Upload
shashank-pandey
View
31
Download
0
Tags:
Embed Size (px)
Citation preview
04/15/2023 1
Impact of Fouling on VCRS and its experimental study
Guided By: Submitted by:Mr. Ankit Kulshreshtha(Project Guide) Piyush Kumar(1101440033) Rishabh Pandey(1101440040) Shantanu Kaushik(1101440051) Shashank Pandey(1101440052)
04/15/2023 2
CONTENTS
TopicsTest rigExperimental Setup DescriptionProperties of RefrigerantActual CycleLosses in VCRSMathematical CalculationsVariation of COP with different
parametersComparison of ResultsFouling MitigationConclusionReferences
Page No.34-910-12131415-2021-32
3334-3536-3738
04/15/2023 3
Fig No. 1 Refrigeration Test Rig [6]
04/15/2023 4
Experimental setup description[6]
1-Thermocouples: Six thermocouples are used in our test rig. The readings of the thermocouples are taken by knob by rotating it .first thermocouple fit at outlet of the condenser. Second and third thermocouples are fitted in the condenser tank and evaporator tank respectively. And remaining thermocouples are fitted in inlet water tank, inlet to condenser and outlet to evaporator.
2-Condenser and evaporator: - as shown in the figurethe tub and tube type condenser and evaporator are used in the kit and the evaporator having insulator on it. These tanks contain the two mechanicalagitators as shown in figure, for the continuous mixture the water,the agitator can be controlled by switch . These tanks have two valves at the lower side of tanks for the water outlet. A copper tube is used for the flow of the refrigerant in spiral form in the tub.
04/15/2023 5
Fig No.2 Condenser[6]
04/15/2023 6
Experimental setup description:-
3-Display devices: our refrigeration test-rig contains LED type display device. All the readings are shown through these display devices.
4-Stirer: A stirer is used for the proper mixing of water and to maintain the temperature uniformity throughout the tank and it is of 1 to 70 hp and 45 watt, 50 Hz and 230 Volt.
5-Rotameter and water tank: rota meter is fitted in between water tank and the condenser and evaporator tank and it contains a motor that is used to raise the pressure of the water and it contains a switch by which the flow of water can be controlled.
04/15/2023 7
Fig No.3 Evaporator[6]
04/15/2023 8
Experimental setup description:-
6-Expansion valve,compressor and drier: in our refrigeration test-rig a reciprocating compressor is used to compress the refrigerant before condenser and it is placed between the evaporator and condenser and it is of 230 volt,50 Hz and single phase. The drier is used to absorb the moisture content and it is placed between the inlet to evaporator and outlet to the condenser. A copper capillary tube type expansion device is being used for the expansion of the refrigerant and it is placed between drier and evaporator.
04/15/2023 9
Experimental setup description:-
7-Pressure gauges: – The two pressure gauges are used , one at high pressure side and other one is placed at the lower pressure side to measure the condenser pressure and evaporator pressure respectively. Means one is suction pressure gauge and other one is discharge pressure gauge, suction pressure gauge having pressure range from 0 to 150 psi and discharge pressure gauge having pressure range from 0 to 300 psi.
04/15/2023 10
Properties of the refrigerant-
Molecular weight: 102.03 g/mol.
Critical point• Critical temperature: 100.95 °C• Critical pressure: 40.6 bar • Critical density: 512 kg/m3
04/15/2023 11
Properties of the refrigerant-
Liquid phase• Liquid density (1.013 bar and 25 °C (77 °F)) : 1206 kg/m3
• Boiling point (1.013 bar) : -26.55 °C• Latent heat of vaporization (1.013 bar at boiling point) :
215.9 kJ/kg• Vapor pressure (at 20 °C or 68 °F) : 5.7 bar• Vapor pressure (at 5 °C or 41 °F) : 3.5 bar• Vapor pressure (at 15 °C or 59 °F) : 4.9 bar• Vapor pressure (at 50 °C or 122 °F) : 13.2 bar
04/15/2023 12
Properties of the refrigerant-
Gaseous phase• Gas density (1.013 bar at boiling point) : 5.28 kg/m3
• Gas density (1.013 bar and 15 °C (59 °F)) : 4.25 kg/m3
• Compressibility Factor (Z) (1.013 bar and 15 °C (59 °F)) : 1
• Specific gravity : 3.25 • Specific volume (1.013 bar and 15 °C (59 °F)) : 0.235
m3/kg
04/15/2023 13
Fig No.4 ACTUAL VAPOR COMPRESSION CYCLE [5]
04/15/2023 14
Fig No.5 Schematic diagram of a simple refrigeration cycle and various losses in VCR system. [5]
04/15/2023 15
MATHEMATICAL CALCULATION [6]
1.Expansion valve: h6 = h7 , at P1 and T1, h1 = 297.1 kJ/kg from table,
at T6 = 40.8 and P6 = 1040 kPa , h6 = 109.7 kJ/kg from table,
pressure loss in condenser = P1 – P6
= 1385.4 – 1040 = 345.4 kPa. Ploss
cond = 25% of Pc
h6 =h7 = 109.7 kj/kg
04/15/2023 16
MATHEMATICAL CALCULATION[6]
2.Evaporator :- T7 = -6.90C, h6 =h7 = 109.7 kj/kg, P7 = 225.6 kPa
h7 = hf + x hfg at 225.6 kPa
109.7 = 42.51 + x(246.32 – 42.51)x = 0.329T4 = 10.30C, Pe = P4 = 170 kPa , h4 = 262.0 kJ/kg
Pressure loss in evaporator = P7 – P4 =55.6 kPa
Plossevap = 25% of Pevap
(Qevap) R = mR ( h4 – h7) = 0.008 (262 – 109.7) = 1.218 kW
(Qevap) W = mW.CPW . ( Two – Twin) = mw.Cpw (T5 –T3)
= 0.046 Х 4.186 (18.3 – 12.4) = 1.134 kW
04/15/2023 17
Qlosss= 1.218 – 1.134 = 0.08 approx 5% of Qevap
(Qmax)evap = mW.CPW ( Twine – Trine )
= mW.CPW ( T5 – T7 ) = 0.046 Х 4.186 (18.3 + 6.9) = 4.84 kW
Ɛ = (Qevap)w / Qmax = 1.134 / 4.84 = 0.23 = 23%.
Ɛ = (Qevap)R / Qmax ) = 1.218 / 4.84 = 0.25 = 25%.
Qlosss = mR ( h4 – h7) - mW.CPW . ( Two – Twin)
Refrigeration effect = mR ( h4 – h7) - 0.05 mR ( h4 – h7) = 1.134 kW
Now, Ɛ = 1 – exp(-NTU)NTU = UA / Cmin
UAe = Cmin. ln(1/ 1 - Ɛ evap)
U = (mW.CPW /Ae) ln(1/1-0.23)
U = ( 0.046 Х 4.186)/0.6619 ln(1/0.77)U = 75.69 watt/m2 0C.
04/15/2023 18
MATHEMATICAL CALCULATION:
3.Compressor:h4 = 262 kJ/kg and S4 = 1.010 kJ/kgK
at 1385.4 = Pb = Pc , Sg = 0.9108 kJ/kgK
since, Sg< S4 hence point lies in the superheated region.
At1385.4 kPa, Sb = 1.006 kJ/kgK at 800C, hb = 308.4 kJ/kg
Ƞ = 0.72 , ƞisentropic = hb – h4 / ha – h4
ha = 262 + (308.4 – 262) / 0.72
= 326.44 kJ/kgAt 326.44 kJ/kg , P = 1385 kPa and T = 920C
04/15/2023 19
MATHEMATICAL CALCULATION:
Heat loss in compressor :mR( h4 - ha) - mR( h4 – hb) = 0.008 (326.44 – 262) – 0.008(308.4 – 262)
= 0.144 kWQloss
discharge + Qlosscomp = mR( h1 - ha) = 0.008(326.44 – 297.1) = 0.234
kWQloss
discharge = 0.234 - .144 = 0.09 kW
(Wcomp)actual = mR (ha - h4) = 0.008 (326.44 – 262) = 0.515 kW
(Wcomp)isentropic = mR (hb - h4) = 0.008(308.4 – 262) = 0.371 kW
COP = RE / Wcomp = 1.134 / 0.515 = 2.2
04/15/2023 20
MATHEMATICAL CALCULATION:
4.Condenser:(Qcond)w =mW.CPW . ( Twoc – Twinc) = 0.046 Х 4.186 (26 – 18.3)
= 1.48 kW(Qcond)R = mR (h1 – h6) = 0.008(297.4 – 109.7) = 1.49 kW
Qmax = mW.CPW (69.1 – 18.3) = 9.76 kW
Ɛcond = (Qcond)w / Qmax = 1.48 / 9.76 = 0.1516i.e. 15.16%
Now, Ɛ = 1 – exp(-NTU)NTU = UA / Cmin
UAc = Cmin. ln(1/ 1 - Ɛcond)
U = (0.046 Х 4.186) / 0.3301.ln(1/1-0.15)U = 94.66 watt/m2 0C
04/15/2023 21
VARIATION OF COP, REFRIGERATION EFFECT AND COMPRESSOR WORK WITH MASS FLOW RATE:-
Input
variables
RE Wcomp COP UCond Uevap
mw1
0.046(kg/s)
1.134 kW 0.515 kW 2.04 94.66
(w/m2 0C)
75.69
(w/m2 0C)
mw2
0.07(kg/s)
1.002 kW 0.552 kW 1.80 144
(w/m2 0C)
115.7
(w/m2 0C)
mw3
0.09(kg/s)
0.990 kW 0.672 kW 1.47 185
(w/m2 0C)
148.7
(w/m2 0C)
04/15/2023 22
Fig No.6 Graph (Mass flow rate vs COP)
COP
Mass flow rate of water (kg/s)
0.046 0.07 0.09000000000000010
0.5
1
1.5
2
2.5COP
COP
04/15/2023 23
Fig No.7 Graph (COP vs Ucond)
COP2.04 1.8 1.47
0
20
40
60
80
100
120
140
160
180
200
Ucond (w/m2 0C)
Ucond (w/m2 0C)
04/15/2023 24
Fig No.8 Graph (COP vs Uevap)
COP
2.04 1.8 1.470
20
40
60
80
100
120
140
160 Uevap (w/m2 0C)
Uevap (w/m2 0C)
04/15/2023 25
Fig No.9 Graph (Mass flow rate of water vs Refrigeration Effect)
Mass flow rate of water (kg/sec)
0.046 0.07 0.090.9
0.95
1
1.05
1.1
1.15
REFRIGERATION EFFECT (kW)
REFRIGERATION EFFECT (kW)
04/15/2023 26
Fig No.10 Graph (Compressor Work vs COP)
Compressor work (kW)
0.515 1.002 0.990
0.5
1
1.5
2
2.5
COP
COP
04/15/2023 27
Fig No.11 Graph (COP vs Wcomp)
COP2.04 1.8 1.47
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Wcomp (kW)
Wcomp (kW)
04/15/2023 28
Fig No.12 Graph (Mass flow rate of water in condenser(kg/sec) vs COP)
COP
Mass flow rate of water in condenser(kg/sec)
0.028 0.046 0.052 0.0660
0.5
1
1.5
2
2.5
3
3.5
4
04/15/2023 29
Fig No.13 Graph (Compressor work(watt) vs COP)
COP
Compressor work(watt)
208 245 266 3080
0.51
1.52
2.53
3.54
04/15/2023 30Fig No.15 Graph (Condenser pressure(bar) vs COP)
COP
Condenser pressure(bar)
9.3 10.3 10.8 11.40
0.5
1
1.5
2
2.5
3
04/15/2023 31
VARIATION OF COP WITH TEMPERATURE:
Input temperature (TWinc) (0C) COP
21.2 2.7
25.2 2.47
28 2.04
28.7 1.88
04/15/2023 32Fig No.16 Graph (Input Temperature vs COP)
COP
04/15/2023 33
COMPARISON BETWEEN MATHEMATICAL AND EXPERIMENTAL RESULTS:INPUTS MATHEMATICAL
RESULT
EXPERIMENTAL
RESULT
ERROR
( %age)
T1 (0C) 70 69.1 1
T6 (0C) 41 40.8 0.5
T7 (0C) -7 -6.9 1
T4 (0C) 10 10.3 2
COP 2.2 2.04 7
RE (kW) 1.134 1.134 0
Wcomp (kW) 0.515 0.555 7
Ucond (watt/m2 0C) 94.66 94.66 0
Uevap (watt/m2 0C) 75.69 75.66 0
Twoe (0C) 12 12.4 3
Twoc (0C) 26.14 26 0.5
04/15/2023 34
Fouling Mitigation
Offline techniques clean heat exchangers by mechanical and/or chemical means while the system is down, which results in lost production time. They are labor-intensive and expensive; as much as 8% of the maintenance costs in a typical industrial plant are due to fouling mitigation in heat exchangers. When offline mitigation requires the use of aggressive chemicals, the company is saddled with additional operating costs, and new problems relating to the increased safety hazards for company personnel and disposal of toxic waste. Moreover, the fouling process starts again immediately after cleaning, and the gradual accumulation of deposits reduces performance until the next cleaning treatment is initiated. These drawbacks make heat exchanger operation with regular offline cleaning expensive, cumbersome and inefficient for the entire industrial process.
04/15/2023 35
Fouling Mitigation
The online method is an ongoing process which uses mechanical means to keep the heat exchanger clean while it operates. Some cleaning systems also use chemicals (which must be carefully adapted to each process), but online mechanical-only cleaning is
both environmentally responsible and highly cost-effective.Online mechanical cleaning boosts performance in two ways: it
does not require system shutdown with temporary loss of operation; and it keeps performance optimal and energy-efficient through continuous cleaning, which does not allow any fouling to occur. In addition, online mechanical cleaning does not only eliminate staff time for cleaning services, but also purchase of chemicals and waste disposal.
04/15/2023 36
CONCLUSION:-
We have successfully validated the performance of VCR system with the help of our mathematical model and we have also studied the effect of various parameters like mass flow rate of water, condenser pressure, evaporator pressure, input temperatures in condenser and evaporator,etc on the COP and vapor compression refrigeration system.
We have also study the fouling phenomenon in the condenser and evaporator of VCR system.After drawing the curves among various parameters we conclude that:
1) As mass flow rate of water increases the COP of VCR system decreases.2) As overall heat transfer coefficient of evaporator increases the COP of
the VCR system decreases.3) As overall heat transfer coefficient of condenser increases the COP of
the VCR system decreases.
04/15/2023 37
CONCLUSION:-
4) As mass flow rate of water increases the refrigeration effect decreases.
5) As compressor work increases the COP of the VCR system decreases.6) As the condenser pressure increases the COP of the VCR system
decreases.7) As the evaporator pressure decreases the COP of the VCR system
decreases.8) As the input temperature increases the COP of the VCR system
decreases.
04/15/2023 38
References
1.Cabello, R., Navarro, J., & Torrella, E. (2005). Simplified steady-state modelling of a single stage vapour compression plant. Model development and validation.Applied thermal engineering, 25(11), 1740-1752.2.Qureshi, B. A., & Zubair, S. M. (2012). The impact of fouling on performance of a vapor compression refrigeration system with integrated mechanical sub-cooling system. Applied Energy, 92, 750-762.3.Qureshi, B. A., & Zubair, S. M. (2014). The impact of fouling on the condenser of a vapor compression refrigeration system: An experimental observation.International Journal of Refrigeration, 38, 260-266.4.Cabello, R., Torrella, E., & Navarro-Esbr , J. (2004). Experimental evaluation of a ı́ �vapour compression plant performance using R134a, R407C and R22 as working fluids. Applied thermal engineering, 24(13), 1905-1917.5.Arora,C.P. (2014) , Actual Vapour Compression Refrigeration Cycle. Refrigeration and Air Conditioning, 114-1156. Katiyar,C.,Yadav,A.,Singh,R.P.,Soni,R.K. & Awasthi,Hrydesh.(2014), Impact of Fouling
on VCR System.