Living unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation Demand (A)Demand (A)Demand (A)LoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation
L1 L2 L3
A (i) Lighting points 65 A + 0.25 Aper living unit
5 + (6 x 0.25) 6.5 6.5 6.5
B (i) 10 A socket outlet 6
15 A + 3.75 Aper living unit
15 + (6 x 3.75) 37.5 37.5 37.5
C Free standing range 6
2.8 Aper living unit
6 x 2.8 16.8 16.8 16.8
D Air conditioner 675% (or x 0.75)
6 x 12.8 x 0.75 57.6 57.6 57.6
FQuick recoveryHWS 6
6 A per living unit
6 x 6 36.0 36.0 36.0
Total demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phase154.4154.4 154.4
Living unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation Demand (A)Demand (A)Demand (A)LoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation
L1 L2 L3
A (i) Lighting points 65 A + 0.25 Aper living unit
5 + (6 x 0.25) 6.5 6.5 6.5
B (i) 10 A socket outlet 6
15 A + 3.75 Aper living unit
15 + (6 x 3.75) 37.5 37.5 37.5
C Free standing range 6
2.8 Aper living unit
6 x 2.8 16.8 16.8 16.8
D Air conditioner 675% (or x 0.75)
6 x 12.8 x 0.75 57.6 57.6 57.6
FQuick recoveryHWS 6
6 A per living unit
6 x 6 36.0 36.0 36.0
Total demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phase154.4154.4 154.4
Living unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation Demand (A)Demand (A)Demand (A)LoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation
L1 L2 L3
A (i) Lighting points 65 A + 0.25 Aper living unit
5 + (6 x 0.25) 6.5 6.5 6.5
B (i) 10 A socket outlet 6
15 A + 3.75 Aper living unit
15 + (6 x 3.75) 37.5 37.5 37.5
C Free standing range 6
2.8 Aper living unit
6 x 2.8 16.8 16.8 16.8
D Air conditioner 675% (or x 0.75)
6 x 12.8 x 0.75 57.6 57.6 57.6
FQuick recoveryHWS 6
6 A per living unit
6 x 6 36.0 36.0 36.0
Total demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phase154.4154.4 154.4
Living unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation Demand (A)Demand (A)Demand (A)LoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation
L1 L2 L3
A (i) Lighting points 65 A + 0.25 Aper living unit
5 + (6 x 0.25) 6.5 6.5 6.5
B (i) 10 A socket outlet 6
15 A + 3.75 Aper living unit
15 + (6 x 3.75) 37.5 37.5 37.5
C Free standing range 6
2.8 Aper living unit
6 x 2.8 16.8 16.8 16.8
D Air conditioner 675% (or x 0.75)
6 x 12.8 x 0.75 57.6 57.6 57.6
FQuick recoveryHWS 6
6 A per living unit
6 x 6 36.0 36.0 36.0
Total demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phase154.4154.4 154.4
Living unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation Demand (A)Demand (A)Demand (A)LoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation
L1 L2 L3
A (i) Lighting points 65 A + 0.25 Aper living unit
5 + (6 x 0.25) 6.5 6.5 6.5
B (i) 10 A socket outlet 6
15 A + 3.75 Aper living unit
15 + (6 x 3.75) 37.5 37.5 37.5
C Free standing range 6
2.8 Aper living unit
6 x 2.8 16.8 16.8 16.8
D Air conditioner 675% (or x 0.75)
6 x 12.8 x 0.75 57.6 57.6 57.6
FQuick recoveryHWS 6
6 A per living unit
6 x 6 36.0 36.0 36.0
Total demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phase154.4154.4 154.4
Living unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLiving unit loading for 6 living units per phaseLoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation Demand (A)Demand (A)Demand (A)LoadGroup
Description of load(given list)
Qty units per phase
Current allowanceper unit(column 4)
Calculation
L1 L2 L3
A (i) Lighting points 65 A + 0.25 Aper living unit
5 + (6 x 0.25) 6.5 6.5 6.5
B (i) 10 A socket outlet 6
15 A + 3.75 Aper living unit
15 + (6 x 3.75) 37.5 37.5 37.5
C Free standing range 6
2.8 Aper living unit
6 x 2.8 16.8 16.8 16.8
D Air conditioner 675% (or x 0.75)
6 x 12.8 x 0.75 57.6 57.6 57.6
FQuick recoveryHWS 6
6 A per living unit
6 x 6 36.0 36.0 36.0
Total demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phaseTotal demand current for six living units per phase154.4154.4 154.4