QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 1 01.29.2014
Energi Savr NodeTM for 0–10 V Energi Savr NodeTM with Softswitch®
The Energi Savr NodeTM (ESN) family is a group of modular products for the control of lighting, receptacles, and other loads. This document describes the following products:
•EnergiSavrNodeTM for 0–10 V (models QSN-4T20-S, QSN-4T16-S-347)
•EnergiSavrNodeTM with Softswitch® (models QSN-4S20-S, QSN-4S16-S-347)
Features•Ratedtoswitch20Areceptacleswithanyoutput.•Defaultconfigurationrequiresnocommissioning.•ProgramusingintegralinterfaceontheESNunit.•Fouroccupancysensorinputsforautomatedcontrolofloadsin
4 zones.•Fourdaylightsensorinputsautomaticallyadjustlightlevelsbased
on the amount of natural light entering through the windows.•FourIRreceiverinputsforpersonalcontrol.•FourinputsforIECPELV/NEC®Class2dry-contactswitches.•IncludesQScontrollinkforseamlessintegrationofloads,control
stations, and QS sensor modules.•PatentedSoftswitch® circuit eliminates arcing at mechanical
contacts when loads are switched, prolonging relay life to an averageof1,000,000cyclesat16A.
•ContactLutronforcompatibilitywithaQuantum® system.
System Example
QSN-4T20-SQSN-4T20-S
QSN-4T20-S
ControlPower120–277 V~
4LoadInputFeeds120–277 V~ ; 347 V~1
40–10VChannels(QSN-4T20-S; QSN-4T16-S-347 only)
4Switched-LoadOutputs (20ASoftswitch® 120–277 V~ ; 347 V~1)
Wired DaylightSensors
(up to 4)2,3
Wired OccupancySensors
(up to 4)2
Wired WallstationorIRReceivers
(up to 4)2IR
Transmitter
IRTransmitter
QSlink
Emergency ContactClosureInput
ContactClosureInput
WiredDaylightSensors(upto4)3
WiredOccupancySensors(upto4)
WiredWallstationorIRreceivers(upto4)
IECPELV/NEC®Class2Dry-ContactSwitch (up to 4) (by others)
seeTouch® QS Wallstation
WirelessCommunication
OR
OR
OR
OR
QSMESN
ProgrammingInterface
RadioPowrSavrTM OccupancySensor(up to 10 per QSM)
RadioPowrSavrTM DaylightSensor (up to 10 per QSM)3
Pico® WirelessController (up to 10 per QSM)
Notes1 For347V~ models only.2 Up to 4 wired devices total (of any type).3 The maximum number of daylight
sensors (wired and wireless) that an ESN unit can support is four (1 per zone).
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 2 01.29.2014
Specifications
Power•ControlPower:120V~; 220–240 V~;
277 V~50/60 Hz•LightningstrikeprotectionmeetsANSI/IEEEstandard62.41-1991.Canwithstandvoltagesurgesofupto6000 V~andcurrentsurgesofupto3000A
•Currentdraw:0.5 Amax•10-yearpowerfailurememory:restoreslightingto
levels prior to power interruption•Latchingrelayskeeppreviouslyilluminatedzoneson
when control power feed is lost
Regulatory Approvals•ULListed•CSA•LutronQualitySystemsregisteredtoISO9001:2008
Environment•AmbientTemperatureOperatingRange:32 ºFto104 ºF(0 ºCto40 ºC)
•Relativehumidity:lessthan90%non-condensing•Forindooruseonly•MeetsNEC®requirementsforinstallationin“other
space used for environmental air”
Terminal Wiring•ControlPowerWiring:14 to12 AWG(2.5to4.0 mm2)•LoadWiring:14 to12 AWG(2.5 to4.0 mm2)•0–10VWiring:20 to12 AWG(0.5 to4.0 mm2)•InputGroupWiring:20 to12 AWG(0.5 to4.0 mm2);
maximum wire run length to each input not to exceed 150 ft(46 m)
•QSLinkWiring:22 to12 AWG(0.5 to4.0 mm2)•ContactClosureWiring:20 to12 AWG(0.5 o4.0 mm2)
Physical Design and Mounting•NEMAType 1,IP-20protection•Surface-mount
Load Types (relay ratings)•Ratedtocontrol20 Areceptacleswithanyoutput.•WhenusingtheEnergiSavrNodeTM to control
receptacles, it may be used with, but is not limited to, the following:– Monitors–Fans–Humidifiers–Printers
Note:Refertothemanufacturer’sguidelinesforacceptable switching methods.
•WhenusingtheEnergiSavrNodeTM to control receptacles,itmayNOTbesuitableforusewithdevicesthatrequireanyofthefollowing:– Shut-down process before power is interrupted,
such as computers.–Cool-downprocessbeforepowerisinterrupted,suchasprojectors.
–Programming,suchasclocksorDVRs.–Longwarm-upcycle.
•Not for use with loads that present a hazard if automatically energized (e.g., heaters).
•Anyreceptaclesthatarecontrolledbyanautomaticcontrol device must be markedwith“u” located on the controlled receptacle outlet where visible after installationasstatedin2014NEC®Article406.3(E).
Load Type
Relay Ratings120 – 277 V~
QSN-4S20-SQSN-4T20-S
347 V~QSN-4S16-S-347QSN-4T16-S-347
Tungsten 20A 16AACGeneralUse 20A 16AElectricDischargeLamp 16A 16AElectric Ballast (NEMA410) 16A 16A
Resistive 20A 16AInductive 20A 16A
Motor 1.0HP120V~2.0HP277V~ —
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 3 01.29.2014
Specifications
Input Default Associations
Inputs/Outputs Zone 1 Zone 2 Zone 3 Zone 4
Group1
Occ XPhoto XIR XSwitch X
Group2
Occ XPhoto XIR XSwitch X
Group3
Occ XPhoto XIR XSwitch X
Group4
Occ XPhoto XIR XSwitch XCCI X X X XEmergencyCCI X X X X
Softswitch® 120 – 277 V~
•Softswitch®relayisratedfor20 Acontinuoususeperchannel.
•Relayismechanicallyheld.
0–10 V Output Ratings (QSN-4T20-S)•Eachoutputsinksupto50 mAmaximum.•Eachoutputsinkscurrentonly(loaddevicemustprovide10 Vsupply).
•ProvidesanIECPELV/NEC®Class 2isolated0–10 VoutputsignalthatconformstoIEC60929.
Occupancy Sensors•Upto16occupancysensorscanbeprogrammedto
the Energi Savr NodeTM device.•ManualProgramming:upto4occupancysensors
wired directly to the Energi Savr NodeTM device, up to 4 occupancy sensors wired to a QS Sensor Module (QSM), and up to 10 wireless occupancy sensors through the same QSM; the total programmed to the Energi Savr NodeTM device cannot exceed 16.
•HHD(iPod/iPhone)Programming:upto16occupancysensors from any source (wired directly to the Energi Savr NodeTM device, wired to any other Energi Savr NodeTMdevice,orwired/wirelessfromanyQSMontheQSlink);thetotalprogrammedtotheEnergiSavrNodeTM device cannot exceed 16.
•UseLutron® occupancy sensors to control one or more zones.
•Lutron® occupancy sensors can be programmed to automatically turn on the lights and receptacles in an area when it becomes occupied and turn off the lights lights and receptacles in an area after it becomes vacant.
•Forspacesthatrequirevacancymodeoperationfor lights, a single occupancy sensor can control a zone of lights in vacancy mode and control a zone of receptacles in occupancy mode.
•EachofthefouroccupancyinputscanpoweroneLutron® occupant sensor.
•Eacharea’soccupiedsceneandunoccupiedscenecan be programmed independently.
•Occupancysensormustprovideadry-contactclosureor solid-state output.
•AdditionaloccupancysensorscanbeusedwiththeEnergi Savr NodeTMdevice.Refertothe“ProgrammingOptionsandFeatures”tableforsystemrules.
Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 4 01.29.2014
Daylight Sensors•Lutron® daylight sensors allow daylight harvesting with
programmable effect on light output.•Fourdaylightsensorscanbeconnecteddirectlytothe
ESN unit.•UseLutron®EC-DIR-WHsensorstocontroloneor
more zones.•Alternatively,upto4sensors(Lutron® wired daylight sensorsorRadioPowrSavrTM daylight sensors) can be assigned when associated with a QSM.
•ThemaximumnumberofLutron® daylight sensors (wired or wireless), either wired directly to the unit or indirectly (associated with a QSM) cannot exceed 4.
•AssociateadditionalQSMsandsensors/controlswith ESN unit when programming with an Apple iPod touch or iPhone.Referto“ProgrammingOptions”section for details.
Contact Closure Input (CCI)•Activatescenesusingmomentaryormaintainedclosuresfromanexternaldevicesuchasatimeclock.
•StartorstopAfterhoursModeusingamaintainedclosure.
•Theattacheddevicemustprovideadry-contactclosure or solid-state output.
•ConfigurableforNormally-Open(NO)orNormally-Closed(NC)operation.
•Inputismiswire-protectedupto36V-.
Specifications (continued)
seeTouch® QS Controls•seeTouch®QSwallstationscanbeconfiguredto
control ESN unit scenes or zones.•Inzonetogglemode,zonebuttonscanbeassignedto
one or more zones on any ESN unit connected to the QSLink.
•Inscenemode,wallstationscanbeassignedtooneormore ESN unitsconnectedtotheQSLink.
•LEDindicatordisplayszoneorscenestatus.Table 1: seeTouch® QS Wallstation Configurations
# ButtonsWallstation Function 1 2 3 5 7
Zone Toggle Scene 1,Off(toggle) 1,Off 1,2,Off 1–4,Off N/A
IR Wallstation or Receiver Input•FourinputsforIRreceiversorwallstationsforcontrol
of lighting zones can be connected directly to the ESN unit
•UseLutron®Pico®wiredcontrolorCC-4BRL-WHwallstation to control one or more zones.
•UseLutron® EC-DIR-WHorEC-IR-WHceiling-mountsensors to control one or more zones.
•UptofouradditionalwiredwallstationsorIRreceiverscan be assigned when associated with a QSM.
•AssociateadditionalQSMsandsensors/controlswith ESN unit when programming with an Apple iPod touch or iPhone.Referto“ProgrammingOptions”section for details.
Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 5 01.29.2014
IEC PELV / NEC® Class 2 Dry-Contact Switches•FourinputsforIECPELV/NEC®Class2dry-contact
switches can be assigned to turn on and off one or more zones.
•Configureformomentaryormaintainedoperation.
QS Link Limits•EachESN unitcanprovideupto14PowerDrawUnits(PDUs)forotherQSdevices.RefertotheQSLinkPowerDrawUnitspecificationsubmittal(Lutron® P/N 369405)formoreinformationconcerningPDUs.
•TheQSLinkcanhaveupto100devicesand100 zones.
•EachESN unit counts as 1 device towards the 100 devicelimit.
•EachESN unit counts as 4 zones towards the 100 zonelimit.
QSM (QS Sensor Module)•UsetheQSMtointegrateRadioPowrSavrTM occupancysensors,RadioPowrSavrTM daylight sensors,andPico® wireless controllers to control zones on the ESN unit.
•Associate1QSMperESN unit with manual programming.
•AssociatemultipleQSMsperESN unit with Apple iPod touch or iPhoneprogramming(requiresQSE-CI-AP-DandWi-Firouter).See“ProgrammingOptions”fordetails.
•Assignupto10RadioPowrSavrTM occupancy sensors per ESN unit via QSM.
•Assignupto4RadioPowrSavrTM daylight sensors per ESN unit via QSM.
•Assignupto10Pico® wireless controllers per ESN unit via QSM.
•ThesensorsandPico® wireless controllers associated withtheQSMshouldbemountedwithin60ft(18m)line of sight, or 30 ft (9 m) through walls, of the QSM.
•Wireandpowerupto4wiredsensorsperQSM–DaylightSensors–OccupancySensors–Infrared(IR)ReceiversorWallstations
•RefertoQSMSpecificationSubmittalformoreinformation.
Specifications (continued)
Emergency Contact Closure Input•Bydefault,contactclosureinputfromLutron® EmergencyLightingInterface(LUT-ELI-3PH),security,orfirealarmsystemsturnsallzonesontofulloutputwhen emergency state is detected.
•Emergencycontactclosureinputisnormallyclosed(NC).TheESN unitisshippedwithajumperpre-installed.
•Responseofeachzoneisconfigurable.•Attacheddevices,bydefault,willgotomaximum
output and ignore control inputs.•Nooperationswillbealloweduntilemergencysignalis
cleared.•Theattacheddevicemustprovideadry-contact
closure or solid-state output.•Inputismiswire-protectedupto36V-.•EmergencyCCIcannotcontrolotherESNunits.
Functionality with GRAFIK Eye® QS•ESN unitfollowsGRAFIKEye® QS scene activations whenassociatedwiththeGRAFIKEye® QS.
•ESN unit responds to commands initiated by the GRAFIKEye® QS astronomictimeclockwhenassociatedwiththeGRAFIKEye® QS.
•ESN unit operates in afterhours mode when associatedwithaGRAFIKEye® QS that is in afterhours mode.
Functionality with QSE-IO•ESN unit responds to scene commands initiated by theQSE-IOiftheQSE-IODIPswitcheshavebeensetto either scene selection mode, zone toggle mode, partition mode, or occupancy sensor mode.
Functionality with QSE-CI-NWK-E•IntegrateESN unitwithtouchscreens,PCs,A/V
systems, or other digital systems and devices.•Recallscenesandset/adjustzonelevels.
Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 6 01.29.2014
•Wirelessroutermayberemovedfornormaloperation.•EthernetconnectionmaybemadeviaanESNProgrammingInterface(QSE-CI-AP-D)oranESNQSunitwithintegralEthernetjack.
•LutronrecommendsthatanESNProgrammingInterface(orESNQSunitwithEthernetjack)bewiredtoanEthernetjackinthespaceforeaseofaccessand proximity to power for the wireless router.
•Workswithanystandardwirelessrouterthatsupportsmulticastpackets.
•Apple iPod touch or iPhone can program all ESN QS unitsconnectedtoanESNProgrammingInterfaceviatheQSLink(exceptwhenpartofaQuantum® system).
•ESNappisrequiredandisavailablefromtheApple iTunes Storeonlinemarketplace.
Programming Options
Manual Programming•UsebuttonsonthefrontoftheESNunit.•UsemanualprogrammingininstallationswithonlyoneESNunitandwithoneQSMorfewerontheQSlink.
HHD Programming•RequiresESNProgrammingInterface(QSE-CI-AP-D).•RequiresApple iPod touch or iPhone mobile digital
device.•Usetheintuitiveprogrammingapplicationforthe
Apple iPod touch or iPhone to program systems with multipleESNunitsandQSMsontheQSlink.
•WirelessrouterrequiredforprogrammingwithanApple iPod touch or iPhone only.
QSLink
QSLink
QSM QSM QSM
ESN Unit ESN Unit ESN Unit
Apple iPod touch or iPhone mobile digital device
WirelessRouter (by others)
ESNProgrammingInterface QSE-CI-AP-D
DedicatedEthernetConnectionfor ESN units1,2
1 StandardCAT5/CAT5Ecable:Totallengthnottoexceed300ft(100m)2 Note:ESNunitsarenotdesignedtoexistonanopennetwork.Connectiontoanopennetwork
could result in reduced performance and Ethernet connectivity issues.
Apple,iPhone,iPodtouch,andiTunesStorearetrademarksofAppleInc.,registered in the U.S. and other countries.
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 7 01.29.2014
Programming Options and Features
Manual Programming HHD Programming•RequiresESNProgrammingInterfaceQSE-CI-AP-D•RequiresApple iPod touch or iPhone mobile digital device
ESNunitsconnectedto1 QSLink
Not more than 1 Multiple (100 QS devices and 100 zone limits apply)
QSMsconnectedto1QSlink Not more than 1 Multiple (100 QS devices limit applies)Wired Occupancy SensorsSystemLimits •4connecteddirectlytoESNunit;
•Upto4wiredtoQSM•Maximumof16occupancysensorsperESN•Upto100totaloccupancysensorsperQSlink(wiredand
wireless)Canbeassignedto… Anyzone(s)ontheESNunit Zones on ESN unit or share to other ESN units on same
QS linkOccupancyDependencySupported
No Yes
Wireless Occupancy SensorsSystemLimits Associate10occupancysensorstoQSM
to control zones on the ESN unit•Maximumof16occupancysensorsperESN•Upto100totaloccupancysensorsperQSlink(wiredand
wireless)Canbeassignedto… Anyzone(s)ontheESNunit Zones on ESN unit or share to other ESN units on same
QS linkOccupancyDependencySupported
No Yes
Wired Daylight SensorsSystemLimits Maximum of 1 daylight sensor per zone
connected directly to the ESN unit or to the QSM
•Maximumof2daylightsensorsperzone;•Upto100totaldaylightsensorsperQSlink(wiredand
wireless)Canbeassignedto… Anyzone(s)ontheESNunit Zones on ESN unit or share to other ESN units on same
QS linkDisabledaylightinginScenes No YesWireless Daylight SensorsSystemLimits •Maximumof1daylightsensorperzone;
•Associatewirelessdaylightsensorstothe QSM
•Maximumof2daylightsensorsperzone;•Associateupto10wirelessdaylightsensorsperQSM;•Upto100totaldaylightsensorsperQSlink(wiredand
wireless)Canbeassignedto… Anyzone(s)ontheESNunit Zones on ESN unit or share to other ESN units on same
QS linkDisabledaylightinginScenes No YesPico® Wireless ControllersSystemLimits Associate10Pico® wireless controllers to
QSM to control zones on the ESN unitUpto100totalcontrolsperQSlink(wiredwallstations,Pico®wirelesscontrollers,IRreceivers)
Canbeassignedto… AnyzoneonthelocalESNunit Zones on ESN unit or share to other ESN units on same QS link
IR Receivers and WallstationsSystemLimits •4connectdirectlytotheESNunit;
•Upto4wiredtotheQSMUpto100totalcontrolsperQSlink(wiredwallstations,Pico®wirelesscontrollers,IRreceivers)
Canbeassignedto… AnyzoneonthelocalESNunit Zones on ESN unit or share to other ESN units on same QS link
Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a801.29.2014
Programming Options and Features (continued)
Manual Programming HHD Programming•RequiresESNProgrammingInterfaceQSE-CI-AP-D•RequiresApple iPod touch or iPhone mobile digital device
NEC® Dry-Contact Switches InputsCanbeassignedto… Anyzone(s)ontheconnectedESN Anyzone(s)ontheconnectedESNContact Closure InputCanbeassignedto… Anyzone(s)ontheESNunit AnyoralllocalESNunitzonesFunctions •Sweeptooff
•Enable/disableafterhours•Turnontopresetandturnoff
•Sweeptooff•Enable/disableafterhours•Turnontopresetandturnoff•Loadshed
AfterhoursConfiguration •Afterhourstimeout:15minutes•Blink-warntimeout:5minutes
Afterhourstimeoutandblink-warntimeoutsareconfigurable
Emergency Contact Closure InputCanbeassignedto… Anyzone(s)ontheESNunit AnyoralllocalESNzonesEmergencyLightlevel Configurable ConfigurableseeTouch® QS wallstationsSceneKeypadsassignedto… Anyzone(s)ontheESNunit Anyzone(s)ononeormoreESNunitsontheQSlinkScene+OffKeypadsassignedto…
Anyzone(s)ontheESNunit Anyzone(s)ononeormoreESNunitsontheQSlink
Zonetogglekeypadbuttonsassignedto…
Anyzone(s)ontheESNunit Anyzone(s)ononormoreESNunitsonthelink
ChangeKeypadtoSceneorZone
Yes Yes
Changingkeypadstoshade,panic,finetune
No Yes
Zone Configuration ParametersLoadtype 0–10, 10–0, or switched 0–10, 10–0, or switchedHigh-endtrim Adjustable AdjustableLow-endtrim Adjustable AdjustableAbsoluteminimumlevel Adjustable AdjustableScenesAvailablescenes Scenes1–16+Off Scenes1–16+OffGRAFIKEye® QS Sharescenes,timeclockevents,afterhours
events, or remote zone mapping to ESN unitsonQSLink
Sharescenes,timeclockevents,afterhoursevents,orremotezonemappingtoESNunitsonQSLink
QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancyQSE-CI-NWK-E Yes Yes
Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 9 01.29.2014
Mechanical DimensionsAlldimensionsshownasin(mm)
0.20 (5.16) Ø
1.22 (30.99)
1.00 (25.40)
11.25 (285.75)
13.25 (336.55)
0.88 (22.35)
9.25 (234.95)
7.50 (190.50)
Donotusesideknockouts
LineVoltageShield
1.66 (42.16)
3.16 (80.26)
1.31 (33.27)
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 10 01.29.2014
Wiring: QS Link
Onlyterminals1,3,and4connected betweendevicesthatsupplyPDUs
Terminal2NEVERconnected betweendevicesthatsupplyPDUs
DevicesthatsupplyPDUs
Devicesthat consumePDUs
COM+24 VMUXMUX
COM
MUXMUX
QSM
QSM QSM
Wired QSKeypad
Wired QSKeypad
Wired QSKeypad
Wired QSKeypad
QSInput/ OutputInterface
QSInput/ OutputInterface
QSLink power supply**
QSLink:noterm
inal2
QSLink:noterm
inal2
QSLink:all4terminals
QSLink:all4terminals
QSLink:all4terminals
All4terminalsconnectedtoQSlink devicesthatconsumePDUs
ESN QS unit
ESN QS unit
Terminal 2 (+24 V) NEVERconnected*
Terminal 2 (+24 V) NEVERconnected*
Terminal 2 (+24 V) NEVERconnected*
QS Link Wiring Rules* Terminal2(+24V)shouldNEVERbeconnectedbetweendevicesthatsupplyPDUs.**ForQSLinkpowersupplywiringconnectiondetails,refertotheinstallationinstructionsforthespecificpowersupplymodelbeingused.
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 11 01.29.2014
Wiring: IEC PELV / NEC® Class 2 Inputs
Blue/Gray**
Black
Red
OccupancySensorDaylight/IRSensor*
IRTransmitter IRTransmitter
Note: Maximum wire run length to each input not to exceed 150 ft (46 m).
IRReceiverorWired Wallstation*
IECPELV/NEC®Class2 Dry-ContactSwitch
Red
Black
Yello
w
20 V: 20 V-
Occ:OccupancySensor
Daylight:DaylightSensor
IR:IRReceiver*
Switch:IECPELV/NEC®Class2
Com:Common
LUTRON
Note: There are four input groups; each group has the same inputs as shown in the diagram below.
Group1shown Group2shown
Whi
teIR
Black
COM
Red
20 V
Input Group Wiring• 20 to12 AWG(0.5 to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in•lb(0.5N•m)
* Note:OnlyoneIRdevicemaybeconnectedperinput.IftheIRsignalfromadaylightsensorisconnected, a wall control may not be connected to the same input, and vice-versa.
**Connectthegraywireon-Rmodeloccupancysensors.
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 12 01.29.2014
Wiring: Contact Closure Inputs (CCI and Emerg)Contact Closure Wiring
• 20to12 AWG(0.5to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in•lb(0.5N•m)
CCI:ContactClosureInput
COM:Common
Emerg: Emergency
COM:Common
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 13 01.29.2014
Wiring: 4 Circuits, Multiple FeedsLoad Wiring
• Two(2)14to12 AWG(2.5to4.0 mm2)• Striplength:3/8 in(8.5 mm)• Torque:7in-lb(0.79N•m)
0–10 V Wiring (QSN-4T20-S)• 20to12 AWG(0.5to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in-lb(0.5N•m)• ConnectonlyIECPELV/NEC®Class2circuitsorconnectonlynon-IEC
PELV/NEC®Class2circuitsto0–10Vzones1–4.• 0–10Vzones1–4arenotisolatedfromeachother.• Negative(–)terminalsarenotinternallyconnectedtoeachother;both
positive (+) and negative (–) connections must be made.• Followallnationalandlocalcodesforseparationrequirements.
Warning. Entrapment / Fire Hazard.Toavoidtheriskofentrapment,seriousinjury,ordeath,thesecontrolsmustnotbeusedtocontrolequipmentwhichisnotvisiblefromeverycontrollocationorwhichcouldcreatehazardoussituationssuchasentrapmentifoperatedaccidentally.Examplesofsuchequipmentwhichmustnotbeoperatedbythesecontrolsinclude(butarenotlimitedto)motorizedgates,industrialdoors,spaceheaters,etc.Itistheinstaller’sresponsibilitytoensurethattheequipmentbeingcontrolledisvisiblefromeverycontrollocationandthatonlysuitableequipmentisconnectedtothesecontrols.Failuretodosocouldresultinseriousinjuryordeath.
DistributionPanel
Neutral
NeutralNeutral
Neutral
Neutral
Ground
Hot
Hot
HotHot
HotHot
Neutral
Neutral Wires
GroundLug
Switc
hedHot(1B)
Switc
hedHot(2
B)
Switc
hedHot(3
B)
Switc
hedHot(4
B)
HotFee
d(1A)
HotFee
d(2A)
HotFee
d(3A)
HotFee
d(4A)
Load
Load
Zone Switching:120–277 V~
0–10 V Zones:(QSN-4T20-S)
0–10 V Wiring(QSN-4T20-S)
Zone 1
Zone 1
+
1A 2A 3A 4A1B 2B 3B 4B
+++
++
++
––
––
––
––
Zone 3
Zone 3
Zone 2
Zone 2
Zone 4
Zone 4
0–10VOutputs
u
u
Attention InstallerAnyreceptaclesthatarecontrolledbyanautomaticcontroldevicemustbemarkedwith“u” located on the controlled receptacle outlet wherevisibleafterinstallationasstatedin2014NEC®Article406.3(E).
Zone 4
Zone 3
Zone 2
Zone 1
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 14 01.29.2014
Wiring: 4 Circuits, Multiple Feeds, 120 V~ Receptacles and 347 V~ LightingLoad Wiring
• Two(2)14to12 AWG(2.5to4.0 mm2)• Striplength:3/8 in(8.5 mm)• Torque:7in-lb(0.79N•m)
0–10 V Wiring (QSN-4T16-S-347)• 20to12 AWG(0.5to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in-lb(0.5N•m)• ConnectonlyIECPELV/NEC®Class2circuitsorconnectonlynon-IEC
PELV/NEC®Class2circuitsto0–10Vzones1–4.• 0–10Vzones1–4arenotisolatedfromeachother.• Negative(–)terminalsarenotinternallyconnectedtoeachother;both
positive (+) and negative (–) connections must be made.• Followallnationalandlocalcodesforseparationrequirements.
Warning. Entrapment / Fire Hazard.Toavoidtheriskofentrapment,seriousinjury,ordeath,thesecontrolsmustnotbeusedtocontrolequipmentwhichisnotvisiblefromeverycontrollocationorwhichcouldcreatehazardoussituationssuchasentrapmentifoperatedaccidentally.Examplesofsuchequipmentwhichmustnotbeoperatedbythesecontrolsinclude(butarenotlimitedto)motorizedgates,industrialdoors,spaceheaters,etc.Itistheinstaller’sresponsibilitytoensurethattheequipmentbeingcontrolledisvisiblefromeverycontrollocationandthatonlysuitableequipmentisconnectedtothesecontrols.Failuretodosocouldresultinseriousinjuryordeath.
120 V~ DistributionPanel
347 V~ DistributionPanel
Attention InstallerAnyreceptaclesthatarecontrolledbyanautomaticcontroldevicemustbemarkedwith“u” located on the controlled receptacle outlet wherevisibleafterinstallationasstatedin2014NEC®Article406.3(E).
Neutral
Neutral
Ground
Ground
Hot
Hot
Hot
Hot
Hot
Neutral
Neutral Wires
GroundLug
Switc
hedHot(1B)
Switc
hedHot(2
B)
Switc
hedHot(3
B)
Switc
hedHot(4
B)
HotFee
d(1A)
HotFee
d(2A)
HotFee
d(3A)
HotFee
d(4A)
Load
Load
Zone Switching:120–347 V~
0–10 V Zones:(QSN-4T16-S-347)
0–10 V Wiring(QSN-4T16-S-347)
Zone 1
Zone 1
+
1A 2A 3A 4A1B 2B 3B 4B
+++
++
++
––
––
––
––
Zone 3
Zone 3
Zone 2
Zone 2
Zone 4
Zone 4
0–10VOutputs
u
u
Zone 4
Zone 3
Zone 2
Zone 1
Voltage BarrierSeparates 120 V~ and 347 V~ asrequiredby2012CanadianElectricalCode,Article12-3030
QSN
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers
369791a 15 01.29.2014
DistributionPanelA
DistributionPanelB
Ground
Hot
Hot
Hot
Ground
Ground
Neutral
Neutral
Neutral
Neutral Wires
GroundLug
Switc
hedHot(1B)
Switc
hedHot(2
B)
Switc
hedHot(3
B)
Switc
hedHot(4
B)
HotFee
d(1A)
Load
Load
Load
Load
Zone Switching:120–277 V~; 347 V~
0–10 V Zones:(QSN-4T20-S)
0–10 V Wiring(QSN-4T20-S)
Wiring: 4 Circuits, Single FeedLoad Wiring
• Two(2)14to12 AWG(2.5to4.0 mm2)• Striplength:3/8 in(8.5 mm)• Torque:7in-lb(0.79N•m)
0–10 V Wiring (QSN-4T20-S)• 20to12 AWG(0.5to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in-lb(0.5N•m)• ConnectonlyIECPELV/NEC®Class2circuitsorconnectonlynon-IEC
PELV/NEC®Class2circuitsto0–10Vzones1–4.• 0–10Vzones1–4arenotisolatedfromeachother.• Negative(–)terminalsarenotinternallyconnectedtoeachother;both
positive (+) and negative (–) connections must be made.• Followallnationalandlocalcodesforseparationrequirements.
Zone 1
Zone 3
Zone 2
Zone 4
Zone 1
1A 2A 3A 4A1B 2B 3B 4BZone
3Zone
2Zone
4
++
++
++
++
––
––
––
––
0–10VOutputs
Recommended