Introduction• Modbus is a serial communications protocol originally
published by Modicon (now Schneider Electric)
Its Application ?• Used to establish master-slave/client-server communication
between intelligent devices
• Openly published and royalty-free
• Modbus enables communication between many (approximately 247) devices connected to the same network
Communication between MODBUS devices• MODBUS devices communicate using a master-slave technique
in which only one device (the master) can initiate transactions (called queries).
• The other devices (slaves) respond by supplying the requested data to the master
• A slave is any peripheral device (I/O transducer, valve, network or other measuring device), which processes information and sends its output to the master .
• Masters can address individual slaves, or can initiate a broadcast message to all slaves.
Basic Modbus Network
Basic Modbus Transaction
Modbus frames:• The messages exchanged between the master and the slave are
called frames.
• There are two types of Modbus frames: Protocol Data Unit (PDU) and Application Data Unit (ADU).
• The PDU frames : function Code+ data.
• The ADU frames : Add+FC+data+Error check .
• The FC -> action to perform and the data -> information to be used for this action.
Modbus Data Types• Modbus transactions always perform a set of actions by reading
or writing to a set of four data ,used by the Modbus application layer.
Limitations • Since Modbus is a master/slave protocol, there is no way for a
field device to "report by exception"
• The master must routinely poll each field device, and look for changes in the data.
• Modbus is restricted to addressing 247 devices on one data link, which limits the number of field devices that may be connected to a master station .
• Modbus protocol provides no security against unauthorized commands .
Modbus Recap
Query
• Modbus is restricted to addressing 247 devices on one data link, which limits the number of field devices that may be connected to a master station .
• The address field in the Modbus-defined frame is only 8 bits wide. This would provide for 256 slave addresses
• Address 0 is reserved as a "broadcast" address.• Eight other "reserved" addresses that are not valid for a slave
• Source :http://stackoverflow.com/questions/22523716/modbus-slave-count-limitation
• Source : http://www.control.com/thread/1369186948(Modbus Over Serial Line V1.02", page 8, Section 2.2 Modbus Addressing rules, "from 248 to 255: Reserved“)
256-1- 8= 247
Accessing The Data• 16-bit Unsigned Registers And Single-bit Coils • Input Registers And Holding Registers• Input Coils And Status Coils
• 64 kb of space is allocated for registers and coils
Byte-Ordering
Modbus Data structureInput
Registers
Input Coils Status
Coils
Holding Registers65536
0Max of 64 kb of space is allocated for registers and coils
Bits – 1 Bit
Short Integer – 8 bits
Unsigned Integer – (0 to 65536)
Signed Integer – (-32768 to +32767)
32 bit Integer
64 bit Integer
MSB16 bit
LSB16 bit
MSB16 bit 16 bit 16 bit LSB16 bit
Modbus ASCII vs Modbus RTU
• In Modbus RTU, bytes are sent consecutively with a 3-1/2 character space between messages for a delimiter. This allows the software to know when a new message is starting.
•Any delay between bytes will cause Modbus RTU to interpret it as the start of a new message.
•Modbus ASCII marks the start of each message with a colon character " : " (hex 3A).
•The end of each message is terminated with the carriage return and line feed characters (hex 0D and 0A)
• Delimiter is a sequence of one or more characters used to specify the boundary between separate data streams.
ModBus RTU Frame Format
Modbus ASCII vs Modbus RTU
MODBUS PROTOCOL ON OSI MODEL
Application
Presentation
Session
Transport
Network
Data Link
Physical
Serial Line Master / Salve HDLC Ethernet Data Link
RS485 Ethernet Physical Layer
RS232 RS485
Modbus Messaging on TCP/IP
IPTCP
Modbus Application Layer
OSI Model Modbus Serial Modbus Plus Modbus TCP
Modbus RS232-RS485
UART
3.3 V
0 V
PHYDigital
Electrical Signals
Modbus RS232
• RS232 is an Electrical Standard for Physical Drivers that put Electrical signals on the wire
• Point to Point Connection • Full Duplex• Maximum Cable Length 50 FT.• Maximum Data Rate 20kb/s
PHYDigital
Electrical Signals
Rx
Tx
GND
Tx
Rx
GND
Modbus RS485PHY
DigitalElectrical Signals
•Multi- Point Connection (up to 32 devices )
•Half Duplex
•Maximum Cable Length 4,000 FT.
•Maximum Data Rate 100kbps
Tx Rx
Rx
Master Slave A
Slave B
Rx
Tx
Master / Slaves State Diagrams
IdleThis is the initial state after power-upA request can only be sent in "Idle" state
After sending a request, the Master leaves the "Idle" state, and cannot send a second request at the same time
Waitingfor reply
When a reply is received, the Master checks the reply before starting the data processing.In case of an error detected on the frame, a retry is performed
Processingreply
When a unicast request is sent to a slave, the master goes into "Waiting for reply" state, and a “Response Time-out” is started.
It prevents the Master from staying indefinitely in "Waiting for reply" state. Value of the Response time-out is application dependant.
If no reply is received, the Response time-out expires, and an error is generated. Then the Master goes into "Idle" state, enabling a retry of the request. The maximum number of retries depends on the master set-up.
Master / Slaves State Diagrams
Idle
When a broadcast request is sent on the serial bus, no response is returned from the slaves.
Nevertheless a delay is respected by the Master in order to allow any slave to process the current request before sending a new one. This delay is called "Turnaround delay".
Therefore the master goes into "Waiting Turnaround delay" state before going back in "idle" state and before being able to send another request.
Waiting turnaround delay
Ethernet Physical Layer
MODBUS PROTOCOL ON OSI MODEL
Application
Presentation
Session
Transport
Network
Data Link
Physical
Serial Line Master / Salve Ethernet Data Link
RS232 RS485
Modbus Messaging on TCP/IP
IPTCP
Modbus Application Layer
OSI Model Modbus Serial Modbus TCP
HDLC
RS485
Modbus Plus
•Despite the name, Modbus Plus is not a variant of Modbus.
•It is a different protocol, involving token passing.
•It is a proprietary specification of Schneider Electric
• Modbus TCP/IP is simply the Modbus RTU protocol with a TCP interface that runs on Ethernet.
• TCP/IP refers to the Transmission Control Protocol and Internet Protocol
Modbus TCP/IP
Function of TCP is to ensure that all packets
of data are received correctly
IP makes sure that messages are correctly addressed and routed
The rules for
organizing and interpreting
the data
The Modbus TCP/IP message is simply a Modbus communication encapsulated in an Ethernet TCP/IP wrapper.
In general, Modbus TCP/IP uses TCP/IP and Ethernet to carry the data of the Modbus message structure between compatible devices.
Modbus TCP/IP Client/Server Model
The MODBUS messaging service provides a Client/Server communication between devices connected on an Ethernet TCP/IP network.
This client / server model is based on four type of messages:
· MODBUS Request,· MODBUS Confirmation,· MODBUS Indication,· MODBUS Response
MODBUS ClientMODBUS Server
A MODBUS Request is the message sent on the network by the Client to initiate a transaction,
A MODBUS Indication is the Request message received on the Server side
A MODBUS Response is the Response message sent by the Server
A MODBUS Confirmation is the Response Message received on the Client side
Modbus TCP/IP Client/Server Model
Request Indication
Confirmation Response
Modbus TCP/IP Data Frame
Application Data Unit (ADU)
Address Function Code Data Checksum
Modbus Serial FrameFunction
Code Data
Modbus Application Protocol (MBAP) Header Protocol Data Unit (PDU)
TransactionIdentifier
ProtocolIdentifier
LengthField
Unit ID
The Modbus commands and user data are encapsulated into the data container of a TCP/IP telegram without being modified in any way.
Modbus TCP/IP Data Frame
TransactionIdentifier
ProtocolIdentifier
LengthField
Unit ID Function Code Data
Function Code DataAddress Checksum
The Modbus error checking field (checksum) is not used, as the standard Ethernet TCP/IP link layer checksum methods are used.
The Modbus Address field is replaced by the unit identifier in Modbus TCP/IP,
Modbus Serial Frame
Modbus TCP/IPFrame
Modbus TCP/IP Data Frame
TransactionIdentifier
ProtocolIdentifier
LengthField
Unit ID
Modbus TCP/IPFrame
Transaction Identifier - It is used for transaction pairing, MODBUS server copies the identification of a MODBUS Request
This is important because, in MODBUS TCP, the server can handle many requests at the same time. This is not possible in MODBUS Serial.
MBAP
Function Code Data
MODBUS Client(Initialized by the
Client) MODBUS Server
Request
TransactionIdentifier
TransactionIdentifier
Modbus TCP/IP Data Frame
TransactionIdentifier
ProtocolIdentifier
LengthField
Unit ID
Modbus TCP/IPFrame
MBAP
Function Code Data
Protocol Identifier – This field is always 0 for Modbus services and other values are reserved for future extensions
Modbus TCP/IP Data Frame
TransactionIdentifier
ProtocolIdentifier
LengthField
Unit ID
Modbus TCP/IPFrame
MBAP
Function Code Data
Length - The length field is the size of the following fields, including the Unit Identifier ,Function Code , data fields.
Modbus TCP/IP Data Frame
TransactionIdentifier
ProtocolIdentifier
LengthField
Unit ID
Modbus TCP/IPFrame
MBAP
Function Code Data
The Unit identifier is typically used to address the MODBUS slave
The TCP/IP StackIn General TCP/IP allows blocks of binary data to be exchanged between computers
The primary function of TCP is to ensure that all packets of data are received correctly,IP makes sure that messages are correctly addressed and routed
What does each Layer Specify ?
The flow of data from a sender to a receiver using the TCP/IP stack
Each layer on the sending stack communicates with the corresponding layer of the receiving stack through information stored in headers As you move the data down the stack of the sender, each stack layer adds its own header to messageThe higher layers are encapsulated by the lower layers
Conversely, this header information is removed by the corresponding layer at the Receiver
Application User Data (ADU)
CONSTRUCTION OF A TCP/IP-ETHERNET DATA PACKET
Application
TCPTransport
IPNetwork
EthernetData Link
Physical
Application User Data (ADU)
Application User Data (ADU)