View
23
Download
1
Category
Preview:
Citation preview
RESIDENTIAL LOAD CENTERTYPICAL OF 11
PANEL
U LO-- < Ø
FOURTH FLOOR
RESIDENTIAL LOAD CENTERTYPICAL OF 11
PANEL PANELT HP13
THIRD FLOOR
RESIDENTIAL LOAD CENTERTYPICAL OF 11
PANELT [-
SECOND FLOOR
14,750A AVAILABLE FAULT CURRENT -
On On On On On On On On On °7 7
On On On On On On On On O - @�570- @ EL PAPNE
On On On On On On On On . __
38,993A AVAILABLE FAULT CURRENT 12GRADE
29,904A AVAILABLE FAULT CURRENT
42015A AVALABLE FAULT CURRENT- ----------------------------------------------------------------- ----------- _-_-_-_-_- ___ _-_-_-_-_----_-_-_-L_____________________________.______________________________J
BUILDING 1ELECTRICAL RISER DIAGRAMNOT TO SCALE
RISER NOTESUTILITY TRANSFORMER, PROVIDE AND INSTALL CONCRETE PAD PER THE UTILITY'SELECTRICAL SERVICE STANDARDS.
PROVIDE AND INSTALL MODULAR METERING FOR RESIDENTIAL TENANTS. METERINGTO CONSIST OF A THREE PHASE 1200A MAIN CIRCUIT BREAKER, A THREE PHASEHORIZONTAL BUS, AND 9-4 HIGH METER STACKS. EACH METER STACK SHALL BESINGLE PHASE AND EACH METER CAN SHALL CONTAIN A METER SOCKET AND A125A/2P LOAD CIRCUIT BREAKER. METER SOCKETS SHALL BE ACCEPTABLE TO THEELECTRICAL UTILITY.
PROVIDE AND INSTALL A UTILITY APPROVED CT CABINET.
INSTALL A UTILITY PROVIDED METER SOCKET. CONNECT TO THE CT CABINET WITH A1 1/4" CONDUIT.
800A SERVICE SWITCH FUSED AT 400A WITH CLASS L FUSES.
200A SERVICE SWITCH FUSED AT 200A WITH CLASS J FUSES. INSTALL ABOVE THEMETER, SHOWN BESIDE THE METER ON THE RISER FOR CLARITY.
THREE PHASE RETAIL TENANT PANELBOARD.
THREE PHASE DISTRIBUTION PANELBOARD FOR THE HOUSE SERVICE.
4 SETS OF 4-500 KCMIL, EACH SET IN A 4" CONDUIT.
4-#4/0 IN A 3" CONDUIT.
2 SETS OF 4-500 KCMIL, EACH SET IN A 4" CONDUIT.
4-#4/0, 1-#4 GROUND WIRE IN 2 1/2" CONDUlT.
4-500 KCMIL, 1-#3 GROUND WIRE IN A 3 1/2" CONDUIT.
GROUND SERVICE TO INCOMING WATER SERVICE PIPE AND ANY STRUCTURAL STEELWITH #3/0 COPPER, AND TO FOOTING REINFORCING STEEL WITH #4 COPPER.
GROUND SERVICE TO INCOMING WATER SERVICE PIPE AND ANY STRUCTURAL STEELWITH #2 COPPER, AND TO FOOTING REINFORCING STEEL WITH #4 COPPER.PROVIDE ANY OTHER GROUNDING REQUIRED BY THE UTILITY FOR THEIR EQUIPMENT.
GROUND SERVICE TO INCOMING WATER SERVICE PIPE AND ANY STRUCTURAL STEELWITH #2/0 COPPER, AND TO FOOTING REINFORCING STEEL WITH #4 COPPER.PROVIDE ANY OTHER GROUNDING REQUIRED BY THE UTILITY FOR THEIR EQUIPMENT.
3-#1, 1-#6 GROUND WIRE IN A 1 1/4" CONDUIT.
4" PVC CONDUIT TO THE UTILITY TRANSFORMER FOR PRIMARY SERVICE.COORDINATE EXACT ROUTING AND REQUIREMENTS WITH THE UTILITY.
PROVIDE AND INSTALL A UTILITY APPROVED 200A THREE PHASE FEED THROUGHMETER SOCKET. GROUND PER UTILITY REQUIREMENTS.
2 SETS OF 4-500 KCMIL AND 1-#1/0 GROUND WIRE, EACH SET IN A 3 1/2"CONDUIT.
4-#1/0, 1-#4 GROUND WIRE IN 2" CONDUlT.
PANELHP11
1I
FIRST FLOOR
BASEMENT
DRAWING
RELEASE {OG
J3-21-14 - PDP Submittal12-01-14 - 65% SetJ1-09-15 - FDP SubmittalJ1-14-15 - Permit SetJ3-20-15 - 98% Review SetJ4-03-15 - 98% CD's
REVISIONS
DATE
March 21, 2014
[os No.
908 Broadway, Suite 200Kansas City, MO 64105-1590 3HEET No.Ph: 816.842.2800Fx: 816.842.4884
www.bgrengineers.com
Recommended