

Sm1

Sn

M3

KN

Y01

YM

M2

SE

YF

JM1

M

QF

Mitop

Y02

SPSD

Fluair 100/200: 3 to 17.5 kVRI operating mechanismAuxiliary diagram

Auxiliary diagram

Fluair cubicle IP 5XFluair cubicle IP 3X

The Fluairswitchgear is

available in IP 3Xor IP 5X

(on request)

Page 9: F200

9Schneider Electric

The cable connection compartment, which is accessedfrom the rear of the panel, is entirely enclosed by metalwalls.

This compartment contains:

■ gland plates, fitted out to receive single-core orthree-core dry-insulated cables with synthetic cableterminations,

■ non-magnetic cable supports to prevent externalcable damage due to eddy currents,

■ panels earth wire which interconnects, externally,the metal frames of the different panels so that theycan be earthed,

■ measuring transformers (see facing page).

Cable connection is made simple by the clearance leftbetween the floor and gland plates and the largeamount of space left free within the compartment.

Circuit-breaker panel

Fluair 100/200: 3 to 17.5 kVCable connection compartment

Cable connection compartment of a circuit-breaker panel

OptionsThe following optional accessories are available:

■ 3 voltage capacitive dividers, incorporated into the insulators which support theterminal plates, and connected to 3 “ neon ” indicators mounted on the front plate,to indicate whether the cables are live or dead,

■ an earthing switch, used to earth and short-circuit the cable ends before work isperformed on the cable connection compartment, this switch comprises:

❐ a fast-acting closing mechanism, independent of the operator,❐ an interlock which will not allow it to be operated until the circuit-breaker contactorhas been withdrawn,❐ the positively driven flag, mounted on the front plate, the switch position isclearly visible from the front and rear of the panel,

■ two contacts to indicate the “ closed ” position (1 contact) and the “ open ”position (1 contact) of the earthing switch,

■ the equipment required for connection of single or three-core cables insulatedwith impregnated paper (contact us for details),

■ earthing switch with making capacity is not supplied as standard. It is available onrequest.

Page 10: F200

10 Schneider Electric

The active components of the dry-insulationmeasuring transformers (current and voltagetransformers) are sealed in an insulating resin.

They supply power to the “ current ” and “ voltage ”circuits of the measurement and/or protectiondevices.

These compact transformers have very goodelectrical and mechanical characteristics.

Current transformersCurrent transformers are accomodated inside cableconnection compartment and come in 3 types .

■ conventional type, with 1, 2 or 35 A secondary windings (1 A as an option).

■ air core current sensor (CSP), non-saturating, withlinear response and broad dynamic range.

■ core balance type (CSH), provides more sensitiveprotection by direct measurement of earth fault current.

Measuring transformers in a circuit-breaker panel, showing optionalfunctional voltage transformer with fuse

Fluair 100/200: 3 to 17.5 kVMeasuring transformers

Optional functional voltage transformer with fuse

Standard fixed type voltage transformer (fuse optional)

Voltage transformersAs a standard, voltage transformers are of the fixedtype (fixed fuse can be supplied as an option).

Functional voltage transformers can be supplied as anoption. They are protected by a built-in fuse, and canbe operated simultaneously from the rear of the panelwithout interruption to the busbar.

When the functional voltage transformers are in theisolated position, the replacement of a fuse can beperformed using a padlockable shutter.

Page 11: F200

11Schneider Electric

Circuit-breaker panel single-busbar

The busbar compartmentforms a distributiontrunking enclosed bymetal partition walls.The system of busbars isthus totally safe, since nomoving parts are insidethe compartment.

Busbar compartment

Fluair 100/200: 3 to 17.5 kVBusbar compartment

Double-busbar panelsCircuit-breaker double-busbar panels are used whentwo separate power supply circuits are used to ensurecontinuity of service.

Each busbar system is housed in an independentcompartment. The two compartments contain bareplate copper busbars, bolted onto the supports(insulated bars optional).

In the “ incoming ” or “ outgoing ” panels, the circuit-breaker is connected to 2 branching isolators whichconnect it to either one or other of the 2 busbar sets.The isolators can be operated mechanically using alever located on the rear panel.

The branching isolators can be interlockedmechanically by a key system.

As an option, each isolator can be fitted with:

■ electrical control,■ an electrical interlock system.

Circuit-breaker panel double-busbar

Single-busbar panelsIn single-busbar panels, this compartment containsbare plate copper busbars bolted onto the supports(insulated bars optional).

Page 12: F200

12 Schneider Electric

The control compartment which is located at thefront of the Fluair panel, is also separated from theother compartments by metal partition walls.

This compartment contains all the protection andcontrol units required to perform protection,automation and measurement functions.

Control compartment of a circuit-breaker panel

Fluair 100/200: 3 to 17.5 kVControl compartment

Sepam rangeSepam replaces measuring instruments such asammeters, voltmeters, watt meters, power meters, etc.It displays alarm and operating messages inassociation with the protection functions and controllogic, which eliminates the need for indicator lamps.

The front panel includes:■ light-up alphanumeric display that is simple andlegible from several meters away.

■ keys used to select the measurements to bedisplayed and acknowledge messages. As a securitymeasure, these keys do not provide access to theprotection settings.

■ a dedicated door providing access to:❐ the outlet for connection of the TSM 2001 pocketsetting terminal,❐ the housing for the cartridge that contains thedifferent application programs needed for Sepamoperation.

Settings and operationA TSM 2001 pocket terminal is used to set Sepam parameters and makeadjustments.

The pocket terminal, equipped with a keyboard and a display unit with four 20-character lines, has an operating system that comprises user-friendly menus.

The terminal may also be used to look up maintenance information such as faultcurrent value, number of breaker operations, sum of breaking kA, etc…

As a security measure, access to Sepam parameters is protected by a password.

MER

LING

ERINM

ERLIN

GERIN

MER

LING

ERIN

MERLINGERIN

sepam 1000

I1=

162A

I2=

161A

I3=

163A

THD= 2

%reset

I on

SF6

ext

Io >> 51n

Io > 51n

I > 51

Trip

on

0 off

clear

Sepam 2000

Sepam 1000

Circuit monitor Power meter

Page 13: F200

13Schneider Electric

User-friendly, dependableoperator interfaceThe “ Monitoring & control Software ” operator interfaceis designed to be used by electricians. Theergonomics is intuitive, making the package easy tounderstand and use on a daily basis.

In addition, the operator interface offers a field ofaction that is defined for each operator according topasswords assigned by the installation securitymanager.

ArchitectureThe user terminal consists of a compatible personalcomputer. It is directly connected to the Sepamprotection units via a standard communication bus.

The control station may easily be connected to ahigher level monitoring and control system viaEthernet.

Monitoring & controlsoftwareThe “ Monitoring & control software ”product is a software package designed tocontrol and monitor Fluair switchboards.

The use of “Monitoring & control software”improves quality of service:■ efficiency in daily use and operationsthanks to a user-friendly user interface,■ continuity of service by fastintervention provided by remote control ofthe Fluair switchboard,■ understanding and analysisof events and loads.

Modular designThe software unit capacity and functionality may be scaled in accordance with thesize of the switchboard.

This also provides the option of starting with a small set of monitoring and controlequipment, and then completing it later on, by adding a substation or electricalnetwork monitoring and control system.

Basic functionsThe main functions are:

■ installation display by chained mimic diagrams (animated single-line diagram,device position, energized parts, current faults…),■ real time access to Sepam protection unit measurements (display ofmeasurements, remote control, protection curves and settings…),■ alarm management (tracking, diagnosis…),■ data analysis (measurements, monitoring curves, data logging…),■ power consumption analysis.

Fluair 100/200: 3 to 17.5 kVSwitchboard monitoring and control

Disturbance recording

Supervisory control system

Page 14: F200

14 Schneider Electric

PowerLogic systemThe PowerLogic system integrates all the intelligent components of the electricalnetwork, using standard communications and powerful software. This gives you thetools you need to manage the cost and quality of power.

PowerLogic software provides you the tools ...■ standard software - configure it yourself in minutes,

■ many standard displays and reports available instantly,

■ create your own custom displays, drawings and reports,

■ harmonics analysis and voltage disturbance monitoring.

Flexible communications deliver the information ...■ ethernet networking based on open TCP / IP protocol - transparent access viayour intranet or the Internet,

■ scaleable system architecture lets you start small and add devices and upgradeyour system as you want.

Schneider ensures your complete satisfaction■ engineering services available for on-site start-up assistance, training, andtechnical support,

■ broad range of components can be installed on existing equipment by anymanufacturer,

■ field-upgradeable products and periodic software upgrades ensure the system willcontinue to meet new or changing needs.

Harmonic analysis is availableany time you need it, withsimultaneous capture ofcurrent and voltage waveforms,plus summary information.

With a record of each voltagesag, you can diagnoseproblems and prevent futuredowntime.

Fluair 100/200: 3 to 17.5 kVSwitchboard monitoring and control

Page 15: F200

15Schneider Electric

The incoming panelsupplies power to andprotects the switchboard.The outgoing panelsupplies power to andprotects an outgoingcircuit and/or take-offs(motors, transformers,etc.).

These panels are fittedout according to the ratedcurrent and degree ofprotection:■ standard type panel forIP3X,■ panel with front doorfor IP5X (consult us).

The coupling panel isdesigned to connect 2half busbar sets to:■ provide continuity ofsupply when a powersource is switched off,■ connect severalsources in parallel.

These panels, alwaysassociated withbusrisers, are also fittedout to suit the ratedcurrent:■ standard type panel forIP3X,■ panel with front doorfor IP5X (consult us).

Fluair 100/200: 3 to 17.5 kVPanel selection (630 to 3150 A)

The incoming panelsupplies power to andprotects the switchboard.The outgoing panelsupplies power to andprotects an outgoingcircuit and/or take-offs(motors, transformers,etc.).

These panels are fittedout according to the ratedcurrent and degree ofprotection:■ standard type panel forIP3X,■ panel with front doorfor IP5X (consult us).

■ optional isolatablefused potentialtransformer

Double busbar panels

Circuit-breaker incoming and outgoing panels

Single busbar panels

Circuit-breaker incoming and outgoing panels

Standard panel With front door (option)

Circuit-breaker coupling (with busriser)

Buscoupler panel Busriser panel

Page 16: F200

16 Schneider Electric

Auxiliary circuitsThe auxiliary conductors can be led out to theoutside via:■ the ground, underneath each panel or at the end ofthe switchboard.■ overhead, at the rear of each panel.

(1) The circuit-breaker panels are designed to be fitted withsingle-core (max outside diameter 60 mm) or three-core (maxoutside diameter 95 mm) dry-insulated power cables.

Cables insulated with impregnated paper can also be used,(please consult us for details).

(2) “ Isolated ” position.

(3) “ withdrawn ” position.

(4) all dimensions are given for indication only. Exactdimensions depend on configurations, (please consult us fordetails).

Fluair 100/200: 3 to 17.5 kVCharacteristics and dimensions

≥ 500

H

800

≥ 500

1110

D

260(2) 817(3)

1400

360

1476

351

2190

1945

1455

0

551

150

650

0

2000

2100

N.B.: for other ratings, please consult us

rated rated dry cablevoltage current quantity (1)

(kV) (A) D 1-core 3-core7.2 630/1250/1600 1945 2 2

2190 4 42500/3150 2190 5 3

12 630/1250/1600 1945 2 22190 4 4

2500/3150 2190 5 317.5 630/1250/1600 1945 2 2

2190 4 42500/3150 2190 5 3

Connection capacity (per phase)

panel type rated current approximateweight

(A) (kg)circuit- ≤ 1600 600breaker 3150 720panelbusriser ≤ 1600 380

3150 430

Approximate weight

panel type rated current dimensions(A) (mm)

H W (4) D (4)

incoming ≤ 1600 2100 650 1945or outgoing 2100 650 2190

3150 2100 900 19452100 900 2190

coupling ≤ 1600 2100 650 14553150 2100 900 1700

busriser ≤ 1600 2100 650 14553150 2100 900 1700

Dimensions

Page 17: F200

17Schneider Electric

Page 18: F200

As standards, specifications and designs change from time to time, please ask forconfirmation of the information given in this publication.

68,Tayaran st, Nasr City,Cairo, EgyptP.O. Box 2658 El Horreyatel : (202) 40 10 119Fax: (202) 26 18 908http://www.schneider.com.eg

Schneider Electric Egypt

SEE 05031 / E

Design, production & publishing: Communication - Schneider EgyptPrinting: Trust Advertising Co.