46
Phillip Wall - MIEAust [email protected] Earthing Systems in Mining Operations managing transfer voltage hazards 25th Electrical Engineering Safety Seminar - Nov 2015

Earthing systems in mines - Phillip Wall

Embed Size (px)

Citation preview

Page 1: Earthing systems in mines - Phillip Wall

Phillip Wall - MIEAust [email protected]

Earthing Systems in Mining Operations – managing transfer voltage hazards

25th Electrical Engineering Safety Seminar - Nov 2015

Page 2: Earthing systems in mines - Phillip Wall

Segregate and contain? OR

Bond all systems?

Earthing Systems in Mines

A high Earth Potential Rise (EPR) needs to be adequately managed

Should we:

Slide 1

Page 3: Earthing systems in mines - Phillip Wall

Earthing Systems in Mines Managing transfer

voltage hazards

Page 4: Earthing systems in mines - Phillip Wall

Fault Current

Impedance to Ground

Buried Earth Grid

Voltage = Earth Potential Rise

(EPR)

Page 5: Earthing systems in mines - Phillip Wall

Voltage = Earth Potential

Rise (EPR)

V Touch Voltage

Transfer Hazard V

Step Voltage V

Page 6: Earthing systems in mines - Phillip Wall

Mandatory commonly bonded systems:

Power Systems AS/NZS 3007 AS 2067 Single combined earthing systems Unless:

• Underground mining • Voltage limits cannot be achieved

Page 7: Earthing systems in mines - Phillip Wall

Mandatory commonly bonded systems:

Lightning Protection Systems

AS/NZS 1768 & AS/NZS 3007 Single combined earthing systems Unless:

• Underground mining

Page 8: Earthing systems in mines - Phillip Wall

• Reduce: impedance of the earthing system, earth fault current or fault clearing time • Surface insulating layers, grading rings or bonding concrete reinforcement • Separation of HV and LV earthing systems • Combined HV and LV earthing systems • Isolation • Protective barriers or signs • Remove non compliant infrastructure (eg telco pit)

Risk Management Treatment Methods

Page 9: Earthing systems in mines - Phillip Wall

Mitigation methods for Lightning effects

- Minimizing the lightning collection area

- Supplementary bonding underground in accordance to the principles of AS/NZS1768

- Insulation between separate earthing systems

- Reducing earth connection resistances

Page 10: Earthing systems in mines - Phillip Wall

Lightning Protection Systems in Mines

• Surface installations, protection - AS/NZS 1768

• For underground mines, bonding principles in underground - AS/NZS 1768

Transfer of lightning to other parts of the mine?

• Minimised through separated earthing systems.

Page 11: Earthing systems in mines - Phillip Wall

Boreholes:

• Voltages can be controlled with PVC insulation. (Dielectric Isolation)

• Stopping the casing short (say 10m above roof mesh) is a similar outcome to PVC for current.

ACARP PROJECT FINDINGS Project C22003 published 1/6/2015

‘Investigation of the Potential Lightning Impacts on Underground Coal Mines’

Source: ‘Investigation of the Potential Lightning Impacts on Underground Coal Mines’ by Prof. David Cliff

Page 12: Earthing systems in mines - Phillip Wall

ACARP PROJECT FINDINGS Boreholes (cont):

• Attenuation ↑ lower soil resistivity

deeper the mine

• Impulsive volts ~ tens of kV on roof mesh

• Gaps in roof mesh - reduced currents

Project C22003 published 1/6/2015

Page 13: Earthing systems in mines - Phillip Wall

Direct strike to surface transformers feeding U/G parts

ACARP PROJECT FINDINGS Project C22003 published 1/6/2015

• Large Voltages (~MV) transferred by cable screens to U/G parts

• Potential difference in U/G

soil → cable screen armour was found to be very high.

• Voltages relatively independent of mine depth, frequency and length of power cable

Page 14: Earthing systems in mines - Phillip Wall

• Smaller than direct strike BUT still significant

• The potentials in U/G Parts↑significantly

for increasing cable lengths for higher freq.

ACARP PROJECT FINDINGS Project C22003 published 1/6/2015

Indirect strike to a cable due to a horizontal lightning channel

Page 15: Earthing systems in mines - Phillip Wall

Why would we separate earthing systems?

• Majority of cases safer to commonly bond.

– Improves overall system impedance

– Lower EPRs and touch hazards

– Simplest and easiest configuration to maintain

– Less damage to equipment

Separate or Common Earthing Systems?

Page 16: Earthing systems in mines - Phillip Wall

Why would we separate?

Page 17: Earthing systems in mines - Phillip Wall

A note on separations – two scenarios

1. Separation between power systems EPR from a power system fault:

Main Substation

mine infrastructure (or Mine Surface Earth)

What is the source of electrical energy?

Page 18: Earthing systems in mines - Phillip Wall

A note on separations

2. Separation for lightning transfer

surface

underground

Page 19: Earthing systems in mines - Phillip Wall

Separated Power Earthing Systems

When EPR cannot be managed through Common Bonding. Sparse networks

Separation comes with a few difficulties:

• Confusion from multiple earthing systems

• Hazards within yard due to different potentials on earths

• Lightning Flashover – correct insulation levels

• Earth switches/switchboard earths maintenance

• Single point bonding / cable damage

Page 20: Earthing systems in mines - Phillip Wall

Common Bonded vs Separated

Q: Do the scales tilt at any point?

A: Yes, however the optimum arrangement is not always apparent;

Lower touch voltages with more exposure

vs

Higher touch voltages with less exposure

Each system differs and requires detailed assessment.

Page 21: Earthing systems in mines - Phillip Wall

Independent

Earthing System

Impedance Earthed - IT systems:

The earthable point of the power system is either isolated from earth or earthed through an impedance

Provide for the safe management of voltages during earth faults

Page 22: Earthing systems in mines - Phillip Wall

Impedance Earthed systems

According to AS/NZS 3007:2013

“There is potential benefit for electrical supplies entering underground being impedance earthed systems”

Readily controls touch and transfer potential

Page 23: Earthing systems in mines - Phillip Wall

Typical Earthing systems … and how they go together:

Network Earth

Mine Surface Earth (MSE)

Mine Underground Earth (MUE)

Lightning Earth

Page 24: Earthing systems in mines - Phillip Wall

Network Earth … is the Earthing system associated with the incoming supply.

Irrespective of earth connection to the upstream Network

substation, the earth fault belongs to network.

Page 25: Earthing systems in mines - Phillip Wall

Mine Earth

Page 26: Earthing systems in mines - Phillip Wall

Q: What is a Lightning Earth?

A: An earth termination intended to discharge lightning currents into the general mass of the earth.

Lightning Earth and transfer effects

Page 27: Earthing systems in mines - Phillip Wall

What happens when the structure is used as a downconductor?

Can there be Lightning and Power System separation?

Lightning Earth and transfer effects

Page 28: Earthing systems in mines - Phillip Wall

Lightning Earth and Mine Earths

Unless suitably protected, all surface structures can be assumed to be incorporated into a lightning earth.

Page 29: Earthing systems in mines - Phillip Wall

Power Systems Separation

Neutral Earthing Resistor

Page 30: Earthing systems in mines - Phillip Wall

Power Systems Separation

What is this earth?

Page 31: Earthing systems in mines - Phillip Wall

Where to earth?

Power Systems Separation

Page 32: Earthing systems in mines - Phillip Wall

Insulated and isolated earth

Power Systems Separation

Page 33: Earthing systems in mines - Phillip Wall

Two earthing systems within the one yard

Power Systems Separation

Page 34: Earthing systems in mines - Phillip Wall

Insulated and Isolated

Earth Bar

Power Systems Separation

Page 35: Earthing systems in mines - Phillip Wall

Power Systems Separation

NER connected to Network Earth

Page 36: Earthing systems in mines - Phillip Wall

How to connect these?

Power Systems Separation

Page 37: Earthing systems in mines - Phillip Wall

Screens bared back and insulated Single point

bonded at Mine Earth

Power Systems Separation

Page 38: Earthing systems in mines - Phillip Wall

Controlled Area

Single point bonded at Mine Earth

Power Systems Separation

Single point bonded at

Network Earth

Page 39: Earthing systems in mines - Phillip Wall

Feeder Maintenance

Breaker 1 open Earth Switch 1 closed

Breaker 2 open Earth Switch 2 closed

Page 40: Earthing systems in mines - Phillip Wall

Lightning transfer effects and U/G mines

According to AS/NZS 3007:

No likelihood of transfer:

AS/NZS 1768.

If likely transfer effects:

No direct connection

Lightning earth Mine Undergroud Earth (MUE)

Page 41: Earthing systems in mines - Phillip Wall

Where do we provide the separation?

Mine Earths – Surface and Underground?

Screens bared back

Page 42: Earthing systems in mines - Phillip Wall

Mine Underground Earth

Page 43: Earthing systems in mines - Phillip Wall

• Transfer mechanisms

- Transition from Surface to UG

- Through different districts in UG areas

• Areas of interest:

- sealed areas

- working faces

- return airways

U/G Bonding Practices

Page 44: Earthing systems in mines - Phillip Wall

Borehole Mitigations

• Depends on the construction type of borehole and what services use the borehole

U/G Bonding Practices

- High Voltage feeders

- Gas Drainage / Dewatering / Submersible pumps

- Ballast / Concrete / Stone dust drop holes

- Steel lined air shafts

- Piezometers and Extensometers

- Tube bundle (caternaries) and communications

Page 45: Earthing systems in mines - Phillip Wall

Before sealing up longwalls

• Breaks in mesh in gate roads

• Removal or breaking of pipe lengths and cables

• Removing or treatment of mesh at seals

• Careful attention to pipe penetrations through seals

U/G Bonding Practices

Page 46: Earthing systems in mines - Phillip Wall

Mines are being asked to implement controls to minimise lightning effects. Effective earthing systems such as separated systems are shown to reduce energy transfer.

Summary