Trane EarthWise Air Systems 2014

1

EarthWise Air Systems

An Introduction to

High Performance HVAC Air Systems

Simon Ho – IR CSe: Simon.Ho@irco.com

www.trane.com

3

AirsideEnergy Recovery

Trane EarthWise Air Systems 2014

2

4

Airside Energy Recovery (ER)

• Why Recover Energy ?

– A method of improving system efficiency using the exhaust air stream

– Exhaust air is a major energy recovery heat sink

• BCA requires the use of ‘energy reclaim system’ when

– OA quantity is > 1.2x of code minimum per AS1668.2 (e.g. Code min OA for offices is 10 L/s/person)

– Crowded areas with less than 1m2/person (e.g. cafe, restaurants, auditoriums) with OA exceeding 1,000 L/s

� alternately use demand controlled ventilation (DCV)

5

Code and Trends

• Demand for increasing airflow rates for IAQ - increases

energy consumption, e.g. Green Star IEQ-1 awards

• 1 credit for 50% over code minimum

• 2 credits for 100% over code minimum

• 3 credits for 150% over code minimum

• Airside system design has evolved from floor by floor

AHUs to central plants serving facade zones

– Efficiency in zoning, minimizes reheat

– OA and EA path proximity makes ER more feasible

• Integrated Controls Makes it Easy

– Optimize using HVAC equipment with unit mounted controls

Trane EarthWise Air Systems 2014

3

6

Air-to-Air EROA Pre-conditioning

EAEA

OAOA

Heat

Exch

an

ge

Recovered energy to pre-cool or preheat

Sensible ortotal energy

7

drydry--bulb temperaturebulb temperature

hu

mid

ity ra

tioh

um

idity

ratioRARA

OAOA

sensibleenergy recovery

OA'OA'

RA’RA’

Trane EarthWise Air Systems 2014

4

8

drydry--bulb temperaturebulb temperature

hu

mid

ity ra

tioh

um

idity

ratio

OA'OA'

RARA

OAOA

totalenergy recovery

9

ER Effectiveness

Sensible effectiveness

Total effectiveness

εεεε = ××(T1 – T2)

(T1 – T3)ρρρρmin ×× Vmin

ρρρρs ×× Vs

εεεε = ××(h1 – h2)

(h1 – h3)ρρρρmin ×× Vmin

ρρρρs ×× Vs

airair--toto--airairheat exchangerheat exchanger

XX44

supply side

XX33

XX22XX11

exhaust side

ρρρρs ×× Vs

ρρρρmin ×× Vmin

Trane EarthWise Air Systems 2014

5

10

SASA

“series”energy transfer

coolingcoolingcoilcoil

RARA

SASA

“parallel” energy recovery

coolingcoolingcoilcoil

Air-to-Air ERSupply Air Tempering (reheat after Dehum)

Recovered heat used for reheat

11

OA Treatment Comparison

• Dedicated OA System (DOAS)

• Compare ER types: cool-reheat, RAC, EW, CDQ for

OA treatment

• OA 5,000 L/s @ 32/26°C

• RA 4,500 L/s @ 25°C/50% RH

• Required SA @ 18°C, 7 g/kg (8.7°CDP)

– Dependent on internal air system type, design RH% and latent load requirements

– Cooler SA contributes to sensible cooling; warmer SA requires more reheat

– Consider part load

Trane EarthWise Air Systems 2014

6

12

DOAS: Cool Reheat

EAEA

OAOA

RARA

SASA

5 5 mm33/s/s

4.5 4.5 mm33/s/s25°C/50%RH

32/26°C

18°C, 7g/kg

8.9°C, 7g/kg 5 5 mm33/s/s

RHT

SPACE

13

Cool Reheat

OA

SACA

REHEAT56 kW

RA

Trane EarthWise Air Systems 2014

7

14

Run Around Coil

Run Run

around around

coilcoil

EAEA

OAOA

RARA

SASA

5 5 mm33/s/s

4.5 4.5 mm33/s/s25°C/50%RH

32/26°C

18°C, 7g/kg

8.9°C, 7g/kg

5 5 mm33/s/s

29.1/25.3 °C

EAT CA

15

RAC

OA

SACA

REHEAT56 kW

RA EA

EAT

Trane EarthWise Air Systems 2014

8

16

Total Energy Recovery

totaltotal--

energyenergy

wheelwheel

EAEA

OAOA

RARA

SASA

5 5 mm33/s/s

4.5 4.5 mm33/s/s25°C/50%RH

32/26°C

18°C, 7g/kg

8.9°C, 7g/kg

5 5 mm33/s/s

27.3/21.0 °C

EAT CA

17

EW

OA

SACA

REHEAT56 kW

RA

EAT

Trane EarthWise Air Systems 2014

9

18

Air-to-Air Energy Recovery Technologies (airside)

• Run Around Coil (Coil Loop)

• Plate Heat Exchanger

• Heat Pipe

• Heat (Energy) Wheel

19

expansion tankexpansion tank

pumppump

threethree--waywaymixing valvemixing valve

EAEA

OAOA

sensible-energy recovery devices

Coil Loop

• 45% – 60% sensible

effectiveness

• Very flexible

• No cross-leakage

• Capacity modulation

using variable-speed

pump or mixing valve

• Compact

Trane EarthWise Air Systems 2014

10

20

sensible-energy recovery devices

Fixed-Plate Heat Exchanger

• 60% – 70% sensible

effectiveness

• Capacity modulation

using face-and-bypass

dampers

• Very low cross-leakage

EAEA

OAOA

22

sensible-energy recovery devices

Heat Pipe

• 30% – 55% sensible

effectiveness

• Capacity modulation

using bypass dampers

or tilt control

• Little or no cross-

leakage

Trane EarthWise Air Systems 2014

11

23

total-energy recovery devices

Total-Energy Wheel

• 65% – 80% total

effectiveness

• Capacity modulation

using bypass dampers

or variable speed

• Some cross-leakage

• Self cleaning (dry

particles)

24

EA

OA

OA

EA

Fixed Plate Heat Exchanger Total Energy Wheel

Packaged AHU Solutions

• Factory mounted and tested controls

–Reduces site installation and commissioning time

–Single source responsibility

Trane EarthWise Air Systems 2014

12

25

EfficientDehumidification

26

HVAC Dehumidification

• Dehumidification is moisture removal from OA or SA

• Dehumidification is an energy intensive process

– Use conventional cold cooling coils or desiccants

– Can reduce some energy input with air-to-air HR, but may still not meet moisture content or dew point target (not dry enough)

• Applications

– High OA demand buildings

– Green buildings with increased OA rates for better indoor air quality

– Humidity controlled environments e.g. operating theatres, ICU, museums, art galleries, pharmaceutical, dry storage etc

Trane EarthWise Air Systems 2014

13

27

HVAC Dehumidification

• Commercial offices: trend in use of sensible only

equipment in conditioned space like chilled beams,

chilled ceilings, displacement ventilation, underfloor air

distribution

– Increased dehumidification requirements of dedicated outside air systems (DOAS) which now has to process both the OA load as well as the space latent load

– Leads to requirements for dry air (low moisture content, low dew point) supplied into the space to handle latent loads

28

HVAC Dehumidification

• Green Star awards 1 credit in IEQ-15 for maintaining

space RH < 60% at part load conditions

– At part load conditions space RH increases due to lower SHR caused by lower sensible loads compared to design conditions

– High space RH increases risk of mould in high RH areas (IEQ-15)

• Many Green Star jobs do not claim this point due to

costs of installing an active desiccant wheel system;

also energy penalty using active heat

– Solution in efficient dehumidification equipment

Trane EarthWise Air Systems 2014

14

29

Performance of Desiccant WheelsDesiccant Isotherms

ability tohold water

vapor

high

relative humidity, %

low

0 60 1004020 80

Type III(CDQ) regenerates below 80% RH

Type I

Type II

typicalmixed-air

conditions

typicalleaving-coilconditions

Active heat to ‘dry out’

30

Type II Series DesiccantTrane CDQ (Cool Dry Quiet)

Trane CDQ Type III Desiccant

Condensate

CoilCA

OA

RA

SASA

MAMA'

WA

TE

R V

AP

OR

Cooling CoilCHW or DX

PR

EH

EA

T

CDQ WHEEL in CLCPMoisture laden air

Co

ol d

eh

um

idif

ied

air

AHU with integrated passive desiccant wheel to produce supply air with lower dew point than conventional cooling coils

RE

HE

AT

Trane EarthWise Air Systems 2014

15

31

Trane CDQ - DOAS

Trane CDQ Type III Wheel

CONDENSATE

Coil

PR

EH

EA

T

CA

OA

RA

SA

LR

WA

TE

R V

AP

OR

11.6/11.5C 99% 8.4g/kg

18.0/12.7C 55% 7.0g/kg 8.7C DP

30.0/26.3C 75% 20.2g/kg

Cooling Coil

5,000 L/s 32/26C, 62.5% 18.8g/kg

0 L/s

RE

HE

AT

13.6/10.9C 72% 7.0g/kg

EAT

32

CDQ

OA

SA

CA

LR

REHEAT

27 kWREHEATAVOIDED

30 kW

CA’

Trane EarthWise Air Systems 2014

16

33

Trane CDQ with AC HR Chiller

Coil

PR

EH

EA

T

CA

OA

RA

SA

WA

TE

R V

AP

OR

11.6/11.5C 99% 8.4g/kg

18.0/12.7C 55% 7.0g/kg 8.7C DP

5,000 L/s 32/26C, 62.5% 18.8g/kg

0 L/s

RE

HE

AT

CO

OL

ING

CO

IL

• Preheat for dehumidification during humid times

• Reheat to achieve target SADB

34

Dehumidification with Energy Recovery vsType III Desiccant

Reduces Cooling energy by reducing air-on

Reheat required to achieve desired SADB

Potential for contamination

Exhaust air stream required

Energy Recovery CDQ

Reduces Cooling energy by dehumidification, raising air-off conditions

Minimize Reheat required to achieve desired SADB

No contamination

Exhaust airstream not required

Trane EarthWise Air Systems 2014

17

35

CDQ + EW Dual Path Dual Wheel

TRANE CDQ WHEEL

Coil

CA

OA

LR

11.7/11.6C 98% 8.4g/kg

25.8/21.2C 67% 13.6g/kg

29.7/24.1C 63.6% 16.7g/kg

RE

HE

AT

18/12.7C 55% 7.0g/kg

EN

ER

GY

WH

EE

L

OA

CO

OL

ING

CO

IL

23.0/18.4C, 65.1% 11.4g/kg

SA

RA`4,500 L/s 25.0C 50% 9.9g/kg

EA

LW1

WA

TE

R V

AP

OR

CD

Q W

HE

EL

5,000 L/s 32/26C, 62.5% 18.8g/kg

13.5/10.8C 73% 7.0g/kg

LW1

36

CDQ + EW Dual Path

OA

SA

CA

LR

REHEAT

28 kW

RA

LW1EA

Trane EarthWise Air Systems 2014

18

37

Series CDQ + EW Dual Wheel

TRANE CDQ WHEEL

Coil

PR

EH

EA

T

CA

OA

LR

WA

TE

R V

AP

OR

11.8/11.7C 98% 8.5g/kg

18.0/12.7C 55% 7.0g/kg 8.7C DP

25.3/21.4C 71% 14.4g/kg

5,000 L/s 32/26C, 62.5% 18.8g/kg

RE

HE

AT

13.8/11.0C 72% 7.0g/kg

EN

ER

GY

WH

EE

L

OAC

OO

LIN

G C

OIL

5,000 L/s 27.3/21.0C, 57.3% 13.0g/kg

SA RA

EA

LW1

4,500 L/s 25.0C 50% 9.9g/kg

38

Series CDQ + EW

OA

SA

CA

LR

REHEAT

26 kW

RA

LW1

EA

Trane EarthWise Air Systems 2014

19

41

Type III Series Desiccant AHU Trane CDQ

• Enhanced dehumidification device

– Not an Energy Recovery Device as it does not require an exhaust air stream

– No contamination

• Extends the dehumidification range of conventional

CHW systems (3 to 8K lower dew point)

– No need for high temperature regeneration

– Nil or minimized reheat

• Energy efficient way to control humidity with factory

packaged controls

• Further improvement in efficiency used in conjunction

with Energy Wheel in Dual Wheel application

Recommended