Update on NY State & NY City Energy Codes
Lee Brandt, LC, IALD, LEED AP BD+CPrincipal
HLB Lighting Design
LEDucationProvider Number
Update on NY State & NY City Energy CodesCourse Number
Lee E BrandtMarch 29, 2017
Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-AIA members are available upon request.
This course is registered with AIA CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner ofhandling, using, distributing, or dealing in any material or product.___________________________________________
Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
3/29/2017
2
This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written
permission of the speaker is prohibited.
© HLB Lighting Design Inc. 2017
Copyright Materials
Course Description• NY state and thus NY city
have recently adopted new energy codes. This seminar will update the audience on lighting related items for the newly adopted codes. A summary of changes will be provided.
Learning Objectives• Codes in use as of 10/3/2016
• Changes from IECC 2012 to 2015
• Changes from Std. 90.1 2010 to 2013
• NY State amendments to the base codes
• NY City amendments to State items and base codes
3/29/2017
3
Where can you find the codes?• NYS
– https://www.dos.ny.gov/dcea/noticadopt.html
• NYC– http://www1.nyc.gov/site/buildings/codes/2016‐energy‐conservation‐code.page
– For purchase ($112)• https://a856‐citystore.nyc.gov/2/Municipal‐Publications/11/Rules‐Regulations/2290/2016‐New‐York‐City‐Energy‐Conservation‐Code
When?
• Effective Date 10/3/16
3/29/2017
4
Items of Note• Changes in IECC 2015 & Standard 90.1 2013
– Both are “re‐written”
– LPD’s – Whole Building/Building Area and Space by Space
– IECC – Decorative allowance back
– 90.1 – many more spaces require bi‐level lighting
– IECC’s Mandatory Additional Efficiency Package Options• 6 options, pick 1
– 10% under either Building or Space by Space (New Construction only)
– Enhanced Digital Lighting Controls
Items of Note• Power requirements
– 90.1 – NYS Amendment changed voltage drop language (Section 8.4.1) to match National Electric Code language – combined voltage drop of 5%
– 90.1 – 50% Automatic Receptacle control is still there (8.4.2) – AND more spaces!
Items of Note• NYC Amendments
– Historic Buildings – Must be on National or State list. – No change, but a reminder:
• 90.1 – Dwelling Units within commercial buildings STILL have to comply• IECC and 90.1 – incorporated LL48 language on occupancy and vacancy
sensors like before.• Occupancy Sensors OFF within 20 minutes
– OPEN OFFICES now require occupancy sensor control– Reduced LPD for Open and Enclosed office and Retail Sales Area– Alterations
• IECC = 20% threshold [NYC]• Standard 90.1 = 20% threshold [NYC]
3/29/2017
5
Compliance Path Options• NYS and NYC ‐ IECC 2015 Prescriptive
– Efficiency Options for new construction only
• NYS ‐ IECC 2015 Performance– Building energy cost < 85% of reference building
• NYS and NYC ‐ Std. 90.1 2013 Prescriptive
• NYS and NYC ‐ Std. 90.1 2013 Performance (2 paths)
New York CityIECC Performance Path removed
Envelope and Power Requirements
Envelope – Window to Wall Ratio(no change)
IECC 2015 – C402.4.1• Prescriptive:
– 30% Max OR
– 40% Max when
• >25% conditioned floor area in daylight zone
• Automatic daylighting controls installed
• Certain VT requirements
STD. 90.1 – Tables 5.5.1‐8• Prescriptive
– 40% (No change)
– Allowance for Street Level vertical fenestration (5.5.4.4.1 Exception 3.)
– Limits fenestration on East & West facing walls (5.5.4.5) (no change)
3/29/2017
6
Envelope – Window to Wall Ratio
• Prescriptive Path
• Benefits of daylighting = 0
• Use Performance Paths!
Envelope – Skylight RequirementsIECC 2015 – C402.3.2• Prescriptive:
– Directly under roof w/ ceiling >15’
– Spaces > 2,500 sq ft
– Certain space types
– Daylight zone / area requirements associated with Skylights
• Multi‐level lighting controls (C405.2.3.3)
STD. 90.1 ‐ 5.5.4.2.3 • Prescriptive:
– Directly under roof w/ ceiling >15’
– Spaces > 2,500 sq ft
– Certain space types
– Daylight zone / area requirements associated with Skylights
• Multi‐level lighting controls (9.4.1.1.f)
Power – Voltage DropIECC 2015
• No requirements
STD. 90.1 – 8.4.1
• Mandatory– 2% for feeders
– 3% for branch circuits
New York State & New York CityCHANGED THE LANGUAGE TO MATCH NATIONAL ELECTRIC CODE (NEC)
3/29/2017
7
PowerAutomatic Receptacle Control
IECC 2015
• No requirements
STD. 90.1 – 8.4.2
• Mandatory– Private offices, conference
rooms AND
– Print/Copy rooms, break rooms, classrooms, and individual work stations
– 25% of modular furniture circuits
Lighting
Lighting – Scope – Dwelling Units(no change)
IECC 2015 – C405.1/R404.1
• > 75% of lamps in permanently installed light fixtures shall use high efficacy lamps
– Does not include low voltage lighting!
– High Efficacy =
• CFL
• <T8 linear fluorescent
• >60 lumens / watt for > 40 watt lamp
STD. 90.1 – 9.1.1• ExceptedNew York City
DWELLING UNITS ARE NOT EXCEPTED!! They do not have to apply with Lighting Section if they meet IECC language
3/29/2017
8
Lighting – Scope ‐ AlterationsIECC 2015 – C101.4.3
• Exception for <10% replacement of luminaires in a space as long as power is not increased
• Replacement of lamps + ballasts ok (need not comply with code) if LPD not increased
STD. 90.1 – 9.1.2
• Exception for <10% of connected lighting load such that LPD is not increased
• All other alterations must comply with LPD and auto shutoff (9.4.1.1)– Including lamps + ballasts
replacement
– Including exterior alterations
New York CityMADE THRESHOLD 20%
New York CityAlterations to comply with all control requirements
Controls
Automatic ControlIECC 2015 – C405.2.2.1
– Automatic Time Switch controls shall be installed
– Exception for areas with occupancy sensors.
STD. 90.1 – 9.4.1.1
– Automatic Controls to shut off interior lighting shall be installed
• Time of day
• Occupant sensor
• Signal from other system indicating unoccupied space
3/29/2017
9
Occupancy SensorsIECC 2015 – C405.2.1• Required in:
– Classrooms/Lecture/Training– Conference / Meeting Rooms– Copy/Print Rooms– Employee lunch and break rooms– Private offices– Restrooms– Storage Rooms– Janitorial Closets– Spaces< 300 sq. ft– Warehouses
• Auto‐off within 30 min
STD. 90.1 – 9.4.1.1.b.c.g.h• Auto‐off within 20 min
New York City amendmentsAuto‐off within 20 min!
Occupancy Sensors – Open Offices
• Open Offices require occupancy sensors (full on ok)
• Auto‐off within 20 min
New York CityAffects both IECC and Std. 90.1
Automatic Control ‐ FunctionsIECC 2015 – C405.2.1.1 • Manual or Auto ON
– Auto ON only if <50% power• OK for 100% on in corridors,
stairwells, restrooms, entrance areas, and lobbies, or areas requiring 100% on for safety
• NYC – OK for 100% on in open offices
• Warehouses – separate for each aisle
• Auto OFF (full) required
STD. 90.1 – 9.4.1.1.b.c.g.h
• Manual or Auto ON– Auto ON only if <50% power
• OK for 100% on in some spaces including open offices – see table 9.6.1
• Auto OFF (partial) 9.4.1.1.g– Spaces that used to be exempt
from auto‐off (corridors, stairs, lobbies, warehouses)
• Auto OFF (full) 9.4.1.1.h– Most spaces
3/29/2017
10
Manual/Local ControlsIECC 2015 – C405.2.2.3
– Manual lighting controls required in almost all areas (some exceptions)
STD. 90.1 – 9.4.1.1.a
– Manual lighting controls required in almost all spaces (some exceptions)
Light Reduction ControlsIECC 2015 – C405.2.2.2
– 50% reduction in each area where time‐switch controls are installed.
• Important exceptions – Spaces with one luminaire <
100 watts– Spaces that use less than 0.6
w/sf– Corridors, equipment rooms,
public lobbies, electrical/mechanical rooms
– Above exceptions must have a manual control
– Daylight zones with controls per C405.2.3
STD. 90.1 – 9.4.1.1.d
– Each area with manual control (many space types) shall have one control step between 30 and 70% in addition to off.
• Can be accomplished with dimming, step ballast, zoning
Daylighting ControlsIECC 2012 – C405.2.3• Daylight‐responsive controls are required for
lights in daylight zones– >150 watts of general lighting
• Calibration required• Offices, classrooms, labs, library reading rooms
– continuous dim from full to 15%• Appears other areas can be controlled on/off
or steps• Shall be capable of complete shut off• Sidelight zones facing different orientations
shall be controlled separately• Toplight and sidelight daylight zones shall be
controlled separately• Not required for retail and other exceptions
STD. 90.1 – 9.4.1.1.e and f.• Photocontrols shall control lights in
primary sidelighted and toplighted areas– >150 watts of general lighting
– >300 watts of general lighting for primary and secondary sidelighted areas (separate zones)
• Calibration required
• Continuous dim or at least one control point between 50% and 70%, a second at between 20% and 40%, a third at full off.
• General lighting overlapping toplightedand sidelighted areas shall be controlled together
• Not required for retail and other exceptions
3/29/2017
11
Sidelighting DefinitionSTD. 90.1 – 3.2 DefinitionsIECC ‐ C405.2.3.2
• Sidelight Daylight Zone– Floor area next to vertical
fenestration (window, roof monitor, clerestory)
– >24 sq. ft of window
– If existing buildings, Tvis >0.20
• Primary sidelighted areas
• Secondary sidelighted areas
Sidelighting DefinitionIECC
Sidelighting DefinitionSTD. 90.1
3/29/2017
12
Toplighting /Skylight Zone DefinitionSTD. 90.1 – 3.2 DefinitionsIECC – C405.2.3.3
• Toplight Daylight Zone– Floor area underneath a roof
fenestration assembly (skylight, roof monitor)
• Daylight Area Under Skylights (including roof monitor)
Toplighting /Skylight DefinitionIECC
Toplighting /Skylight DefinitionIECC
3/29/2017
13
Toplighting /Skylight DefinitionIECC
Toplighting /Skylight DefinitionSTD. 90.1
Interior Lighting Control Requirements (summary)
• Each space is required to have or is limited by:– Local on/off control– Manual on restrictions– Partial automatic‐on (via occupancy or time control)– Partial automatic‐off (via occupancy or time control) (full off complies)
[not IECC/NYC path]– Automatic full off (via occupancy or time control)– Bi‐level control available to occupant– Scheduled automatic off– Daylight control – continuous dimming or step [no more manual
control in IECC/NYC path]
3/29/2017
14
• Space by Space Method
• Controls required for each space are listed with LPD
– REQ = mandatory
– ADD1 = at least one of these must be implemented
– ADD2 = at least one of these must be implemented
– Some helpful footnotes – especially for electrical and mechanical rooms (note #7) – add’l LPD
Standard 90.1 Table 9.6.1
Standard 90.1 Table 9.6.1
Additional Interior Controls(no change)
STD. 90.1‐ 9.4.1.3IECC ‐ C405.2.4
• Mandatory –Dedicated/separate control for Display/Accent, Case, Non‐visual and Demonstration
• Task Lights – sensor on the luminaire or on the wall
3/29/2017
15
Additional Interior Controls Guest Rooms
STD. 90.1 ‐ 9.4.1.3.bIECC ‐ C405.2.4.3
• Auto‐off (lighting and switched receptacles) within 20 min OR keycard activation
• Bathrooms shall have separate device to turn off all bathroom lighting within 30 min
– 5 watt night light exempt
• Auto‐off (lighting and switched receptacles) within 20 min OR keycard activation
Exterior Lighting ControlsIECC 2012 – C405.2.5 STD. 90.1 – 9.4.1.4
• Automatic control to keep lights off when sufficient daylight available
– Façade and landscape lighting
• Auto shut‐off b/t midnight or business closing and 6am or business opening
– All other exterior lighting including signage shall be controlled automatically to reduce connected load by minimum of 30%
• From midnight to 6am (or within one hour of business close / open) OR
• Any period of inactivity > 15 min
STD90.1 only – 9.4.1.2
9.4.1.3
Daylight Transition Zone
• Garage must have automatic shut off controls (9.4.1.1.i)
• Occupancy sensor to decrease power of each luminaire by 30%
• <3600 sq ft zone
• Daylight transition zone, separate control – 50% reduction from sunset to sunrise
• Daylight responsive lighting zone within 20’ of perimeter wall
Daylight Transition Zone
20’ Daylight Control Zone
3,600 sq ft max control zone
Exterior Lighting ControlsParking Garage
3/29/2017
16
Lighting Power Density
Interior Lighting Power
• Building Area about the same as 2012
• Reduced LPD’s from 2012 for Space by Space
– Decorative allowance is back! (C405.4.2.2.1.2.)
STD. 90.1 – 9.5.1 AND 9.6.1IECC 2015 ‐ C405.4.2 (1) AND (2)
• Building Area about the same as 2010
• A few changes on Space by Space
• New allowance for spaces for the visually impaired
Interior Lighting PowerOffice Areas
STD. 90.1 Z–9.6.1IECC 2015 ‐ C405.4.2 (2)
New York CitySpace by Space Reductions‐ Office/Enclosed – 1.0 w/sf [from 1.11]‐ Office/Open Plan – 0.9 w/sf [from 0.98]
3/29/2017
17
Interior Lighting PowerRetail Sales Areas
STD. 90.1 –9.6.2.bIECC 2015 ‐ C405.4.2 .2.1.1
• Base allowance – 1000 watts
• 1.44 w/sf (base code)• Base allowance – 500 watts
• 1.59 w/sf (base code)
+ Base Allowance
+ Retail Area 1 * 0.6 w/sf
+ Retail Area 2 * 0.6 w/sf
+ Retail Area 3 * 1.4 w/sf
+ Retail Area 4 * 2.5 w/sf
New York CitySpace by Space Reduction‐ Retail Sales Area – 1.3 w/sf
Interior Lighting PowerAdditional Allowances (90.1)
STD. 90.1 – TABLE 9.6.1IECC – N/A
• Room Cavity Ratio additional allowance for tall and unique shaped rooms and corridors less than 8’ wide
– 20% increase on LPD!
Interior Lighting PowerAdditional Allowances (90.1)
STD. 90.1 – TABLE 9.6.3IECC – N/A
• Additional control methods – in addition to Mandatory controls = extra wattage
– Specific conditions and applications
3/29/2017
18
Exterior Lighting Power
• No major changes
– Tradable / Non‐tradable
– Matches Std. 90.1 except Building Façade which is lower
– Area calculation is above grade wall area
STD. 90.1 – 9.4.2.2IECC ‐ C405.5.2(2)• No major changes
– Tradable / Non‐tradable
– Lighting Zones ‐ Has LZ0
– Matches IECC/NYC path except Building Façade
– Area calculation is wall area or length
– Also has categories for Landscaping and Loading Docks
Functional TestingSTD. 90.1 – 9.4.4 IECC – C408.3
• Controls have to be tested
• Daylighting controls actually reduce electric lighting
• Placement and sensitivity of sensors
• Documentation required
• Third party – they produce report
Additional Efficiency Package Requirements
IECC 2012 – C406• Mandatory for New Construction only
– Additional Efficiency Package Options! Project must chose 1
• Efficient HVAC equipment
• Reduced LPD C406.3
• Enhanced Lighting Controls C406.4
• On‐site renewable energy
• Dedicated outdoor air system
• High Efficiency service water heating
– Lighting may be the common choice• Building Area OR Space by Space tables
with 10% reduction
• Enhanced Controls
STD. 90.1 • No requirement
3/29/2017
19
What you learned• Codes in use as of 10/3/2016
• Changes from IECC 2012 to 2015
• Changes from Std. 90.1 2010 to 2013
• NY State amendments to the base codes
• NY City amendments to State items and base codes
This concludes The American Institute of Architects Continuing Education Systems Course
Lee Brandt, LC, IALD, LEED AP BD+CPrincipalHLB Lighting [email protected]
QUESTIONS?
Lee Brandt, LC, IALD, LEED AP BD+CPrincipalHLB Lighting [email protected]