PART I. GENERAL PROVISIONS
DIVISION 16 - ELECTRICAL SPECIFICATIONS
ELECTRICAL SPECIFICATIONS LEGEND
ELECTRICAL SYMBOLS
DATA OUTLET, HEIGHT AS NOTED ON PLANS WITH 3/4 " EMPTY
CONDUIT TO ABOVE CEILING. PROVIDE PULL WIRE.
1. SCOPE: PROVIDE ALL LABOR, MATERIAL, AND EQUIPMENT IN
ACCORDANCE WITH THESE SPECIFICATIONS, AND THE
ACCOMPANYING DRAWINGS TO PROVIDE A COMPLETE AND
PROPERLY OPERATING ELECTRICAL SYSTEM FOR THE
BUILDING.
A. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL OF THE
FOLLOWING MATERIAL AND EQUIPMENT UNDER THIS
DIVISION OF THE SPECIFICATIONS, UNLESS NOTED OTHERWISE:
PANELBOARDS; LIGHTING FIXTURES; LAMPS; RACEWAYS; 600 VOLT
WIRE AND CABLE; WIRING DEVICES; DEVICE PLATES; DEVICE, PULL,
AND JUNCTION BOXES; SAFETY SWITCHES; MOTOR STARTERS;
LIGHTING CONTROLS; CIRCUIT BREAKERS; FUSES; TIME
CLOCKS; EQUIPMENT IDENTIFICATION (NAMEPLATES AND
DIRECTORIES); WIRE AND CABLE TERMINATIONS; CONNECTIONS TO
INDIVIDUAL UNITS OF EQUIPMENT FOR THE WALK-IN FREEZERS
AND COOLERS; AND TEMPORARY POWER.
B. THE FOLLOWING MATERIAL AND EQUIPMENT WILL BE FURNISHED
AND/OR INSTALLED BY OTHERS, OR UNDER OTHER
DIVISIONS OF THE SPECIFICATIONS, UNLESS NOTED OTHERWISE:
LOW VOLTAGE (24 VOLT) WIRE AND CABLE, COMMUNICATION
DEVICES, SECURITY EQUIPMENT, POINT OF SALE (POS) EQUIPMENT,
SIGNAGE, CONCRETE BASES FOR SITE LIGHTING POLES.
C. THE FOLLOWING MATERIAL AND EQUIPMENT WILL BE FURNISHED BY
OTHERS, OR UNDER OTHER DIVISIONS OF THE SPECIFICATIONS,
AND INSTALLED BY THE CONTRACTOR, UNLESS NOTED
OTHERWISE: SITE LIGHTING FIXTURES AND POLES.
2. GENERAL REQUIREMENTS: ALL WORK SHALL BE PERFORMED BY
SKILLED LICENSED ELECTRICIANS IN ACCORDANCE WITH THE
BEST PRACTICES OF THE TRADE, MEETING THE REQUIREMENTS OF
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE,
APPLICABLE FEDERAL, STATE AND LOCAL CODES, AND THE
REQUIREMENTS OF THE ELECTRICAL UTILITY COMPANY
FURNISHING THE SERVICES. ALL NECESSARY CONSTRUCTION
PERMITS AND CERTIFICATES OF INSPECTION SHALL BE
PURCHASED AND OBTAINED UNDER THIS CONTRACT.
A. COORDINATION: ALL OUTLETS MUST BE ACCURATELY LOCATED,
PARTICULARLY APPLIANCE OUTLETS WHICH SHALL BE LOCATED
FROM THE DIMENSIONS GIVEN ON THE DRAWING AND FIELD
VERIFIED. REVIEW THE ARCHITECTURAL, PLUMBING AND HEATING
AND VENTILATING PLANS IN ORDER TO COORDINATE THIS WORK
WITH OTHER TRADES, AND COOPERATE WITH THEM IN THE ENTIRE
INSTALLATION.
3. SERVICE VOLTAGE: THESE DRAWINGS ARE FOR A METERED,
UNDERGROUND BUILDING SERVICE OF 120/208 VOLT, THREE
PHASE, FOUR WIRE, 60 HERTZ. ALL KITCHEN AND AIR
CONDITIONING EQUIPMENT HAS BEEN DESIGNED AND PURCHASED
FOR USE ON THIS ELECTRICAL SYSTEM. THE CONTRACTOR SHALL
CONTACT THE ELECTRICAL UTILITY AND VERIFY ALL OF THE ABOVE
SERVICE CHARACTERISTICS, AND THE AVAILABLE FAULT CURRENT.
4. SERVICE EQUIPMENT: THE SERVICE SHALL BE LOCATED AS SHOWN
ON THE SITE PLAN, OR AS INDICATED IN THE INSTRUCTIONS
TO BIDDERS. UTILITY POLES, PADS FOR UTILITY TRANSFORMERS,
CURRENT TRANSFORMER ENCLOSURES, METERING EQUIPMENT,
SERVICE MASTS, AND OTHER RELATED MATERIALS AND
EQUIPMENT SHALL BE APPROVED, FURNISHED, AND INSTALLED AS
REQUIRED. INCLUDE THE COST OF ALL THE ABOVE ITEMS, SERVICE
CONNECTIONS, AND METER CHARGES IN THE BASE BID. MAIN
SERVICE SWITCHES AND CURRENT TRANSFORMER CABINETS
SHALL BE INCLUDED IN THE BASE BID. UNLESS NOTED OTHERWISE,
A MAIN SERVICE SWITCH WITH CURRENT LIMITING FUSES MAY BE
USED WHEN THE AVAILABLE FAULT CURRENT (AFC) IS EXCESSIVE,
IN ORDER TO USE STOCK PANELBOARDS, WITH 10K OR 22K AIC
RATINGS.
PART II. MATERIALS
1. MATERIALS: ALL MATERIALS SHALL BE NEW AND OF THE QUALITY
INDICATED BY THE SPECIFIED BRAND NAMES. SUBSTITUTIONS OF
MATERIAL OF EQUAL QUALITY BY OTHER MAJOR MANUFACTURERS
OF COMMERCIAL EQUIPMENT MAY BE ACCEPTABLE PROVIDED A
LIST OF SUCH SUBSTITUTIONS IS APPROVED IN WRITING BY
POPEYE'S ARCHITECTURE AND ENGINEERING DEPARTMENT. THE
CONTRACTOR SHALL SUBMIT A SUBSTITUTION LIST IN TRIPLICATE
AT LEAST FIVE DAYS PRIOR TO THE BID OPENING.
SINGLE FACE EXIT LIGHT W/EMERGENCY BATTERY
PACK AND TWO (2) EMERGENCY LIGHT HEADS. SEE
FIXTURE SCHEDULE
BRACKET OR WALL MOUNTED LIGHT FIXTURE. LETTER
DENOTES MARK, SEE FIXTURE SCHEDULE.
FLUORESCENT LIGHT FIXTURE. LETTER
DENOTES MARK. SEE FIXTURE SCHEDULE.
FLUORESCENT LIGHT FIXTURE ON NIGHT LIGHT CIRCUIT.
FLUORESCENT LIGHT FIXTURE. LETTER
DENOTES MARK. SEE FIXTURE SCHEDULE.
PENDANT LIGHT FIXTURE. LETTER
DENOTES MARK. SEE FIXTURE
SCHEDULE.
RECESSED DOWN LIGHT FIXTURE. LETTER
DENOTES MARK. SEE FIXTURE SCHEDULE.
8" VERTICAL FLUORESCENT RECESSED LIGHT
FIXTURE. LETTER DENOTES MARK. SEE
FIXTURE SCHEDULE.
TOGGLE SWITCH - SINGLE POLE - HUBBEL #HBL1221-I.
DUPLEX RECEPTACLE; NUMBER SUBSCRIPT INDICATES
MOUNTING HEIGHT ABV FINISHED FLOOR IF DIFFERENT THAN
SPECIFIED. HUBBEL #5362-I
DUPLEX RECEPTACLE - IN WEATHER PROOF ENCLOSURE
OR COVER, GROUND FAULT INTERUPTER.
RECEPTACLE FLUSH MOUNTED IN CEILING.
VERIFY EXACT LOCATION AND NEMA
CONFIGURATION.
DUPLEX RECEPTACLE - ISOLATED GROUND SURGE
PROTECTED - HUBBELL #IG-5362-OSP FOR POS EQUIP.
& PRINTERS
DUPLEX RECEPTACLE - ISOLATED GROUND SURGE
PROTECTED; MOUNTED IN CEILING. HUBBELL #IG-5362-OSP
FOR MONITORS
SPECIAL PURPOSE
RECEPTACLE
208/120 PANELBOARD.
DISCONNECT SWITCH SIZE AS NOTED.
DOOR SWITCH MOUNTED IN DOOR FRAME (F.B.C.)
SEE ELECTRICAL NOTES.
ABOVE FINISHED FLOOR.
ABOVE FINISHED CEILING.
GROUND FAULT INTERUPTING
FURNISHED BY CONTRACTOR.
WEATHERPROOF
UNLESS NOTED OTHERWISE.
CONDUIT RUN CONCEALED IN WALLS OR CL. SPACES. ARROWS
INDICATE HOMERUNS. SUBSCRIPT INDICATES PANEL AND
CIRCUIT NUMBERS. SLASH MARKS INDICATE NUMBER OF
CONDUCTORS. EQUIPMENT GROUNDING CONDUCTOR
REQUIRED IN ALL CONDUITS NOT INDICATED WITH WITH
HASHMARK.
SAME AS ABOVE NOTE EXCEPT RUN CONDUIT
BELOW FLOOR
EXHAUST FAN.
SUPPLY FAN.
FLY FAN
JUNCTION OR OUTLET BOX.
JUNCTION OBOXFOR SIGN-MOUNT SWITCH NEAR SIGN. MAKE ALL
CONNECTIONS REQ'D. VERIFY ALL ASPECTS WITH SIGNAGE
VENDOR. SEE ARCHITECTURAL ELEVATIONS FOR HEIGHT AND
LOCATION AS SHOWN.
JUNCTION BOX FOR SMOKE DETECTOR (F.B.C.) 120v
WIRING BY THIS CONTRACTOR.
COMBINATION DUAL DATA OUTLET AND TELEPHONE OUTLET
HEIGHT AS NOTED ON PLANS WITH 3/4 " EMPTY CONDUIT TO
ABOVE CEILING. PROVIDE PULL WIRE.
TELEPHONE OUTLET, WALL TYPE, 24" AFF U.N.O ON PLANS WITH
3/4 " EMPTY CONDUIT TO ABOVE CEILING. PROVIDE PULL WIRE.
PROVIDE 'ON/OFF' SELECTOR SWITCH AND PILOT LIGHT IN NEMA
4 STAINLESS STEEL ENCLOSURE MOUNTED ON THE FACE OF
THE HOOD. PROVIDED BY HOOD MANUFACTURER.
SPEAKER; CEILING MOUNTED
SPEAKER OUTLET IN WALL STUB 3/4" CONDUIT TO
SPACE ABOVE ACCESSIBLE CEILING. PROVIDE PULL
WIRE.
TRANSFORMER MOUNTED ACCESSIBLE
ELECTRIC DOOR PUSHBUTTON:
EDWARDS #590 48" MOUNTING HEIGHT
ELECTRIC DOOR BUZZER: 8" BELOW
CEILING
PHOTOCELL
A. PANELBOARDS: PANELBOARDS SHALL BE BOLT-IN CIRCUIT
BREAKER TYPE, AS SHOWN ON THE PLANS. PANELS SHALL
BE OF PANELBOARD CONSTRUCTION, 20 INCHES WIDE
(MINIMUM), 5-3/4" TO 6-1/2" DEEP, UL LISTED, AND MEET UL
67, UL 50, AND FEDERAL SPECIFICATION W-P-115B AS TYPE 1,
CLASS 1, WITH BOLT-ON CIRCUIT BREAKERS, COPPER BUS BARS,
NEUTRAL BUS, GROUND BUS, AND A HINGED LOCKABLE DOOR.
CABINETS SHALL BE CODE GAUGE, GALVANIZED STEEL, MOUNTED
AS SHOWN. PROVIDE TYPEWRITTEN CIRCUIT DIRECTORIES WITH
CLEAR PLASTIC PROTECTORS IN ALL PANELS. ALL WIRES SHALL
BE TAGGED WITH PANEL AND CIRCUIT NUMBERS. PANEL "MP"
SHALL BE UL LISTED AND LABELED AS SUITABLE FOR USE AS
SERVICE ENTRANCE EQUIPMENT. APPROVED MANUFACTURERS
OF PANELS ARE SQUARE D/TELEMECHANIQUE, CUTLER-HAMMER,
GENERAL ELECTRIC, WESTINGHOUSE, AND SIEMENS (I-T-E).
B. LIGHTING FIXTURES: ALL LIGHTING FIXTURES SHALL BE UL LISTED,
COMMERCIAL QUALITY. REFER TO NATIONAL ACCOUNT
SCHEDULE. REVIEW AT: WWW.POPEYESDEVELOPMENT.COM;
PASSWORD: lagniappe
C. LAMPS: ALL NEW FLUORESCENT LAMPS (F40T8) SHALL BE COOL
WHITE, OR COLOR IMPROVED COOL WHITE, WITH A 4100 DEGREE K
COLOR TEMPERATURE, 2950 MIN INITIAL LUMENS, 20,000 HOURS
RATED LIFE, AND 62 MIN CRI, UNLESS NOTED OTHERWISE.
D. WIRING DEVICES: ALL WIRING DEVICES SHALL BE UL LISTED,
COMMERCIAL SPECIFICATION GRADE. SWITCHES SHALL BE RATED
20 AMPS AT 120/277 VOLTS, AC. STANDARD RECEPTACLES SHALL
BE 20 AMP, DUPLEX, GROUNDING TYPE, IN NEMA
CONFIGURATIONS, UNLESS NOTED OTHERWISE. SWITCHES IN THE
SAME LOCATION SHALL BE GANGED BEHIND A SINGLE PLATE.
DEVICE PLATES IN THE KITCHEN AREA SHALL BE METAL,
ALUMINUM OR STAINLESS STEEL. DEVICE PLATES IN THE DINING
AREA SHALL BE THERMOPLASTIC PLASTIC (NYLON) OR METAL,
COLOR AS APPROVED BY THE ARCHITECT OR OWNER. APPROVED
MANUFACTURERS OF SWITCHES AND RECEPTACLES ARE
HUBBELL, ARROW HART, BRYANT, LEVITON, PASS & SEYMOUR,
GENERAL ELECTRIC, SLATER, OR EQUAL.
1. SWITCHES:
a. SINGLE POLE: HUBBELL HBL1221-I, OR EQUAL.
b. THREE WAY: HUBBELL HBL1223-I, OR EQUAL.
2. RECEPTACLES:
a. NEMA 5-20R: HUBBELL 5362I, OR EQUAL.
b. NEMA 5-20R-IG: HUBBELL IG-5362, OR EQUAL.
c. NEMA 5-20R-IG/SS: HUBBELL IG-5362-OS, OREQUAL.
d. NEMA 5-20R-GFCI: HUBBELL GF5362-I, OR EQUAL.
e. NEMA 6-20R: HUBBELL 5462-I, OR EQUAL.
f. OTHERS: COMMERCIAL OR INDUSTRIAL GRADE, UL LISTED,
FEDERAL SPECIFICATION WC596F.
3. WP PLATES: WEATHERPROOF COVERS ARE PERMITTED UNDER
NEC ARTICLE 406.8(B)(I).
4. NATIONAL ACCOUNT: REFER TO THE NATIONAL ACCOUNT
DIRECTORY. THE FOLLOWING EQUIPMENT MAY BE AVAILABLE:
MAIN SERVICE PANELBOARD WITH BREAKERS INSTALLED,
LIGHTING AND DISTRIBUTION PANELBOARDS WITH BREAKERS
INSTALLED, ROOF-TOP DISCONNECTS FOR HVAC UNITS AND
KITCHEN HOOD FANS, LIGHTING CONTACTOR PANEL, AND SHUNT
TRIP SYSTEMS (IF REQUIRED PER LOCAL CODE).
5. EXCAVATIONS: PERFORM ALL NECESSARY EXCAVATING AND
BACK-FILLING REQUIRED FOR THIS INSTALLATION. ALL
EXCAVATIONS BELOW THE BOTTOM OF FOOTINGS SHALL BE
BACKFILLED WITH 3000 PSI CONCRETE. WHERE DITCHES ARE CUT
FOR OUTSIDE RUNS OF CONDUIT, REPLACE AND TAMP THE EARTH
IN 12" LAYERS AND LEAVE THE GROUND LEVEL AND EQUAL TO ITS
ORIGINAL CONDITION.
6. CONDUIT AND FITTINGS: CONDUIT PERMITTED: (A) RIGID
GALVANIZED STEEL (RGS), (B) EMT, (C) PVC, AND (D) ENT. TYPES
UTILIZED SHALL BE RUN ONLY AS PERMITTED PER CODE. ALL
WIRING SHALL BE RUN IN CONDUIT. CONDUIT PLACED IN
CONCRETE OR RUN UNDERGROUND SHALL BE RIGID GALVANIZED
CONDUIT OR PVC. IF PVC IS USED, ALL ELBOWS, SWEEPS AND
STUB-UPS SHALL BE RGS. CONDUIT EXPOSED OR RUN IN
MASONRY WALLS ABOVE GRADE MAY BE PVC OR EMT WHERE
ALLOWED BY LOCAL CODES. IF EMT IS NOT PERMITTED, RIGID
SCREWED GALVANIZED PIPE CONDUIT AND FITTINGS SHALL BE
USED. IF SHIELDED CABLE IS REQUIRED FOR CONTROL
CIRCUITRY, IT SHALL BE TAN, GREY OR ANY NEUTRAL COLOR
OTHER THAN THAT AS SPECIFIED FOR POWER DISTRIBUTION. NO
CONDUIT SMALLER THAN 3/4" SHALL BE INSTALLED EXCEPT FOR
TWO-WIRE SWITCH LEGS. ALL CONDUIT BENDS SHALL BE FREE
FROM DENTS AND KINKS. ALL CONDUITS SHALL BE ELECTRICALLY
CONTINUOUS FROM THE SERVICE EQUIPMENT TO ALL OUTLETS,
AND SHALL BE SECURED TO ALL METAL BOXES WITH ONE LOCK
NUT OUTSIDE, AND ONE INSIDE THE BOX WITH A REINFORCED
BAKELITE BUSHING. IF PVC, OR ENT, IS USED, THEN APPROPRIATE
SIZED, ELECTRICALLY CONTINUOUS, BOND WIRES SHALL BE RUN
FROM THE SERVICE EQUIPMENT TO ALL OUTLETS, AND SHALL BE
SECURED TO EACH WIRING DEVICE PER THE NATIONAL
ELECTRICAL CODE. WHERE CONNECTIONS ARE TO BE MADE
BETWEEN CONDUIT TERMINATIONS AND MOTORS, EQUIPMENT, OR
APPARATUS NECESSITATING FLEXIBLE CONNECTIONS, APPROVED
FLEXIBLE CONDUIT SHALL BE USED. OUTDOOR CONNECTIONS TO
FANS, HVAC UNITS, OR ROTATING EQUIPMENT SHALL B MADE WITH
HELICAL WOUND, LIQUIDTIGHT, FLEXIBLE STEEL CONDUIT.
EXPOSED CONDUIT SHALL BE SUITABLY SUPPORTED AT
INTERVALS NOT TO EXCEED FIVE (5) FEET. DURING
CONSTRUCTION, CONDUIT SHALL BE KEPT FREE OF ALL FOREIGN
MATTER BY USE OF CAPPED BUSHINGS ON ALL TURNED UP ENDS.
PAPER OR WOOD PLUGS ARE NOT ACCEPTABLE FOR THIS
PURPOSE.
7. WIRE AND CABLES: ALL WIRE AND CABLES SHALL BE
UNDERWRITERS LABORATORIES' LISTED, AND LABELED, AND
CONFORM WITH APPLICABLE STANDARDS OF UL (44, AND 83),
NEMA (WC-5, AND WC-7), IPCEA (S-61-402, AND S-66-524), FEDERAL
SPECIFICATIONS (J-C-30A(1), AND HH-I-595C), ANSI, AND OTHER
APPLICABLE INDUSTRY STANDARDS. CONNECTORS AND LUGS
SHALL MEET UL PUBLICATION 486. ALL BRANCH CIRCUIT WIRING
SHALL BE 600 VOLT, COPPER, 75 DEGREE C (MIN), TYPE
THHN/THWN WITH A MINIMUM SIZE OF #12 AWG, UNLESS NOTED
OTHERWISE. WIRE SIZES OF #8 AWG AND LARGER SHALL BE
STRANDED. SERVICE AND FEEDER CABLES SHALL BE 600 VOLT,
STRANDED COPPER, 75 DEGREE C (MIN), TYPE XHHW. ALL
CIRCUITS SHALL HAVE A SEPARATE GROUND CONDUCTOR.
PROVIDE GREEN-INSULATED GROUND WIRE IN ALL RACEWAYS,
CABLE ASSEMBLIES, AND WHERE NOTED. SIZE EQUIPMENT
GROUNDS PER TABLE 250-122 OF THE NATIONAL ELECTRICAL
CODE. INSULATION COLOR CODES SHALL BE BLACK, RED, AND
BLUE (PHASE), WHITE (NEUTRAL), AND GREEN (GROUND).
A. ALL WIRING SHALL BE INSTALLED IN CONDUIT, EXCEPT WHERE
SPECIFICALLY SHOWN ON THE DRAWINGS. NON-METALLIC
SHEATHED (TYPE NM) CABLE IS NOT PERMITTED.
B. ALL BRANCH CIRCUIT, COMMUNICATION, SIGNALING, AND
CONTROL WIRING TO KITCHEN, FIRE PROTECTION, AND OTHER
EQUIPMENT SHALL BE ROUTED ABOVE THE CEILING. VERIFY
WHETHER OR NOT THE SPACE ABOVE THE CEILING IS USED AS A
SPACE FOR RETURN AIR FOR THE ENVIRONMENTAL AIR SYSTEM.
IF IT IS USED FOR RETURN AIR, PROVIDE APPROVED RACEWAYS
FOR ALL OVERHEAD WIRING PER NEC ARTICLE 300-22(B). IF IT IS
NOT "OTHER SPACE USED FOR ENVIRONMENTAL AIR", APPROVED
LOW VOLTAGE CABLES MEETING THE REQUIREMENTS OF NEC
ARTICLES 725 AND 760 MAY BE RUN WITHOUT RACEWAYS, UNO.
ALL SAFETY CONTROL WIRING FOR FIRE PROTECTION SYSTEMS,
SHUNT TRIPS, ETC. SHALL BE RUN IN A RACEWAY IN ACCORDANCE
WITH NEC ARTICLES 725.25 AND 725.28.
8. SITE LIGHTING: THE G.C. WILL FURNISH THE SITE LIGHTING
PACKAGE, AS REQUIRED FOR THE SPECIFIC LOCATION. UNDER
THIS SPECIFICATION SECTION, PROVIDE 1" RIGID GALVANIZED
STEEL ELECTRICAL CONDUIT, AND THE REQUIRED WIRING FROM
THE PANEL TO THE POLE. SET FIXTURES AND POLES ON
CONCRETE BASES, AS PROVIDED UNDER SPECIFICATION SECTION
3A: CONCRETE. GROUND/BOND ALL SITE LIGHTING
FIXTURES/POLES PER THE NEC. THE BRANCH CIRCUIT
CONDUCTORS SHALL BE INCREASED FROM #10 AWG TO #8 AWG IF
THE HORIZONTAL DISTANCE FROM THE PANEL TO THE POLE IS
GREATER THAN EIGHTY (80) FEET. ALL SITE LIGHTING SHALL BE
CONTROLLED THROUGH THE LIGHTING CONTROL SYSTEM SHOWN
ON THE DRAWINGS. REFER TO THE SITE PLAN FOR
QUANTITY AND LOCATION OF ALL SITE LIGHTING. SET FIXTURES
AS SPECIFIED, AND AIM AFTER DARK FOR UNIFORM LIGHT
DISTRIBUTION.
9. SIGNAGE LIGHTING: PROVIDE A 1" RIGID GALVANIZED STEEL
ELECTRICAL CONDUIT, AND WIRING, FROM THE PANEL TO
ALL ILLUMINATED SIGNS AS SHOWN ON THE LIGHTING AND
SITE PLANS. GROUND/BOND EACH SIGN. SIGNS WILL BE
FURNISHED AND INSTALLED BY THE OWNER, OR UNDER A
SEPARATE CONTRACT, UNO. POWER AND WIRING SHALL BE
FURNISHED AND INSTALLED UNDER THIS SECTION OF THE
SPECIFICATIONS.
OTHER WIRING:
A. FURNISH AND INSTALL ALL POWER WIRING AND CONDUIT AS
INDICATED ON THE DRAWINGS FOR ROOF-TOP HVAC EQUIPMENT,
KITCHEN HOOD FANS, AND WALK-IN FREEZER AND COOLER
EQUIPMENT. DISCONNECT SWITCHES, AVAILABLE FROM THE
NATIONAL ACCOUNT, SHALL BE FURNISHED AND INSTALLED FOR
EACH UNIT OF HVAC EQUIPMENT, AND FOR KITCHEN EQUIPMENT
WITHOUT A CORD AND PLUG. BEFORE ENERGIZING ANY
EQUIPMENT, VERIFY THAT THE CORRECT POWER SUPPLY
VOLTAGE, AMPACITY, AND PHASING HAS BEEN PROVIDED AT THE
LOAD SIDE OF THE DISCONNECT.
B. FURNISH AND INSTALL THE LIGHTING CONTACTOR PANEL, AND ALL
ASSOCIATED POWER WIRING, AS INDICATED. THE LIGHTING
CONTACTOR PANEL IS CUSTOM BUILT, AND AVAILABLE FROM THE
NATIONAL ACCOUNT.
10. EMPTY CONDUIT: LEAVE A #12 AWG PULL WIRE IN ALL EMPTY
CONDUITS.
11. BOXES AND WIREWAYS: ALL JUNCTION BOXES, PULL BOXES,
WIREWAYS, ETC, SHALL BE SIZED IN ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE.
12. EQUIPMENT IDENTIFICATION: PROVIDE NAMEPLATES FOR ALL
PANELBOARDS, CONTROLS, AND OTHER ELECTRICAL EQUIPMENT.
EQUIPMENT VISIBLE TO THE PUBLIC SHALL BE IDENTIFIED WITH
ENGRAVED LAMINATED NAMEPLATES ATTACHED WITH STAINLESS
STEEL FASTENERS. ELECTRICAL EQUIPMENT NOT VISIBLE TO THE
PUBLIC MAY BE NEATLY IDENTIFIED WITH BLACK PERMANENT
MARKERS.
PART III. EXECUTION
1. TESTS: MAKE ALL TESTS NECESSARY TO ENSURE THAT THE
ENTIRE INSTALLATION IS FREE FROM IMPROPER GROUNDS, AND
FROM SHORTED AND/OR OPEN CONDUCTORS. VOLTAGE,
CURRENT, AND ROTATION TESTS SHALL BE MADE BEFORE ANY
MOTORS ARE PLACED IN OPERATION. ALL LOADS SHALL BE
BALANCED ACROSS PHASES. CHECK TO SEE THAT ALL LIGHTS
WORK, AND ARE CONTROLLED BY SWITCHES INDICATED ON
DRAWINGS, OR CIRCUIT BREAKERS SO INDICATED ON PANEL
SCHEDULE.
2. GUARANTEE: FURNISH A GUARANTEE IN WRITING TO THE
OWNER THAT ALL WORK EXECUTED UNDER THIS SECTION
IS FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP
FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL
ACCEPTANCE. IN ADDITION, DURING THE TERM OF THIS
GUARANTEE, THE REPAIR AND/OR REPLACEMENT OF ANY
DEFECTIVE WORK, AND ALL RESULTING DAMAGES SHALL BE
MADE AT NO ADDITIONAL EXPENSE TO THE OWNER.
3. TEMPORARY POWER: AT THE PROJECT SITE, PROVIDE A 100
AMP, 120/240 VOLT, SINGLE PHASE, SERVICE WITH POWER
OUTLETS ADEQUATE FOR TEMPORARY CONSTRUCTION
POWER. TEMPORARY LIGHTING SHALL BE MAINTAINED IN
ALL AREAS OF THE BUILDING UNTIL PERMANENT POWER
SOURCES HAVE BEEN ENERGIZED. TEMPORARY SERVICE SHALL
BE PROVIDED UNDER SECTION 1A OF THESE
SPECIFICATIONS.
4. CLEAN-UP: LEAVE THE ELECTRICAL PORTION OF THE WORK IN A
CLEAN AND FINISHED CONDITION.
5. SHOP DRAWINGS: PROVIDE SHOP DRAWINGS FOR THE
FOLLOWING ITEMS: PANELBOARDS, LIGHTING FIXTURES.
6. AS-BUILT DRAWINGS: MAINTAIN AS-BUILT DRAWINGS, UPDATED
DAILY DURING CONSTRUCTION, AND PRESENT THE OWNER
WITH ONE SET UPON COMPLETION. PROVIDE THE OWNER'S
PERSONNEL WITH ON-SITE INSTRUCTION IN THE
OPERATION AND MAINTENANCE OF THE COMPLETED
ELECTRICAL SYSTEM.
BALCONY UPLIGHT FIXTURE
CHECKED:
DATE:
PO
PE
YE
S
LK
1
26
0-D
L-P
LU
S P
RO
TO
TY
PE
E.I.F
.S
. / S
IM
UL
AT
ED
S
TO
NE
LO
UIS
IA
NA
K
IT
CH
EN
L
K-P
LU
S D
ES
IG
N S
TA
ND
AR
DS
60 S
EA
TS
/ D
UA
L-L
IN
E P
RO
DU
CT
IO
N
ELECTRICAL DATA
SHEET
and SPECIFICATIONS
E0
04/17/15
KR
REVISIONS:
FREEZER
WALK-IN
MENWOMEN
ELECTRICAL PANELS
COOLER
WALK-IN
SET FOR 30 MIN TIME DELAY WHEN TURNED OFF.
AND ADJUSTIBLE TIMER & BLOCK
PROVIDE DPDT RELAY
SQUARE D #8501-KP12V20
& #8501 NR51 BASE
B-16DIR SIGNS
N
ROOR FACING NORTH
(TYPICAL)
B-20
PE
OFF
ON
AUTO
PROVIDE PUSHBUTTON
SQUARE D #9001 KR1 RH13
& #9001KN202 "OFF"
LEGEND
MOUNT ON ROOF
(TYPICAL)
OPTIONAL
FACING NORTH
A-32
NO
R1
NC
OFF
PARKING
B-15
B-18
B-21
B-19
SPARE
8" W x 13" H x 6" D
NOMINAL ENCL. DIMENSIONS-
SD D #8903-LG80VO2
AT 20 AMP EACH (TYPICAL)
LIGHTING CONTACTOR W/ 8 POLES
B-38
SPARE
LC1
NOMINAL ENCL. DIMENSIONS-
LIGHTING CONTACTOR W/ 8 POLES
AT 30 AMP EACH (TYPICAL)
PYLON SIGN
MENU BOARD
PYLON SIGN
SIGN BLDG FRT
A-34
A-36
A-40
A-38
A-42
WALL ART
SPARE
SPARE
8" W x 13" H x 6" D
SD D #8903-LG80VO2
PARKING
PARKING
PARKING
PARKING
PARKING
LC2
EX
ON ROOF
CONTROL MOUNTED
REMOTE PE
120V
N
B-7
H
PE
WP
FIXTURE
LIGHT
H
38
REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, EXTERIOR ELEVATIONS AND
WALL SECTIONS FOR DIMENSIONED LOCATIONS OF LIGHTING FIXTURES.
NOTE:
VIA LC-3
B-28,30
CONTACTOR DIAGRAM NOTES:
LIGHTING CONTACTOR W/ 6 POLES
B-28
B-30
B-32
SD D #8903-LG80VO2
8" W x 13" H x 6" D
AT 20 AMP EACH (TYPICAL)
NOMINAL ENCL. DIMENSIONS-
CANOPY LIGHTS
CANOPY LIGHTS
CANOPY LIGHTS
SPARE
SPARE
SPARE
LC3
SHEET NOTES:
A-32,34,36,38,40,42 VIA LC2
# 8'S
WP
B-19:21 VIA LC1
WP
POPEYES RADIO SYSTEM
LABOR INCLUDES INSTALLATION OF 150' OF 12 GAUGE SPEAKER WIRE.
NUMBER OF SPEAKERS MAY VARY DUE TO DESIGN CONSIDERATIONS
CHANNEL MASTER
ECOHO STAR
PASO
QUAM
QUAM
VARIOUS
1.0 ANTENNA
3000
VARIOUS
QC-10
1
1
1
3
701
MODEL #16, BLACK
OWI
SSB-2
ERD-8
MU 3130 BGM
MAKE
BOSE
MODEL
4
2
2
1
QUANTITY
4
3. PROVIDE REMOTE MOUNTED (ON ROOF) PE CELL FOR ALL EXTERIOR FIXTURE, TYPE 'WP' NOT ON THE LIGHTING CONTACTOR.
2. ALL OUTLETS FOR LIGHTS SHALL BE SUPPORTED INDEPENDENTLY OF CEILING
4 LAMP ELECTRONIC BALLAST > 20% THD ELECTRONIC
SYSTEM USING 1/4 " ALL THREAD ROD.
1. SEE ARCHITECTURAL DETAILS FOR MOUNTING LOCATIONS.
CW20
FIXTURE NOTES:
PE
M
NOMENCLATURE
1/4 GEB
A12
COLD WEATHER BALLAST
FACTORY INSTALLED PHOTOCELL
METAL HALIDE SOURCE
PATTER #12 ACRYLIC PRISMATIC LENS
DEFINITIONS
5" x 7 GAUGE x 25' SQUARE STEEL POLE
(VERFIFY COUNTS AND TYPE WITH SITE PLAN)
VERIFY WIND LOAD TO ENSURE POLE SIZE IS SUFFICIENT.NOTE:
5
LL1
SITE LIGHTING
LL2
10
16
8
1000 WATT MH FLOODLIGHT
SECURITY
SECURITY
HERMITAGE
GOOSENECKS 100WMH - OUTDOOR
EX6
11 H
LED EXIT EMERGENCY COMBO
CL
MARK
3
A15
QTY.
COOLER/FREEZER
2 x 4 LAY-IN ELECTRONIC BALLAST
EXITRONIX
HILITE
COLUMBIA
MANUFACTURER
SSSP25-5-7-DBZ
BRONZE
EDJ31111
ASBF000MH-DM-MT
PF346315721216
BRONZE
MH1000/U/BT56
EVERGREEN
VEXUBPWHEL-90R
H811/C/GU/602-100MH
BY COOLER MANUFACTURER
JT824-332G-FSA12-3EU
LIGHT FIXTURE
WHITE
COLOR
INCLUDED
(3) F0735
BULBS
LIGHT FIXTURE SCHEDULE
MUZAK MBS 8-ST3, BLACK 2
QUAM
SEE THE NATIONAL ACCOUNT VENDOR LIST FOR EQUIPMENT SUPPLIER.
LABOR WARRANTY FOR TWO YEARS IS PROVIDED ON ALL PARKING LOT LIGHTING THRU HERMITAGE LIGHTING NATIONAL ACCOUNTS.
NO SUBSTITUTION ALLOWED FOR SPECIFIED LIGHT FIXTURES.
N/A
(1) MH100/U/MED
42 LL4 6" RECESSED DOWNLIGHT JUNO PL642EU-28B-WH
(7) 15W (GU-24)
ALL "EX" EMERGENCY & EXIT LIGHTING FIXTURES SHALL BE
CONNECTED AHEAD OF ROOM/AREA SWITCHES PER
NATIONAL ELECTRICAL CODE (NEC) ARTICLE 700-12(f).
ELECTRICAL CONTRACTOR SHALL VERIFY EXACT SIGN(S) WIRING
REQUIREMENTS WITH THE SIGN SUPPLIER PRIOR TO SUBMITTING
A BID FOR THE ELECTRICAL.
PROVIDE 2P/30A NEMA 3R, FUSED DISCONNECT SWITCH W/
LIQUID-TIGHT FLEXIBLE CONNECTION TO PYLON SIGN. FUSE
SIZE PER SIGN MFR'S RECOMMENDATION.
PROVIDE RACEWAYS, WIRING, AND LAMPS (F40T8) FOR ALL LIGHT
FIXTURES FURNISHED W/ THE FREEZER/COOLER/STORAGE UNIT.
LIGHT FIXTURES SHALL BE INSTALLED BY ELECTRICAL
CONTRACTOR. COORDINATE THE INSTALLATION OF SWITCHES AND
PLATES WITH THE EQUIP. SUPPLIER.
G.C. TO VERIFY EXACT ELECTRICAL REQUIREMENTS FOR ILLUMINATED
SITE/MONUMENT SIGN STRUCTURE W/ SIGN SUPPLIER PRIOR TO
INSTALLATION. G.C. TO PROVIDE FINAL ELECRICAL HOOK-UP.
TO SITE LIGHTING -
TYPICAL. SEE SITE
PLAN TO VERIFY
LOCATION AND
QUANTITY. SEE NOTE 7
LP
LP
1. THE LIGHTING CONTACTORS
SHALL BE HELD MAGNETICALLY IN A
NEMA 1 ENCLOSURE. THE SIGN &
CANOPY LIGHTING SHALL BE SET TO
COME ON FIRST, EVEN ON
RAINY/CLOUDY DAYS AND THE
PARKING LOT LIGHTING SHALL BE
SET TO COME ON LATER. THE
CONTROLS SHALL BE WIRED SO
THAT EACH GROUP OF LIGHTING
(SIGNAGE/CANOPY ADN PARKING
LOT) IS INDEPENDENT, AND MAY BE
MANUALLY SWITCHED OFF AT
CLOSING WITH ITS SELECTOR
SWITCH VIA TIME DELAY RELAY -
SEE CONTACTOR DIAGRAM DETAIL
THIS SHEET.
SET FOR DUSK
OR RAINY/CLOUDY
DAYS; MOUNT ON
SET FOR DARK,
R1
LOCATE SEL. SWITCH
CONTROLS FOR LC-1, LC3
LIGHTING CONTACTORS, AND
PUSHBUTTON CONTROL FOR
LC-2 LIGHTING CONTACTOR
AT THIS LOCATION
VERIFY LOCATION
ON SITE PLAN
PREVIEW BOARD ON
CLEARANCE SIGN
DRIVE-THRU
MENU BOARD
TO DIRECTION SIGNS. VERIFY LOCATIONS AND
QUANTITY OF SIGN ON SITE PLAN.
2
3 D1
D
BALCONY RECESSED SOFFIT LIGHT
SECURITY
SECURITY
851-DL-100MH-FP-WH-120
MIC100MHEV/RL6009 EVERGREEN
(1) MH100/U/MED
(1) MH100/U/MED
VERIFY THE EXACT LOCATION OF SIGNS, AND FASCIA
BOXES BEFORE INSTALLATION OF JUNCTION BOXES.
HOMERUNS MAY BE COMBINED AS ALLOWED BY THE NATIONAL
ELECT. CODE ALL CONDUIT SHALL BE SIZED PER THE 2002 NEC.
ELECTRICAL CONTRACTOR SHALL VERIFY THE LOCATION OF
THE PYLON SIGN ON THE SITE PLAN.
THE BUILDING SIGNAGE, PYLON SIGN, FASCIA LIGHTING,
BUILDING SIGN LIGHTING, DRIVE-THRU MENUBOARD(S), AND SITE
LIGHTING SHALL BE WIRED THRU THE LIGHTING CONTACTORS
FOR AUTOMATIC & MANUAL CONTROL.
J-BOX ON HOOD FOR PRE-WIRED HOOD LIGHTS.
NOT USED.
ROUTE CIRCUIT VIA EXTERIOR/SIGN LIGHTING CONTACTOR
(SEE CONTROL SCHEMATIC DIAGRAM SHEET E1.
FIXTURE TYPE "B1" EQUIPPED WITH EMERGENCY LIGHTING BATTERY
PACK, THE BATTERY PACK SHALL BE WIRED AHEAD OF ANY SWITCHES.
36"x8"x8" SHEET METAL GUTTER FOR BALLAST AND CAPACITORS FOR
FIXTURES "H". MOUNT GUTTER ABOVE CEILING TO INTERIOR STUDS.
LOCATE LIGHTING AND
FAN ON/OFF CONTROL
SWITCHES "a, b, c, d & e"
AT THIS LOCATION
H
38
LTG CONT. LC-1, 2 &
3 CONTACTORS, SEE
DIAGRAM THIS
SHEET & POWER
RISER SHEET E3.
(1) 15W
(3) 15W
WHITE
WHITE
J-BOX FOR SPEAKER AT
10'-4" A.F.F.,
CENTERLINE
SHUTTER UPLIGHT / CUSTOM COLOR
CAST ROUND BOX COVER FOR FIXTURE
B-15
SIGN ACCENT
VIA LC1
J-BOX FOR SPEAKER
AT 14'-6" A.F.F.,
CENTERLINE
J-BOX FOR SPEAKER AT
14'-6" A.F.F.,
CENTERLINE
B-32
VIA
LC-3
PYLON SIGN -
REFER TO SITE
PLAN FOR SEE
NOTES 5 & 7
RECESSED SPEAKERS* (DINING)
RECESSED SPEAKERS* (KITCHEN)
OUTDOOR BOX SPEAKERS*
AMPLIFIER
SPEAKER SUPPORT
SPEAKER BACKCAN
CABLE, CONNECTORS, HARDWARE AND
SHELF
AREA VOLUME CONTROL
RECEIVER
DISH
7 LL3 PENDENT HERMITAGE FLAVORIETY
ER
ER3
EM4 EMERGENCY LIGHTING UNIT
REMOTE EMERGENCY LIGHTING UNIT
(2) BLUE
(3) AMBER
(2) RED
26W TRT
WALL PACK w/ PHOTO CELL (REAR DOOR)WP1 SWP-100MH-DB-MT BRONZE (1) MH100/U/MEDSECURITY
PENDENT
PENDENT HERMITAGE
WP
C9
26W TRIPLE TUBE
6" RECESSED WALLWASHER WHITE
ALL LIGHT FIXTURES LISTED IN THE ABOVE SCHEDULE SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR,
EXCEPT AS NOTED IN PARAGRAPH, PART 1.1.C OF ELECTRICAL SPECIFICATIONS.
PLEASE CONTACT HERMITAGE LIGHTING FOR INFORMATION ON LIGHTING PACKAGE, TEL. (800) 264-3383
(BY SIGN SUPPLIER/BALCONY)
4. BALLAST LOCATION FOR GOOSE NECKS INSTALLED PER N.E.C.
WHITE
JUNO PL642EU-261B-WH
RED
LL90
LL50H-N4EXITRONIX
EXITRONIX WHITE
WHITE (1) 5W
(2) 5W
LL2
66" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
LL2
84" AFF
LL2
84" AFF
LL2
84" AFF
LL2
84" AFF
LL1
66" AFF
LL1
66" AFF
LL1
66" AFF
E12 MANSARD WALL MOUNT UNIT PNK126Q-120N-JCTERON CLEAR (1) 26W
LL2
66" AFF
CRABPOT LIGHTS AT "P" COUNTER TO BE MOUNTED 84" ABOVE FINISH FLOOR.
NOTE:
PENDANT and CRABPOT LIGHTS AT TABLES TO BE MOUNTED 66" ABOVE FINISH FLOOR.
LL1
84" AFF
LL1
84" AFF
CHECKED:
DATE:
PO
PE
YE
S
LK
1
26
0-D
L-P
LU
S P
RO
TO
TY
PE
E.I.F
.S
. / S
IM
UL
AT
ED
S
TO
NE
LO
UIS
IA
NA
K
IT
CH
EN
L
K-P
LU
S D
ES
IG
N S
TA
ND
AR
DS
60 S
EA
TS
/ D
UA
L-L
IN
E P
RO
DU
CT
IO
N
E1
1
LIGHTING PLAN
1/4"=1'-0"
E1
2
DETAIL(PE CONTROL FOR FIXTURE 'WP')
1/4"=1'-0"
E1
3
LIGHTING CONTACTOR DIAGRAM
1/4"=1'-0"
LIGHTING PLAN
E1
04/17/15
KR
REVISIONS:
24"x
60"
5-TI
ER
21"x
54"
4-TI
ER
24"x
54"
4-TI
ER
TRASH
PLAN (SD2) FOR
REFR TO SITE
EXACT LOCATION
FINISHED FLOOR
CEILING GRID
AT 6" ABOVE FINISHED CEILING.
CONDUIT BUSHING WITH TERMINATION
CABLE/S
@ 24"A
,F
,F
,
SINGLE
U.O
.N
.
TEL
DUAL/DOUBLE
TEL
DATA
PULL STRING AS NOTED.
1" OR 3/4" CONDUIT WITH
RECESSED SINGLE GANG
ELECTRICAL BOX.
C
PARTIAL EQUIPMENT SCHEDULE
CO Convenience Outlet 115 1 X
2'-6"
(MIN.)
2'-0"
IN CONC. DRIVE WITHIN 24"
OF PREFAB LOOP
OMIT WIRE REINFORCING MESH
EXTERIOR MENUBOARD
SEE SITE PLAN FOR
ORIENTATION
NOTE: REFER TO MFR. LITERATURE
INSTRUCTIONS FOR PREFAB LOOP
LITERATURE FOR SPECIFIC INSTALLATION
PRE-FAB DETECTOR LOOP
SUPPLIED & INSTALLED BY G.C.
W/ 3/4" BUSHING
WIRELESS DRIVE-THRU
CENTER MODULE
(WALL MOUNTED)
CIRCUIT B-22
120 VOLT DUPLEX
FIN. FLOOR
LOOP DETECTOR
SPEAKER POST.
3/4" CONDUIT TO
VERIFY LOCATION
ON SITE PLAN.
4"x4" J-BOX
COUNTER TOP
HOLE FOR SIGNAL
OUTLET BOX"
"PROVIDE STAINLESS
STEEL COVER PLATE
CEILING GRID
COORDINATE WITH SHEET K2.
SIGNAL 4"x4" J-BOX
Front Service Counter
NOTES:
1. FOR DIRECT CONNECTION EQUIPMENT A LOCAL
DISCONNECTING MEANS SHALL BE PROVIDED IN
ACCORDANCE WITH NEC & LOCAL CODE REQUIREMENTS.
backsplash w/ u/s
POWER PLAN KEY NOTES
REFER TO FOOD SERVICE DRAWING K1 FOR
TAG LOCATIONS NOT SHOWN THIS SHEET.
REFER TO HVAC DRG. M1 FOR EXACT LOCATIONS
FOR MECHANICAL HVAC EQUIPMENT.
3P30A NEMA 3R FUSED DISC. ON WALK-IN COND.
UNIT LOCATED ON ROOF. FUSE PER EQUIPMENT
NAMEPLATE. LIQUID TIGHT FLEX CONNECTION.
MAKE FINAL POWER CONNECTION TO WALK-IN
COOLER EVAPORATOR, PROVIDE MOTOR
SWITCH IN CAST BOX.
MAKE FINAL POWER CONNECTION TO WALK-IN
FREEZER FREEZER EVAP., DEFROSTER, HEAT
TAPE & DOOR HEATER.
PROVIDE LOCAL 3P60A NEMA 3R NON-FUSED
DISC SW. ON A/C RTU'S LOCATED ON ROOF
EQUIP. NAMEPLATE. PROVIDE LIQUID TIGHT
FLEX CONN. TO UNIT.
PROVIDE GFCI PROTECTED 5-20R DUPLEX
RECEPT. INSTALLED IN WP BOX W/ WP
COVER AT RTU. (TYP).
PROVIDE 120V WIRING TO DUCT MOUNTED
SMOKE DETECTORS AND REMOTE
TEST/INDICATORS. FOR EXACT LOCATIONS
OF DUCT DETECTORS, REMOTE INDICATORS
& TEST SW'S. (SEE HVAC PLANS).
E.C. SHALL INSTALL AND WIRE RELAY CONTROL
PANEL PACKAGE FOR HOOD EXHAUST FANS EF-1
AND EF-2. PROVIDE POWER AND INTERLOCK
CONTROL WIRING FOR HP1-F CONTROL PANEL
AND HOOD FIRE SUPPRESSION SYSTEM. SEE
HOOD FAN CONTROL INTERLOCK WIRING DIAGRAM.
SHEET M2. MOUNT STARTERS AND CONTROLS ON
WALL.
"ON/OFF" SELECTOR SWITCH AND PILOT LIGHT
IN NEMA 4X STAINLESS STEEL ENCLOSURE
MOUNTED ON THE FACE OF THE HOOD.
PROVIDED BY HOOD MFR.
PROVIDE 2P30A NEMA 3R FUSED DISC
SWITCH & L.T. FLEX CONNECTION TO ROOF
MTD ICE MAKER COND UNIT, FUSE SIZE PER
MFG'S NAMEPLATE DATA.
PROVIDE CEILING OUTLET W/ISOLATED
GROUND RECEPTACLES SUPPORTED FROM
BLDG. STRUCTURE FOR VIDEO
MONITOR/PRINTER & OR HEADSET. VERIFY
EXACT REQUIREMENTS & LOCATION.
PROVIDE 3/4" x 18" H x 24" W PLYWOOD TELEPHONE
BOARD PAINTED WITH 2 COATS OF "LISTED" FIRE
RETARDANT LIGHT GRAY COLOR PAINT. AT 96" A.F.F.
PROVIDE QUAD RECEPTACLE ADJACENT TO BOARD.
PROVIDE # 6 CU, GROUND TO SERVICE ENTRANCE
GROUND, SEE DETAIL ARCHITECTURAL ELEVATIONS.
PROVIDE CEILING DROPS FOR PRODUCTION
COUNTER BRANCH CIRCUITS TO CEILING
MOUNTED J-BOXES TO SERVE ALL ELECTRICAL
IN CTR.
PRODUCTION COUNTER ELECTRICAL POWER
CIRCUITS: REFER TO PANEL SCHEDULE "C" FOR
CIRCUIT NO'S. REFER TO EQUIPMENT SUPPLIER
SHOP DRAWINGS FOR EXACT LOCATIONS AND
TYPE OF CONNECTIONS FOR EQUIPMENT AND
HEAT LIGHTS IN/OR ON PRODUCTION
COUNTER.
BRANCH CIRCUIT(S) CONTINUED TO
ADDITIONAL OUTLETS, HOMERUN SHOWN
FOR CLARITY ONLY.
OUTLET AND CONNECTION FOR SECURITY
CAMERA. VERIFY EXACT LOCATIONS AND
TYPE CONNECTIONS FOR INDOOR AND
OUTDOOR CAMERAS WITH G.C..
ROUTE ALL CONDUIT ROOF PENETRATIONS
THRU (WITH-IN) ROOF CURBS FOR THE
EQUIPMENT. REFR TO MECH. PLANS FOR
CURB DETAILS. (TYPICAL)
PROVIDE 1" CONDUIT TO 6" ABOVE
CEILING.
HOOD ANSUL FIRE SUPPRESION
SYSTEM.
MAKE FINAL CONNECTION TO
EQUIPMENT
OFFICE EXHAUST FAN SHALL BE INTERCONNECTED TO
OPERATE WITH AREA LIGHTING. INTERLOCK EXHAUST
FAN WITH LIGHTS.
P.O.S. NOTES:
1. ALL P.O.S. (POINT OF SALE) CIRCUITS SHALL HAVE
AN ISOLATED GROUND WIRE BACK TO THE PANEL.
ALL P.O.S. EQUIP. SHALL BE WIRED
INDEPENDENTLY OF ANY NON-P.O.S. EQUIPMENT.
2. ALL RECEPTACLES FOR P.O.S. EQUIPMENT SHALL
BE ISOLATED GROUND WITH SURGE SUPPRESSOR
TYPE. ALL RECEPTACLES FOR P.O.S. EQUIPMENT
SHALL BE SINGLE UNIT, UNLESS A DUPLEX
RECEPTACLE CAN BE USED TO SUPPLY TWO P.O.S.
UNITS. DUPLEX RECEPTACLES MAY BE USED IN
THE MANAGER'S OFFICE FOR NON-P.O.S.
EQUIPMENT (COMPUTER, MUSIC, FIRE ALARM,
SECURITY, ETC.)
3. ALL CIRCUITS FOR P.O.S. EQUIPMENT SHALL BE
CONNECTED TO THE SAME PHASE OF POWER IN
THE PANEL. ALL BRANCH CIRCUIT BREAKERS
SUPPLYING P.O.S. EQUIPMENT SHALL HAVE
LOCKING HANDLES DEVICES.
4. EACH RECEPTACLE TYPE (LOCKING OR STRAIGHT
BLADE) SHALL MATCH THAT OF THE EQUIPMENT
FURNISHED. WHERE P.O.S. EQUIPMENT IS
FURNISHED WITHOUT A PLUG THE RECEPTACLE
SHALL BE LOCKING TYPE. COORDINATE
RECEPTACLE TYPES WITH THE P.O.S. EQUIPMENT
SUPPLIER.
GENERAL NOTES:
A. VERIFY MOUNTING HEIGHTS OF ALL
RECEPTACLES WITH EQUIPMENT SUPPLIED PRIOR
TO INSTALLATION.
B. ALL EQUIPMENT ELECTRICAL OUTLETS ARE
DIMENSIONED TO CENTERLINE OF BOX FROM
ABOVE FINISHED FLOOR.
C. ELECTRICAL CONTRACTOR TO PROVIDE CORD &
PLUG CONNECTIONS FOR EQUIPMENT AS
REQUIRED.
1" CONDUIT
INTERLOCK W/ RTU-2
FOR DRIVE-THRU
AUDIO SYSTEM
SEE DETAIL 4
WP
SP
SPEAKER
POST
FLOOR TO CENTERLINE
48" DENOTES MOUNTING
HEIGHT ABOVE FINISHED
(TYPICAL-INTERIOR OF BLDG.)
OF OUTLET BOX.
E.C. SHALL WIRE &
CONNECT G.C.
PROVIDED REMOTE
ANSUL PULL STATION
E.C. SHALL PROVIDE
3/4" C. STUBBED
ABOVE CEILING FOR
ANSUL SYSTEM
FOR HEAT TRACE AT
GREASE RECOVERY
UNIT. (VERIFY EXACT
LOCATION)
FOR IRRIGATION
CONTROLLER,
(VERIFYEXACTLOCATION)
WP
THIS SHEET
RUN 2 - 2" CONDUITS FROM
TELEPHONE EQUIPMENT BOARD
TO A LOCATION COORDINATED
WITH LOCAL TELEPHONE
COMPANY, OWNER REQUIREMENT
SERVICE CONDUITS SHALL BE
SIZED FOR 25 PAIR (MINIMUM).
TELEPHONE SERVICE CABLE,
CONDUITS SHALL BE INSTALLED
WITH PULLWIRE. CONDUITS RISE
FROM U.G. INSIDE EXTERIOR WALL
AND TURN-OUT WITH 90 DEG ELLS
INSIDE BLDG. AT TERM. BD. SEE
ARCHITECTURAL ELEVATIONS.
OWNER REQUIRED SEPERATE
TELEPHONE SERVICE LINES TO
BUILDING:
(1) LINE FOR VOICE
(1) LINE FOR SECURITY
(1) LINE FOR CREDIT CARD
(1) LINE FOR CASH REGISTER
(1) LINE FOR COMPUTER LINES
E.C. SHALL CONNECT
G.C. PROVIDED DOOR
FLY FAN
E.C. SHALL INSTALL
AND WIRE-G.C.
PROVIDED MICRO
SWITCH IN IN DOOR
FRAME FOR ON/OFF
CONTROL OF DOOR
FLY FAN
TO CENTERLINE OF OUTLET
BOX. 102" DENOTES MOUNTING
HEIGHT ABOVE FINISHED
GRADE/WALKWAY/PAVEMENT
(TYPICAL-EXTERIOR OF BLDG.)
REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT
DIMENSIONED LOCATIONS FOR ALL WALL OUTLETS
POWER CO
METER & MAIN -
SEE RISER
DIAGRAM SHT E3
FOR HEAT TRACING
IN THE COOLER.
NOTE: REFER TO OFFICE ELEVATION
ON SHEETS A12 & A16.
SERVICE SIGN &
PUSH BUTTON
WP J-BOX & DISC SW
4 WIRE TO GREASE
CONTAINER
FOR HEAT TRACING
IN THE FREEZER.
120V / 1ph - To recp't
mounted under sink
120V / 1ph - To recp't
mounted under sink
CHECKED:
DATE:
PO
PE
YE
S
LK
1
26
0-D
L-P
LU
S P
RO
TO
TY
PE
E.I.F
.S
. / S
IM
UL
AT
ED
S
TO
NE
LO
UIS
IA
NA
K
IT
CH
EN
L
K-P
LU
S D
ES
IG
N S
TA
ND
AR
DS
60 S
EA
TS
/ D
UA
L-L
IN
E P
RO
DU
CT
IO
N
E2
1
ELECTRICAL POWER PLAN & DETAILS
1/4"=1'-0"
E2
2
TYP COMM. STUB UP DETAIL
NTS
E2
3
DRIVE-THRU LOOP DETECTOR
NTS
E2
4
DRIVE-THRU AUDIO / TIMERS
NTS
POWER PLAN
E2
04/17/15
KR
REVISIONS:
Current sensors are factory wired but must be
field adjusted for proper operation. With the hood exhaust
fans running, spin the potentiometer dials counterclockwise
until the status "OFF" green LED lights and cooking
equipment contactors de-energize. Then turn dials back
clockwise one full turn. If the current sensors are improperly
adjusted, cooking equipment may not shut off should a
hoods exhaust fan fail. If the cooking equipment fails to
operate while the hood switches are on and the exhaust
fans are running, spin the appropriate setpoint dial
clockwise until the status "ON" red LED lights.
DRW: S. BROADBEAR
REV 2.0
C 2012
PH: (727) 544-6679FX: (727) 544-6670
R
Y1
W1
COOLING
HEATING
24V POWER
R-3,4
R-5,6
R-1,2
RED
GRN
ROOFTOP UNIT
TERMINALS
S.E.C.
FIRE INTERLOCK
TERMINALS
LOW VOLTAGE A/C CONTROL
FIELD WIRING DETAIL
BURGER KING LOW VOLTAGE WIRING CONNECTIONS
DATE: 7 / 19 / 2012
R
G
R
CK1
CKGND
Y1
Y2
W1
W2
C
W2
C
HEATING ST. 2
COMMON
G FAN CONTROL
Y2 COOLING ST. 2
W2
G
Y1
W1
FAN CONTROL
COOLING
HEATING
HEATING ST. 2
CK
CK1 CK 1
CK GND
THERMOSTAT VENSTAR T-2700
R 24V POWER
MISC COOLING ST. 2
C 24V COMMON
UNIT
STAT
1
YEL
BLU
WHT
BLK
BRN
GND
RS+5
RS1
RS GND
RS+5
RS1
RS GND
REMOTE TEMP.
SENSOR ACC0400
(OPTIONAL)
REMOTE SENSOR
REMOTE SENSOR
REMOTE SENSOR
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
ON W/PHOTOCELL IN AUTO,ON/OFF WITH O/R SWITCH,TIMED DELAY TO OFF WITHSECURITY DEPARTURESWITCH
C - 1
C - 2
C - 3
BUILDING/SIGN LTS.
LOT POLE LTS.
LOT POLE LTS.
C - 4
BUILDING/SIGN LTS.
C - 5
BUILDING/SIGN LTS.
ON/OFF W/ PHOTOCELL INAUTO,
ON/OFF WITH O/R SWITCH
C - 7
UNDER HOODFRYER
COOKING EQUIP.
C - 6
UNDER HOODBROILER
COOKING EQUIP.
ON/OFF WITH BROILEREXHAUST FAN SW.
(15MIN. DELAY TO OFF)(ON UPON
INTERRUPTION OF FIRESUPPRESSION LOOP )
MS-1
BROILER HOODEXAUST FAN-1
MS-2
FRYER HOODEXAUST FAN-2
ON/OFF WITH FRYEREXHAUST FAN SW.
(ON UPONINTERRUPTION OF FIRE
SUPPRESSION LOOP)
ON/OFF WITH BROILEREXHAUST FAN SW.
(OFF UPONINTERRUPTION OF FIRE
SUPPRESSION LOOP)
C - 8
REFRIGERATOR/FREEZER/GAS
VALVE
ALWAYS ON EXCEPTUPON INTERRUPTION
OF FIRE SUPPRESSIONLOOP
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
4 P
OL
E C
ON
TA
CT
OR
12
0V
C
OIL
3
0 A
MP
R
ES
.
CO
IL
A
2
N.C
.
N.O
.
R-7FIRE INT.
CO
IL
A
1
12
11
10
9
43
21
87
54
CO
IL
A
2
N.C
.
N.O
.
R-8EF-1
INTERLOCK
CO
IL
A
1
12
11
10
9
43
21
87
54
CIRCUIT - -
CIRCUIT - ___ - ___ LOT POLE LIGHTSCIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
5678
34
21
CIRCUIT - -
CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
9101112CIRCUIT - -
CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
13141516CIRCUIT - -
CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
17181920CIRCUIT - -
CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
21222324CIRCUIT - -
CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
25262728CIRCUIT - -
CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
29303132CIRCUIT - -
CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
33343536CIRCUIT - -
CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
37383940CIRCUIT - -
CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___CIRCUIT - ___ - ___
LOT POLE LIGHTS
BLDG./SIGN LTS.
BLDG./SIGN LTS.
BLDG./SIGN LTS.
UNDER HOOD EQUIP.
FRYER
REFRIGERATORFREEZER
GAS VALVE
FRYER FAN EF-1FRYER FAN EF-1
FRYER FAN EF-2FRYER FAN EF-2
5678
34
21
910111213141516171819202122232425262728293031323334353637383940
AIROTRONICS
TH3P103HAS1
120V AC 1AMP
1 2 3
4
5
5678
34
21
910
NEUTRAL
BUILDING LIGHTS (AUTO)
FIRE INT. 120V LOOP
120VAC CONTROLLOT LIGHTS (AUTO)
LOT LIGHTS (ON)
BUILDING LIGHTS (ON)EX. FANS / COOK EQUIP.
A/C 120V INTERLOCK
L1NNEUTRAL
120VAC CONTROL POWER
P5P6
P3P4
P2P1 PHOTOCELL NEUTRAL
PHOTOCELL LINEPHOTOCELL LOADPHOTOCELL NEUTRALPHOTOCELL LINEPHOTOCELL LOAD
LOT LIGHTS PHOTOCELL
BLDG. LIGHTS PHOTOCELL
INCOMING CONTROL POWER
ROUTE TO TB 6 IN ON/OFF CONTROL PANEL
A1A2
FIRE INTERLOCK (COM.)FIRE INTERLOCK (N.C.)
ROUTE TO HOODS MICROSWITCHES
LOAD SIDE
GROUND
ON/OFF WITH FRYEREXHAUST FAN SW.
(OFF UPONINTERRUPTION OF FIRE
SUPPRESSION LOOP)
F1F2
NEUTRALOPT. ELECT FRY CONT.
ROUTE TO OPTIONAL ELECT. FRY PANEL
LINE SIDE
MOMENTARY
SWITCH FOR O/R
TDR#2
ORG
ORG
BLU
YEL
PUR
BRN ORG
RED
GRY
BLK
BLK
BLK
BLK GRY
PUR
BLU
TB-4
OPTIONAL ELECTRIC FRYER PANEL NEUTRAL
OPTIONAL ELECTRIC FRYER PANEL POWER
C 2012
PH: (727) 544-6679FX: (727) 544-6670
PANEL WIRING
FIELD WIRING
NO CONNECTION
CONNECTION
BRN
BRN
BRN
BRN
ORG
YEL
RED
BLK
WHT
WHT
WHT
WHT
WHT
WHT
WHT
WHT
WHT
WHT
WHT
WHT
BRN
ORG
YEL
RED
WHT
WHT
INTERMATIC
MOD# K4221C
UNOCCUPIED OCCUPIED AUTO OFF ON AUTO OFF ON
LOT LTS.BLDG LTS.KITCHEN A/C
SECURITY DEPARTURE SWITCH
BUILDING CONTROL
OFF ON
UNOCCUPIED OCCUPIED
DINING A/C
EXHAUST FANS
AIROTRONICS
TH3P103HAS1
120V AC 1AMP
TDR#1
TIME DELAY RELAY
1 2 3
7
6
15 P
IN
C
AB
LE
CONT
ROL
CIRC
UIT
BREA
KER
(2A)
KITCHEN A/C UNIT #____
(R) FROM A/C UNIT
G FAN CONTROL
Y-1 COOLING -1
Y-2 COOLING -2
W-1 HEATING -1
W-2 HEATING -2
C- 24V COMMON
(CK1) THERMOSTAT
RU
(R) TO THERMOSTATRT
G
Y1
Y2
W1
W2
C
CK1
(CKGND) THERMOSTAT
CK-
GND
KITCHEN A/C UNIT #____
DINING A/C UNIT #____
DINING A/C UNIT #____
DINING A/C UNIT #____
NEUT
RAL
BUIL
DING
LIG
HTS
(AUT
O)
FIRE
INT.
120V
LOO
P
5 6 7 83 421 9 10
GROU
ND
120V
AC C
ONTR
OLLO
T LI
GHTS
(AUT
O)LO
T LI
GHTS
(ON)
BUIL
DING
LIG
HTS
(ON)
EX. F
ANS
/ COO
K EQ
UIP.
A/C
120V
INTE
RLOC
K
RO
UT
E F
RO
M T
B#2 IN
M
AS
TE
R R
EL
AY
P
AN
EL
(R) FROM A/C UNIT
G FAN CONTROL
Y-1 COOLING -1
Y-2 COOLING -2
W-1 HEATING -1
W-2 HEATING -2
C- 24V COMMON
(CK1) THERMOSTAT
RU
(R) TO THERMOSTATRT
G
Y1
Y2
W1
W2
C
CK1
(CKGND) THERMOSTAT
CK-
GND
(R) FROM A/C UNIT
G FAN CONTROL
Y-1 COOLING -1
Y-2 COOLING -2
W-1 HEATING -1
W-2 HEATING -2
C- 24V COMMON
(CK1) THERMOSTAT
RU
(R) TO THERMOSTATRT
G
Y1
Y2
W1
W2
C
CK1
(CKGND) THERMOSTAT
CK-
GND
(R) FROM A/C UNIT
G FAN CONTROL
Y-1 COOLING -1
Y-2 COOLING -2
W-1 HEATING -1
W-2 HEATING -2
C- 24V COMMON
(CK1) THERMOSTAT
RU
(R) TO THERMOSTATRT
G
Y1
Y2
W1
W2
C
CK1
(CKGND) THERMOSTAT
CK-
GND
(R) FROM A/C UNIT
G FAN CONTROL
Y-1 COOLING -1
Y-2 COOLING -2
W-1 HEATING -1
W-2 HEATING -2
C- 24V COMMON
(CK1) THERMOSTAT
RU
(R) TO THERMOSTATRT
G
Y1
Y2
W1
W2
C
CK1
(CKGND) THERMOSTAT
CK-
GND
COIL A2
N.C.
N.O.
COIL A1
12 11 10 9
4 3 2 1
8 7 5 4
R-1
KITCHEN
SETBACK
COIL A2
N.C.
N.O.
COIL A1
12 11 10 9
4 3 2 1
8 7 5 4
COIL A2
N.C.
N.O.
COIL A1
12 11 10 9
4 3 2 1
8 7 5 4
COIL A2
N.C.
N.O.
COIL A1
12 11 10 9
4 3 2 1
8 7 5 4
COIL A2
N.C.
N.O.
COIL A1
12 11 10 9
4 3 2 1
8 7 5 4
COIL A2
N.C.
N.O.
COIL A1
12 11 10 9
4 3 2 1
8 7 5 4
R-2
DINING
SETBACK
R-3
KITCHEN
A/C FAN
R-4
DINING
A/C FAN
R-5
A/C
FIRE INT.
R-6
A/C
FIRE INT.
HVAC INTERLOCK PANELNFPA-96 COMPLIANT
N C A
CHECKED:
DATE:
PO
PE
YE
S
LK
1
26
0-D
L-P
LU
S P
RO
TO
TY
PE
E.I.F
.S
. / S
IM
UL
AT
ED
S
TO
NE
LO
UIS
IA
NA
K
IT
CH
EN
L
K-P
LU
S D
ES
IG
N S
TA
ND
AR
DS
60 S
EA
TS
/ D
UA
L-L
IN
E P
RO
DU
CT
IO
N
POWER PLAN
E2a
04/17/15
KR
REVISIONS:
1.
GENERAL NOTES:
GND
12
12
12
12
12
12
12
12
12
12
12
SERIES/INTEGRATED RATING
-
12
12
WIRE SIZE
SERIES/INTEGRATED RATING
225 AMP MAIN LUGS ONLY
1P-20
121212TOASTER (C20)
PROVIDE SCREW-ON BREAKER LOCK DEVICE.
PROVIDE SEPARATE GROUND CONDUCTOR IN ALL CONDUITS
TOTALS
NOTES:
(2)
(1)
SPARE
SPACE
FREEZER EVAP (E10)
FREEZER (A54)
HOLD CABT. (D90)
REFRIG. BATTER (A47.4)
SANDWICH (A53.27)
---
PRODUCT ASSEM. (C40)
SPARE
SPARE
SPACE
---
MICROWAVE (D20)
(2)
(2)
(2)
-
10
-
-
-
-
-
- -
-
-
-
10
41
37
39
1P-20
1P-20
1P-20
-
-
-
-
-
-
-
-
31
33
35
27
29
10
12
-
12
12
12
12
1P-20
10
-
10
12
-
12
-
12
1P-25
2P-20
23
25
1P-20
21
19
12
12
12
12
12 12
13
1P-20
1P-20
17
15
1P-20 11
9
12,60811,3329,348
504
-1180
-
1180
2000
1180
-
624
1180
624
376
300
900
- 600
1440
1500
684
100
1212
1P-15
20001180
-
1180
1000
2P-30
42
38
40
8
2P-30
1P-2O
2P-30
32
34
36
28
30
8
8
12 12
2110 100
1600
780
540
600
1P-20
1P-20
1P-20
1P-20
24
26
22
20
12
12
12
12
12
12
12
12
1P-20
1P-20
1P-20
1P-20
1P-20
14
18
16
12
10
12
12
12
12
12
12
12
12
12
12
121P-20360 12390
15
1P-20FRONT SIGN
PROVIDE SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS
PROVIDE SCREW-ON BREAKER LOCK DEVICE.
LIGHTING BRANCH CIRCUIT BREAKERS SHALL BE LISTED FOR SWITCHING DUTY
120/208 VOLTS - 3 PHASE - 4 WIRE - SOLID NEUTRAL
MARINATOR (A31)
CARBONATORS (K42)
FRYER HOOD (EF-2)
LOAD DESCRIPTION
FRYER HOOD (EF-1)
FLUSH MOUNTED - EQUIPMENT GROUND BAR & ISOLATED EQUIPMENT GROUND BAR
CIRCUIT SCHEDULE
WIRE SIZE
PH
12
12
12
12
NOBKRGNDN
12
12
12
12
12
12
12
12
1P-20
1P-20
7
5
1P-20
1P-20
1
3
CKT CKT
VIDEO MONITORS
PYLON SIGN
PYLON SIGN
FLY FAN
SPARE
SPACE
SPACE
SODA DISP'S (K32F)
RECS-G.P.(FRONT CNTR)
POS SYSTEM
SPARE
SECURITY SYS
(2)
(1)
NOTES:
(2)SAFE (M30)
TOTALS
1P-20
1P-20
12
10
10
12
12
12
12
12
-
1212
-
12 12
-
12
12 12
12
1P-20
1P-20
1P-20
1P-20
1P-20
10
12
10
12
10
12 12
10
1P-20
1P-20
1P-20
1P-20
CONN. LOAD (VA)
1728
1320
100
600
PH A
1320 300
PH B
PANEL "A"
10,000 A.I.C.
600 1150
PH C
NPHNO BKR
1P-20
1P-15
1P-20
1P-20
8
6
2
4
12
12
12
12
12
12
12
12
CKT CKT
SQUARE D "NQOD"
11,040
1000
39
41
35
37
780
7,280
--
360
600
29
31
33
25
27
1125
1200
21
23
19
17
100
790
1200 1200
9,754
-
-
42
40
36
38
12
1P-20
1P-20
1P-2012
720
30
790
32
34
26
28
1420
720
600
22
24
500
20
18
-
1P-20
1P-20
1P-20
1P-20
1P-20
-
12
12
12
12
1P-20
1P-20
1P-20
1P-20
12
12
12
12
120/208 VOLTS - 3 PHASE - 4 WIRE - SOLID NEUTRAL
LIGHTING BRANCH CIRCUIT BREAKERS SHALL BE LISTED FOR SWITCHING DUTY
LOAD DESCRIPTION
CIRCUIT SCHEDULE
FLUSH MOUNTED - EQUIPMENT GROUND BAR & ISOLATED EQUIPMENT GROUND BAR
DIGITAL MENUBOARD (Q11)
SODA DISP'S (K31)
KITCHEN & R.R'S. LTG
DINING - PAD FANS
KITCHEN & SALES LTG
TEA BREWER (K74)
RTU RECS & DUCT DET'S
(2)
CKTWIRE SIZE
PH
12
12
12
12
12
12
12
12
1212
12
12
12
12
12
12
12
12
1P-20
1P-20
1P-20
1P-20
GND
12
12
12
12
12
N
12
1P-20
1P-20
BKR
1P-20
PH A
CKT
PH B
600
1380
11
13
7
9
360
360
3
5
NO
1 1384
600500
1000 700
CONN. LOAD (VA)
PANEL "B"
CKTCKTPH C WIRE SIZE
1920
12
500
14
16
8
10
1264 360
4
6
NO
2
12
12
12
12
1P-20
1P-20
1P-20
1P-20
12
12
12
12
PH
12
12
12
1P-20
1P-20
BKR
1P-20
12
12
12
N
SQUARE D "NQOD"
10,000 A.I.C.
225 AMP MAIN LUGS ONLY
PROVIDE SEPARATE GROUND CONDUCTOR IN ALL CONDUITS
PROVIDE BREAKER LOCK DEVICE FOR CIRC'S. #8 & 14.
MAIN BREAKER SHALL BE LISTED FOR AVAILABLE FAULT CURRENT
(ESTIMATED 42,000 A.I.C.) AND FEEDER BREAKERS SHALL BE SERIES LISTED
TO ALLOW USE OF 10,000 A.I.C. DOWNSTREAM BRANCH OR FEEDER BREAKERS
TO MAINTAIN AVAILABLE FAULT CURRENT RATING.
(2)
(1)
(3)
----
SPARE
----
---
---
---
---
PANEL "A"
---
---
---
PANEL "C"
PANEL "B"
SPACE
SPACE
---
SPACE
(2)
12COOLER EVAP. (E10)
HEAT TRACE FRZ (E10)
SITE LIGHTS
---
10
---
SITE LIGHTS
SITE LIGHTS
10
10
12 (2)
SERVICE DOORBELL
SECURITY CAMERA'S
RECEPTS-DINING RM
CLR/FRZR LIGHTS
RECEPTS-DINING RM
WATER HEATER12
12
12
12
IRRIG CONTROLS
REFRIGERATOR (B60)
ANSUL SYSTEM
12
12
12
12
12
(2)
(2)
(2)
(2)
27
NOTES:
TOTALS
41
37
39
3P-225
33
35
31
29
4/04/0
-
-
-
3P-225
3P-225
23
25
21
19
3P-50
--
-
-
-
-
13
17
15
11
9
5366
6740
68,088
- 624
31627
71,135
- 624
28360
10040
9348
5366
4445
- 624
11332
4445
-
2880
624
652
28
67,692
- 624
21231
9690
5366
42
38
40
34
36
32
30
12068
4445
-
2880
624
652
3P-60
3P-60
24
26
22
20
6
6
3P-3014
18
16
12
10
10
---
WALK-IN COOLER (2)
---
---
RTU-2
RTU-1
---
10
10
---
COMPRESSOR (E10)
---
C0MPRESSOR (E10)
10
WIRE SIZE
SERIES/INTEGRATED RATING
600 AMP MAIN LUGS ONLY
SQUARE D "I-LINE" TYPE HCN
DRV THRU DIR. SIGNS
CKT
120/208 VOLTS - 3 PHASE - 4 WIRE - SOLID NEUTRAL
----
LOAD DESCRIPTION
CONV. OVEN (B10)
----
CONV. OVEN (B10)
LOAD DESCRIPTION
GND
OFFICE CAB. FAN
RECEPTS
HOOD CONTROLS
12
12
12
12
EF-3
(2)
(2)
WIRE SIZE
PH
10
-
-
10
NOBKRN GND
3P-30
3P-30
1010
- -
10
-
10
-
7
5
1
3
CKT
FLUSH MOUNTED - EQUIPMENT GROUND BAR
CIRCUIT SCHEDULE
WALL ART LIGHTS
SPACE
POS SYSTEM/PRINTER
DRIVE THRU MENU BD
SPARE
EXT SOFFIT LIGHTS
EXT SOFFIT LIGHTS
EXT SOFFIT LIGHTS
DIGITAL M/B SYSTEM
DRIVE THRU AUDIO
LIGHTING CONTROLS
POS SYS. /PRINTER
(3)
(2)
CABINET = 26" W x 6-1/2" D
PANEL "DP"
CONN. LOAD (VA)
2880
2880
652
-
PH A
2880 4750
PH B
2880 4750
PH C
NBKR PHNO
3P-30
2P-60
8
6
2
4
10
6
CKT CKT
MINIMUM 42,000 A.I.C.
LOAD DESCRIPTION
RECEPTS-TEL EQ BD
RECEPTS - OFFICE
MUSIC SOUND/G.P.
COMPUTER/PRINTER
D/T WINDOW
DINING PENDANT LIGHTS
DINING LIGHTS
(2)
(2)
LOAD DESCRIPTION
WALK-IN FREEZER (2)
GND
SPACE
----
CHUB WARMER (D81)
10
10
10
10
178.2 KVA
@ 1.00 D.F. = 48.1 KVA
@ 0.65 D.F. = 92.5 KVA
@ 1.00 D.F. = 12.4 KVA
@ 1.25 D.F. = 25.3 KVA
KITCHEN EQUIP.
RECEPT & MISC.
TOTAL DEMAND LOAD
HVAC
LIGHTING/SIGNS
12390.0 VA
48028.0 VA
142310.0 VA
20270.0 VA
= 495.0 AMPS
TOTAL AMPS
TOTAL KVA205.0
569.0
KITCHEN EQUIP.
RECEPT & MISC.
TOTAL DEMAND LOAD
HVAC
LIGHTING/SIGNS
= 110.6 AMPS
@ 1.00 D.F. = 3.2 KVA
@ 0.65 D.F. = 13.3 KVA
@ 1.00 D.F. = 3.9 KVA
@ 1.25 D.F. = 9.2 KVA
3240.0 VA
20518.0 VA
3850.0 VA
7380.0 VA
29.6 KVA
TOTAL KVA
TOTAL AMPS
32.8
91.0
2P-30
-
-
8
8
8
TOTAL DEMAND LOAD
RECEPT & MISC.
KITCHEN EQUIP.
HVAC
LIGHTING/SIGNS
= 78.3 AMPS
@ 1.00 D.F. = 2.0 KVA2020.0 VA
28.2 KVA
@ 1.25 D.F. = 16.1 KVA
@ 1.00 D.F. = 8.5 KVA
@ 0.65 D.F. = 1.6 KVA2520.0 VA
8540.0 VA
12890.0 VA
TOTAL AMPS
TOTAL KVA
73.6
26.5
POS SYSTEM, COMPUTER, PRINTERS, MONITORS, CREDIT CARDS AND MODEM(3)
TO BE ON ISOLATED GROUND
(2)
(3)
1800
12 12 12
121212
12 12 12
4
4/0 4/04
4
4/04/0
(4)
(4)
(4)
(4)
PROVIDE HACR TYPE CIRCUIT BREAKER.(4)
(2)
(2)
960
(3)
12 12 12
(3)
- - -
12 12 12
DIGITAL PRE-SELL M/B
3P-60
6
---
RTU-3
---
10
(4)
4445
4445
4445
COOLER EVAP (E10)
12 12 12(2)
3P-3010
WALK-IN COOLER (2)
---
C0MPRESSOR (E10)
1010
(3) 540
WIRE SIZE
SERIES/INTEGRATED RATING
225 AMP MAIN LUGS ONLY
1P-20
16120015
PROVIDE SEPARATE GROUND CONDUCTOR IN ALL CONDUITS
PROVIDE BREAKER WITH SHUNT TRIP INTERLOCKED WIRED
PROVIDE BREAKER WITH GROUND-FAULT CIRCUIT INTERRUPTER.
(3)
UC REFRIG (J40)
SPARE
----
MICROWAVE (D20)
HOLDING BIN (D92)
---
HAND DRYER
SHUNT TRIP SPACE
FRYER/TIMERS (A10.U3)
HOT WTR DISP (D70)
(2)
(1)
(2)
NOTES:
12
10
TOTALS
2P-20
2P-30
12
10
41
39
35
35
12
12
12
1P-20
1P-20
1P-25
1212
1212
29
31
33
25
27
2P-30
2P-20
12
21
23
17
19
25032
2000
21557
437
1238
-
1920
2000
12502850
2040
-
1250
1238
2000
1238
24889
437
2000
1920
1250
42
40
36
38
588 2000
2000
1250
1238
2850
26
2P-20
2P-3030
32
34
28
10
2P-40
2P-20
22
24
18
20
CKT
LIGHTING BRANCH CIRCUIT BREAKERS SHALL BE LISTED FOR SWITCHING DUTY
120/208 VOLTS - 3 PHASE - 4 WIRE - SOLID NEUTRAL
LOAD DESCRIPTION
(H10.4PD)
HEAT LAMPS
---
HOLDING UNIT (F15.1)
PRODUCTION COUNTER
CKTWIRE SIZE
PH
2P-30
13
11
7
9
BKR
2P-30
2P-20
GNDN
1
5
3
NO
FLUSH MOUNTED - EQUIPMENT GROUND BAR
CIRCUIT SCHEDULE
PH BPH A
2578
540
3000
14564250
2578
1456
CONN. LOAD (VA)
PANEL "C"
CKTCKT
PH C
2578
2578 3000
1P-20
1P-20
1P-20
14
12
10
8
2P-40
2P-502
6
4
NO BKR PH N
10,000 A.I.C.
SQUARE D "NQOD"
(3)
HEAT TRACE BOSS (A92)
---
HAND DRYER
SPACE
SPACE
HOT WTR DISP (D70)
ICE CUBER W/REM. (K10)
---
HOLDING BIN (D92)
10
HOLDING CABINET (D94)
---
LOAD DESCRIPTION
LIGHTING (H10.4PD)
BISCUIT HOLD (B65)
GREASE COL SYS (A92)
IMMERS. HEATER (H10.4PD)
GND
= 146.6 AMPS
@ 1.00 D.F. = 0.0 KVA
@ 0.65 D.F. = 52.8 KVA
@ 1.00 D.F. = 0.0 KVA
@ 1.25 D.F. = 0.0 KVA
TOTAL KVA
TOTAL AMPS
0.0 VA
81218.0 VA
0.0 VA
0.0 VA
52.8 KVA
81.2
198.4
KITCHEN EQUIP.
RECEPT & MISC.
TOTAL DEMAND LOAD
HVAC
LIGHTING/SIGNS
TO HOOD FIRE PROTECTION SYSTEM.
10 10
2P-30
10 10
10 10
10
10 10
---
4250
1200
1950
1950
8 8
12 12 12
12 12 12
12 12
12 12
---
---
ICE CUBER W/REM. (K10)
12 12 12
12 12
10 10
---
1920
----
HOLDING BIN (D93)8 8
2P-20 12 12
1P-20 12 12 12
8 8
(H10.4PD)
HEAT LAMPS
(H10.4PD)
HEAT LAMPS
(H10.4PD)
SECTION 250-50 (N.E.C.)
ROD. GROUNDING TO CONFORM TO
DIA. x 10'-0" LENGTH GROUNDING
RUN #2/0 CONDUCTOR TO 5/8 "
ENCL.
IDENTIFICATION
IN 2 1/2" CONDUIT
PANEL
LC3
H-O-A SELECTOR
NEAR OFFICE AREA.
SWITCHES - CONTROLS
LOCATED AT SW STATION
FOR LTG CONTACTORS
LC2
LC1
4 - #4/0, THWN, CU
IN 2 1/2" CONDUIT
# 4 CU GND
PANEL
"C"
"A"
PANEL
"B"
IN (2) 3 1/2" CONDUITS.
(2) RUNS EACH:
# 1/0 CU GND
4 - #350 KCMIL, THWN, CU
"DP"
600A M.C.B
I-LINE
PANEL
FOUNDATION
METAL WATER PIPE
WHERE AVAILBLE
STEEL REBARS IN
PLAQUE
AVAILABLE
FAULT CURRENT
LISTED FOR
CT
WP
# 4 CU GND
4 - #4/0, THWN, CU
REMOTE ROOF MOUNTED
DIAGRAM SHT. E1.
PHOTO-ELEC-CONTROL
FOR (2) SEE WIRING
SWITCH (TYP.)
LTG. CIRCUITS
PARK'G LOT
TO EXTERIOR
LTG. CIRCUITS
TO EXTERIOR
LC3
LC2
LC1
PE
SIGN CIRCUITS
TO EXTERIOR
ENGRAVED SIGN
"MAIN DISCONNECT"
TERMINATE ON POLE
ROUTE TWO RUNS : (4) 350 KCMIL, THWN, CU,
TO POWER CO SERVICE POINT AND TERMINATE
REFER TO CIVIL SITE DWGS FOR LOCATION .
AT SERVICE LOC. PER POWER CO REQMT'S.
PROVIDE & INSTALL
CT CABINET AND
POWER CO REQUIREMENTS
IN (2) 3 1/2" CONDUITS VIA CT CABINET
METER IN ACCORD WITH
METER
OR WHERE REQUIRED
REQUIREMENTS.
PER POWER CO
WEATHER HEADS
POLE - SEE SITE
POWER CO SERVICE
SERVICE
(TYPICAL)
CIVIL PLAN FOR
LOCATION
= 451.1 AMPS
ELECTRICAL SERVICE CONNECTED LOAD
KITCHEN EQUIP. KVA
RECEPT & MISC. KVA
HVAC KVA
TOTAL KVA
LIGHTING/SIGNS
@ 0.65 D.F. = 92.5 KVA
@ 1.00 D.F. = 12.4 KVA
@ 1.25 D.F. = 25.3 KVA
32153.0 VA
142310.0 VA
205000.0 VA
12390.0 VA
20270.0 VA
162.4 KVA
@ 1.00 D.F. = 32.2 KVA
SPACE
- - - -
(2)
12 12 12
12 12 12
(3)
CHECKED:
DATE:
PO
PE
YE
S
LK
1
26
0-D
L-P
LU
S P
RO
TO
TY
PE
E.I.F
.S
. / S
IM
UL
AT
ED
S
TO
NE
LO
UIS
IA
NA
K
IT
CH
EN
L
K-P
LU
S D
ES
IG
N S
TA
ND
AR
DS
60 S
EA
TS
/ D
UA
L-L
IN
E P
RO
DU
CT
IO
N
E3
1
ELECTRICAL POWER RISER DIAGRAM
1/4"=1'-0"
ELECTRICAL PANEL
SCHEDULES and
RISER DIAGRAMS
E3
04/17/15
KR
REVISIONS:
LEGEND
BRACKET COVER
BY P.O.S. VENDOR
A.F.F.
EL. 9'-4"
S.S. STEEL
BRACKET
MONITOR
MONITOR
ASSEMBLY
2.
1.
6'-8
"
(NOT SHOWN)
CONCEAL
SLEEVE TO
POWER CORDS
CHANNELS &
WHT. PLASTIC
ATTACH
BOLTS
W/ (2) 1/4"
BRACKET
MONITOR
CHANNEL
OUTER STEEL
CEILING TILE
PLATE
FLASHING
INNER STEEL
CHANNEL
(2) 1/2"
U-BOLTS
OR JOISTS TOG.C.
TO ROOF TRUSSES
"U" HANGERS
@ EA. END TO
RAFTER PLATE
W/ SIMPSON
DBL. 2X4
BLOCKING
NOTES:
MONITOR BRACKETS TO BE SUPPLIED AND
INSTALLED BY P.O.S. VENDOR.
G.C. TO SUPPLY 2x4 BLOCKING AND
TO SECURE BLOCKING AT LOCATION
PER P.O.S. VENDOR DIRECTION. VERIFY
W/ P.O.S. VENDOR BEFORE INSTALLATION
REGISTER CONNECTIONS
1. CABLES SHALL BE COAX.
2. BUMP BARS SHALL BE MOUNTED TO DELIVERY SYSTEM AT
AREAS MARKED "BB".
3. BUMP BAR CABLES SHALL BE RUN THROUGH DELIVERY
SYSTEM FROM MOUNT UP THROUGH WALLS TO ABOVE THE
CEILING AND BACK TO THE MANAGER STATION.
4. CRT MONITORS SHALL BE MOUNTED ON CEILING BRACKETS
PROVIDED BY REGISTER SYSTEM.
5. WHERE CABLING IS INSTALLED IN WALLS, IT SHALL BE
ROUTED IN A 1" CONDUIT THROUGH WALL TO ABOVE
ACCESSIBLE CEILING.
BUMP BAR WIRING
VIDEO MONITOR AND POS
WIRING
SECURITY WIRING
BB - BUMP BARS
V1 = VIDEO 1
V2 = VIDEO 2
V3 = VIDEO 3
POS- POINT OF SALE
TERMINAL
CRT
FREEZER
WALK-IN
MENWOMEN
ELECTRICAL PANELS
COOLER
WALK-IN
REFERENCE ONLY
COORDINATE WITH
P.O.S. SUPPLIER
CONNECTION
2 POS COUNTER
- SINGLE ORDER
1 COUNTER #1
2 COUNTER #2
3 ORDER TAKER #1
4 DT CASHIER
COORDINATE CAT 6
3 POS COUNTER
- SINGLE ORDER
1 COUNTER #1
2 COUNTER #2
3 COUNTER #3
4 ORDER TAKER #1
5 DT CASHIER
2 POS COUNTER
- DUAL ORDER
1 COUNTER #1
2 COUNTER #2
3 ORDER TAKER #1
4 ORDER TAKER #2
5 DT CASHIER
3 POS COUNTER
- DUAL ORDER
1 COUNTER #1
2 COUNTER #2
3 COUNTER #3
4 ORDER TAKER #1
5 ORDER TAKER #2
6 DT CASHIER
VERIFY ACTUAL CONFIGURATION WITH SITE PLAN
V4 = VIDEO 4
V5 = VIDEO 5
CHECKED:
DATE:
PO
PE
YE
S
LK
1
26
0-D
L-P
LU
S P
RO
TO
TY
PE
E.I.F
.S
. / S
IM
UL
AT
ED
S
TO
NE
LO
UIS
IA
NA
K
IT
CH
EN
L
K-P
LU
S D
ES
IG
N S
TA
ND
AR
DS
60 S
EA
TS
/ D
UA
L-L
IN
E P
RO
DU
CT
IO
N
E4
1
E4
2
P.O.S. WIRING
DIAGRAMS
E4
04/17/15
KR
REVISIONS:
HOLD UP BUTTON
6 + 1
STROBE LIGHT
Dome
IEI KEYPAD
14" Monitor
EXTERIOR DOME CAMERA
GLASS BREAK
DOOR CONTACT
CONTROL PANEL
HORN/SOUNDER
MOTION DETECTOR
(Ceiling Mount)
KEY PAD
DEVICE
2
1
1
1
5
1
DIGITAL VIDEO RECORDER
SYMBOL LEGEND
SYMBOL QTY.SYMBOLDEVICE
1
1
5 + 1
1
1
10
QTY.
PIEZO 1
POPEYES INSTALLATION NOTES
NOTE: PROGRAMMING SEQUENCE SET-UP AT THE NCCC
FOR LOCATIONS WITH OUTDOOR CAMERAS
OUTDOOR POLE MOUNT 15' ABOVE FINISHED PAVEMENT
GROUND ISOLATION TRANSFORMERS
SECURITY CO. TO RUN FLEX CONDUIT INSIDE LIGHT POLES- EC TO RUN CONDUIT
FFROM RESTAURANT TO BASE OF LIGHT POLE & MOUNT JUNCTION BOX 15' ABOVE
FINISHED PAVEMENT ON POLE VIEW DRIVE-UP AND SIDE DOOR
A -1: VIEW MAIN ENTRANCE AND SIDE OF BUILDING
A-2 : VIEW SIDE DOOR AREA OPPOSITE SIDE OF BUILDING FROM DRIVE-THRU
A-3 : VIEW BACK DOOR, DRIVE-THRU MENUBOARD & REAR AREA
A-4 : VIEW SECOND DRIVE-THRU MENUBOARD W/ DUAL ORDER DESIGN
INDOOR CAMERAS
INDOOR CEILING MOUNT IN TINTED DOME
FASTEN SCREW IN CEILING FOR DOMES SO NOT EASILY DROPPED OUT OF TILE
B-1 : VIEW DINING, SALES COUNTER & BEVERAGE COUNTER
B-2 : VIEW DINING, FRONT DOORS, RESTROOM AREA & SALES COUNTER
B-3 : VIEW DINING AREA
B-4 : VIEW SALES COUNTER & SAFE AREA
B-5 : VIEW DRIVE-THRU REGISTER & WINDOW AREA
B-6 : VIEW MANAGER DESK & PREP AREA
B-7 : VIEW FRYERS & PREP AREA
B-8 : VIEW COOLER/FREEZER DOORS
B-9 : VIEW BACK DOOR AND MOP SINK AREA
B-10 : VIEW DRY STORAGE & SINK AREAE
OFFICE AREA
BAC- BURGLAR ALARM CONTROL-VISTA 20SEUL
D-VCR
E-VCR :
F-MONITOR :
QUICK REFERENCE SHEETS
ALARM INSTRUCTION SHEET TO BE MOUNTED ON WALL IN EMPLOYEE ONLY AREA
CLOSEST TO KEYPAD OR IN OFFICE AREA PER CUSTOMER INSTRUCTION
FOR LOCATIONS WITH 6 OR MORE CAMERAS: ADD MULTIPLEXER
LTC 2641/60-PLACE ON SECURITY LOCK FOR NO TAMPER
FOR LOCATIONS WITH 4 CAMERAS OR LESS:
ADD VIDQUAD 4 CHANNEL LTC 2272/60
HUB: HOLD UP BUTTON 441494 SERIES LATCHING HUB
MANAGER AREA-36" AFF OUT OF SITE FROM FRONT COUNTER
DRIVE-THRU WINDOW-18" AFF & OUT OF SITE FROM OUTSIDE
FRYER/PREP AREA
SL: STROBE LIGHT - AS SL-401B-BLUE STROBE MOUNT BEHIND MENU BOARD, IT WILL
FLASH CONTINUOUSLY WHILE BACK DOOR IS OPEN
S: SOUNDER-AS-PAL328N-LOW TONE SOUNDER MOUNT WITH STROBE BEHIND MENU
BOARD, IT WILL SOUND WHEN BACK DOOR IS OPENED, MANAGER WILL SILENCE ST
SOUNDER AT KEYPAD AFTER 1 TONE
MD: MOTION DETECTOR-AP 669 PIR-360 MOTION MOUNT IN STOVE AREA TO GET
AREA FROM DRIVE-UP WINDOW AND GENERAL REAR AREA
LOBBY/PERIMETER AREA/BACK OF HOUSE
KP: KEY PAD-MOUNT 40" AFF WALL ENTERING KITCHEN AREA
FROM LOBBY
GB: FG 1025 GLASS BREAK-LOBBY GLASS ONE EACH SIDE OF
BUILDING SEE DRAWING FOR DEVICE PLACEMENT
C: B4039 CONTACT-ALL EXTERIOR DOORS
BACK DOOR CONTACT TO ACT AS ALARM POINT FOR BACK
DOOR ALARM-24 HOUR LOCATION POINT-SOUNDER & BLUE
STROBE TO ACTIVATE WHEN BACK DOOR IS OPEN
HUB: 3050CT SERIES LATCHING HUB IN
COOLER/FREEZER-MOUNT 18" AFF ON HINGE SIDE OF DOOR,
STUB UP CONDUIT TO PROTECT WIRING FROM
CONDENSATION/DAMAGE NO DRIP LOOP AT HUB
POC : POINT OF CONNECTION TO NKL SAFE-PIGTAIL PROVIDED
BY NKL SAFE
POPEYES ADD ON MODIFICATION NAMES AND
PHONE NUMBERS
1. INSTALLER PLEASE CONTACT YOUR ADT NCCC PROJECT
COORDINATOR FOR ANY ADD-ONS OR MODIFICATIONS TO
YOUR JOB. THEY WILL CONTACT THE NATIONAL
ACCOUNT MANAGER FOR APPROVALS/PAPERWORK.
2. CONTACT THE NATIONAL ACCOUNT MANAGER.
POPEYES PROBLEM RESOLUTION NAMES & PHONE NUMBERS
ACKERMAN / LOCKNET:
NCCC PROJECT COORDINATOR:
NAME:
PHONE NUMBER:
NATIONAL ACCOUNT MANAGER:
AFC/POPEYES:
NEW INSTALLS/NEW CONSTRUCTION MANAGER
EXISTING SITES/RENOVATION PROJECTS/FACILITIES MANAGER
LOSS PREVENTION DIRECTOR:
POPEYES INSTALLATION ACCEPTANCE FORM/CHECKLIST
FOR INSTALL SITE MODIFICATIONS IE/DEVICE PLACEMENT CHANGES FROM
BLUEPRINT, HAVE CUSTOMER INITIAL MODIFY PER SITE OPTION TO SHOW
APPROVAL
CAMERAS
A-CAMERA : FOR LOCATIONS WITH OUTDOOR CAMERAS
OUTDOOR POLE MOUNT 15' ABOVE FINISHED PAVEMENT
YES_____________ N/A______________ MODIFY PER SITE__________
GROUND ISOLATION TRANSFORMERS
YES_____________ N/A______________ MODIFY PER SITE__________
ADT TO RUN CONDUIT INSIDE LIGHT POLES-EC TO RUN CONDUIT FROM
RESTAURANT TO BASE OF LIGHT POLE & MOUNT JUNCTION BOX 15' ABOVE
FINISHED PAVEMENT ON POLE
YES_____________ N/A______________ MODIFY PER SITE__________
A-1; VIEW DRIVE-UP AND SIDE DOOR
YES_____________ N/A______________ MODIFY PER SITE__________
A-2: VIEW BACK DOOR, MENU BOARD & REAR AREA
YES_____________ N/A______________ MODIFY PER SITE__________
A-3: VIEW SIDE DOOR AREA OPPOSITE SIDE OF BUILDING FROM DRIVE-THRU
YES_____________ N/A______________ MODIFY PER SITE__________
B-CAMERA: FOR LOCATIONS WITH INDOOR CAMERAS INDOOR CEILING MOUNT IN
TINTED DOME
YES_____________ N/A______________ MODIFY PER SITE__________
FASTEN SCREW IN CEILING FOR DOMES SO NOT EASILY DROPPED OUT OF TILE
YES_____________ N/A______________ MODIFY PER SITE__________
B-1: VIEW FRONT DOORS, RESTROOM AREA & SALES COUNTER
YES_____________ N/A______________ MODIFY PER SITE__________
B-2: VIEW DRIVE-THRU REGISTER & WINDOW AREA
YES_____________ N/A______________ MODIFY PER SITE__________
B-3: VIEW SALES COUNTER & SAFE AREA
YES_____________ N/A______________ MODIFY PER SITE__________
B-4: VIEW BACK DOOR & COOLER/FREEZER AREA
YES_____________ N/A______________ MODIFY PER SITE__________
B-5: 360 VIEW
YES_____________ N/A______________ MODIFY PER SITE__________
OFFICE AREA
D-VCR LOCK BOX: TC3922 SERIES
YES_____________ N/A______________ MODIFY PER SITE__________
E-VCR: LTC 3924 SERIES PLACE ON SECURITY LOCK FOR NO TAMPER
YES_____________ N/A______________ MODIFY PER SITE__________
QUICK REFERENCE SHEETS
ALARM INSTRUCTION SHEET TO BE MOUNTED ON WALL IN EMPLOYEE ONLY
AREA CLOSEST TO KEYPAD OR IN OFFICE AREA PER CUSTOMER INSTRUCTION
YES_____________ N/A______________ MODIFY PER SITE__________
VCR INSTRUCTION SHEET( 2) 1-REVIEW & 1-RECORD-TO BE MOUNTED ON WALL
CLOSEST TO VCR
YES_____________ N/A______________ MODIFY PER SITE__________
FOR LOCATIONS WITH 6 OR MORE CAMERAS: ADD MULTIPLEXER
LTC 2641/60-PLACE ON SECURITY LOCK FOR NO TAMPER
YES_____________ N/A______________ MODIFY PER SITE__________
FOR LOCATIONS WITH 4 CAMERAS OR LESS:
ADD VIDQUAD 4 CHANNEL LTC 2272/60
YES_____________ N/A______________ MODIFY PER SITE__________
HUB: HOLD UP BUTTON 441494 SERIES LATCHING HUB
MANAGER AREA-36" AFF OUT OF SITE FROM FRONT COUNTER
YES_____________ N/A______________ MODIFY PER SITE__________
DRIVE-THRU WINDOW-18" AFF & OUT OF SITE FROM OUTSIDE
YES_____________ N/A______________ MODIFY PER SITE__________
LOBBY/PERIMETER AREA/BACK OF HOUSE
KP: KEYPAD-MOUNT 40" AFF WALL ENTERING KITCHEN AREA FROM LOBBY
YES_____________ N/A______________ MODIFY PER SITE__________
GB: FG 1025 GLASS BREAK- LOBBY GLASS ONE EACH SIDE OF BUILDING SEE
DRAWING FOR DEVICE PLACEMENT
YES_____________ N/A______________ MODIFY PER SITE__________
C: B4039 CONTACT-ALL EXTERIOR DOORS
YES_____________ N/A______________ MODIFY PER SITE__________
BACK DOOR CONTACT TO ACT AS ALARM POINT FOR BACK DOOR ALARM-24
HOUR LOCATION POINT-SOUNDER & BLUE STROBE TO ACTIVATE WHEN BACK
DOOR IS OPEN
YES_____________ N/A______________ MODIFY PER SITE__________
YES_____________ N/A______________ MODIFY PER SITE__________
POC: POINT OF CONNECTION TO NKL SAFE-PIGTAIL PROVIDED BY NKL SAFE
YES_____________ N/A______________ MODIFY PER SITE__________
FRYER/PREP AREA
SL: STROBE LIGHT-AS SL-401B-BLUE STROBE MOUNT BEHIND MENU BOARD,
IT WILL FLASH CONTINUOUSLY WHILE BACK DOOR IS OPEN
YES_____________ N/A______________ MODIFY PER SITE__________
S: SOUNDER-AS-PAL328N-LOW TONE SOUNDER MOUNT WITH STROBE BEHIND
MENU BOARD, IT WILL SOUND WHEN BACK DOOR IS OPENED, MANAGER WILL
TONE SILENCE SOUNDER AT KEYPAD AFTER 1
YES_____________ N/A______________ MODIFY PER SITE__________
MD: MOTION DETECTOR-AP 669 PIR - 360 MOTION MOUNT IN STOVE AREA TO
GET ARE FROM DRIVE-UP WINDOW AND GENERAL REAR AREA
YES_____________ N/A______________ MODIFY PER SITE__________
POPEYES MATERIAL LIST
CAMERAS
A-CAMERA:
5 OR 6 LOCATIONS ( LOCATIONS W/OUTDOOR CAMERAS )
2 OR 3 GIT100-GROUND ISOLATION TRANSFORMERS
LTC 0430/20-38 SERIES CAMERA W/ 3.5-8MM VARIFOCAL AUTOIRIS LENS
TC 9340A SERIES OUTDOOR HOUSING
TC9211PM POLE MOUNT ADAPTER
BNC CONNECTORS FOR PLENUM CABLE
FLEX CONDUIT FOR OUTDOOR CAMERAS RUN INSIDE POLE FOR CABLING
INDOOR CEILING MOUNT IN TINTED DOME
NOTE: FASTEN SCREW IN CEILING FOR DOMES SO NOT EASILY DROPPED
OUT OF TILE LTC 0430/20-38 SERIES CAMERA W/ 3.5MM-8MM VARIFOCAL
AUTOIRIS LENS
TC 9345MT7 INDOOR TINTED DOME
BNC CONNECTORS FOR PLENUM CABLE
OFFICE AREA
BAC-BURGLAR ALARM CONTROL: VISTA 20SEUL
D-VCR LOCK BOX : TC3922 SERIES
E-VCR: LTC 3924 SERIES PLACE ON SECURITY LOCK FOR NO TAMPER
F-MONITOR: LTC 2813/60 SERIES
ALTV248: 8 POSITION POWER SUPPLY
QUICK REFERENCE SHEETS
ALARM INSTRUCTION SHEET TO BE MOUNTED ON WALL IN EMPLOYEE ONLY
AREA CLOSEST TO KEYPAD OR IN OFFICE AREA PER CUSTOMER
INSTRUCTION
VCR INSTRUCTION SHEETS (2) 1-REVIEW & 1-RECORD-TO BE MOUNTED ON
WALL CLOSEST TO VCR
FOR LOCATIONS WITH 6 OR MORE CAMERAS : ADD MULTIPLEXER LTC
2641/60-PLACE ON SECURITY LOCK FOR NO TAMPER
FOR LOCATIONS WITH 4 CAMERAS OR LESS : ADD VIDQUAD 4 CHANNEL LTC
2272/60
2-HUB: HOLD UP BUTTON 441494 SERIES LATCHING HUB
STOVE/PREP AREA
SL: STROBE LIGHT-AS SL-401B-BLUE STROBE MOUNT BEHIND MENU BOARD,
IT WILL FLASH CONTINUOUSLY WHILE BACK DOOR IS OPEN
S: SOUNDER-AS-PAL328N-LOW TONE SOUNDER MOUNT WITH STROBE
BEHIND MENU BOARD, IT WILL SOUND WHEN BACK DOOR IS OPENED,
MANAGER WILL SILENCE ST SOUNDER AT KEYPAD AFTER 1ST TONE
MD; MOTION DETECTOR-AP 669 PIR-360 MOTION MOUNT IN STOVE AREA TO
GET AREA FROM DRIVE-UP WINDOW AND GENERAL REAR AREA
LOBBY/PERIMETER AREA/BACK OF HOUSE
KP: KEYPAD-MOUNT 40" AFF WALL ENTERING KITCHEN AREA FROM LOBBY
2-GB: FG 1025 GLASS BREAK-LOBBY GLASS ONE EACH SIDE OF BUILDING
SEE DRAWING FOR DEVICE PLACEMENT
3 OR 4-C: B4039 CONTACT-ALL EXTERIOR DOORS BACK DOOR CONTACT TO
ACT AS ALARM POINT FOR BACK DOOR ALARM-24 HOUR LOCAL
POINT-SOUNDER & BLUE STROBE TO ACTIVATE WHEN BACK DOOR IS OPEN
1 OR 2-HUB: 3050CT SERIES LATCHING HUB IN COOLER/FREEZER-MOUNT 18"
AFF ON HINGE SIDE OF DOOR SUB UP IN CONDUIT
1-POC: POINT OF CONNECTION TO NKL SAFE-PIGTAIL PROVIDED BY NKL
SAFE
RELAYS FOR BACK DOOR/POC/ZONE EXPANSION
TELCO JACK
WATTS LINE
ELECTRICAL REQUIREMENTS
ELECTRICAL SUPPLY ALL 120 VAC FOR CAMERA SYSTEM AND BURGLAR
ALARM SYSTEM
SUPPLY 120 VAC FOR ALL CCTV HEAD END EQUIPMENT.
SUPPLY 120 VAC FOR BURGLAR ALARM PANEL.
FOR OUTDOOR CAMERAS ALL TRENCHING, CONDUIT AND PULL STRINGS,
AS WELL
AS A BACK BOX MOUNTED ON THE POLE FOR ELECTRICAL AND COAX
CONNECTIONS.
SECURITY CO. SUPPLY AND INSTALL ALL SECURITY EQUIPMENT RUN ALL
LOW VOLTAGE CABLE FOR THE SECURITY SYSTEM. SET UP, TEST AND
TRAIN ON CCTV AND BURGLAR ALARM SYSTEMS. SPECIFY ALL
LOCATIONS OF DEVICES.
FREEZER
WALK-IN
MENWOMEN
ELECTRICAL PANELS
COOLER
WALK-IN
REFERENCE ONLY
VERIFY LOW VOLTAGE
PERMIT REQUIREMENTS
(Additional camera for dual drive-thru order design)
(Additional button for 2nd drive-thru window design)
2'-9
"
2'-6"
5"
M-11 S/S MANAGER'S
DESK
HOLD-UP BUTTON
CHECKED:
DATE:
PO
PE
YE
S
LK
1
26
0-D
L-P
LU
S P
RO
TO
TY
PE
E.I.F
.S
. / S
IM
UL
AT
ED
S
TO
NE
LO
UIS
IA
NA
K
IT
CH
EN
L
K-P
LU
S D
ES
IG
N S
TA
ND
AR
DS
60 S
EA
TS
/ D
UA
L-L
IN
E P
RO
DU
CT
IO
N
E5
1
SECURITY SYSTEM
PLAN and
SPECIFICATIONS
E5
04/17/15
KR
REVISIONS:
Recommended