Application Economic, bidirectional measurement of liquids with a minimum conductivity of ³ 5 mS/cm in water applications. The electromagnetic measuring principle is unaffected by pressure and temperature. Additionally the flow profile has a minimal effect on the measurement results. Device properties Nominal diameter: DN 25 to 100 (1 to 4") Polyamide liner with worldwide drinking water approvals: KTW, WRAS, NSF, ACS Process pressure: max. 16 bar (232 psi) Durable polycarbonate transmitter housing Graphical local display with operation from the outside (Touch Control) Up to 3 outputs and 1 input including 4-20 mA HART communication Your benefits The lightweight flowmeter with innovative, self- centering sensor Sizing - correct product selection Applicator - the reliable, easy-to-use tool for selecting and sizing measuring devices for every application Installation - simple and efficient Compact wafer design Integrated self-centering for flush mounting Compact and remote version perfectly suited to meet the requirements of the water industry Commissioning - reliable and intuitive Guided parameterization - "Make-it-run" wizards Integrated web server for fast commissioning Operation - increased measurement availability Measurement of volume flow No pressure loss, no moving parts, immune to vibrations Diagnostics; automatic data restore by HistoROM Cost-effective life cycle management by W@M Technical Information Proline Promag D 400 Electromagnetic flow measuring system The lightweight, compact wafer style flowmeter for basic water applications TI01044D/06/EN/01.12 71183811

Electromagnetic flowmeter - Proline Promag D 400

Embed Size (px)

Citation preview

Page 1: Electromagnetic flowmeter - Proline Promag D 400

Application

• Economic, bidirectional measurement of liquids witha minimum conductivity of ³ 5 mS/cm in waterapplications.

• The electromagnetic measuring principle is unaffectedby pressure and temperature. Additionally the flowprofile has a minimal effect on the measurementresults.

Device properties• Nominal diameter: DN 25 to 100 (1 to 4")• Polyamide liner with worldwide drinking water

approvals: KTW, WRAS, NSF, ACS• Process pressure: max. 16 bar (232 psi)• Durable polycarbonate transmitter housing• Graphical local display with operation from the outside

(Touch Control)• Up to 3 outputs and 1 input including 4-20 mA HART

communication

Your benefits

The lightweight flowmeter with innovative, self-centering sensor

Sizing - correct product selectionApplicator - the reliable, easy-to-use tool for selecting andsizing measuring devices for every application

Installation - simple and efficient• Compact wafer design• Integrated self-centering for flush mounting• Compact and remote version perfectly suited to meet

the requirements of the water industry

Commissioning - reliable and intuitive• Guided parameterization - "Make-it-run" wizards• Integrated web server for fast commissioning

Operation - increased measurement availability• Measurement of volume flow• No pressure loss, no moving parts, immune to

vibrations• Diagnostics; automatic data restore by HistoROM

Cost-effective life cycle management by W@M

Technical Information

Proline Promag D 400Electromagnetic flow measuring systemThe lightweight, compact wafer style flowmeter for basic waterapplications

TI01044D/06/EN/01.1271183811

Page 2: Electromagnetic flowmeter - Proline Promag D 400

Table of contents Proline Promag D 400

2 Endress+Hauser

Table of contents

Document information . . . . . . . . . . . . . . . . . . . . . . . . 3Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Function and system design . . . . . . . . . . . . . . . . . . . . 4Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Operable flow range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Protocol-specific data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Performance characteristics . . . . . . . . . . . . . . . . . . . 16Reference operating conditions . . . . . . . . . . . . . . . . . . . . . 16Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . 16Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Influence of ambient temperature . . . . . . . . . . . . . . . . . . . 17

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Mounting kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Length of connecting cable . . . . . . . . . . . . . . . . . . . . . . . . 20Installing the wall-mount housing . . . . . . . . . . . . . . . . . . . 21Special mounting instructions . . . . . . . . . . . . . . . . . . . . . . 22

Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . 22Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Atmosphere . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Mechanical load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . 23

Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Medium temperature range . . . . . . . . . . . . . . . . . . . . . . . 23Conductivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Pressure-temperature ratings . . . . . . . . . . . . . . . . . . . . . . 23Pressure tightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Flow limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Pressure loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24System pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Mechanical construction . . . . . . . . . . . . . . . . . . . . . 25Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Measuring tube specification . . . . . . . . . . . . . . . . . . . . . . . 29Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Mounting bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Fitted electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Certificates and approvals . . . . . . . . . . . . . . . . . . . . 33CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33C-Tick symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Drinking water approval . . . . . . . . . . . . . . . . . . . . . . . . . 34Other standards and guidelines . . . . . . . . . . . . . . . . . . . . . 34

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 34

Application packages . . . . . . . . . . . . . . . . . . . . . . . 35Diagnostics functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . . . 35Communication-specific accessories . . . . . . . . . . . . . . . . . . 35Service-specific accessories . . . . . . . . . . . . . . . . . . . . . . . . 36System components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Standard documentation . . . . . . . . . . . . . . . . . . . . . . . . . 37Supplementary device-dependent documentation . . . . . . . . . . 37

Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . 37

Page 3: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 3

Document information

Symbols used Electrical symbols

Symbol Meaning

A0011197

Direct currentA terminal to which DC voltage is applied or through which direct current flows.

A0011198

Alternating currentA terminal to which alternating voltage is applied or through which alternating current flows.

A0017381

Direct current and alternating current• A terminal to which alternating voltage or DC voltage is applied.• A terminal through which alternating current or direct current flows.

) A0011200

Ground connectionA grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.

* A0011199

Protective ground connectionA terminal which must be connected to ground prior to establishing any other connections.

A0011201

Equipotential connectionA connection that has to be connected to the plant grounding system: This may be a potential equalizationline or a star grounding system depending on national or company codes of practice.

Symbols for certain types of information

Symbol Meaning

A0011182

AllowedIndicates procedures, processes or actions that are allowed.

A0011183

PreferredIndicates procedures, processes or actions that are preferred.

A0011184

ForbiddenIndicates procedures, processes or actions that are forbidden.

A0011193

TipIndicates additional information.

A0011194

Reference to documentationRefers to the corresponding device documentation.

A0011195

Reference to pageRefers to the corresponding page number.

A0011196

Reference to graphicRefers to the corresponding graphic number and page number.

Symbols in graphics

Symbol Meaning

1, 2, 3,... Item numbers

, …, Series of steps

A, B, C, ... Views

A-A, B-B, C-C, ... Sections

A0013441

Flow direction

Page 4: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

4 Endress+Hauser

Symbol Meaning

- A0011187

Hazardous areaIndicates a hazardous area.

. A0011188

Safe area (non-hazardous area)Indicates a non-hazardous area.

Function and system design

Measuring principle Following Faraday's law of magnetic induction, a voltage is induced in a conductor moving through a magneticfield.

In the electromagnetic measuring principle, the flowing medium is the moving conductor. The voltage inducedis proportional to the flow velocity and is supplied to the amplifier by means of two measuring electrodes. Theflow volume is calculated via the pipe cross-sectional area. The DC magnetic field is created through a switcheddirect current of alternating polarity.

I

L

B

I

Ue

A0017035

å 1 Ue = B · L · v ; Q = A · v

Ue Induced voltageB Magnetic induction (magnetic field)L Electrode spacingv Flow velocityQ Volume flowA Piping cross-sectionI Current

Page 5: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 5

Measuring system The device consists of a transmitter and a sensor.

Two device versions are available:• Compact version – the transmitter and sensor form a mechanical unit.• Remote version – the transmitter and sensor are mounted separately from one another.

Transmitter

Promag 400 Device versions and materials:• Compact housing: polycarbonate plastic• Wall-mount housing: polycarbonate plastic

Configuration:• External operation via four-line, illuminated local display with touch control

and guided menus ("Make-it-run" wizards) for applications• Via operating tools (e.g. FieldCare)• Via Web browser (e.g. Microsoft Internet Explorer)

A0017117

Sensor

Promag D Nominal diameter range: DN 25 to 100 (1 to 4")

Materials:• Sensor housing: aluminum coated AlSi10Mg• Sensor connection housing: aluminum coated AlSi10Mg• Liner: polyamide• O-rings: EPDM• Electrodes: 1.4435/316L• Ground disks: 1.4301/304

A0017036

Input

Measured variable Direct measured variables

• Volume flow (proportional to induced voltage)• Electrical conductivity

Calculated measured variables

Mass flow

Measuring range Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy

Flow characteristic values in SI units

Nominaldiameter

Recommendedflow Factory settings

min./max. full scale value(v ~ 0.3/10 m/s

Full scale value currentoutput

(v ~ 2.5 m/s)

Pulse value(~ 2 pulse/s)

Low flow cut off(v ~ 0.04 m/s)

[mm] [in] [dm3/min] [dm3/min] [dm3] [dm3/min]

25 1 9 to 300 75 0.5 1

40 1 ½ 25 to 700 200 1.5 3

50 2 35 to 1 100 300 2.5 5

65 – 60 to 2 000 500 5 8

80 3 90 to 3 000 750 5 12

100 4 145 to 4 700 1 200 10 20

Page 6: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

6 Endress+Hauser

Flow characteristic values in US units

Nominaldiameter

Recommendedflow Factory settings

min./max. full scale value(v ~ 0.3/10 m/s)

Full scale value currentoutput

(v ~ 2.5 m/s)

Pulse value(~ 2 pulse/s)

Low flow cut off(v ~ 0.04 m/s)

[in] [mm] [gal/min] [gal/min] [gal] [gal/min]

1 25 2.5 to 80 18 0.2 0.25

1 ½ 40 7 to 190 50 0.5 0.75

2 50 10 to 300 75 0.5 1.25

– 65 16 to 500 130 1 2

3 80 24 to 800 200 2 2.5

4 100 40 to 1 250 300 2 4

To calculate the measuring range, use the Applicator sizing tool (® ä 36)

Recommended measuring range

"Flow limit" section (® ä 24)

Operable flow range Over 1000 : 1

Input signal Status input

Maximum input values • DC 30 V• 6 mA

Response time Adjustable: 5 to 200 ms

Input signal level • Low signal: DC –3 to +5 V• High signal: DC 12 to 30 V

Assignable functions • Off• Reset totalizers 1-3 separately• Reset all totalizers• Flow override

Output

Output signal Current output

Current output Can be set as:• 4-20 mA HART (active)• 0-20 mA (active)

Maximum output values • DC 24 V (when idle)• 22.5 mA

Load 0 to 700 Ω

Resolution 0.5 µA

Damping Adjustable: 0 to 999 s

Assignable measuredvariables

• Volume flow• Conductivity• Mass flow

Page 7: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 7

Pulse/frequency/switch output

Function • With the order code for "Output; Input", option H: output 2 can be set as a pulse orfrequency output

• With the order code for "Output; Input", option I: output 2 and 3 can be set as a pulse,frequency or switch output

Version Passive, open collector

Maximum input values • DC 30 V• 250 mA

Voltage drop For 25 mA: £ DC 2 V

Pulse output

Pulse width Adjustable:0.05 to 2 000 ms

Maximum pulse rate 10 000 Impulse/s

Pulse value Adjustable

Assignable measuredvariables

• Volume flow• Mass flow

Frequency output

Output frequency Adjustable: 0 to 10 000 Hz

Damping Adjustable: 0 to 999 s

Pulse/pause ratio 1:1

Assignable measuredvariables

• Volume flow• Conductivity• Mass flow

Switch output

Switching behavior Binary, conductive or non-conductive

Switching delay Adjustable: 0 to 100 s

Number of switching cycles Unlimited

Assignable functions • Off• On• Diagnostic behavior• Limit value:

– Volume flow– Conductivity– Mass flow– Totalizer 1-3

• Flow direction monitoring• Status

– Empty pipe detection– Low flow cut off

Signal on alarm Depending on the interface, failure information is displayed as follows:

Current output

4-20 mA

Failure mode Selectable (as per NAMUR recommendation NE 43):• Minimum alarm: 3.6 mA• Maximum alarm: 22 mA• Adjustable value: 3.59 to 22.5 mA

0-20 mA

Failure mode Choose from:• Maximum alarm: 22 mA• Adjustable value: 0 to 22.5 mA

Page 8: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

8 Endress+Hauser

HART

Device diagnostics Device condition can be read out via HART Command 48

Pulse/frequency/switch output

Pulse output

Failure mode Choose from:• Actual value• No pulses

Frequency output

Failure mode Choose from:• Actual value• Defined value: 0 to 12 500 Hz• 0 Hz

Switch output

Failure mode Choose from:• Current status• Open• Closed

Local display

Plain text display With information on cause and remedial measures

Backlight Red backlighting indicates a device error.

Status signal as per NAMUR recommendation NE 107

Operating tool

• Via digital communication: HART protocol• Via service interface

Plain text display With information on cause and remedial measures

Additional information on remote operation (® ä 33)

Web browser

Plain text display With information on cause and remedial measures

Low flow cut off The switch points for low flow cut off are user-selectable.

Galvanic isolation The following connections are galvanically isolated from each other:• Inputs• Outputs• Voltage supply

Protocol-specific data HART

Manufacturer ID 0x11

Device type ID 0x47

HART protocol revision 6.0

Page 9: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 9

Device description files (DTM,DD)

Information and files under:www.endress.com

HART load Min. 250 Ω

Dynamic variables The measured variables can be freely assigned to the dynamic variables.

Measured variables for PV (primary dynamic variable)• Volume flow• Conductivity• Mass flow

Measured variables for SV, TV, QV (secondary, tertiary and quaternarydynamic variable)• Volume flow• Conductivity• Mass flow• Totalizer 1• Totalizer 2• Totalizer 3

Power supply

Terminal assignment Transmitter

0-20 mA/4-20 mA HART connection version with additional outputs and inputs

20 2122 23

24 2526 27

1 2

L+

/L

L-/

N+ +- -

+ +- -

A0017112

Supply voltage

Order code for"Power supply"

Terminal numbers

1 (L+/L) 2 (L-/N)

Option A AC 100 to 230 V

Option B AC/DC 24 V

Signal transmission

Order code for"Output; input"

Terminal numbers

Output 1 Output 2 Output 3 Input 4

26 (+) 27 (-) 24 (+) 25 (-) 22 (+) 23 (-) 20 (+) 21 (-)

Option H • 4-20 mA HART(active)

• 0-20 mA (active)

Pulse/frequencyoutput (passive)

switch output (passive) -

Option I • 4-20 mA HART(active)

• 0-20 mA (active)

Pulse/frequency/switch output (passive)

Pulse/frequency/switch output (passive)

Status input

Page 10: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

10 Endress+Hauser

Remote version

E1

E2

GN

D E

S1

E1

E2

S2

GN

D

E S

5 7 4 37 42 41

6 5 7 8 4 37 36

n.c. n.c.

dc

c d

b

42 41

a

A0017403

å 2 Remote version terminal assignment

a Transmitter: main electronics module with terminalsb Sensor: connection modulec Electrode cabled Coil current cablen.c. Not connected, insulated cable shields

Terminal No. and cable colors: 6/5 = brown; 7/8 = white; 4 = green; 36/37 = yellow

Supply voltage Order code for"Power supply"

Terminal voltage Frequency range

Option A: AC 100 to 230 V AC 85 to 260 V 47 to 63 Hz

Option B: AC/DC 24 V AC/DC 18 to 30 V 44 to 66 Hz/-

Power consumption Transmitter

Order code for"Power supply"

Maximum power consumption

Option A: AC 100 to 230 V 30 VA

Option B: AC/DC 24 V 30 VA/8 W

Current consumption Transmitter

Order code for"Power supply"

Maximum currentconsumption

Maximum switch-oncurrent

Option A: AC 100 to 230 V 145 mA 25 A (< 5 ms)

Option B: AC/DC 24 V 350 mA 27 A (< 5 ms)

Power supply failure • Totalizers stop at the last value measured.• Configuration is retained in the plug-in memory (HistoROM DAT).• Error messages (incl. total operated hours) are stored.

Page 11: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 11

Electrical connection Connecting the transmitter

2 2 1 4 3 2 2 1

A B

A0017113

A Compact versionB Remote version1 Cable entry for supply voltage2 Cable entry for signal transmission3 Cable entry for coil current cable4 Cable entry for electrode cable

Remote version connection

1 2

A0017267

1 Electrode cable2 Coil current cable

• Fix the cable run or route it in an armored conduit.Cable movements can influence the measuring signal especially in the case of low fluid conductivities.

• Route the cable well clear of electrical machines and switching elements.• Ensure potential equalization between sensor and transmitter (® ä 13).

Connection examples

0/4...20 mA

+

2

1

3

+

_

A0017162

å 3 Connection example for 0-20 mA current output (active) and 4-20 mA current output (active)

1 Automation system with current input (e.g. PLC)2 Analog display unit: observe maximum load (® ä 6)3 Transmitter

Page 12: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

12 Endress+Hauser

4

4...20 mA

+

5

21 3

6

+

_

A0016800

å 4 Connection example for 4-20 mA HART current output (active)

1 Automation system with current input (e.g. PLC)2 Observe cable specification (® ä 15)3 Connection for HART operating devices (® ä 33)4 Resistor for HART communication (³ 250 W): observe maximum load (® ä 6)5 Analog display unit: observe maximum load (® ä 6)6 Transmitter

1

+

_

12345

2

+

+–

3

A0016801

å 5 Connection example for pulse/frequency output (passive)

1 Automation system with pulse/frequency input (e.g. PLC)2 Voltage supply3 Transmitter: observe input values (® ä 7)

1

+_

+

_

2

+

_ 3

A0016802

å 6 Connection example for switch output (passive)

1 Automation system with switch input (e.g. PLC)2 Voltage supply3 Transmitter: observe input values (® ä 7)

Page 13: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 13

1

+ _

+

_

2

+

_3

A0017163

å 7 Connection example for status input

1 Automation system with status output (e.g. PLC)2 Voltage supply3 Transmitter: observe input values (® ä 7)

Potential equalization Requirements

Please consider the following to ensure correct measurement:• Same electrical potential for the fluid and sensor• Company-internal grounding concepts• Pipe material and grounding

Connection examples for standard situations

Metal, grounded pipe

This connection method also applies:• For plastic pipes• For pipes with insulating liner

A0017516

Connection example in special situations

Unlined and ungrounded metal pipe

This connection method also applies in situations where:• The customary potential equalization is not used• Equalizing currents are present

A0017517

Page 14: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

14 Endress+Hauser

Note the following when installing:• Connect both pipe flanges to one another via a ground cable and ground them.• Connect the connection housing of the transmitter or sensor to ground potential by means of the ground

terminal provided for the purpose. Mount the ground cable directly on the conductive flange coating of thepipe with the flange screws.

Ground cable Copper wire, at least 6 mm2 (0.0093 in2)

For remote device versions, the ground terminal in the example always refers to the sensor and not tothe transmitter.

The necessary ground cable can be ordered from Endress+Hauser .

Pipe with a cathodic protection unit

This connection method is only used if the following two conditions are met:• Metal pipe without liner or pipe with electrically conductive liner• Cathodic protection is integrated in the personal protection equipment

1 /

+–

2 /2 /

3 /

A0017518

Ground cable Copper wire, at least 6 mm2 (0.0093 in2)

1. Connect the measuring device to the power supply such that it is floating in relation to the protectiveground.

2. Install the sensor in the pipe in a way that provides electrical insulation.

3. Connect the two flanges of the pipe to one another via a ground cable.

4. Guide the shield of the signal lines through a capacitor.

For remote device versions, the ground terminal in the example always refers to the sensor and not tothe transmitter.

The necessary ground cable can be ordered from Endress+Hauser .

Terminals Transmitter• Supply voltage cable: plug-in screw terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)• Signal cable: plug-in screw terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)• Electrode cable: plug-in screw terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)• Coil current cable: screw terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)

SensorScrew terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)

Page 15: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 15

Cable entries Transmitter and sensor• Cable gland:

– For standard cable: M20 × 1.5 with cable Æ 6 to 12 mm (0.24 to 0.47 in)– For reinforced cable: M20 × 1.5 with cable Æ 9.5 to 16 mm (0.37 to 0.63 in)

• Thread for cable entry:– NPT ½"– G ½"– M20

If metal cable entries are used, use a grounding plate.

Cable specification Permitted temperature range

• –40 °C (–40 °F)...³ 80 °C (176 °F)• Minimum requirement: cable temperature range ³ ambient temperature + 20 K

Power supply cable

Standard installation cable is sufficient.

Signal cable

Current output

• For 0-20 mA and 4-20 mA: standard installation cable is sufficient.• For 4-20 mA HART: Shielded cable recommended. Observe grounding concept of the plant.

Pulse/frequency/switch output

Standard installation cable is sufficient.

Status input

Standard installation cable is sufficient.

Connecting cable for remote version

Electrode cable

Standard cable 3 ´ 0.38 mm2 (20 AWG) with common, braided copper shield (Æ ~ 7 mm (0.28")) andindividually shielded cores

Conductor resistance £ 50 W/km (0.015 W/ft)

Capacitance: core/shield £ 420 pF/m (128 pF/ft)

Operating temperature –20 to +80 °C (–68 to +176 °F)

Coil current cable

Standard cable 2 ´ 0.75 mm2 (18 AWG) with common, braided copper shield (Æ ~ 7 mm (0.28")) andindividually shielded cores

Conductor resistance £ 37 W/km (0.011 W/ft)

Capacitance: core/core,shield grounded

£ 120 pF/m (37 pF/ft)

Operating temperature –20 to +80 °C (–68 to +176 °F)

Test voltage for cableinsulation

£ AC 1433 V r.m.s. 50/60 Hz or ³ DC 2026 V

Page 16: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

16 Endress+Hauser

1

2

3

4

5

6

7

a b

A0003194

å 8 Cable cross-section

a Electrode cableb Coil current cable1 Core2 Core insulation3 Core shield4 Core jacket5 Core reinforcement6 Cable shield7 Outer jacket

Operation in zones of severe electrical interference

The measuring system meets the general safety requirements (® ä 34) and EMC specifications(® ä 23).

Grounding is by means of the ground terminal provided for the purpose inside the connection housing. Thestripped and twisted lengths of cable shield to the ground terminal must be as short as possible.

Performance characteristics

Reference operatingconditions

To DIN EN 29104• Fluid temperature: +28 ± 2 °C (+82 ± 4 °F)• Ambient temperature range: +22 ± 2 °C (+72 ± 4 °F)• Warm-up period: 30 min

Installation• Inlet run > 10 ´ DN• Outlet run > 5 ´ DN• Sensor and transmitter grounded.• The sensor is centered in the pipe.

To calculate the measuring range, use the Applicator sizing tool (® ä 36)

Maximum measured error Accuracy of outputs

o.r. = of reading; o.f.s. = of full scale value

The outputs have the following base accuracy specifications.

Current output

Accuracy Max. ±0.05 % o.f.s. or ±5 µA

Pulse/frequency output

Accuracy Max. ±50 ppm o.r.

Error limits under reference operating conditions

o.r. = of reading

Page 17: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 17

Pulse output±0.5 % o.r.± 1 mm/s (0.04 in/s)

Fluctuations in the supply voltage do not have any effect within the specified range.

2.5

[%]

2.0

1.5

1.0

0.5

0

0.5 %

0 1 2 4 6 8 10 [m/s]

v

5 10 15 20 25 30 32 [ft/s]0

A0003200

å 9 Maximum measured error in % o.r.

Repeatability o.r. = of reading

max. ±0.1 % o.r. ± 0.5 mm/s (0.02 in/s)

Influence of ambienttemperature

o.r. = of reading; o.f.s. = of full scale value

Current output

Temperature coefficient Typically ±50 ppm/°C o.r. or ±1 µA/°C

Pulse/frequency output

Temperature coefficient Max.±50 ppm/°C

InstallationNo special measures such as supports are necessary. External forces are absorbed by the construction of thedevice.

Mounting location Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the next pipe elbow: h =³ 2 × DN

h

A0017061

Page 18: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

18 Endress+Hauser

To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the followingmounting locations in the pipe:• Highest point of a pipeline.• Directly upstream of a free pipe outlet in a down pipe.

Installation in down pipes

Install a siphon or a vent valve downstream of the sensor in down pipes whose length h ³ 5 m (16.4 ft).Thisprecaution is to avoid low pressure and the consequent risk of damage to the measuring tube. This measurealso prevents the system losing prime, which could cause air pockets.

For information on the liner's resistance to partial vacuum (® ä 24)

h

2

1

A0017064

å 10 Installation in a down pipe

1 Vent valve2 Pipe siphonh Length of down pipe

Installation in partially filled pipes

A partially filled pipe with a gradient necessitates a drain-type configuration. The empty pipe detection (EPD)function offers additional protection by detecting empty or partially filled pipes.

• Do not install the sensor at the lowest point in the drain: risk of solids accumulating.• It is advisable to install a cleaning valve.

³5 ×

DN

³2 ×

DN

A0017063

Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction(direction of medium flow through the piping).An optimum orientation position helps avoid gas and air accumulations and deposits in the measuring tube.

Vertical

This is the optimum orientation for self-emptying piping systems.

A0015591

Page 19: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 19

Horizontal

The measuring electrode plane must be horizontal. This prevents brief insulation of the two measuringelectrodes by entrained air bubbles.

A

1 1

A

A0017195

å 11 Horizontal orientation

1 Measuring electrodes for signal detection

Inlet and outlet runs If possible, install the sensor upstream from fittings such as valves, T-pieces or elbows.

Observe the following inlet and outlet runs to comply with accuracy specifications:• Inlet run ³ 5 ´ DN• Outlet run ³ 2 ´ DN

5 × DN³ ³ 2 × DN

A0016275

Adapters Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-diameterpipes. The resultant increase in the rate of flow improves measuring accuracy with very slow-moving fluids.

The nomogram shown here can be used to calculate the pressure loss caused by reducers and expanders:• Calculate the ratio of the diameters d/D.• From the nomogram read off the pressure loss as a function of flow velocity (downstream from the reduction)

and the d/D ratio.

The nomogram only applies to liquids with a viscosity similar to that of water.

Page 20: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

20 Endress+Hauser

100

10

0.5d / D

[mbar]

0.6 0.7 0.8 0.9

1 m/s

2 m/s

3 m/s

4 m/s

5 m/s

6 m/s

7 m/s

8 m/s

1

Dd

max. 8°

A0016359

Mounting kit The sensor is installed between the pipe flanges using a mounting kit. The device is centered using the recesseson the sensor. Centering sleeves are also provided depending on the flange standard or the diameter of thepitch circle.

A mounting kit – consisting of mounting bolts, seals, nuts and washers – can be ordered separately (see"Accessories" section (® ä 35)).

5

1

2

3

4

A0018060

å 12 Mounting the sensor

1 Nut2 Washer3 Mounting bolts4 Centering sleeve5 Seal

Length of connecting cable To ensure correct measuring results when using the remote version,observe the maximum permitted cable length Lmax. This length is determined by the conductivity of the fluid.– If measuring liquids in general: 5 mS/cm– If measuring demineralized water: 20 mS/cm

Page 21: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 21

200

100

5

10 100 200

L max

[m][m]

[µS/cm]

L max[ft]

200 6000 400

A0016539

å 13 Permitted length of connecting cable for remote version

Area shaded gray = permitted rangeLmax = length of connecting cable in [m] ([ft])[mS/cm] = fluid conductivity

Installing the wall-mounthousing

Wall mounting

149 (5.85)

210.5

(8.2

9)

=

5.8 (0.23)

mm (in)

18 (0.71) =

14 (0.55)

5.8 (0.23)

A0017138

Page 22: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

22 Endress+Hauser

Pipe mounting

ø 20…70( 0.79…2.75)ø

~

~4.0)

102 (

mm (in)

4 x

4 x SW 8

PH 2

A0017135

A separate mounting kit can be ordered from Endress+Hauser for pipe mounting (® ä 35).

Special mounting instructions Weather protection cover

To ensure that the optional weather protection cover can be easily opened, maintain the following minimumhead clearance: 350 mm (13.8 in)

Environment

Ambient temperature range Transmitter –20 to +50 °C (–4 to +122 °F)

Local display The readability of the display may be impaired at ambient temperatures below–20 °C (–4 °F).

Sensor –20 to +60 °C (–4 to +140 °F)

Mount the transmitter separately from the sensor if both the ambient and fluidtemperatures are high.

Liner Do not exceed or fall below the permitted temperature range of the liner(® ä 23).

If operating outdoors:• Install the measuring device in a shady location.• Avoid direct sunlight, particularly in warm climatic regions.• Avoid direct exposure to weather conditions.

Weather protection covers can be ordered from Endress+Hauser: see "Accessories" section (® ä 35)

Storage temperature The storage temperature corresponds to the operating temperature range of the measuring transmitter and theappropriate measuring sensors.

Page 23: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 23

• Protect the measuring device against direct sunlight during storage in order to avoid unacceptably high surfacetemperatures.

• Select a storage location where moisture cannot collect in the measuring device as fungus or bacteriainfestation can damage the liner.

• If protection caps or protective covers are mounted these should never be removed before installing themeasuring device.

Atmosphere If a plastic transmitter housing is permanently exposed to certain steam and air mixtures, this can damage thehousing.

If you are unsure, please contact your Endress+Hauser Sales Center for clarification.

Degree of protection Transmitter• As standard: IP66/67, type 4X enclosure• When housing is open: IP20, type 1 enclosure

SensorAs standard: IP66/67, type 4X enclosure

Shock resistance Acceleration up to 2 g following IEC 600 68-2-6

Vibration resistance Acceleration up to 2 g following IEC 600 68-2-6

Mechanical load • Protect the transmitter housing against mechanical effects, such as shock or impact; the use of the remoteversion is sometimes preferable.

• Never use the transmitter housing as a ladder or climbing aid.

Electromagnetic compatibility(EMC)

• As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)• Complies with emission limits for industry as per EN 55011 (Class A)

Details are provided in the Declaration of Conformity.

Process

Medium temperature range 0 to +60 °C (+32 to +140 °F) for polyamide

Conductivity • ³ 5 mS/cm for liquids in general• ³ 20 mS/cm for demineralized water

Note that in the case of the remote version, the requisite minimum conductivity also depends on the cablelength (® ä 20).

Pressure-temperature ratings Permitted process pressure

40 50 60 70 80 90 100 110 120 130 140 15030 [°F]

[psi]

40

0

80

120

160

200

240

280

0

[bar]

5 10 15 20 25 30 35 40 5545 50 60 650 [°C]

4

8

12

16

20

A0017088

Page 24: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

24 Endress+Hauser

Pressure tightness Measuring tube: 0 mbar abs. (0 psi abs.) at a fluid temperature of £ +60 °C (+140 °F)

Flow limit The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The optimum velocityof flow is between 2 to 3 m/s (6.56 to 9.84 ft/s). Also match the velocity of flow (v) to the physical propertiesof the fluid:• v < 2 m/s (6.56 ft/s): for abrasive fluids (e.g. potter's clay, lime milk, ore slurry)• v > 2 m/s (6.56 ft/s): for fluids producing buildup (e.g. wastewater sludges)

For an overview of the measuring range full scale values, see the "Measuring range" section (® ä 5)

Pressure loss • No pressure loss occurs if the sensor is installed in a pipe with the same nominal diameter.• Pressure losses for configurations incorporating adapters according to DIN EN 545 (® ä 19)

System pressure • Never install the sensor on the pump suction side in order to avoid the risk of low pressure, and thus damageto the liner.

• Furthermore, install pulse dampers if reciprocating, diaphragm or peristaltic pumps are used.

• For information on the liner's resistance to partial vacuum (® ä 24)• For information on the measuring system's resistance to vibration and shock (® ä 23), (® ä 23)

A0015594

Vibrations In the event of very strong vibrations, the pipe and sensor must be supported and fixed. It is also advisable tomount the sensor and transmitter separately.

For information on the permitted resistance to vibration and shock (® ä 23), (® ä 23)

L

A0016266

å 14 Measures to prevent vibration of the device

L > 10 m (33 ft)

Page 25: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 25

Mechanical construction

Design, dimensions Compact version

Order code for "Housing", option M "Compact, polycarbonate"

DN 25…40(1"…1½" )

DN 50(2")

DN 65…100(2½"…4")

mm(in)

d 1

e 1

d 1

d 2

d 1

d 2

e 1e 1

e 2

d 2

A

B

F

H

G

D

C

E

A0017147

Dimensions in SI units

DN 1) A B C D E F G H d 1 d 2 e 1 2)

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

25 216 189 165 84 164 207 43 55 86 24 68

40 216 189 165 84 175 227 52 69 104 38 87

50 216 189 165 84 186 248 62 83 124 50 106

65 216 189 165 84 196 266 70 93 139 60 125

80 216 189 165 84 200 275 75 117 151 76 135

100 216 189 165 84 214 303 89 148 179 97 160

1) EN (DIN), JIS2) max. Æ seals

Page 26: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

26 Endress+Hauser

Dimensions in US units

DN 1) A B C D E F G H d 1 d 2 e 1 2) e 2 2)

[in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in]

1 8.50 7.44 6.50 3.31 6.46 8.15 1.69 2.17 3.39 0.94 2.68 –

1 ½ 8.50 7.44 6.50 3.31 6.89 8.94 2.05 2.72 4.11 1.50 3.43 –

2 8.50 7.44 6.50 3.31 7.32 9.76 2.44 3.27 4.88 1.97 4.17 –

3 8.50 7.44 6.50 3.31 7.72 10.5 2.95 4.61 5.94 2.99 – 5.43

4 8.50 7.44 6.50 3.31 7.87 10.8 3.50 5.83 7.05 3.82 6.30 –

1) ASME2) max. Æ seals

Transmitter remote version

Order code for "Housing", option N "Remote, polycarbonate"

B

A

KG

F

H

L

JJ

CD

E

A0017148

Dimensions in SI units

A B C D E F

[mm] [mm] [mm] [mm] [mm] [mm]

165 185 15 25 225 80

Page 27: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 27

G H J K L

[mm] [mm] [mm] [mm] [mm]

50 53 56 88.5 53

Dimensions in US units

A B C D E F

[in] [in] [in] [in] [in] [in]

6.5 7.28 0.59 0.98 8.86 3.15

G H J K L

[in] [in] [in] [in] [in]

1.97 2.09 2.2 3.48 2.09

Sensor remote version

E

C

B

A

DN 25…40(1"…1½")

DN 50(2")

DN 65…100(2½"…4")

mm(in)

D

F

H

G

d 1

e 1

d 1

d 2

d 1

d 2

e 1e 1

e 2

d 2

A0010717

Dimensions in SI units

DN 1) A B C D E F G H d 1 d 2 e 1 2)

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

25 129 163 143 55 102 192 43 235 86 24 68

40 129 163 143 69 102 203 52 255 104 38 87

50 129 163 143 83 102 214 62 276 124 50 106

Page 28: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

28 Endress+Hauser

DN 1) A B C D E F G H d 1 d 2 e 1 2)

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

65 129 163 143 93 102 224 70 294 139 60 125

80 129 163 143 117 102 228 75 303 151 76 135

100 129 163 143 148 102 242 89 331 179 97 160

1) EN (DIN), JIS2) max. Æ seals

Dimensions in US units

DN 1) A B C D E F G H d 1 d 2 e 1 2) e 2 2)

[in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in]

1 5.08 6.42 5.63 2.17 4.02 7.56 1.69 9.25 3.39 0.94 2.68 –

1 ½ 5.08 6.42 5.63 2.72 4.02 7.99 2.05 10.0 4.11 1.50 3.43 –

2 5.08 6.42 5.63 3.27 4.02 8.43 2.44 10.9 4.88 1.97 4.17 –

3 5.08 6.42 5.63 4.61 4.02 8.98 2.95 11.9 5.94 2.99 – 5.43

4 5.08 6.42 5.63 5.83 4.02 9.53 3.50 13.0 7.05 3.82 6.30 –

1) ASME2) max. Æ seals

Weight Compact version

Weight data:• Including the transmitter (1.15 kg (2.54 lbs))• Excluding packaging material

Weight in SI units

Nominal diameter EN (DIN), JIS

[mm] [in] [kg]

25 1 4.5

40 1 ½ 5.1

50 2 5.9

65 – 6.7

80 3 7.7

100 4 10.4

Weight in US units

Nominal diameter ASME

[mm] [in] [lbs]

25 1 9.9

40 1 ½ 11.2

50 2 13.0

65 – 14.8

80 3 17.0

100 4 22.9

Page 29: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 29

Transmitter remote version

1.15 kg (2.54 lb)

Sensor remote version

Weight data:• Including the transmitter housing• Excluding the connecting cable• Excluding packaging material

Weight in SI units

Nominal diameter EN (DIN), JIS

[mm] [in] [kg]

25 1 2.5

40 1 ½ 3.1

50 2 3.9

65 – 4.7

80 3 5.7

100 4 8.4

Weight in US units

Nominal diameter ASME

[mm] [in] [lbs]

25 1 5.5

40 1 ½ 6.8

50 2 8.6

65 – 10.4

80 3 12.6

100 4 18.5

Measuring tube specification Pressure rating EN (DIN)

Nominal diameter Pressure rating Mounting bolts Length internal diameter

Centering sleeves Measuring tube

[mm] [in] [mm] [in] [mm] [in] [mm] [in]

25 1 PN 16 4 ´ M12 ´ 145 5.71 54 2.13 24 0.94

40 1 ½ PN 16 4 ´ M16 ´ 170 6.69 68 2.68 38 1.50

50 2 PN 16 4 ´ M16 ´ 185 7.28 82 3.23 50 1.97

65 1) – PN 16 4 ´ M16 ´ 200 7.87 92 3.62 60 2.36

65 2) – PN 16 8 ´ M16 ´ 200 7.87 – 3) – 3) 60 2.36

80 3 PN 16 8 ´ M16 ´ 225 8.86 116 4.57 76 2.99

100 4 PN 16 8 ´ M16 ´ 260 10.24 147 5.79 97 3.82

1) EN (DIN) flange: 4-hole ® with centering sleeves2) EN (DIN) flange: 8-hole ® without centering sleeves3) A centering sleeve is not required. The device is centered directly via the sensor housing.

Page 30: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

30 Endress+Hauser

ASME pressure rating

Nominal diameter Pressure rating Mounting bolts Length internal diameter

Centering sleeves Measuring tube

[mm] [in] [mm] [in] [mm] [in] [mm] [in]

25 1 Class 150 4 ´ UNC ½" ´ 145 5.70 – 1) – 1) 24 0.94

40 1 ½ Class 150 4 ´ UNC ½" ´ 165 6.50 – 1) – 1) 38 1.50

50 2 Class 150 4 ´ UNC 5/8" ´ 190.5 7.50 – 1) – 1) 50 1.97

80 3 Class 150 8 ´ UNC 5/8" ´ 235 9.25 – 1) – 1) 76 2.99

100 4 Class 150 8 ´ UNC 5/8" ´ 264 10.4 147 5.79 97 3.82

1) A centering sleeve is not required. The device is centered directly via the sensor housing.

Pressure rating JIS

Nominal diameter Pressure rating Mounting bolts Length internal diameter

Centering sleeves Measuring tube

[mm] [in] [mm] [in] [mm] [in] [mm] [in]

25 1 10K 4 ´ M16 ´ 170 6.69 54 2.13 24 0.94

40 1 ½ 10K 4 ´ M16 ´ 170 6.69 68 2.68 38 1.50

50 2 10K 4 ´ M16 ´ 185 7.28 – 1) – 1) 50 1.97

65 – 10K 4 ´ M16 ´ 200 7.87 – 1) – 1) 60 2.36

80 3 10K 8 ´ M16 ´ 225 8.86 – 1) – 1) 76 2.99

100 4 10K 8 ´ M16 ´ 260 10.24 – 1) – 1) 97 3.82

1) A centering sleeve is not required. The device is centered directly via the sensor housing.

Materials Transmitter housing

• Order code for "Housing", option M, N: polycarbonate plastic• Window material: polycarbonate plastic

Transmitter cable entries

Order code for "Housing", option M "Compact, polycarbonate"; option N "Remote, polycarbonate"

The various cable entries are suitable for hazardous and non-hazardous areas.

Electrical connection Material

Cable gland M20 × 1.5 Plastic

Thread G ½"via adapter

Nickel-plated brass

Thread NPT ½"via adapter

Nickel-plated brass

Connecting cable for remote version

• Electrode cable: PVC cable with copper shield• Coil current cable: PVC cable with copper shield

Sensor housing

Aluminum coating AlSi10Mg

Page 31: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 31

Sensor connection housing

Aluminum coating AlSi10Mg

Sensor cable entries

Order code for "Housing", option N "Remote, polycarbonate"

The various cable entries are suitable for hazardous and non-hazardous areas.

Electrical connection Material

Cable gland M20 × 1.5 Nickel-plated brass

Thread G ½"via adapter

Nickel-plated brass

Thread NPT ½"via adapter

Nickel-plated brass

Liner

Polyamide

Electrodes

1.4435/316L

Process connections

• EN 1092-1 (DIN 2501)• ASME B16.5• JIS B2220

List of all available process connections

Seals

O-rings made from EPDM

Accessories

Weather protection cover

Stainless steel 1.4301

Ground disks

1.4301/304

Mounting bolts Tensile strength• Galvanized steel mounting bolts: strength category 5.6 or 5.8• Stainless steel mounting bolts: strength category A2–70

Fitted electrodes Measuring electrodes (x 2) made of 1.4435/316L

Process connections • EN 1092-1 (DIN 2501)• ASME B16.5• JIS B2220

For information on the materials of the process connections (® ä 31)

Page 32: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

32 Endress+Hauser

Operability

Operating concept Operator-oriented menu structure for user-specific tasks• Commissioning• Operation• Diagnostics• Expert level

Rapid and safe commissioning• Guided menus ("Make-it-run" wizards) for applications• Menu guidance with brief explanations of the individual parameter functions

Reliable operation• Operation in the following languages:

– Via local display:English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese, Japanese,Bahasa (Indonesian), Vietnamese, Czech

– Via "FieldCare" operating tool:English, German, French, Spanish, Italian, Dutch, Japanese

– Via Web browser:English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese, Japanese,Bahasa (Indonesian), Vietnamese, Czech

• Uniform operating philosophy applied to device, operating tools and Web browser• If replacing the electronic module, transfer the device configuration via the plug-in memory (HistoROM DAT)

which contains the process and measuring device data and the event logbook. No need to reconfigure.

Efficient diagnostics increase measurement availability• Troubleshooting measures can be called up via the device, operating tools and Web browser• Diverse simulation options and optional line recorder functions

Local operation

ESC

1

A0017120

1 Operation with touch control

Display elements

• 4-line display• White background lighting; switches to red in event of device errors• Format for displaying measured variables and status variables can be individually configured• Permitted ambient temperature for the display: –20 to +50 °C (–4 to +122 °F)

The readability of the display may be impaired at temperatures outside the temperature range.

Operating elements

External operation via touch control; 3 optical keys: , , E

Page 33: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 33

Remote operation Via HART protocol

1 2 3 5

74 6

A0017124

å 15 Options for remote operation via HART protocol

1 Control system (e.g. PLC)2 Field Communicator 4753 Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)4 Commubox FXA195 (USB)5 Field Xpert SFX1006 VIATOR Bluetooth modem with connecting cable7 Transmitter

Via service interface (CDI-RJ45)

2

1

3

A0017119

1 Service interface (CDI -RJ45) of the measuring device with access to the integrated Web server2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with

"FieldCare" operating tool with COM DTM "CDI Communication TCP/IP"3 Standard Ethernet connecting cable with RJ45 connector

Certificates and approvals

CE mark The measuring system is in conformity with the statutory requirements of the applicable EC Directives. Theseare listed in the corresponding EC Declaration of Conformity along with the standards applied.

Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.

Page 34: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

34 Endress+Hauser

C-Tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media Authority(ACMA)".

Ex approval cCSAus

Currently, the following versions for use in hazardous areas are available:

NI (Ex nA, Ex nL)Class I Division 2 Groups ABCD; NIFW*

*= NIFW parameter as per Control Drawings

Drinking water approval • ACS• KTW/W270• NSF 61• WRAS BS 6920

Other standards andguidelines

• EN 60529Degrees of protection provided by enclosures (IP code)

• EN 61010-1Protection Measures for Electrical Equipment for Measurement, Control, Regulation and LaboratoryProcedures.

• IEC/EN 61326Emission in accordance with Class A requirements. Electromagnetic compatibility (EMC requirements)

• ANSI/ISA-S82.01Safety Standard for Electrical and Electronic Test, Measuring, Controlling and related Equipment - GeneralRequirements. Pollution degree 2, Installation Category II

• CAN/CSA-C22.2 No. 1010.1-92Safety requirements for Electrical Equipment for Measurement and Control and Laboratory Use. Pollutiondegree 2, Installation Category II

• NAMUR NE 21Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment.

• NAMUR NE 32Data retention in the event of a power failure in field and control instruments with microprocessors

• NAMUR NE 43Standardization of the signal level for the breakdown information of digital transmitters with analog outputsignal.

• NAMUR NE 53Software of field devices and signal-processing devices with digital electronics

• NAMUR NE 105Specifications for integrating fieldbus devices in engineering tools for field devices

• NAMUR NE 107Status classification as per NE107

Ordering informationDetailed ordering information is available from the following sources:• In the Product Configurator on the Endress+Hauser website: www.endress.com ® Select country ®

Instruments ® Select device ® Product page function: Configure this product• From your Endress+Hauser Sales Center: www.endress.com/worldwide

Product Configurator - the tool for individual product configuration• Up-to-the-minute configuration data• Depending on the device: Direct input of measuring point-specific information such as measuring range

or operating language• Automatic verification of exclusion criteria• Automatic creation of the order code and its breakdown in PDF or Excel output format• Ability to order directly in the Endress+Hauser Online Shop

Page 35: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 35

Application packagesMany different application packages are available to enhance the functionality of the device. Such packagesmight be needed to address safety aspects or specific application requirements.

The application packages can be ordered from Endress+Hauser either directly with the device or subsequently.Detailed information on the order code in question is available from your local Endress+Hauser sales center oron the product page of the Endress+Hauser website: www.endress.com.

Diagnostics functions Package Description

HistoROM extendedfunction

Comprises extended functions concerning the event log and the activation of the measuredvalue memory (data logger).

Event log:Memory volume is extended from 20 message entries (basic version) to up to 100 entries.

Data logging (line recorder):• Memory capacity for up to 1000 measured values is activated.• 250 measured values can be output via each of the 4 memory channels. The recording

interval can be defined and configured by the user.• Data logging is visualized via the local display or FieldCare.

AccessoriesVarious accessories, which can be ordered with the device or subsequently from Endress+Hauser, are availablefor the device. Detailed information on the order code in question is available from your local Endress+Hausersales center or on the product page of the Endress+Hauser website: www.endress.com.

Device-specific accessories For the transmitter

Accessories Description

Promag 400 transmitter Transmitter for replacement or storage. Use the order code to define the followingspecifications:• Approvals• Output / input• Display / operation• Housing• Software

Weather protection cover Is used to protect the measuring device from the effects of the weather: e.g. rainwater, excessheating from direct sunlight or extreme cold in winter.

Connecting cable for remoteversion

Coil current and electrode cables, various lengths, reinforced cables available on request.

Pipe mounting set Pipe mounting set for transmitter.

Compact ® remoteconversion kit

For converting a compact device version to a remote device version.

For the sensor

Accessories Description

Ground disks for flangeconnections

Are used to ground the fluid in lined measuring tubes to ensure proper measurement.

For details, see Installation Instructions EA00070D

Communication-specificaccessories

Accessories Description

Page 36: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

36 Endress+Hauser

Commubox FXA191 HART For intrinsically safe HART communication with FieldCare via the RS232C interface.

For details, see "Technical Information" TI00237F

Commubox FXA195 HART For intrinsically safe HART communication with FieldCare via the USB interface.

For details, see "Technical Information" TI00404F

Commubox FXA291 Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser CommonData Interface) and the USB port of a computer or laptop.

For details, see "Technical Information" TI00405C

HART Loop ConverterHMX50

Is used to evaluate and convert dynamic HART process variables to analog current signalsor limit values.

For details, see "Technical Information" TI00429F and Operating InstructionsBA00371F

WirelessHART adapter Is used for the wireless connection of field devices.The WirelessHART adapter can be easily integrated into field devices and existinginfrastructures, offers data protection and transmission safety and can be operated in parallelwith other wireless networks with minimum cabling complexity.

For details, see Operating Instructions BA00061S

Fieldgate FXA320 Gateway for the remote monitoring of connected 4-20 mA measuring devices via a Webbrowser.

For details, see "Technical Information" TI00025S and Operating InstructionsBA00053S

Fieldgate FXA520 Gateway for the remote diagnostics and remote configuration of connected HART measuringdevices via a Web browser.

For details, see "Technical Information" TI00025S and Operating InstructionsBA00051S

Field Xpert SFX100 Compact, flexible and robust industry handheld terminal for remote configuration and forobtaining measured values via the HART current output (4-20 mA).

For details, see Operating Instructions BA00060S

Service-specific accessories Accessories Description

Applicator Software for selecting and sizing Endress+Hauser measuring devices:• Calculation of all the necessary data for identifying the optimum flowmeter: e.g. nominal

diameter, pressure loss, accuracy or process connections.• Graphic illustration of the calculation results

Administration, documentation and access to all project-related data and parameters overthe entire life cycle of a project.

Applicator is available:• Via the Internet: https://wapps.endress.com/applicator• On CD-ROM for local PC installation.

W@M Life cycle management for your plantW@M supports you with a wide range of software applications over the entire process: fromplanning and procurement, to the installation, commissioning and operation of themeasuring devices. All the relevant device information, such as the device status, spare partsand device-specific documentation, is available for every device over the entire life cycle.The application already contains the data of your Endress+Hauser device. Endress+Hauseralso takes care of maintaining and updating the data records.

W@M is available:• Via the Internet: www.endress.com/lifecyclemanagement• On CD-ROM for local PC installation.

Page 37: Electromagnetic flowmeter - Proline Promag D 400

Proline Promag D 400

Endress+Hauser 37

FieldCare FDT-based plant asset management tool from Endress+Hauser.It can configure all smart field units in your system and helps you manage them. By usingthe status information, it is also a simple but effective way of checking their status andcondition.

For details, see Operating Instructions BA00027S and BA00059S

System components Accessories Description

Memograph M graphicdisplay recorder

The Memograph M graphic data manager provides information on all the relevant measuredvariables. Measured values are recorded correctly, limit values are monitored and measuringpoints analyzed. The data are stored in the 256 MB internal memory and also on a SD cardor USB stick.

For details, see "Technical Information" TI00133R and Operating InstructionsBA00247R

DocumentationThe following document types are available:• On the CD-ROM supplied with the device• In the Download Area of the Endress+Hauser Internet site: www.endress.com ® Download

Standard documentation Device type Communication Document type Documentation code

5D4B**- - - - - Brief Operating Instructions KA01112D

HART Operating Instructions BA01061D

Supplementary device-dependent documentation

Device type Document type Approval Documentation code

5D4B**- Installation Instructions Specified for eachindividual accessory

Registered trademarksHARTÒ

Registered trademark of the HART Communication Foundation, Austin, USA

MicrosoftÒRegistered trademark of the Microsoft Corporation, Redmond, Washington, USA

ApplicatorÒ, FieldCareÒ, Field XpertTM, HistoROMÒ

Registered or registration-pending trademarks of the Endress+Hauser Group

Page 38: Electromagnetic flowmeter - Proline Promag D 400
Page 39: Electromagnetic flowmeter - Proline Promag D 400
Page 40: Electromagnetic flowmeter - Proline Promag D 400