Energy Saving in Alcatel-LucentOffice SustainabilityOffice Sustainability
Kris Van Doren
Sustainability Manager EMEA
April 2014
Outline
This presentation provides an overview of sustainability initiatives in the ALU
office environment that significantly impact the electricity and gas
consumption (hence grid load profile)
� Alcatel-Lucent Corporate Sustainability Objectives
� Measuring is Knowing: Energy Scan
� Heating Pumps
All Rights Reserved © Alcatel-Lucent 2014
� Heating Pumps
� Reduction of Gas Consumption
� Analysis of Cold Production
2 | Energy Savings
MAJOR INITIATIVES: CARBON FOOTPRINTAlcatel-Lucent’s commitment
All Rights Reserved © Alcatel-Lucent 20143 | Energy Savings
Commitment | Alcatel-Lucent committed to a 50% reduction of its carbon footprint by 2020
Carbon Footprint Reduction – Our Path to 50% by 2020
1,000,000
1,200,000
1,400,000
1,600,000
Car
bon
Foo
tprin
t (C
O2
tons
)
24%
42%
All Rights Reserved © Alcatel-Lucent 20144 | Energy Savings
-
200,000
400,000
600,000
800,000
2008 2012 2016 2020
Car
bon
Foo
tprin
t (C
O
Get our house in order
Facility energy efficiency
Less air transport
Building consolidation
IT server consolidation
Reduced business travel
Ask more from Suppliers
Efficient Contract Mfrs.
Efficient travel partners
More efficient shipping
Partner Engagement
-Renewables for the rest
Renewable Energy
Renewable energy credits
50%
Carbon Footprint Reduction – status today
All Rights Reserved © Alcatel-Lucent 20145 | Energy Savings
All Rights Reserved © Alcatel-Lucent 2014
To Measure is to Know: Energy Scan
6 | Energy Savings
Electricity Consumption in our buildings
Energy Scan
Mainly labs
All Rights Reserved © Alcatel-Lucent 20147 | Energy Savings
Mainly offices
Smart Metering
•“if you can not measure it, you can not improve it”
All Rights Reserved © Alcatel-Lucent 20148 | Energy Savings
Measuring is knowing: Energy Scan
Smart Metering � SM@RTLAB
All Rights Reserved © Alcatel-Lucent 20149 | Energy Savings
All Rights Reserved © Alcatel-Lucent 2014
Heat Pump Project: Buildings D and E
10 | Energy Savings
Warmtepomp
Collector Ketel 1/2
Heating pump – recuperation of heat
Schematic Diagram with Heating Pump Integrated
All Rights Reserved © Alcatel-Lucent 2014
23 °C
Koelgroep 2
11 | Energy Savings
U/maand maand Gas DE 62% equivalente WP744 u jan 344.389 kWh 463 kWth672 u feb 305.276 kWh 454 kWth744 u maa 253.524 kWh 341 kWth720 u apr 147.248 kWh 205 kWth382 u mei 57.838 kWh 151 kWth
jun 38.137 kWhjul 8.092 kWh
aug 2.114 kWh370 u sept 55.763 kWh 151 kWth744 u okt 101.576 kWh 137 kWth720 u nov 134.048 kWh 186 kWth744 u dec 157.790 kWh 212 kWth
Heating pump
All Rights Reserved © Alcatel-Lucent 2014
5.840 u Benuttiging warmtepomp
kWth
100 kWth
200 kWth
300 kWth
400 kWth
500 kWth
600 kWth
700 kWth
800 kWth
744
u
1.41
6 u
2.16
0 u
2.90
4 u
3.62
4 u
4.34
4 u
5.09
6 u
5.84
0 u
ALU 100 %
D-E 62 %
12 | Energy Savings
Similar project in other ALU sites (Switzerland, Germany)
Artikel in Energie Magazine
All Rights Reserved © Alcatel-Lucent 201413 | Energy Savings
All Rights Reserved © Alcatel-Lucent 2014
Reduction on Gas Consumption
14 | Energy Savings
Reduction Natural Gas
� Adaptations
� Introducing day/night regime for DE building
� Switching off of heating in meeting rooms between 18:00h and 7:00h
� Switching off humidifiers in summer time
A degree-day is a measure of heating or cooling. A zero degree-day is when both heating and
cooling consumption is at a minimum, which is useful with power utility companies in
All Rights Reserved © Alcatel-Lucent 201415 | Energy Savings
cooling consumption is at a minimum, which is useful with power utility companies in
predicting seasonal low points in energy demand.
Gas Consumption (kWh) versus degree-day(Dd)
0
100.000
200.000
300.000
400.000
500.000
600.000
700.000
jan/0
7fe
b/07
mrt /
07apr/0
7m
ei /07
jun/07
jul/07
aug/0
7se
p /07
okt/0
7no
v/07
dec/0
7
kWh
0
50
100
150
200
250
300
350
400
450
Gd
kWh
Graaddagen
Gasverbruik (kWh) versus graaddagen(Gd)
0
100.000
200.000
300.000
400.000
500.000
600.000
jan/0
8fe
b/08
mrt/
08ap
r/08
mei/
08jun
/08
jul/0
8au
g/08
sep/
08ok
t/08
nov/0
8de
c/08
kWh
050100150200250300350400450
Gd
kWh
Graaddagen
Realised savings
� Gas Savings
� 5.300MWh in 2007, 1563 MWh in 2013
� 70,5% savings (2007-2013)
All Rights Reserved © Alcatel-Lucent 201416 | Energy Savings
All Rights Reserved © Alcatel-Lucent 2014
Analysis of Cold Production
17 | Energy Savings
Analyses of Cold Production (1)
Old situation: Ice production during night, melting down during office hours
All Rights Reserved © Alcatel-Lucent 201418 | Energy Savings
Analyses of Cold Production (2)
� Ice production during night is not efficient: only COP of 2,9
� Solution:
� use ice buffer for emergy cases and use direct chilling during day/night
� Saving on yearly base: 30.000€
Comparison Cooling 2010 versus 2008,2009
All Rights Reserved © Alcatel-Lucent 201419 | Energy Savings
0
50.000
100.000
150.000
200.000
250.000
300.000
350.000
jan feb mrt apr mei jun jul aug sep okt nov dec
kWh
Month
2008
2009
2010
Artikel in Facility Management
All Rights Reserved © Alcatel-Lucent 201420 | Energy Savings
All Rights Reserved © Alcatel-Lucent 2014
Environmental Charter
21 | Energy Savings
•Environmental CharterIn June, 2013 Alcatel-Lucent was presented with the Antwerp Environmental Charter.
All Rights Reserved © Alcatel-Lucent 2014
ALU Number One in the Dow Jones Sustainability Index
All Rights Reserved © Alcatel-Lucent 201423 | Energy Savings
Saving Energy
All Rights Reserved © Alcatel-Lucent 201424 | Energy Savings
Eco-Sustainable Networks
•xxx
Reducing the Carbon Footprint
Innovation and Engagement
Enabling a Low Carbon Economy
Transforming communications
All Rights Reserved © Alcatel-Lucent 201425 | Milieucharter 2010-2011 | Eindaudit | Mei 2011
Transforming communications
for a sustainable planet