COMMERCIAL REFRIGERATION AT HIGH PERFORMANCE ENERGY APRIL 2016
Presentation Contents ALDI Aust ral ia 1. Current Refrigerat ion – CO2/ R134a system performance/ analysis
2. Chest Freezer Performance/ Analysis
3. ALDI Refrigerat ion Future – CO2 Transcrit ical Systems
Other Supermarkets around Aust ral ia: 1. Woolworths
2. Coles Australia
3. Coles Coburg
4. Coles Coburg - Liquorland
New developments across Asia Paci f ic Possible barriers to CO2 t ranscri t ical in Aust ral ia Possible commercial applicat ions for natural refr igerants in Aust ral ia
Refrigeration Systems Found in a typical ALDI store
▸ Current ly ut ilise CO2 Cacade/ R134a systems. ▸ Us ed For Chiller, Freezer Rooms and Multideck Cas es
▸ Typically 5 kWr on low Temp and 89 kWr on Med Temp
▸ 145 + s tores ins talled s ince 2014
Performance & Results
▸ Small efficency improvement
▸ Good refrigeration performance
▸ Elimniated all R404a leaks /emmis ions
Issues and Learning
▸ Initial cos t premium (now eliminated)
▸ S ome ups killing of ins tallers required (becoming indus try s tandard) .
ALDI CO2 Cacade/R134a systems
▸ Needs high s ide plant
operating – may have relief valve dis charge (not a major problem).
▸ R290 ut ilised on both Ches t and Top Freezer units
▸ Each has < 150g of Hydrocarbon charge
▸ Each unit has VS D compres s or and EC fans on condens er/s ub cooler.
ALDI Chest Freezers
Performance & Results
▸ Very reliable
▸ 6.7 kWhrs/ 24 hrs for 670L net volume
▸ Can have significant ly
less central plant as low temp load is removed from the central racks
Issues and Learning
▸ 6.7 kWhrs/ 24 hrs for 670L net volume
▸ Need department of mines rego if used in QLD
▸ Service mechanics need extra training
ALDI Chest Freezers
▸ Use policy of no major
cut ins/ major service in store.
CO2 TRANSCRITICAL
Performance & Results ▸ Utilis es one low temp boos ter compres s or and 3 medium
temp compres s ors
▸ S ingle Gas Cooler with adiabatic water s prays and s mall water chiller running on R290 and high pres s ure s ub cooler
▸ S ite has no s ynthetic refrigerant , s o overall TEWI is reduced for the s ys tems life
CO2 TRANSCRITICAL
Issues and Learning
▸ Cos t premium for initial ins tallations .
▸ Tes ts run in February 2016 s howed the s ys tem would overload if ran without water s prays , res ulting in s ome CO2 releas e from the LT receiver.
Performance and Results
▸ Very good multideck performance
▸ Ran 1 year without any major fault
▸ Reduced energy us age f0r majority of operating conditions below 30 degC
▸ For December, overall the s ame as s imilar s tores , better for colder months
Future
▸ Improve reliability of s ubcooler
▸ S ource OEM units on
natural refrigerants
▸ Reduce s ize of boos ter
▸ CO2 integral units on water loop
▸ Only enable water s prays at peak ambient
▸ Cons ider parrallel compres s ion and ejectors for next generation
Woolworths Australia
▸ Many CO2/R134a ins tallations in the pas t few years
(indus try s tandard).
▸ Two CO2 trans critical plants in New Zealand underway.
Coles Coburg North Store – System Description
▸ Als o s erving s tore airconditioing via chilled
water from 3 parallel compres s ion compres s ors and chilled water heat exchange
▸ Alfa Laval gas cooler with adiabatic water s prays .
▸ High pres s ure s ub cooling via plate heat exchangers to the parallel compres ion s uction.
▸ S ys tem has heat reclaim on dis charge.
▸ Has emergency compres s or/condens er to maintain pres s ure in cas e of fault.
▸ 1 s tore CO2 trans critical us ing two large bitzer compres s or racks
▸ S erving 6 freezer cas e s tubs and 14 medium temp s tubs per rack including BOH freezer and chiller rooms
Coles Coburg North Store
Performance and Results ▸ General concensus is happy with
res ults
▸ S ignificant energy s avings reported (>15%) s ince commis s ioning in June.
▸ This s tore s ucces s will be a catalys t for future ins tallations .
Issues and Learning ▸ Trial of Hot gas defros t has been reverted
back to electric – no s ignificant energy difference reported.
▸ S ome oil foaming is s ues (currently being worked through)
▸ Failure of oil s eparator (due to internal implos ion).
▸ S ome learning due to s eparation of commis s ioning res pons ibility from initial ins tallation crew.
▸ Condens ing via waterloop to dry cooler with
adiabatic s prays
▸ Hydrocrabon charges of 650-850g per cas e (greater than 150g limit) – requires cas es to be built in as part of ris k/compliance review.
▸ Us ing OEM (Carter UK) equipment.
Coles Coburg Liquor Land – Hydrocarbon R1270
System description ▸ 2 X 3.75m & 1x2.5m Multideck liquor dis play cas es , pre packaged with 2
hermetic compres s ors on each cas e.
Other Installations – New Zealand
System Features ▸ CO2 transcrit ical with
air cooled gas coolers
▸ Low Temp and Med Temp And Hot water Reclaim
▸ High s tanding pres s ure avoids need for s tandby power 120 bar high s ide 60 bar low s ide
▸ Have multiple s tores in Place
Issues and Learning ▸ Need to cons ider
implications of s pecialis t controls s ys tems which need overs eas as s is tane for modifications etc.
▸ New Zealand has a form of carbon levy on high GWP refrigerants – this helps make the cas e for CO2 Trans critical
Barriers in Australia to Adoption of CO2 Transcritical and natural Refrigeration
Cost Premium ▸ Higher init ial Cost - offs et by lower lifecycle cos t
▸ HFOs not cons idered as long term s olution and are expens ive
▸ Trans critical cos ts will be reduced as volume of ins tallations increas e
Expertise
▸ Lack of s kills and knowledge arround trans critical and natural refrigerants
▸ This is a ‘chicken and egg’ s cenario – as demand increas es , s witched on companies and mechanics will ups kill to meet demand.
Barriers in Australia to Adoption of CO2 Transcritical and natural Refrigeration
Regulatory Barriers ▸ Inconsistent and uninformed OH& S regulators
– Better licens ing programs are required
▸ S tandards (s uch as AS 1677) need replacing (IS O 5149 to be releas ed late 2016?).
▸ Concern on who carries the ris k for new applications utilis ing this technology – What is the definition of a competent pers on?
▸ Where are our indus try bodies ? – s eem to be taking a pas s ive approach, Mis s ed opportunites .
Training Faculties and Courses
▸ Aus tralian TAFE s ys tems facing many hurdles – Demand is needed to pull incentives for cours e development
– A Better licens ing s ys tem that rewards technicians who has ups killed
Barriers in Australia to Adoption of CO2 Transcritical and natural Refrigeration
▸ Chilled water from parallel compres s ion s upermarket refrigeration (e.g. Coles
Coburg North)
▸ Direct Expans ion CO2 in multis ys tem applications (e.g. Equizine in Thornbury)
▸ Chilled water forom high temp s tage of ammonia refrigeration s ys tem (e.g. Aldi)
▸ Future applications of Air cooled Hydrocarbo water chillers
▸ S mall charge Hydrocarbon s plit s ys tems
Natural Refrigerants & HVAC systems in commercial applications