Upload
bccomfort
View
421
Download
1
Embed Size (px)
DESCRIPTION
THE Energy Standard. Ratings for envelope, HVAC equipment, power, lighting levels. Copied by Canada (National Energy Code), referenced by the rest of the world. Still not in effect in Alberta, but it is in effect in various forms in most of the US.
Citation preview
ASHRAE 90.1-2010 Envelope Highlights
January 7th, 2013
YOUR CONTACTS
• Henry Leung, P.Eng., MBA, LEED AP Senior Design Engineer
• Amir Tehrani, P.Eng., LEED AP
Contract Manager, Partner
AGENDA1. ASHRAE 90.1 Overview
2. Compliance Paths
3. Cost
4. Envelope
5. Mechanical
6. Electrical
To provide minimum requirements for the energy-efficient design of buildings except low-rise residential buildings
30% Energy savings compared to ASHRAE 90.1-2004
OVERVIEW
National Energy Code for Canada
2011
i.e. Canadian ASHRAE 90.1
Mandatory Provisions(required for
most compliance options)
Building System Compliance Options
Energy Code Compliance
Prescriptive Option
Energy Cost Budget
Trade Off Option
Simplified
Envelope
HVAC
Lighting
SWH
Power
Other
Compliance Approaches
LEED
• LEED Canada NC 2009 - Valid until at least 2015
1. ASHRAE 90.1-20072. MNECB 1997
• LEED v4 1. ASHRAE 90.1-20102. maybe NECB 2011
COST
ENVELOPE
SECTION 5ABOVE-GRADE WALL INSULATION
Four types of walls are defined Mass walls
– heat capacity determined from Table A3.1B or A3.1C
– R-value is for continuous insulation or when uninterrupted by framing other than metal clips no closer than 24 in. o.c. horizontally and 16 in. o.c. vertically
Metal building wall R-value – for insulation compressed between metal
wall panels and the steel structure Steel-framed wall R-value
– for uncompressed insulation installed in the cavity between steel studs
Wood-framed and other R-value – for uncompressed insulation installed in
the cavity between wood studs; also acceptable to be continuous insulation uninterrupted by studs
ENVELOPE
Allowed if they don’t increase energy usage of building
Installation of storm windows
Replacement of glazing in existing sash and frame
Alterations to envelope cavities provided they are insulated to full depth with a nominal R-3.0 per in.
Roof and floor alterations where no new cavities are created
Replacement of roof membranes
Replacement of existing doors
Replacement of existing fenestration, provided area of replacement is no more than 25% of total fenestration area
Section 5Envelope Alteration Exceptions
Envelope
Envelope
SECTION 5 – 5.5.4.2.3SKYLIGHT FENESTRATION AREA
Skylights are required in enclosed spaces that are• ≥ 5,000 ft2 and• Ceiling heights > 15 ft and• Space types
– Office - Convention Center– Transportation– Lobby - Automotive Service– Workshop– Atrium - Manufacturing– Concourse - Non-refrigerated
Warehouse– Corridor - Retail– Storage - Distribution/Sorting Area– Gymnasium/Exercise Center
SECTION 5 – 5.5.4.2.3SKYLIGHT FENESTRATION AREA
Total skylight area is either:• Minimum of 3% of roof area with a skylight VLT at least 0.40 OR• Such that the daylight area under skylights is a minimum of half the floor
area and provides a minimum skylight effective aperture of at least 1%Exceptions• Climate zones 6-8• Spaces with LPDs < 0.5 W/ft2
• Shaded spaces• Daylight area under rooftop monitors is > 50% of floor area• Documented that 90% of skylight area is shaded on June 21 (Northern
Hemisphere)/December 21 (Southern Hemisphere) at noon by permanent features
• Required daylight area under skylights may be reduced by amount of:• primary sidelighted area with sidelighting effective aperture > 0.15• secondary sidelighted area with sidelighting effective aperture >
0.30 with general lighting controlled by continuous daylight dimming
SECTION 5 – 5.5.4.5FENESTRATION ORIENTATION
Vertical fenestration area to meet this requirement:
Area South ≥ Area West and Area South ≥ Area East
Exceptions:• Buildings shaded by other buildings within 20 ft to the south
which is at least ½ as tall as the proposed building• Buildings with shade on 75% of the west and east• Alterations and additions that don’t increase vertical
fenestration area
N
No! Yes!
HVAC1. Economizers required for > 4 ton RTU
2. Energy Recovery > 5000 CFM units
HVAC Equipment Covered Air conditioners and condensing units Heat pumps (air, water, and ground source) Water-chilling packages (chillers) Packaged terminal and room air conditioners and heat pumps Furnaces, duct furnaces and unit heaters Boilers Heat rejection equipment (cooling towers) Heat transfer equipment (heat exchangers) Variable refrigerant flow (VRF) air conditioners VRF air-to-air and applied heat pumps Air conditioners serving computer rooms
SECTION 6 – 6.4.1.1 MINIMUM EQUIPMENT EFFICIENCY
DCV must be provided for each zone with a area > 500 ft² and the design occupancy > 40 people/1000 ft² where the HVAC system has:
An air-side economizer, Automatic modulating control of the OSA dampers, or A design outdoor airflow > 3,000 cfm
SECTION 6 – 6.4.3.9 (6.3.2Q)DEMAND CONTROL VENTILATION
Demand control ventilation (DCV): a ventilation system capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less
than design occupancy.
LIGHTING• Lighting alteration requirements take effect at 10%
replacement• Include exterior areas• Include renovations even when it is just
lamp/ballast replacement
≥ 50% of all 125 volt 15- and 20-amp receptacles (including those in modular partitions) must be controlled by an automatic control device in these space types
Private offices Open offices Computer classrooms
Exceptions Receptacles designated for equipment requiring 24 hr operation Spaces with security or safety concerns
Automatic control devices must function on:
Time-of-day controller provided to control ≤ 25,000 ft2 and not more than one floor
Occupant sensor to turn off receptacles within 30 minutes of occupant leaving the space
Signal from another control or alarm that indicates the area is unoccupied
SECTION 8 – 8.4.2AUTOMATIC RECEPTACLE CONTROL
Automatic lighting shutoff control device required
EXCEPT: Lighting for 24-hour operation Patient care spaces Areas with safety or security concerns
Compliance options:
Control lights on a scheduled basis (automatic time switch) Time-of-day controller Controls ≤ 25,000 ft2 and not more than one floor
Occupant sensor Turn lights off within 30 minutes of occupant leaving the space
Signal from another control or alarm that indicates the area is unoccupied
SECTION 9 - 9.4.1MANDATORY AUTOMATIC SHUTOFF
At least one for each room or space enclosed by ceiling-height partitions
– To have at least one control step between 30% and 70% (inclusive) of full lighting power in addition to all off
• Exceptions:– Lighting in corridors, electrical/mechanical rooms, public
lobbies, restrooms, stairways, and storage rooms– Spaces with only 1 luminaire with rated input power <
100W– Space types with lighting power allowance of < 0.6 W/ft2
– in spaces ≤ 10,000 ft2, each control serves 2,500 ft2 maximum and in spaces > 10,000 ft2, serves 10,000 ft2 maximum
Readily accessible to occupants Override of any time-of-day control for
no more than 2 hours Remote location is allowed to
accommodate areas where safety or security is a concern
SECTION 9 – 9.4.1.2MANDATORY: INDIVIDUAL SPACE CONTROL
Occupancy sensors are required in: Classrooms and lecture halls Conference, meeting, and training
rooms Employee lunch/break rooms Storage and supply rooms between 50
ft2 and 1000 ft2
Rooms used for document copying and printing
Office spaces < 250 ft2
Restrooms Dressing, locker, and fitting rooms
Exceptions:– Spaces with multi-scene control
systems– Shop and lab classrooms– Areas with safety or security concern– Lighting required for 24 hour operation
SECTION 9 – 9.4.1.2 MANDATORY INDIVIDUAL SPACE CONTROLS
Parking garage lighting to be automatically controlled, including daylighting• Must reduce lighting power by minimum of 30% when no activity
detected for no more than 30 minutes within a lighting zone ≤ 3,600 ft2
• Daylight transition zone lighting– Controlled separately to automatically turn on lighting during
daylight hours and off at sunset• Automatically reduce power in response to daylight for luminaires
within 20 ft of any perimeter wall that has– a net opening to wall ratio of ≥ 40% and– no exterior obstructions within 20 ft
Exceptions• Daylight transition zones and ramps without parking are exempt
from 30% reduction and daylight control• Applications using HID of 150W or less or induction lamps are
exempt from 30% reduction
SECTION 9 – 9.4.1.3 PARKING GARAGE LIGHTING CONTROL