Kavoori Consultants 1
ELECTRICAL SAFETY AUDIT
K. R. GovindanKavoori Consultants
22, Janakiraman street,West Mambalam
Chennai, 600 033.Tele: 044 24846139
Kavoori Consultants 2
SCOPE OF SAFETY AUDIT
Inspection of the electrical equipments and components of a system for
safe installation, adequacy for normal load and fault levels, safety for normal operation
Kavoori Consultants 3
System equipments and components:
High tension power incoming feeder, isolator and breaker arrangements
Power and distribution transformers Primary power distribution system, Secondary bus duct / cable arrangements Secondary panel, breakers Indication and annunciation arrangements
Kavoori Consultants 4
System equipments and components:
Grounding arrangements Earthing stations and system, Feeder arrangements, Neutral grounding and equipment grounding
effectiveness, Cables galleries, tunnels, ducts, laying
arrangements and fire protection Distribution substations M V and LV switchgear and MCC stations Battery bank and battery room
Kavoori Consultants 5
System equipments and components: Grounding arrangements Earthing stations and system, Feeder arrangements, Neutral grounding and equipment grounding
effectiveness, Cables galleries, tunnels, ducts, laying
arrangements and fire protection Distribution substations M V and LV switchgear and MCC stations Battery bank and battery room
Kavoori Consultants 6
System equipments and components:
Lighting distribution:Lighting panels
Fire alarm and mulsifier systemsElectrical installations in Process Areas Electrical installations in Utilities, Effluent and Water Treatment Plants, Investigation in to recent electrical accidents and cause analysis,
Kavoori Consultants 7
System equipments and components:
Fire water system and Main and jockey pumps for their control systems,
Static protections employed in hazardous material handling areas,
Selection of enclosures for electrical control and
power equipments in hazardous areas, Emergency stand-by power:
Kavoori Consultants 8
System equipments and components:
Records
Electrical failures records and cause analysis.Operation, Maintenance of these equipments, Preventive and predictive maintenance practices and
Kavoori Consultants 9
System equipments and components:
routine tests carried out on control gears from the safety angle of view,
Compliance with Safety and Statutory Requirements
Hazardous area classification and equipment compliance.
Kavoori Consultants 10
Operation and maintenance practices
Permit work clearances and procedures Safety precautions and practices Normal and emergency operation and
procedures Compliance with Safety and Statutory
Requirements:
Kavoori Consultants 11
Personnel protective appliances and implements:
Adequacy of protective gears available Adequacy of metering and measuring
equipments First aid and safety practices
Kavoori Consultants 12
Fire and safety:
Electrical Fire fighting equipments and systems
Fire water and pumping systems and their controls.
Kavoori Consultants 13
OBJECTIVES OF ELECTRICAL SAFETY AUDIT:
To assess the safety of equipments:From damage during normal operation.Capability of the protective system to protect the equipment’s in the event of electrical faults.
Kavoori Consultants 14
To assess the safety of the personnel:
Are the operating and maintenance personnel aware of electrical hazards?
Is statutory regulation fulfilled? During emergencies also?
(Power failures, Electrical fault)
Kavoori Consultants 15
To assess the System’s capability:
Is the system adopted safe for maintenance personnel for carrying out electrical job Safely?
Does the system adopted satisfies statutory regulations (Maintenance practices)
Does the system provide Review mechanism for checking adequacy of electrical safety?
Does the system provide amendment of Safety practices & Communication with relevant personnel?
Kavoori Consultants 16
Other aspects:
Assessment of the existing systems’ adequacy, strength and weakness,
Is the Electrical System adequately protected against external causes?
Is there a relevant safety manual available on operation and maintenance and emergency procedures?
Kavoori Consultants 17
Emergency Preparedness:
Adequacy, suggestion for improvements. Call for site employees suggestion Involve them in the task Educate them Create awareness and constant
consciousness
Kavoori Consultants 18
ELECTRICAL SAFETY
MOST IMPORTANT ESPECIALLY FOR PETROCHEMICAL INDUSTRIES
Kavoori Consultants 19
ELECTRICITY IS
A good servant, but
a bad master
You control it, it will serve you nicely
Do not allow it to control you
Electricity excuses nobody
Accidents do not happen; they are caused
Kavoori Consultants 20
ELECTRICAL SAFETY
ELECTRICITY Convenient, clean, useful source of energy Easily transformed into other energies Mechanical, chemical and heat Easily produced Conveniently transmitted to long distances
without much loss
Kavoori Consultants 21
BUT POTENTIALLY A SOURCE OF GREAT DANGER AND HAZARD!
1. Shocks, some times fatal
2. Injuries and burns
3. Permanent deformation of the victim and
4. When used in a hazardous atmosphere, electricity may be a potential source of ignition.
Kavoori Consultants 22
Much development taken place in equipment usage, designed to be safe.
But not proof against misuse and neglect Understand hazardous Do not take risk, in doubt ask Electricity does not excuse any one A good servant but a bad master.
Kavoori Consultants 23
Electricity is:A Good Servant – But a bad master
Six Golden rules:1. Follow all safety rules2. Adhere To established procedures3. Use proper control gears4. Never take anything for granted5. Always be alert6. Keep your mind on the job.
You control electricityIt will serve you nicely!
Do not allow it to control you!
Kavoori Consultants 24
Accidents do not happenThey are caused
Due to Ignorance Negligence Inadvertence Third person’s ignorance Not using safety gears Not having enough knowledge or experience Over confidence due to long experience
Kavoori Consultants 25
Accidents do not happenThey are caused
Not checking the system for
* Alternate power source
* Residual charges
* Low voltage reverse feeding
* Ring main system
* Multiple sources
Kavoori Consultants 26
Accidents do not happenThey are caused
Inefficient or no supervision Non co-operation from co-workers Consuming intoxicating drinks,
substances Family problems Natural calamities Fatigue due to lack of rest
Kavoori Consultants 27
Accidents do not happenThey are caused
Lack of proper display of caution boards
Not checking the conditions of safety gears
Improper fire extinguishing equipments
Improper protective equipments Lack of maintenance of safety gears
Kavoori Consultants 28
WHAT IS ELECTRICITY?
AMPERES?VOLTS?WATTS?
FLOW OF CURRENT AMPERES
WITH POTENTIAL DIFFERENCE VOLTS ACROSS A RESISTANCE OHMS
FLOW OF CURRENT GIVES POWER WATTS
POWER FLOWING FOR A PERIOD ENERGY
Kavoori Consultants 29
How electricity works for you?
4AMPS = 240VOLTS/60 OHMS
VOLTAGE MAKES CURRENT FLOW
THROUGH A RESISTANCE. `
Kavoori Consultants 30
4AMPS = 240VOLTS/60 OHMS
VOLTAGE MAKES CURRENT FLOW
THROUGH A RESISTANCE.
240 V 960W
60 (Heater)
4 AMPS
4 AMPS
Kavoori Consultants 31
4AMPS = 240VOLTS/60 OHMS
VOLTAGE MAKES CURRENT FLOW
THROUGH A RESISTANCE.
240 V 960W
60 (Heater)
4 AMPS
4 AMPS
Voltage and current
Kavoori Consultants 32
4AMPS GOES TO HEATER
4AMPS RETURNS BACK
WHERE FROM 960W POWER CAME?
HOW ELECTRICITY WORKS FOR YOU ?
Kavoori Consultants 33
WATER FROM HIGHER LEVEL
DOES MORE WORK
MORE HEIGHT - MORE ENERGY
CALLED POTENTIAL ENERGY
HOW ELECTRICITY WORKS FOR YOU ?
Kavoori Consultants 34
HOW ELECTRICITY WORKS FOR YOU ?
WATER GOES THRO’ A TURBINE
GIVES THE ENERGY - OR DOES WORK
BUT IT IS NOT CONSUMED! CURRENT - AMPERE - SAME LIKE WATER
DOES WORK AND RETURNS
Kavoori Consultants 35
HOW ELECTRICITY WORKS FOR YOU ?
POTENTIAL DIFFERENCE - VOLTS
LIKE HEIGHT - MORE VOLTS MORE WORK
1 AMPERE FROM 1 VOLTS - 1 WATT POWER
WATT (POWER) = VOLT X AMPS.(P. D.X CURRENT)
Kavoori Consultants 36
WHAT IS POWER? WHAT IS ENERGY?
ENERGY IS QUANTITY OF WORK DONE POWER IS RATE OF DOING WORK. 100LTRS OF WATER TO BE BOILED
1KW HEATER TAKES 2HRS. 2KW HEATER WILL TAKE 1HR.
ENERGY = POWER X TIME.
KILO WATT X HOUR = KILO WATT HOUR =K W hr
Kavoori Consultants 37
ELECTRICITY - CONTROL FOR SAFETY
Proper control of electricity assures safety Electrical power should be isolated before
development of a hazardous situation Imminent fault development to be foreseen and
preventive action taken Only control – faulty circuits should be isolated
1. Immediately and
2. Automatically
Kavoori Consultants 38
Immediate isolation of faulty section; How?Possible to watch continuously?
MAJOR PROBLEM -Insulation failureHAZARDS Shock to personnel, Fire hazardsTotal equipment damage, Power system collapseMechanical damage
Fault location impossible
ELECTRICITY - CONTROL FOR SAFETY
Kavoori Consultants 39
How to monitor continuously & isolate automatically?
Make electricity do it; but, How?
Make fault current grow quickly to a large value
and actuate protective isolating devices.
Good, but how?
Current will flow from Phase to neutral or, Phase to phase
Kavoori Consultants 40
FAULT or INSULATION FAILURE
Provide short circuit or low resistance pathsfor phase and neutral (or) phase and phase
PHASE TO PHASENo hazard! The breaker or fuse isolates faulty section or
equipmentBETWEEN LIVE PARTS AND BODY
HAZARDOUS!People work on equipment, in contact with them
Insulation failure results in electric shock or injury to them!SOME TIME FATAL!
Kavoori Consultants 41
CONNECT BODY TO GROUND SOLIDLY
Insulation failure (fault) makesthe fault current grow to a large value;
actuate protective devices andisolate the faulty equipment or line
IMPORTANT! SYSTEM NEUTRAL SHOULD HAVE BEEN
GROUNDED!
If ground resistance high, low fault current;protective system not operates;
higher fault voltage drop and greater hazard
Kavoori Consultants 42
NEUTRAL GROUNDINGNeutral not grounded; but equipments grounded
A
C B
a
c b
MOTOR NO.1
MOTOR NO.2
Kavoori Consultants 43
NEUTRAL GROUNDING
A
C B
a
c b
MOTOR NO.1
MOTOR NO.2
Kavoori Consultants 44
PROPER NEUTRAL GROUNDING ASSURES
Reliability, Safety and Equipment protection
Power system transformer neutralConnected to earth by Two copper or G. I strips to exclusive neutral electrode, to earth bus
Earth electrode resistance to beLess than 2 ohms
Transformer and equipment bodyTwo connections to earth bus
Kavoori Consultants 45
WHAT IF NEUTRAL NOT GROUNDED?
No current flows to ground.Another fault - another equipmentMay be another phase
All faults - high resistanceLow current- no automatic isolation
Full phase voltage, Danger to human life415 V SHOCK FATAL!
Fault current through available pathFire hazardSputtering ground
Kavoori Consultants 46
CONTROLING ELECTRICITY
Mainly isolation of faultily equipment or circuits
To avoid hazards Isolation should be
Automatic, Very fast And very accurate
Protective elements can protect only equipments and systems and not human beings
Human heart is highly sensitive to passage of electrical current
Kavoori Consultants 47
CONTROLING ELECTRICITY
Controlling elements are
1. Fuses
a. Wire fuses
b. Enclosed fuses
c. HRC fuses
2. Circuit Breakers
a. Automatic circuit breakers
b. Fused switches and switch fuses
c. Manual isolators
Kavoori Consultants 48
PORTABLE EQUIPMENT Single phase Use 3 core cable
Three phase use 4 core cable
Care of safety appliances:Rubber gloves /gauntlets
Rubber matFace shield / goggles
Discharge rodsaprons
Testers/test lamps Multi-meters
Kavoori Consultants 49
BALANCED LOAD Neutral Current
Y
B
N
R5 A 5 A 5 A
5 A 5 A 0 A
Kavoori Consultants 50
The Resistance of Earth System: Major sub stations: 1 OhmOther sub stations: 2 OhmsDistribution transformer stations 5 Ohms Earth connection should be able to carry at least ½ Sec.
Area of Cross Section: Fault Current 15,000.
Kavoori Consultants 51
Electrical Safety
Permit System:Modern industries switch boards, M. C.C.S, distribution boards located ~ Away from the equipments connected ~ In separate rooms or enclosures
Not in direct view of equipments.Only authorized persons can enter or operate.
Good practice!
Kavoori Consultants 52
Many crafts work on the same equipment
But controlled equipment not seen or in the vicinity
Fool proof method required to assure safety of
1. Persons working
2. Equipments against damage.
Kavoori Consultants 53
Permit Systems:
1. Work permit system:
Line clear: Written format (permit) signed by issuer after switching off power.
Issuer locks switches
Receiver signs and returns permit after work is completed.
Issuer cancels permit & energizes line-equipment.
Not very fool proof - Many crafts involved.
Kavoori Consultants 54
2. Tag Out System:
Better system
Tag with detachable portions with non detachable duplicates.
Issuer signs duplicate,issues detachable portion to craft leaders
Each craft leader returns detachable portion signed after work is completed.
After receiving all issued portions and getting signed in the duplicates. issuer removes tag and energizes equipment - line.
Kavoori Consultants 55
Eqpt No: 1.Plant:Issuing authority:Receiver: Time:Date:Approx duration:Others:
Eqpt No: 1.Plant: Issuer:I declare that my men and materials are clear of the above equipment and it can be energized. Date: Time:Receiver:
Non-detachable portion: Detachable portion:
Eqpt No: 2.Plant:Issuing authority:Receiver: Time:Date:Approx duration:Others:
Eqpt No: 2.Plant: Issuer:I declare that my men and materials are clear of the above equipment and it can be energized. Date: Time:Receiver:
TAG – OUT SYSTEM
Kavoori Consultants 56
Open Position
Kavoori Consultants 57
LOCK OUT SYSTEM
Closed Position
Kavoori Consultants 58
ELECTRIC CURRENT EFFECT ON HUMAN
Less than 0.5 milli amps – not felt
0.5 to 12 milli amps – painful, causes start
Above 12 milli amps – muscles contracts
Possibility of holding on and heart stopping
Less current more time to stop heart
50 milli amperes for 200 milli seconds can stop the heart
Kavoori Consultants 59
DO NOT TAKE THIS AS A GUIDELINE!
High skin resistance limits the current
Cuts skin and dampness will reduce the resistance
Cautions – wet places very dangerous
Good bonding and earthing needed
Kavoori Consultants 60
PRECAUTION AGAINST ELECTRIC SHOCKS
1. Good electrical installation and maintenance practice
2. The use of low voltage or High Frequency above 15 kHz.
3. The earthing and bonding of all metal work which might become live and
4. The installation of special protection such as armoring, screening, and earth leakage circuit breakers.
Kavoori Consultants 61
SHORT CIRCUIT CURRENTS
Short circuits causes 20 times normal currents
1000 kVA transformer gives 30,000 ampere Agonizing injuries to the human, fuses metal,
ignite flammable liquid and vapors.
Kavoori Consultants 62
MICROWAVE OVENS
Articles in microwave ovens are heated by microwaves.
The microwaves are at the frequency of approximately 2.45GHZ
A magnetron microwave generator is employed to produce microwaves
These waves cause molecules of water and other compounds to rotate or vibrate
Kavoori Consultants 63
MICROWAVE OVENS
The vibration creates heat which cooks the food or boils the liquids
Efficiency: A typical oven of 1100 Watts delivers 700Watts
microwave energy 400 Watts dissipated as heat by the wave generating
components
Kavoori Consultants 64
MICRO WAVE OVEN - HAZARDS
Liquids in container with smooth surface can super heat.
Reach temperatures above normal boiling point without boiling
Boiling can start explosively when the liquid is disturbed that is when taken out from the container.
Closed containers and eggs can explode due to steam generation
Kavoori Consultants 65
MICRO WAVE OVEN - HAZARDS
Tin foil, aluminum foil, ceramic decorative metal can cause sparks
RADIATION: Exposure to micro wave radiation is injurious
to health Legal limit of radiation is 1 mW/cm2, at 5 cm
from a new oven For used oven five times this limit is
acceptable
Kavoori Consultants 66
MICRO WAVE OVEN - HAZARDS
Mandatory requirements for radiation leakage limitation for ovens produced after 1971;
Less than 5 mW /cm2, approximately at two inches of the surfaces of the oven
Micro waves are not as bad as X-rays or ultra violet radiation.
The oven front glass window is made up of special screen which blocks micro wave radiation leakage
Shut off the oven if any damage to this noticed This should be immediately repaired
Kavoori Consultants 67
MICROWAVE OVEN- CONSTRUCTION
The cooking chamber is a Faraday cage enclosure; Prevents radiation from escaping through. Oven door - glass panel for easy viewing, But with a layer of conductive mesh for shielding. Size of the mesh is much less than the microwave
radiation wavelength of 12 cm, The radiation can not pass through the door But visible light, with much shorter wavelength, can
pass through the door.
Kavoori Consultants 68
NEUTRAL AND GROUND (Continued)
Never, never use ground wire as neutralNeutral conductor carries return or unbalance currentBut, earth conductor carries fault current only.Earth conductor as neutral, will carry current- Any loose connection or high resistance joint, voltage builds upEquipment bodies, earth bus give shock; Arcing, fire hazards etc.
Kavoori Consultants 69
NEUTRAL AND GROUND (Continued)
Our System Is “Neutral Grounded System” or Simply “Grounded System”At all generating, distribution points, the neutral is grounded.That is, the neutral is grounded at:Power transformers And generators of E.B., Distribution Transformer and Generators.System parameters to be:
Phase to Phase Voltage 415v Phase to Neutral Voltage 240v Contact Voltage 240v
Insulation Failure Less Hazardous.
Kavoori Consultants 70
EARTH ROD TOP CLAMPED TO EARTH BONDING TAPES.
Kavoori Consultants 71
Code of practice for grounding: Guide lines: substations: 1. Sufficiently low neutral to ground resistance
2. Gradient control on the surface, equipments to ground or across two parts that will come in
contact simultaneously.
Touch potential or step potential:
Should not exceed 55 volts
3. For grounding calculation: 3secs.
Kavoori Consultants 72
4. Grounding conductor: Around the S.S. Perimeter ~ mesh of 4m x 5m
5. No of ground rods: Max. Ground fault current 500. Should be distributed entire grid.
6. Min. Size 6 S.W.G. G. I. Wire
7. Size of EQ. Size of copper: Short circuit current in Amps sq”. 15000 X n n = number of parallel paths..(Current Density : 1500amps/sq”. For 30secs)
Kavoori Consultants 73
8. Earthing conductors should never be * Run in metal conduits
* In cement troughs Etc.
Recommended Size of Earthing Conductor: Fault Current Size of Cu. Earthing Cond.K.A. Cross section Dimension Sq. Inch Not exceeding 22 0.2 1 ½ X 3/16“
30 0.3 1 ½ X 3/16” 44 0.5 2 X 1/4
Acceptable Temperature rise: Due to passage of fault current = 450oC.
Kavoori Consultants 74
ELECTRICITY AND HUMAN REACTION
Which is more dangerous?
Alternating Current or
Direct Current ?
AC more dangerous.
DC welding plants lesser risky;
90 volts AC welding machine dangerous
Burn hazards
Kavoori Consultants 75
CURRENT AND FREQUENCY
Higher frequency lesser risk 12 to 13 milliamps at 50 HZ cause hold on At 500 HZ this current no effect But higher frequency deeper the burn Micro exposure cause cataracts High frequency does not cause paralysis.
Electrical frequency - effect on human
Kavoori Consultants 76
Electrical frequency - effect on human
THRESHOLD OF FEELING: DC 3 milli ampere; AC 50 HZ – 1 milli ampere; 9 milli
ampere at 10 KHz DC applied to nerve fibre – muscle moves once, then
releases 8 pulses per second – muscles stay contracted Hence, 50 Hz cycle so very dangerous Current through heart stops Death follow if heart stopped between 3 to 8 minutes
Kavoori Consultants 77
HUMAN HEART
4. Heart stops completely – cardiac arrest
Failure of heart to deliver oxygenated blood to the head – irreversible damage – death follow in a very short time
Dry skin high voltage, severe burn Not necessary electrocuting the victim Low voltage at wet or sweating skin cause
death No evidence of burning.
Kavoori Consultants 78
If path of the current is through chest Most fatal accident occur at consumer voltages In mechanical terms the human heart is a compact
280 g assembly, comprising two separate 2-stage displacement pumps working in series and in synchronism. It has a continuous rating of about 4-5W and a short-time rating of at least 20W. Its ‘specification’ requires it to be
Self-powered by extraction of energy from the pumped medium (I.e, by using some of the oxygen from the blood)
Completely maintenance-free Capable of continuous operation at 6—74
strokes/min for at least 600 000 h with 100% reliability
Kavoori Consultants 79
Self-regulating by nervous control from the brain.
Two ways heart upset by passage of electric currents
1. Stop completely (I.e) Cardiac arrest2. Heat muscle fails contract in unison Start tremble or twitch No effective pumping action; cardiac
fibrillation or ventricular fibrillation If not quickly rectified can cause death No burning – survivors recover completely.
Kavoori Consultants 80
THE HUMAN HEART
Chambers and ValvesThe heart is divided
into 4 chambers: 1. Right Atrium (RA)
2. Right Ventricle (RV)
3. Left Atrium (LA)
4. Left Ventricle (LV)
Kavoori Consultants 81
Schematic diagram of the function of the heart
1. Vena cava (carrying blood from capillaries and liver to the heart via the veins)
2. Right and left atria (reception vessels)3. Right and left ventricles (main pumps)4.a. Tricuspid valve (non-return valve)4.b. Mitral valve (non – return valve) 5. Right and left auricles (priming pumps)6. Pulmonary arterial valve (non-return
valve)7. Pulmonary arteries (supply to the
lungs)8. Pulmonary veins (supply from lungs to
heart)9. Aortic valve (non-return valve)10. Aorta (main discharge line from the
heart to the body)11. Heart muscle or myocardium (pump
drive)
Kavoori Consultants 82
THE HUMAN HEART
A hallow cone shaped muscle located between the lungs
2/3rd is to the left of the middle line of the body and 1/3rd to the right
Heart muscle contracts (Systole), pumps blood out of the heart
Right side of the heart collects oxygen poor blood from the body
Pumps to lungs In lungs blood picks up oxygen release CO2
Left side collects oxygen rich blood and pumps to the body
Kavoori Consultants 83
THE HUMAN HEART
Cells through out the body get oxygen to function properly Phase maker cells create electrical impulses and the heart
beats Heart beat rate changes as we age:
Newborn 1303 months 1406 months 1301 year 1202 years 1153 years 1004 years 1006 years 1008 years 9012 years 85Adult 60 - 100
Kavoori Consultants 84
HEART THE PUMP – SPECIFICATIONS
A compact 280 g assembly Comprising two separate 2 –stage displacement pumps working
in series and in synchronism Has a continuous rating of about 4-5W and a short-time rating of
at least 20 W An average heart pumps 2.4 ounces (70 milliliters) per
heartbeat Or, pumps 1.3 gallons (5 liters) per minute Heat of 70 years old has pumped 48 million gallons
(184,086,000 liters)! Self-powered by extraction of energy from the pumped medium
(I.e. by using some of the oxygen from the blood) Completely maintenance-free Capable of continuous operation at 60-74 strokes /min for at
least 600 000 h with 100% reliability Self-regulating by nervous control from the brain.
Kavoori Consultants 85
CATHODIC PROTECTION
Locations – oxidation reaction Metal attains a local positive – anodic corrosion Reduction reaction – cathodic corrosion Soil made positive – with respect to metal surface Anodic corrosion reduced, cathodic corrosion
increases Impressed voltage cathodic protection Protected structure
Kavoori Consultants 86
CATHODIC PROTECTION
All points negative with respect to soil or water
Depends Upon Anode location and distance from the structure Electrical resistance between various parts of
the structure Differing surface condition of the structure Non uniformity resistivity of ground Between anode and structure
Kavoori Consultants 87
CODES OF PRACTICE (COP)
Marking code: Ex o – Oil immersion Marking code: Ex p – Pressuried apparatus Marking code: Ex q – Powder/sand filling Marking code: Ex d – Flame proof enclosure Marking code: Ex e – Increased safety Marking code; Ex ia and Ex ib ( ia is safer than ib) –
Intrinsic safety Marking code: Ex m – Encapsulation Marking code: Ex ia or Ex ib – Intrinsically safe
systems Marking code: Ex N – Type of protection N Marking code: Ex s – Special protection
Kavoori Consultants 88
COMMON UNSAFE PRACTICES
Wiring: Working with the mains ON Replacing an open fuse Providing switch in neutral line instead of phase line Working with wet feet or hands Opening a bras lamp-holder which may be live Unprotected socket outlets
Portable electrical appliances Ineffective or no earthing Working on live appliances without insulated tools or gloves Damp floor or feet.
Kavoori Consultants 89
STATIC ELECTRICITY
Electricity from word elektron, Greek for amber Created when two surfaces in contact separate Greater effect if sliding Most effective in insulating material because charges
cannot move directly to recombine Conductors – charges recombine and do not build up Starts with one volt-rises to several thousands volts
Kavoori Consultants 90
STATIC ELECTRICITY
Fine powders Very much subject to static accumulation Become highly charged whenever poured, sieved, mixed,
ground or blown Transfer the charge to the container If container earthed the charges leaks away
Chargers in Liquids: Oils and explosive liquids = non conducting retain charges Charges in liquid generated to dangerous potential level when Liquid flowing through a pipe
Kavoori Consultants 91
STATIC ELECTRICITY
Liquid flowing through a fine mesh filter Undissolved or immiscible particles moving within the liquid The presence of two different liquid phases Mist, spray or droplets moving through a gas or falling within a
vessel
Charges in Gases Charging process not like liquids or solids Gets and streams or containing particles, solid or liquid
generates charge from or impart charge two other items of the equipment
Release of CO2 or LPG cause considerable cooling – formation of CO2 snow and LPG mist – dangerous from static point of view
Kavoori Consultants 92
STATIC ELECTRICITY
Cleaning by compressed air – disturbed dust and spray present possible hazard; all nearby metal object should be earthed
Particle free – explosive gas will not produce static charge – but readily ignited by a very small low energy ESD
High pressure spray painting may generate potentials of kilo Volts
Hand held spray gun (1) possible high voltage shock (2) presence flammable atmosphere, danger of fire explosion
Kavoori Consultants 93
LIGHTNING - STATIC ELECTRICITY, Contd.,
Rate of rise of discharge reach 200 kA/s Equivalent to 100 mega hertz., Inductance H, a bend or a loop in the conductor;
high impedance Cause high potential and jumping across Similarly a very low capacitance – very low
impedance discharge reflected in adjacent metallic objects
Selections of pipe line are electrically isolated Remain pipe work bonded at site Isolating flanges may have spark gaps