QSN ® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers 369791a 1 01.29.2014 Energi Savr NodeTM for 0–10 V Energi Savr NodeTM with Softswitch® The Energi Savr NodeTM (ESN) family is a group of modular products for the control of lighting, receptacles, and other loads. This document describes the following products: • Energi Savr NodeTM for 0–10 V (models QSN-4T20-S, QSN-4T16-S-347) • Energi Savr NodeTM with Softswitch® (models QSN-4S20-S, QSN-4S16-S-347) Features • Rated to switch 20 A receptacles with any output. • Default configuration requires no commissioning. • Program using integral interface on the ESN unit. • Four occupancy sensor inputs for automated control of loads in 4 zones. • Four daylight sensor inputs automatically adjust light levels based on the amount of natural light entering through the windows. • Four IR receiver inputs for personal control. • Four inputs for IEC PELV/NEC® Class 2 dry-contact switches. • Includes QS control link for seamless integration of loads, control stations, and QS sensor modules. • Patented Softswitch® circuit eliminates arcing at mechanical contacts when loads are switched, prolonging relay life to an average of 1,000,000 cycles at 16 A. • Contact Lutron for compatibility with a Quantum® system. System Example QSN-4T20-S QSN-4T20-S Control Power 120–277 V~ 4 Load Input Feeds 120–277 V~ ; 347 V~ 1 4 0–10 V Channels (QSN-4T20-S; QSN-4T16-S-347 only) 4 Switched-Load Outputs (20 A Softswitch® 120–277 V~ ; 347 V~ 1 ) Wired Daylight Sensors (up to 4) 2,3 Wired Occupancy Sensors (up to 4) 2 Wired Wallstation or IR Receivers (up to 4) 2 IR Transmitter IR Transmitter QS link Emergency Contact Closure Input Contact Closure Input Wired Daylight Sensors (up to 4) 3 Wired Occupancy Sensors (up to 4) Wired Wallstation or IR receivers (up to 4) IEC PELV/NEC® Class 2 Dry-Contact Switch (up to 4) (by others) seeTouch® QS Wallstation Wireless Communication OR OR OR OR QSM ESN Programming Interface Radio Powr SavrTM Occupancy Sensor (up to 10 per QSM) Radio Powr SavrTM Daylight Sensor (up to 10 per QSM) 3 Pico® Wireless Controller (up to 10 per QSM) Notes 1 For 347 V~ models only. 2 Up to 4 wired devices total (of any type). 3 The maximum number of daylight sensors (wired and wireless) that an ESN unit can support is four (1 per zone).

Energi Savr Node for 0-10 V/Softswitch (SPEC) 369791 · • Associate additional QSMs and sensors/controls with ESN unit when programming with an Apple iPod touch or iPhone. Refer

Embed Size (px)

Citation preview

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 1 01.29.2014

Energi Savr NodeTM for 0–10 V Energi Savr NodeTM with Softswitch®

The Energi Savr NodeTM (ESN) family is a group of modular products for the control of lighting, receptacles, and other loads. This document describes the following products:

•EnergiSavrNodeTM for 0–10 V (models QSN-4T20-S, QSN-4T16-S-347)

•EnergiSavrNodeTM with Softswitch® (models QSN-4S20-S, QSN-4S16-S-347)

Features•Ratedtoswitch20Areceptacleswithanyoutput.•Defaultconfigurationrequiresnocommissioning.•ProgramusingintegralinterfaceontheESNunit.•Fouroccupancysensorinputsforautomatedcontrolofloadsin

4 zones.•Fourdaylightsensorinputsautomaticallyadjustlightlevelsbased

on the amount of natural light entering through the windows.•FourIRreceiverinputsforpersonalcontrol.•FourinputsforIECPELV/NEC®Class2dry-contactswitches.•IncludesQScontrollinkforseamlessintegrationofloads,control

stations, and QS sensor modules.•PatentedSoftswitch® circuit eliminates arcing at mechanical

contacts when loads are switched, prolonging relay life to an averageof1,000,000cyclesat16A.

•ContactLutronforcompatibilitywithaQuantum® system.

System Example

QSN-4T20-SQSN-4T20-S

QSN-4T20-S

ControlPower120–277 V~

4LoadInputFeeds120–277 V~ ; 347 V~1

40–10VChannels(QSN-4T20-S; QSN-4T16-S-347 only)

4Switched-LoadOutputs (20ASoftswitch® 120–277 V~ ; 347 V~1)

Wired DaylightSensors

(up to 4)2,3

Wired OccupancySensors

(up to 4)2

Wired WallstationorIRReceivers

(up to 4)2IR

Transmitter

IRTransmitter

QSlink

Emergency ContactClosureInput

ContactClosureInput

WiredDaylightSensors(upto4)3

WiredOccupancySensors(upto4)

WiredWallstationorIRreceivers(upto4)

IECPELV/NEC®Class2Dry-ContactSwitch (up to 4) (by others)

seeTouch® QS Wallstation

WirelessCommunication

OR

OR

OR

OR

QSMESN

ProgrammingInterface

RadioPowrSavrTM OccupancySensor(up to 10 per QSM)

RadioPowrSavrTM DaylightSensor (up to 10 per QSM)3

Pico® WirelessController (up to 10 per QSM)

Notes1 For347V~ models only.2 Up to 4 wired devices total (of any type).3 The maximum number of daylight

sensors (wired and wireless) that an ESN unit can support is four (1 per zone).

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 2 01.29.2014

Specifications

Power•ControlPower:120V~; 220–240 V~;

277 V~50/60 Hz•LightningstrikeprotectionmeetsANSI/IEEEstandard62.41-1991.Canwithstandvoltagesurgesofupto6000 V~andcurrentsurgesofupto3000A

•Currentdraw:0.5 Amax•10-yearpowerfailurememory:restoreslightingto

levels prior to power interruption•Latchingrelayskeeppreviouslyilluminatedzoneson

when control power feed is lost

Regulatory Approvals•ULListed•CSA•LutronQualitySystemsregisteredtoISO9001:2008

Environment•AmbientTemperatureOperatingRange:32 ºFto104 ºF(0 ºCto40 ºC)

•Relativehumidity:lessthan90%non-condensing•Forindooruseonly•MeetsNEC®requirementsforinstallationin“other

space used for environmental air”

Terminal Wiring•ControlPowerWiring:14 to12 AWG(2.5to4.0 mm2)•LoadWiring:14 to12 AWG(2.5 to4.0 mm2)•0–10VWiring:20 to12 AWG(0.5 to4.0 mm2)•InputGroupWiring:20 to12 AWG(0.5 to4.0 mm2);

maximum wire run length to each input not to exceed 150 ft(46 m)

•QSLinkWiring:22 to12 AWG(0.5 to4.0 mm2)•ContactClosureWiring:20 to12 AWG(0.5 o4.0 mm2)

Physical Design and Mounting•NEMAType 1,IP-20protection•Surface-mount

Load Types (relay ratings)•Ratedtocontrol20 Areceptacleswithanyoutput.•WhenusingtheEnergiSavrNodeTM to control

receptacles, it may be used with, but is not limited to, the following:– Monitors–Fans–Humidifiers–Printers

Note:Refertothemanufacturer’sguidelinesforacceptable switching methods.

•WhenusingtheEnergiSavrNodeTM to control receptacles,itmayNOTbesuitableforusewithdevicesthatrequireanyofthefollowing:– Shut-down process before power is interrupted,

such as computers.–Cool-downprocessbeforepowerisinterrupted,suchasprojectors.

–Programming,suchasclocksorDVRs.–Longwarm-upcycle.

•Not for use with loads that present a hazard if automatically energized (e.g., heaters).

•Anyreceptaclesthatarecontrolledbyanautomaticcontrol device must be markedwith“u” located on the controlled receptacle outlet where visible after installationasstatedin2014NEC®Article406.3(E).

Load Type

Relay Ratings120 – 277 V~

QSN-4S20-SQSN-4T20-S

347 V~QSN-4S16-S-347QSN-4T16-S-347

Tungsten 20A 16AACGeneralUse 20A 16AElectricDischargeLamp 16A 16AElectric Ballast (NEMA410) 16A 16A

Resistive 20A 16AInductive 20A 16A

Motor 1.0HP120V~2.0HP277V~ —

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 3 01.29.2014

Specifications

Input Default Associations

Inputs/Outputs Zone 1 Zone 2 Zone 3 Zone 4

Group1

Occ XPhoto XIR XSwitch X

Group2

Occ XPhoto XIR XSwitch X

Group3

Occ XPhoto XIR XSwitch X

Group4

Occ XPhoto XIR XSwitch XCCI X X X XEmergencyCCI X X X X

Softswitch® 120 – 277 V~

•Softswitch®relayisratedfor20 Acontinuoususeperchannel.

•Relayismechanicallyheld.

0–10 V Output Ratings (QSN-4T20-S)•Eachoutputsinksupto50 mAmaximum.•Eachoutputsinkscurrentonly(loaddevicemustprovide10 Vsupply).

•ProvidesanIECPELV/NEC®Class 2isolated0–10 VoutputsignalthatconformstoIEC60929.

Occupancy Sensors•Upto16occupancysensorscanbeprogrammedto

the Energi Savr NodeTM device.•ManualProgramming:upto4occupancysensors

wired directly to the Energi Savr NodeTM device, up to 4 occupancy sensors wired to a QS Sensor Module (QSM), and up to 10 wireless occupancy sensors through the same QSM; the total programmed to the Energi Savr NodeTM device cannot exceed 16.

•HHD(iPod/iPhone)Programming:upto16occupancysensors from any source (wired directly to the Energi Savr NodeTM device, wired to any other Energi Savr NodeTMdevice,orwired/wirelessfromanyQSMontheQSlink);thetotalprogrammedtotheEnergiSavrNodeTM device cannot exceed 16.

•UseLutron® occupancy sensors to control one or more zones.

•Lutron® occupancy sensors can be programmed to automatically turn on the lights and receptacles in an area when it becomes occupied and turn off the lights lights and receptacles in an area after it becomes vacant.

•Forspacesthatrequirevacancymodeoperationfor lights, a single occupancy sensor can control a zone of lights in vacancy mode and control a zone of receptacles in occupancy mode.

•EachofthefouroccupancyinputscanpoweroneLutron® occupant sensor.

•Eacharea’soccupiedsceneandunoccupiedscenecan be programmed independently.

•Occupancysensormustprovideadry-contactclosureor solid-state output.

•AdditionaloccupancysensorscanbeusedwiththeEnergi Savr NodeTMdevice.Refertothe“ProgrammingOptionsandFeatures”tableforsystemrules.

Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 4 01.29.2014

Daylight Sensors•Lutron® daylight sensors allow daylight harvesting with

programmable effect on light output.•Fourdaylightsensorscanbeconnecteddirectlytothe

ESN unit.•UseLutron®EC-DIR-WHsensorstocontroloneor

more zones.•Alternatively,upto4sensors(Lutron® wired daylight sensorsorRadioPowrSavrTM daylight sensors) can be assigned when associated with a QSM.

•ThemaximumnumberofLutron® daylight sensors (wired or wireless), either wired directly to the unit or indirectly (associated with a QSM) cannot exceed 4.

•AssociateadditionalQSMsandsensors/controlswith ESN unit when programming with an Apple iPod touch or iPhone.Referto“ProgrammingOptions”section for details.

Contact Closure Input (CCI)•Activatescenesusingmomentaryormaintainedclosuresfromanexternaldevicesuchasatimeclock.

•StartorstopAfterhoursModeusingamaintainedclosure.

•Theattacheddevicemustprovideadry-contactclosure or solid-state output.

•ConfigurableforNormally-Open(NO)orNormally-Closed(NC)operation.

•Inputismiswire-protectedupto36V-.

Specifications (continued)

seeTouch® QS Controls•seeTouch®QSwallstationscanbeconfiguredto

control ESN unit scenes or zones.•Inzonetogglemode,zonebuttonscanbeassignedto

one or more zones on any ESN unit connected to the QSLink.

•Inscenemode,wallstationscanbeassignedtooneormore ESN unitsconnectedtotheQSLink.

•LEDindicatordisplayszoneorscenestatus.Table 1: seeTouch® QS Wallstation Configurations

# ButtonsWallstation Function 1 2 3 5 7

Zone Toggle Scene 1,Off(toggle) 1,Off 1,2,Off 1–4,Off N/A

IR Wallstation or Receiver Input•FourinputsforIRreceiversorwallstationsforcontrol

of lighting zones can be connected directly to the ESN unit

•UseLutron®Pico®wiredcontrolorCC-4BRL-WHwallstation to control one or more zones.

•UseLutron® EC-DIR-WHorEC-IR-WHceiling-mountsensors to control one or more zones.

•UptofouradditionalwiredwallstationsorIRreceiverscan be assigned when associated with a QSM.

•AssociateadditionalQSMsandsensors/controlswith ESN unit when programming with an Apple iPod touch or iPhone.Referto“ProgrammingOptions”section for details.

Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 5 01.29.2014

IEC PELV / NEC® Class 2 Dry-Contact Switches•FourinputsforIECPELV/NEC®Class2dry-contact

switches can be assigned to turn on and off one or more zones.

•Configureformomentaryormaintainedoperation.

QS Link Limits•EachESN unitcanprovideupto14PowerDrawUnits(PDUs)forotherQSdevices.RefertotheQSLinkPowerDrawUnitspecificationsubmittal(Lutron® P/N 369405)formoreinformationconcerningPDUs.

•TheQSLinkcanhaveupto100devicesand100 zones.

•EachESN unit counts as 1 device towards the 100 devicelimit.

•EachESN unit counts as 4 zones towards the 100 zonelimit.

QSM (QS Sensor Module)•UsetheQSMtointegrateRadioPowrSavrTM occupancysensors,RadioPowrSavrTM daylight sensors,andPico® wireless controllers to control zones on the ESN unit.

•Associate1QSMperESN unit with manual programming.

•AssociatemultipleQSMsperESN unit with Apple iPod touch or iPhoneprogramming(requiresQSE-CI-AP-DandWi-Firouter).See“ProgrammingOptions”fordetails.

•Assignupto10RadioPowrSavrTM occupancy sensors per ESN unit via QSM.

•Assignupto4RadioPowrSavrTM daylight sensors per ESN unit via QSM.

•Assignupto10Pico® wireless controllers per ESN unit via QSM.

•ThesensorsandPico® wireless controllers associated withtheQSMshouldbemountedwithin60ft(18m)line of sight, or 30 ft (9 m) through walls, of the QSM.

•Wireandpowerupto4wiredsensorsperQSM–DaylightSensors–OccupancySensors–Infrared(IR)ReceiversorWallstations

•RefertoQSMSpecificationSubmittalformoreinformation.

Specifications (continued)

Emergency Contact Closure Input•Bydefault,contactclosureinputfromLutron® EmergencyLightingInterface(LUT-ELI-3PH),security,orfirealarmsystemsturnsallzonesontofulloutputwhen emergency state is detected.

•Emergencycontactclosureinputisnormallyclosed(NC).TheESN unitisshippedwithajumperpre-installed.

•Responseofeachzoneisconfigurable.•Attacheddevices,bydefault,willgotomaximum

output and ignore control inputs.•Nooperationswillbealloweduntilemergencysignalis

cleared.•Theattacheddevicemustprovideadry-contact

closure or solid-state output.•Inputismiswire-protectedupto36V-.•EmergencyCCIcannotcontrolotherESNunits.

Functionality with GRAFIK Eye® QS•ESN unitfollowsGRAFIKEye® QS scene activations whenassociatedwiththeGRAFIKEye® QS.

•ESN unit responds to commands initiated by the GRAFIKEye® QS astronomictimeclockwhenassociatedwiththeGRAFIKEye® QS.

•ESN unit operates in afterhours mode when associatedwithaGRAFIKEye® QS that is in afterhours mode.

Functionality with QSE-IO•ESN unit responds to scene commands initiated by theQSE-IOiftheQSE-IODIPswitcheshavebeensetto either scene selection mode, zone toggle mode, partition mode, or occupancy sensor mode.

Functionality with QSE-CI-NWK-E•IntegrateESN unitwithtouchscreens,PCs,A/V

systems, or other digital systems and devices.•Recallscenesandset/adjustzonelevels.

Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 6 01.29.2014

•Wirelessroutermayberemovedfornormaloperation.•EthernetconnectionmaybemadeviaanESNProgrammingInterface(QSE-CI-AP-D)oranESNQSunitwithintegralEthernetjack.

•LutronrecommendsthatanESNProgrammingInterface(orESNQSunitwithEthernetjack)bewiredtoanEthernetjackinthespaceforeaseofaccessand proximity to power for the wireless router.

•Workswithanystandardwirelessrouterthatsupportsmulticastpackets.

•Apple iPod touch or iPhone can program all ESN QS unitsconnectedtoanESNProgrammingInterfaceviatheQSLink(exceptwhenpartofaQuantum® system).

•ESNappisrequiredandisavailablefromtheApple iTunes Storeonlinemarketplace.

Programming Options

Manual Programming•UsebuttonsonthefrontoftheESNunit.•UsemanualprogrammingininstallationswithonlyoneESNunitandwithoneQSMorfewerontheQSlink.

HHD Programming•RequiresESNProgrammingInterface(QSE-CI-AP-D).•RequiresApple iPod touch or iPhone mobile digital

device.•Usetheintuitiveprogrammingapplicationforthe

Apple iPod touch or iPhone to program systems with multipleESNunitsandQSMsontheQSlink.

•WirelessrouterrequiredforprogrammingwithanApple iPod touch or iPhone only.

QSLink

QSLink

QSM QSM QSM

ESN Unit ESN Unit ESN Unit

Apple iPod touch or iPhone mobile digital device

WirelessRouter (by others)

ESNProgrammingInterface QSE-CI-AP-D

DedicatedEthernetConnectionfor ESN units1,2

1 StandardCAT5/CAT5Ecable:Totallengthnottoexceed300ft(100m)2 Note:ESNunitsarenotdesignedtoexistonanopennetwork.Connectiontoanopennetwork

could result in reduced performance and Ethernet connectivity issues.

Apple,iPhone,iPodtouch,andiTunesStorearetrademarksofAppleInc.,registered in the U.S. and other countries.

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 7 01.29.2014

Programming Options and Features

Manual Programming HHD Programming•RequiresESNProgrammingInterfaceQSE-CI-AP-D•RequiresApple iPod touch or iPhone mobile digital device

ESNunitsconnectedto1 QSLink

Not more than 1 Multiple (100 QS devices and 100 zone limits apply)

QSMsconnectedto1QSlink Not more than 1 Multiple (100 QS devices limit applies)Wired Occupancy SensorsSystemLimits •4connecteddirectlytoESNunit;

•Upto4wiredtoQSM•Maximumof16occupancysensorsperESN•Upto100totaloccupancysensorsperQSlink(wiredand

wireless)Canbeassignedto… Anyzone(s)ontheESNunit Zones on ESN unit or share to other ESN units on same

QS linkOccupancyDependencySupported

No Yes

Wireless Occupancy SensorsSystemLimits Associate10occupancysensorstoQSM

to control zones on the ESN unit•Maximumof16occupancysensorsperESN•Upto100totaloccupancysensorsperQSlink(wiredand

wireless)Canbeassignedto… Anyzone(s)ontheESNunit Zones on ESN unit or share to other ESN units on same

QS linkOccupancyDependencySupported

No Yes

Wired Daylight SensorsSystemLimits Maximum of 1 daylight sensor per zone

connected directly to the ESN unit or to the QSM

•Maximumof2daylightsensorsperzone;•Upto100totaldaylightsensorsperQSlink(wiredand

wireless)Canbeassignedto… Anyzone(s)ontheESNunit Zones on ESN unit or share to other ESN units on same

QS linkDisabledaylightinginScenes No YesWireless Daylight SensorsSystemLimits •Maximumof1daylightsensorperzone;

•Associatewirelessdaylightsensorstothe QSM

•Maximumof2daylightsensorsperzone;•Associateupto10wirelessdaylightsensorsperQSM;•Upto100totaldaylightsensorsperQSlink(wiredand

wireless)Canbeassignedto… Anyzone(s)ontheESNunit Zones on ESN unit or share to other ESN units on same

QS linkDisabledaylightinginScenes No YesPico® Wireless ControllersSystemLimits Associate10Pico® wireless controllers to

QSM to control zones on the ESN unitUpto100totalcontrolsperQSlink(wiredwallstations,Pico®wirelesscontrollers,IRreceivers)

Canbeassignedto… AnyzoneonthelocalESNunit Zones on ESN unit or share to other ESN units on same QS link

IR Receivers and WallstationsSystemLimits •4connectdirectlytotheESNunit;

•Upto4wiredtotheQSMUpto100totalcontrolsperQSlink(wiredwallstations,Pico®wirelesscontrollers,IRreceivers)

Canbeassignedto… AnyzoneonthelocalESNunit Zones on ESN unit or share to other ESN units on same QS link

Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a801.29.2014

Programming Options and Features (continued)

Manual Programming HHD Programming•RequiresESNProgrammingInterfaceQSE-CI-AP-D•RequiresApple iPod touch or iPhone mobile digital device

NEC® Dry-Contact Switches InputsCanbeassignedto… Anyzone(s)ontheconnectedESN Anyzone(s)ontheconnectedESNContact Closure InputCanbeassignedto… Anyzone(s)ontheESNunit AnyoralllocalESNunitzonesFunctions •Sweeptooff

•Enable/disableafterhours•Turnontopresetandturnoff

•Sweeptooff•Enable/disableafterhours•Turnontopresetandturnoff•Loadshed

AfterhoursConfiguration •Afterhourstimeout:15minutes•Blink-warntimeout:5minutes

Afterhourstimeoutandblink-warntimeoutsareconfigurable

Emergency Contact Closure InputCanbeassignedto… Anyzone(s)ontheESNunit AnyoralllocalESNzonesEmergencyLightlevel Configurable ConfigurableseeTouch® QS wallstationsSceneKeypadsassignedto… Anyzone(s)ontheESNunit Anyzone(s)ononeormoreESNunitsontheQSlinkScene+OffKeypadsassignedto…

Anyzone(s)ontheESNunit Anyzone(s)ononeormoreESNunitsontheQSlink

Zonetogglekeypadbuttonsassignedto…

Anyzone(s)ontheESNunit Anyzone(s)ononormoreESNunitsonthelink

ChangeKeypadtoSceneorZone

Yes Yes

Changingkeypadstoshade,panic,finetune

No Yes

Zone Configuration ParametersLoadtype 0–10, 10–0, or switched 0–10, 10–0, or switchedHigh-endtrim Adjustable AdjustableLow-endtrim Adjustable AdjustableAbsoluteminimumlevel Adjustable AdjustableScenesAvailablescenes Scenes1–16+Off Scenes1–16+OffGRAFIKEye® QS Sharescenes,timeclockevents,afterhours

events, or remote zone mapping to ESN unitsonQSLink

Sharescenes,timeclockevents,afterhoursevents,orremotezonemappingtoESNunitsonQSLink

QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancyQSE-CI-NWK-E Yes Yes

Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 9 01.29.2014

Mechanical DimensionsAlldimensionsshownasin(mm)

0.20 (5.16) Ø

1.22 (30.99)

1.00 (25.40)

11.25 (285.75)

13.25 (336.55)

0.88 (22.35)

9.25 (234.95)

7.50 (190.50)

Donotusesideknockouts

LineVoltageShield

1.66 (42.16)

3.16 (80.26)

1.31 (33.27)

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 10 01.29.2014

Wiring: QS Link

Onlyterminals1,3,and4connected betweendevicesthatsupplyPDUs

Terminal2NEVERconnected betweendevicesthatsupplyPDUs

DevicesthatsupplyPDUs

Devicesthat consumePDUs

COM+24 VMUXMUX

COM

MUXMUX

QSM

QSM QSM

Wired QSKeypad

Wired QSKeypad

Wired QSKeypad

Wired QSKeypad

QSInput/ OutputInterface

QSInput/ OutputInterface

QSLink power supply**

QSLink:noterm

inal2

QSLink:noterm

inal2

QSLink:all4terminals

QSLink:all4terminals

QSLink:all4terminals

All4terminalsconnectedtoQSlink devicesthatconsumePDUs

ESN QS unit

ESN QS unit

Terminal 2 (+24 V) NEVERconnected*

Terminal 2 (+24 V) NEVERconnected*

Terminal 2 (+24 V) NEVERconnected*

QS Link Wiring Rules* Terminal2(+24V)shouldNEVERbeconnectedbetweendevicesthatsupplyPDUs.**ForQSLinkpowersupplywiringconnectiondetails,refertotheinstallationinstructionsforthespecificpowersupplymodelbeingused.

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 11 01.29.2014

Wiring: IEC PELV / NEC® Class 2 Inputs

Blue/Gray**

Black

Red

OccupancySensorDaylight/IRSensor*

IRTransmitter IRTransmitter

Note: Maximum wire run length to each input not to exceed 150 ft (46 m).

IRReceiverorWired Wallstation*

IECPELV/NEC®Class2 Dry-ContactSwitch

Red

Black

Yello

w

20 V: 20 V-

Occ:OccupancySensor

Daylight:DaylightSensor

IR:IRReceiver*

Switch:IECPELV/NEC®Class2

Com:Common

LUTRON

Note: There are four input groups; each group has the same inputs as shown in the diagram below.

Group1shown Group2shown

Whi

teIR

Black

COM

Red

20 V

Input Group Wiring• 20 to12 AWG(0.5 to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in•lb(0.5N•m)

* Note:OnlyoneIRdevicemaybeconnectedperinput.IftheIRsignalfromadaylightsensorisconnected, a wall control may not be connected to the same input, and vice-versa.

**Connectthegraywireon-Rmodeloccupancysensors.

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 12 01.29.2014

Wiring: Contact Closure Inputs (CCI and Emerg)Contact Closure Wiring

• 20to12 AWG(0.5to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in•lb(0.5N•m)

CCI:ContactClosureInput

COM:Common

Emerg: Emergency

COM:Common

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 13 01.29.2014

Wiring: 4 Circuits, Multiple FeedsLoad Wiring

• Two(2)14to12 AWG(2.5to4.0 mm2)• Striplength:3/8 in(8.5 mm)• Torque:7in-lb(0.79N•m)

0–10 V Wiring (QSN-4T20-S)• 20to12 AWG(0.5to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in-lb(0.5N•m)• ConnectonlyIECPELV/NEC®Class2circuitsorconnectonlynon-IEC

PELV/NEC®Class2circuitsto0–10Vzones1–4.• 0–10Vzones1–4arenotisolatedfromeachother.• Negative(–)terminalsarenotinternallyconnectedtoeachother;both

positive (+) and negative (–) connections must be made.• Followallnationalandlocalcodesforseparationrequirements.

Warning. Entrapment / Fire Hazard.Toavoidtheriskofentrapment,seriousinjury,ordeath,thesecontrolsmustnotbeusedtocontrolequipmentwhichisnotvisiblefromeverycontrollocationorwhichcouldcreatehazardoussituationssuchasentrapmentifoperatedaccidentally.Examplesofsuchequipmentwhichmustnotbeoperatedbythesecontrolsinclude(butarenotlimitedto)motorizedgates,industrialdoors,spaceheaters,etc.Itistheinstaller’sresponsibilitytoensurethattheequipmentbeingcontrolledisvisiblefromeverycontrollocationandthatonlysuitableequipmentisconnectedtothesecontrols.Failuretodosocouldresultinseriousinjuryordeath.

DistributionPanel

Neutral

NeutralNeutral

Neutral

Neutral

Ground

Hot

Hot

HotHot

HotHot

Neutral

Neutral Wires

GroundLug

Switc

hedHot(1B)

Switc

hedHot(2

B)

Switc

hedHot(3

B)

Switc

hedHot(4

B)

HotFee

d(1A)

HotFee

d(2A)

HotFee

d(3A)

HotFee

d(4A)

Load

Load

Zone Switching:120–277 V~

0–10 V Zones:(QSN-4T20-S)

0–10 V Wiring(QSN-4T20-S)

Zone 1

Zone 1

+

1A 2A 3A 4A1B 2B 3B 4B

+++

++

++

––

––

––

––

Zone 3

Zone 3

Zone 2

Zone 2

Zone 4

Zone 4

0–10VOutputs

u

u

Attention InstallerAnyreceptaclesthatarecontrolledbyanautomaticcontroldevicemustbemarkedwith“u” located on the controlled receptacle outlet wherevisibleafterinstallationasstatedin2014NEC®Article406.3(E).

Zone 4

Zone 3

Zone 2

Zone 1

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 14 01.29.2014

Wiring: 4 Circuits, Multiple Feeds, 120 V~ Receptacles and 347 V~ LightingLoad Wiring

• Two(2)14to12 AWG(2.5to4.0 mm2)• Striplength:3/8 in(8.5 mm)• Torque:7in-lb(0.79N•m)

0–10 V Wiring (QSN-4T16-S-347)• 20to12 AWG(0.5to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in-lb(0.5N•m)• ConnectonlyIECPELV/NEC®Class2circuitsorconnectonlynon-IEC

PELV/NEC®Class2circuitsto0–10Vzones1–4.• 0–10Vzones1–4arenotisolatedfromeachother.• Negative(–)terminalsarenotinternallyconnectedtoeachother;both

positive (+) and negative (–) connections must be made.• Followallnationalandlocalcodesforseparationrequirements.

Warning. Entrapment / Fire Hazard.Toavoidtheriskofentrapment,seriousinjury,ordeath,thesecontrolsmustnotbeusedtocontrolequipmentwhichisnotvisiblefromeverycontrollocationorwhichcouldcreatehazardoussituationssuchasentrapmentifoperatedaccidentally.Examplesofsuchequipmentwhichmustnotbeoperatedbythesecontrolsinclude(butarenotlimitedto)motorizedgates,industrialdoors,spaceheaters,etc.Itistheinstaller’sresponsibilitytoensurethattheequipmentbeingcontrolledisvisiblefromeverycontrollocationandthatonlysuitableequipmentisconnectedtothesecontrols.Failuretodosocouldresultinseriousinjuryordeath.

120 V~ DistributionPanel

347 V~ DistributionPanel

Attention InstallerAnyreceptaclesthatarecontrolledbyanautomaticcontroldevicemustbemarkedwith“u” located on the controlled receptacle outlet wherevisibleafterinstallationasstatedin2014NEC®Article406.3(E).

Neutral

Neutral

Ground

Ground

Hot

Hot

Hot

Hot

Hot

Neutral

Neutral Wires

GroundLug

Switc

hedHot(1B)

Switc

hedHot(2

B)

Switc

hedHot(3

B)

Switc

hedHot(4

B)

HotFee

d(1A)

HotFee

d(2A)

HotFee

d(3A)

HotFee

d(4A)

Load

Load

Zone Switching:120–347 V~

0–10 V Zones:(QSN-4T16-S-347)

0–10 V Wiring(QSN-4T16-S-347)

Zone 1

Zone 1

+

1A 2A 3A 4A1B 2B 3B 4B

+++

++

++

––

––

––

––

Zone 3

Zone 3

Zone 2

Zone 2

Zone 4

Zone 4

0–10VOutputs

u

u

Zone 4

Zone 3

Zone 2

Zone 1

Voltage BarrierSeparates 120 V~ and 347 V~ asrequiredby2012CanadianElectricalCode,Article12-3030

QSN

® Specif icat ion Submittal page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM 0–10 V/Softswitch® 20 A Receptacle/Fixture Controllers

369791a 15 01.29.2014

DistributionPanelA

DistributionPanelB

Ground

Hot

Hot

Hot

Ground

Ground

Neutral

Neutral

Neutral

Neutral Wires

GroundLug

Switc

hedHot(1B)

Switc

hedHot(2

B)

Switc

hedHot(3

B)

Switc

hedHot(4

B)

HotFee

d(1A)

Load

Load

Load

Load

Zone Switching:120–277 V~; 347 V~

0–10 V Zones:(QSN-4T20-S)

0–10 V Wiring(QSN-4T20-S)

Wiring: 4 Circuits, Single FeedLoad Wiring

• Two(2)14to12 AWG(2.5to4.0 mm2)• Striplength:3/8 in(8.5 mm)• Torque:7in-lb(0.79N•m)

0–10 V Wiring (QSN-4T20-S)• 20to12 AWG(0.5to4.0 mm2)• Striplength:1/4 in(6 mm)• Torque:5in-lb(0.5N•m)• ConnectonlyIECPELV/NEC®Class2circuitsorconnectonlynon-IEC

PELV/NEC®Class2circuitsto0–10Vzones1–4.• 0–10Vzones1–4arenotisolatedfromeachother.• Negative(–)terminalsarenotinternallyconnectedtoeachother;both

positive (+) and negative (–) connections must be made.• Followallnationalandlocalcodesforseparationrequirements.

Zone 1

Zone 3

Zone 2

Zone 4

Zone 1

1A 2A 3A 4A1B 2B 3B 4BZone

3Zone

2Zone

4

++

++

++

++

––

––

––

––

0–10VOutputs