www.lpqi.org IEC 60364-5-52 Electrical installations of buildings – Part 5-52: Selection and erection of electrical equipment – Wiring systems Standard prescriptions LPQI is a member of Core partner LPQIves has been co-financed by Angelo Baggini – [email protected] Franco Bua - [email protected] Neutral conductor sizing

Sizing the neutral in harmonic-rich environments

Embed Size (px)

Citation preview

Page 1: Sizing the neutral in harmonic-rich environments

www.lpqi.org

IEC 60364-5-52Electrical installations of buildings –Part 5-52:Selection and erection of electrical equipment – Wiring systems

Standard prescriptions

LPQI is a member of

Core partner

LPQIves has been co-financed by

Angelo Baggini – [email protected]

Franco Bua - [email protected]

Neutral conductor sizing

Page 2: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Standard prescriptions

IEC 60364-5-52 Art. 524.3For polyphase circuits where each phase conductor has a cross-sectional area greater than 16 mm2 in copper or 25 mm2 in aluminium, the neutral conductor may have a smaller cross-sectional area than that of the line conductors if the following conditions are simultaneously fulfilled:

– the expected maximum current including harmonics, if any, in the neutral conductor during normal service is not greater than the current-carrying capacity of the reduced cross sectional area of the neutral conductor;

– the neutral conductor is protected against overcurrentsaccording to the rules of 431.2 of IEC 60364-4-43;

– the size of the neutral conductor is at least equal to 16 mm2 in copper or 25 mm2 in aluminium.

Page 3: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Il mondo è cambiato per sempreThe world …

Page 4: Sizing the neutral in harmonic-rich environments

www.lpqi.org

… changed forever!

Page 5: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Theorethical background

Page 6: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Theorethical backgroundBalanced linear loads

Page 7: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Theorethical backgroundUnbalanced linear loads

Page 8: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Non linear unbalanced loads

Theorethical background

Page 9: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Theorethical background3rd order harmonics

Page 10: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Sizing criteria

IEC 60364-5-52 Annex DReduction factors

for harmonic currents in four-core and five-core cables

Third harmonic content of phase

current (%)

Size selection is based on phase

current

Size selection is based on neutral

current

0-15 1,00 - 15-33 0,86 - 33-45 - 0,86

45 - 1,00

Page 11: Sizing the neutral in harmonic-rich environments

www.lpqi.org

installation method C

Example

Phases 3

design load 37,5 A

Number of cores 4

Insulation EPR

Installation method Clipped to a wall

Page 12: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Example

Harmonics free environment

– Cable size related to phase currents

– ⇒ 4 mm2

Page 13: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Office # 1

3 h = 22%

− IN = 37,5 · 0,22 · 3 = 24,7 A − IF = 37.5 A − IN < IF size related to phase

current− Equivalent phase current:

− ⇒ 6 mm2

(IEC 60364-5-52 tab. A.52-5 )

Example

6,4386,0

5,37=

Page 14: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Office # 2

3 h = 40%

− IN = 37,5 · 0,4 · 3 = 45 A − IF = 37.5 A − IN > IF size related to neutral

current− Equivalent neutral current:

− ⇒ 10 mm2

(IEC 60364-5-52 tab. A.52-5 )

Example

3,5286,0

45=

Page 15: Sizing the neutral in harmonic-rich environments

www.lpqi.org

Lighting equipment FLC

3 h = 72% + 9 h = 33,9% + …

− IN = 37,5 · 1,30 · 3 = 146,2 A − IF = 37.5 A − IN > IF size related to neutral

current− Equivalent neutral current:

− ⇒ 35 mm2

(IEC 60364-5-52 tab. A.52-5 )

2,1461

2,146=

Example