22
ACTURA 48 701z POWER SYSTEMS USER AND INSTALLATION MANUAL Document Number: UIM48701z-R2 REVISION DATE: 19/10/2007

Uim48701z r2

Embed Size (px)

Citation preview

Page 1: Uim48701z r2

ACTURA 48 701z POWER SYSTEMS

USER AND INSTALLATION MANUAL

Document Number: UIM48701z-R2

REVISION DATE: 19/10/2007

Page 2: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 2

List of Contents List of Contents ..............................................................................................................2 1 Power System .......................................................................................................3

1.1 Description .....................................................................................................................3 2 Sub-Assemblies .....................................................................................................4

2.1 Mechanical Layout ..........................................................................................................4 3 System Supervision Unit.........................................................................................5

3.1 Description .....................................................................................................................5 4 Installation............................................................................................................6

4.1 Unpacking ......................................................................................................................6 4.2 Cabinet Mounting............................................................................................................6 4.3 Installation of Rectifier Modules .......................................................................................7 4.4 Earthing .........................................................................................................................7 4.5 AC Input Connections......................................................................................................8 4.6 DC Load Output Connections ...........................................................................................9 4.7 Outgoing Alarm Connections..........................................................................................11 4.8 Digital Inputs Connections .............................................................................................12 4.9 Battery Installation........................................................................................................12

5 Communication Setup for WEB Interface ............................................................... 14 6 Spare Parts List ................................................................................................... 18

6.1 Recommended Spares...................................................................................................18 7 Annexure ............................................................................................................ 19

7.1 Technical Specifications – Power System ACTURA 48 701z ............................................19 7.2 Technical Specifications – Rectifier Module R48-3200.......................................................20 7.3 Failure Report...............................................................................................................21

Page 3: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 3

1 Power System 1.1 Description

The ACTURA 48 701z is a flexible power system suitable for communication networks and IT applications requiring small to medium range power. This is a -48V DC (positive common) modular rectifier system. The system is supplied in a cabinet which includes provision for load and battery distribution. Space for various types of batteries forms an integral part of the system. The flexible system configurations, which are designed to meet various demands, include the choice of different types of rectifiers, controllers, range of supervision units and a two stage low voltage load disconnect. For details, refer to the respective manuals. The ACTURA 48 701z is suitable for supplying loads of up to 12.8KW with N+1 rectifier module redundancy. This system includes a 23-inch 5-rectifier sub-assembly, 23-inch distribution sub-assembly and a 4-battery System Cabinet.

Fig 1.1 : Example of ACTURA 48 701z

SYSTEM CABINET

SYSTEM CONTROLLER

DISTRIBUTION SUB-ASSEMBLY

BATTERY STRING 1

BATTERY STRING 2

BATTERY STRING 4 BATTERY STRING 3

RECTIFIER SUB ASSEMBLY

RECTIFIER MODULE

MULTI-FUNCTION UNIT

BATTERY CIRCUIT BREAKER

Page 4: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 4

2 Sub-Assemblies 2.1 Mechanical Layout

Fig 2.1 : Example of sub-assemblies

DC LOAD DISTRIBUTION CIRCUIT BREAKERS

AC INPUT ISOLATOR

DC DISTRIBUTION AC DISTRIBUTION

RECTIFIER MODULE

RECTIFIER MODULE STATUS LEDs

SYSTEM CONTROLLER

USER INTERFACE BOARD CONTROLLER STATUS LEDs

RECTIFIER AC INPUT CIRCUIT BREAKERS

OPTIONAL SURGE ARRESTOR

MULTI-FUNCTION UNIT

Page 5: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 5

3 System Supervision Unit 3.1 Description

Fig 3.1 : Front view of the installed Advanced Controller Unit (ACU)

The System Controller is controller is available in two versions: Standard Controller Unit (SCU) and Advanced Controller Unit (ACU). This controller is responsible for supervising and controlling the power system. An Ethernet port enables connection to a laptop / PC to facilitate advanced system monitoring and control (ACU only).

The Controller is equipped with a LCD display for local indication of system parameters such as: output system voltage, load current, battery temperature, battery block voltages, battery currents and alarms.

All system parameters can be adjusted utilising the LCD display and keypad i.e. the 6 buttons located on the Controller’s front panel.

The Controller facilitates advanced functionality such as: • comprehensive system supervision • comprehensive alarms for easy diagnostics • comprehensive battery management, battery charge current limit and temperature

compensated float charge • dual low voltage battery disconnect • battery discharge data logging and alarm history storage • Programmable Logic Control (PLC)

WEB browser is used as a PC user interface, intended for configuration, test, installation and maintenance of Power Systems.

For more information on System Controller/s, refer to the respective SCU or ACU Manuals.

LCD DISPLAY

STATUS LEDs

USER CONTROLS (KEYPAD)

ETHERNET PORT

CONTROLLER EJECTION LEVER

Page 6: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 6

4 Installation

All ACTURA 48 701z Power Systems must be installed as per instructions of this chapter.

4.1 Unpacking

1. The Power System is factory tested and inspected. Upon receiving the Power System, make sure that all the boxes listed in the shipping specification are delivered, and that they have the correct type numbers.

2. The final unpacking of each unit should not be done until just before the installation. There might be loose parts packed with the units (e.g. screws) and to prevent losing them, the unpacking should be done when installing the equipment.

3. The Power System is delivered completely wired and configured to accept up to 5 rectifier modules (configuration dependant).

4. The Rectifier modules are separately packed, and the actual quantity to be installed depends on the load requirement and the battery recharge requirement.

5. When unpacking the Rectifier modules from the carton, first visually inspect them for damage that might have occurred during transportation. If a Rectifier module appears to have been physically damaged, do not install it into the Power System or attempt to switch it on. Damaged equipment should be returned to Emerson (refer to Failure Report chapter).

4.2 Cabinet Mounting

The System Cabinet can be fixed to the floor and to the wall by means of L-shaped brackets (refer to Figure 4.1). During transportation, both brackets are mounted at the top-rear of the cabinet.

Fig 4.1: Floor and wall mounting

WALL MOUNTING BRACKET

FLOOR MOUNTING BRACKET

Page 7: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 7

4.3 Installation of Rectifier Modules

1. Ensure that AC input isolator, all AC circuit breakers and the AC supply from the Distribution Board are switched off.

2. Align the Rectifier module with the guide rails inside the Rectifier sub-assembly, ensuring the correct orientation of the module.

3. Release the rectifier ejection lever. 4. Gently slide the module into the guide rails until its rear connectors plug into the

respective receptacles at the back. 5. Close the rectifier ejection lever to lock the rectifier in place. 6. Should the rectifier NOT fit, check that it is correct for the voltage used. A 24V

Rectifier module cannot be connected to the 48V system or vice versa. 7. For more information on rectifiers, refer to the respective rectifier manuals.

4.4 Earthing

An earth stud is provided for DC earthing connections (cabinet and positive common DC output) located inside, on the top left-hand side of the system cabinet. The Power System’s DC output is floating, i.e. not connected to earth potential. This is the -48V system and if required, the positive DC output (battery positive busbar) can be connected to earth.

Fig 4.2: Earth stud

SYSTEM EARTH STUD

BATTERY POSITIVE BUSBAR

Page 8: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 8

4.5 AC Input Connections 1. Ensure that the AC supply from the Distribution Board is switched off, before any

AC connections are made. 2. Remove the cabinet top cover by removing the screws holding it in place. This will

provide top access to the Distribution sub-assembly. 3. Open the Distribution fascia by turning the thumb screw marked as “Cover

Release Screw” and lightly pulling it. The Distribution fascia is hinged at the bottom.

4. Remove the AC protection cover, by loosening the screws securing it. Access can now be gained to the AC input connection terminals (L1, L2, L3, N and PE) as shown in Figure 4.3.

Fig 4.3: Example of AC distribution The Power System can be connected to either a single-phase (1+N+PE) or three-phase (3+N+PE) AC input supply. Single Phase (1+N+PE) Connection The AC input cable should enter the cabinet at the top right-hand side. Recommended minimum circuit breaker rating in the distribution board for single-phase connection is > 100A for ACTURA 48 701z. For the single-phase (1+N+PE) connection, a 3-core cable rated in accordance with the circuit breaker in the Main Distribution Board and Local Standards/Directives must be used to provide AC supply to the Power System. For Single phase operation, all three phase terminals (L1, L2 & L3), must be linked together (link not provided). After the AC input supply cable has been terminated, it must be strapped to the cable strap point provided on the AC Distribution where the cable exits the enclosure (refer to Figure 4.3).

CABLE STRAP POINT

L1, L2 and L3 CONNECTIONS

PROTECTIVE EARTH CONNECTION

OPTIONAL SURGE ARRESTOR

NEUTRAL CONNECTION

Page 9: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 9

Three Phase (3+N+PE) Connection The AC input cable should enter the cabinet at the top right-hand side. Recommended minimum circuit breaker rating in the distribution board for 3-phase connection is > 40A per phase for ACTURA 48 701z. For the three-phase (3+N+PE) connection, a 5-core cable rated in accordance with the circuit breaker in the Main Distribution Board and Local Standards/Directives must be used to provide AC supply to the Power System. After the AC input supply cable has been terminated, it must be strapped to the cable strap point provided on the AC Distribution where the cable exits the enclosure (refer to Figure 4.3).

4.6 DC Load Output Connections

Fig 4.4: Example of DC load distribution The standard DC distribution caters for termination of Priority loads and Normal loads. The Normal Load “NL” circuit breakers (also known as Low Priority “LP”) and Priority Load “PL” circuit breakers (also known as High Priority “HP”) are grouped as per Figure 4.4. The number and grouping of circuit breakers is configuration dependant. The purpose of the circuit breakers may be indicated on the “Load Distribution Label” (if applicable). The positive load connections are to be terminated on the common positive busbar at the back of the load circuit breakers. The positive load cables must be connected to the tunnel terminals or M8 bolts (refer to Figure 4.5) and tightened. Maximum recommended cable size is 50mm², minimum recommended cable size is 2.5mm², torque of 4 to 5Nm. The negative load connections are made to the relevant distribution circuit breakers. Maximum recommended cable size is 50mm² (circuit breaker dependant), minimum recommended cable size is 2.5mm². The recommended torque for circuit breaker terminals is 2 to 3 Nm.

LOAD DISTRIBUTION LABEL

NORMAL LOAD CIRCUIT BREAKERS

PRIORITY LOAD CIRCUIT BREAKERS

Page 10: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 10

Mount cable in tunnel terminal UNDERNEATH Common busbar before tightning.

Fig 4.5: Termination of negative load cables

The System Controller monitors the status of the distribution circuit breakers. For monitoring purposes, each circuit breaker is assigned with a sense wire (circuit breaker sense wire), which must be connected to it. The circuit breaker sense wires must be connected to the load circuit breakers together with the negative load cables. The circuit breaker sense wires are colour coded and grouped into 5 banks. Black: Group 1 – circuit breaker position 1, 2, 3, 4 and 5 Brown: Group 2 – circuit breaker position 6, 7, 8, 9 and 10 Red: Group 3 – circuit breaker position 11, 12, 13, 14 and 15 Orange: Group 4 – circuit breaker position 16, 17, 18, 19 and 20 Yellow: Group 5 – circuit breaker position 21, 22, 23, 24 and 25. Note that each group of circuit breaker sense wires are equipped with a spare, 6th wire, which is to be used as a replacement in an unlikely event of sense wire failure. All un-used sense wires must be placed into the trunking, located behind the circuit breakers. The DC output cables should be strapped to the cable strain relief strap points, provided at the back of the Distribution sub-assembly. These cables should be then routed through the top of the battery cabinet (holes are provided). Cable size shall be selected in accordance with circuit breaker rating and allowable voltage drop. The maximum recommended voltage drop is 400mV. To meet the voltage drop, the following formula could be used as a guideline for selecting the minimum cross-sectional area required for the load cables: Amin [mm2] = 0.05 x L [m] x I [Adc] Amin Minimum cross-sectional area of load cable in mm2 L total length of positive and negative cable in meters I circuit breaker rating in amperes DC.

Page 11: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 11

4.7 Outgoing Alarm Connections Eight potential free relays for the purpose of outgoing alarms are provided on the User Interface Board, located above the System Controller (refer to Figures 2.1 and 3.1). Every relay output has N/C (normally closed) and N/O (normally-open) contacts. The relay mapping to specific alarm are Emerson configurable functions (also refer to the respective SCU or ACU Manuals). For the SCU and the ACU, the outgoing alarm relays are grouped in the following manner (default configuration): • Relay RL1 – AC Failure, AC Voltage High, AC Voltage Low 1, AC Voltage Low 2 • Relay RL2 – DC Voltage low 1 • Relay RL3 – DC Voltage Low 2 • Relay RL4 – DC Voltage High 1, DC Voltage High 2 • Relay RL5 – Multiple Rectifier Failure, Rectifier Failure, Rectifier Fan Failure,

Rectifier HVSD, Rectifier AC Failure, Rectifier Protect, Rectifier Not Responding • Relay RL6 – Load Fuse • Relay RL7 – Battery Fuse • Relay RL8 – Spare

ALARM RELAY OUTPUTS

DIGITAL POWER FOR INPUTS DIGITAL INPUTS

Fig 4.6: Outgoing Alarm Relays and Digital Inputs

Page 12: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 12

4.8 Digital Inputs Connections The System Controller offers a comprehensive Programmable Logic Control (PLC). For details on this function, refer to the respective SCU or ACU Manuals. Eight isolated Digital Inputs and their DC supply points are provided for the purpose of PLC. These inputs are located on the User Interface Board, above the System Controller (refer to Figures 2.1 and 3.1). By default, these inputs are not configured, but can be configured to meet the customers’ needs. For input connection points, refer to Figure 4.6.

4.9 Battery Installation The battery distribution cabling is pre-wired as standard. The system cabinet comprises four battery shelves. The battery space available for each string in standard configuration is: 540mm (W) x 570mm (D) x 320mm (H). Each battery shelf is designed to accommodate four (VRLA) 12V-battery blocks with front terminals. Four 12V-battery blocks are always connected in series. Suitable links (not provided) should be used for connecting battery blocks in a string. The front terminal battery blocks must be placed next to each other (refer to Figure 4.8). Repeat the following procedure for each battery string installed. Battery string 1 is always at the bottom of the cabinet (refer to Figure 1.1). 1. Switch all four battery circuit breakers off (located next to each battery shelf). 2. Remove the Battery compartment cover by removing the four M6 screws (if

applicable). 3. Place all four 12V battery blocks on a shelf. 4. The negative battery cable, located on the left-hand side of the battery cabinet,

must be connected to the negative battery pole. 5. The positive battery cable, located on the right hand side, must be connected to

the positive battery pole. 6. Please consult the Battery manufacturer for the correct torque on the battery

terminals. 7. Replace the Battery compartment cover (if applicable). Battery temperature sensors are factory fitted and do not require installation.

Page 13: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 13

The String Voltage Equalisers are optional items (configuration dependant).

Fig 4.7: String Voltage Equaliser Battery Sense Terminal Ring Some system configurations offer more advanced battery management (addition of SM BAT unit for block voltage and individual string current monitoring). In such instances, for the Power System to be able to perform such advanced battery management, the battery sense wiring and the terminal rings must be mounted on the battery poles. A set of battery sense wires and terminal rings must be attached to each installed battery. Each wire in a set is marked, indicating the required connection to the specified 12V battery block. The 12V battery blocks in a string are numbered from 1 to 4. The block connected to the positive (red) battery wire is Block 1, while the one connected to the negative (blue) battery wire is Block 4.

Fig 4.8: Example of Battery Block installation and numbering

Block 4-

Block 4+

Block 3+

Block 2+

Block 1+

Battery Negative Pole

Battery Positive Pole

Block Block Block Block Block Block Block Block 4- 4+ 3- 3+ 2- 2+ 1- 1+

4 3 2 1

Page 14: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 14

5 Communication Setup for WEB Interface

Only the Advanced Controller Unit (ACU) is supporting the WEB interface. There are two means of communication to the ACU: direct (cable and Ethernet Switch) and remote (via LAN). Please note that WEB Interface has a limit of 5 users which could simultaneously log onto the ACU. Minimum Hardware and Software Requirements - 1 x Petium III, 1GHz processor based PC or Laptop, - 1 x Standard Ethernet Network Cable, - Operating system: Windows 2000 or Windows XP (ensure that you have

administrator rights on your user profile), - Internet Explorer 6, - Log-on access to ACU via WEB Interface (user name and password for browsing

only or for changing ACU parameters). Connections Connect the standard Ethernet Network cable between the ACU “Ethernet Port” and the PC “Ethernet Port”. ACU Setup For successful communication with ACU, determine the following ACU parameters: - IP Address (default: 192.168.0.1) - Subnet Mask (default: 255.255.254.0) - Default Gateway (default: none) Using the front panel keypad, follow the link below: Press “Enter” button, Main Menu / Parameter Set / <enter user name: admin and password: 1> /System Parameter / <set IP Address, Subnet Mask and Default Gateway>. The last screen will show the IP Address of ACU, Subnet Mask and Default Gateway (write it down).

Page 15: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 15

PC setup Ensure that you are not connected to any network i.e. you will be running your PC/laptop offline. Boot up you PC/laptop and enter your Windows log-on user name and password. Please note that you must have administrator rights. Within the Windows desktop, right click on the “My Network Places” icon and click on “Properties”.

In the next window, right click on “Local Area Connection” and click on Properties.

Page 16: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 16

In the next window, select “Internet Protocol (TCP/IP)” and click on button “Properties”.

For communication via LAN, note that the below parameters are specific to your network (LAN) and therefore must be changed appropriately. If the communication with ACU is directly via Ethernet cable, then the parameters may be left to their default values. In the next window, select “Use the following IP address” radio button and enter the following. - IP address: The first 3 segments of IP address must be identical to the ACU IP

address, while the fourth segment must differ. Example: 192.168.0.2 - Subnet Mask: the same as the ones entered into the ACU. Example:

255.255.254.0 - Default Gateway: the same as the ones entered into the ACU (if using the default

ACU setting, then do not set this parameter). Click on “OK” button and close all other open windows.

Page 17: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 17

Now, you need to setup your Internet Explorer for correct operation. Launch the Internet Explorer. Click on “Tools” and then “Internet Options…”.

In the following window, select “Connections” tab and then click on “LAN Settings…” button.

In the following window, uncheck the “Use the proxy server for your LAN”. Click “OK” buttons in all windows.

Communicating with ACU In the “Address” field of the Internet Explorer, enter the ACU’s IP address (example: http:// 192.168.0.1) and click on “Go” button. Once the communication is established, in the first screen of ACU WEB Interface, you will be prompted your “User Name” (default: admin) and “Password” (default: 1). For more details on WEB interface, please refer to the ACU User Manual.

Page 18: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 18

6 Spare Parts List

6.1 Recommended Spares

DESCRIPTION OF ITEM

ORDERING CODE

5A DC Circuit Breaker CBI 9445 10A DC Circuit Breaker CBI 9060 15A DC Circuit Breaker CBI 9079 20A DC Circuit Breaker CBI 9061 32A DC Circuit Breaker CBI 9062 63A DC Circuit Breaker CBI 9821 100A DC Circuit Breaker CBI 9633 150A DC Circuit Breaker CBI 9703 200A Battery Circuit Breaker CBI 10075 25A AC Circuit Breaker CBI (rectifier input) 10070 3-pole AC Disconnect Switch 63A CBI 9063 Class II Surge Arrestor 20kA, 3ph+N, pitch 4x13mm (optional) 10069 Combo Surge Arrestor, 3ph+N, with alarm, pitch 4x18mm (optional) 10324 Rectifier Module 48V 3.2kW (R48-3200) 10049 Rectifier Module Blanking Cover 3x2U (DMBM4.120.071/N) 10050 ACU - Advanced Controller Unit M800D (configuration dependant) 10067 SCU – Standard Controller Unit M501D (configuration dependant) 10068 SM BAT (configuration dependant) 10054 SM IO (configuration dependant) 10076 SM AC (configuration dependant) 10077 Connector Board 1x2U Mini/Medium (S6415X2) 10080 System Interface Card 10102 Battery Sense Cable Set for SM BAT, 5m (SMB11SL1) 10079 Controller Temperature Sensor 3m (W75C5FSL2) 10055 Controller Temperature Sensor 10m (W74C5FSL1) 10071 SM Unit Temperature Sensor 10m (SMIO11SL1) 10056 String Voltage Equaliser 48V (configuration dependant) 9675 Battery String Sense Wiring Harness (for Equaliser only) 9738 Battery Circuit Breaker Sense Wire Harness 10035 Normal Load Contactor (ACTURA 48 701z) 9901 Battery Contactor (ACTURA 48 701z) 9901 Load Circuit Breaker Sense Wire Harness (for 25 CBs) 10063 Load Circuit Breaker Sense Wire Connector (10-way) 9414

Page 19: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 19

7 Annexure

7.1 Technical Specifications – Power System ACTURA 48 701z

Rectifier Type R48-3200 Input Data Nominal Input Voltage 200 to 240Vac, 1φ (1+N+PE) Operational Input Voltage 85 to 290Vac Nominal Frequency Range 45 to 65Hz Maximum Input Current, 1φ <100Aac Power Derating below 176Vac Output data Nominal Output Voltage -48Vdc Adjustable Output Voltage Range -42Vdc to -58Vdc Maximum Output Current 335A Maximum Output Power 16kW Power Derating above 45°C System Common Positive Distribution / Protection AC Input Terminals up to 35mm2 AC Input Switch 63A, 3-phase AC Input Isolator Surge Protection Optional Rectifier Input Circuit Breakers 5 x 25A 48V Load Distribution up to 25 circuit breakers up to 50mm2 (circuit breaker rating dependant) Battery Distribution 4 x 200A circuit breakers Battery Capacity up to 4 x 165Ah (12V front terminal battery blocks) Alarm Interface 8 x Alarm Relay Outputs (potential free contacts) Minimum rating - 10mA @ 5Vdc Maximum rating 2A @ 30Vdc / 0.5A @ 125Vac 8 x Digital Inputs User Interface LCD Display, user control keypad – full functionality Ethernet Port (configuration dependant, ACU only) Environmental Data Operational Temperature Range -5° to +70°C Temperature Range (full power) -5° to +45°C Relative Humidity < 90% (non-condensing)

Altitude 0 to 2000m ASL Cooling Front to back thermally controlled forced air-cooling

Marking CE EMC EN 300 386-2 class B Electrical Safety IEC 60950 Mechanical Data Dimensions (H x W x D) 1800 x 600 x 600mm Max configuration 5 x rectifier modules, 4 x 165Ah battery strings Net Weight (approximately) 150kg, excluding rectifiers and batteries

Page 20: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 20

7.2 Technical Specifications – Rectifier Module R48-3200

R48-3200 Input Data Nominal Input Voltage Range 200 to 240Vac Operational Input Voltage 85 to 290Vac Input Frequency Range 45 to 65Hz Maximum Input Current <20Aac Power Factor 0.99 Total Harmonic Distortion < 5% from 50 to 100% of rated load Output Data Nominal Output Voltage 48Vdc Factory Set Output Voltage 53.5V Adjustable Output Voltage Range 42Vdc to 58Vdc Maximum Output Power 3200W Output Power, derated for input voltage 85 to 176Vac Output Power, derated for temperature above 50°C Maximum Output Current 67A Efficiency 92% Psophometrically Weighted Noise ≤ 1mV at 5 to 100% of rated load Control & Monitoring Rectifier alarm & signalling Alarm & status reported via CAN bus to System

Controller Visual Indication Green LED – Normal Operation Flashing Green LED – Rectifier indicator Yellow LED – Alarm Flashing Yellow LED – Rectifier Comms Failure Red LED – Failure Flashing Red LED – Fan failure Protection AC Input over- and under-voltage protection AC Input over-current protection DC Output over-voltage protection DC Output over-current and short circuit protection Overheat protection Environmental Data Operational Temperature Range -40° to +75°C Full Power Temperature Range -40° to +45°C Storage Temperature Range -40° to +75°C Relative Humidity 0% to 95% (non-condensing)

Altitude 0 to 2000m ASL Cooling Front to back thermally controlled forced air-cooling

Marking CE EMC EN 300 386:2001 class B Electrical Safety IEC 60950

Mechanical Data Dimensions (W x H x D) 132 x 86 x 287 mm Enclosure IP20 Net Weight 3.5kg

Page 21: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 21

7.3 Failure Report

THIS FORM MUST BE SENT TO: COMPLETED BY: Date:

CUSTOMER’S CONTACT DETAILS:

Customer Service Centre

Emerson Network Power South Africa Pty Ltd P.O Box 1931 Sunninghill 2157 Johannesburg South Africa Fax: +27 11 807 8103

e-mail: [email protected]

FAULTY PRODUCT DETAILS: ENVIRONMENTAL CONDITIONS AT TIME OF FAILURE:

TYPE NO: Temperature:

SERIAL NO.

Humidity:

EMPLOYED IN WHAT SYSTEM:

Air handling i.e. open or closed environment:

FAULT DISCOVERED UPON:

1. Delivery 2. Unpacking

3. Installation

4. Initial test

5. After operation of ……….Years.

6. Other________________

____________________________________________________________________________________

SOURCE OF FAILURE IN YOUR OPINION:

1. Design

2. Manufacturing

3. Documentation

4. Transportation

5. Installation

6. Handling

7. Other__________________________________

WHAT WAS THE CONSEQUENCE OF THE FAILURE:

1. Inconvenienced

2. Resulted in a Site Visit

3. Emergency Site Visit

4. Temporary interruption of service

5. Extended interruption

of service 6. Other______________

________________________________________________________________________

Page 22: Uim48701z r2

ACTURA 48 701z Power Systems

ACTURA UIM48701z-R2 22

Check list for the System: Do all SM units communicate with the System Controller?

Do all Rectifiers communicate with the System Controller?

Are both contactors powered?

Can you establish communications with the System Controller?

What is the total load current?

What are the amounts of current for Normal Load & Priority Load?

How many battery strings are installed?

What is the capacity of each battery string?

Are the batteries configured correctly?

Are the date and time set correctly on the System Controller?

List the Active Alarms:

Can you access all the history logs?

If so, please attach to this form.

Check list for the rectifiers: Is there any visible mechanical damage?

Is the AC power within the operating range of the rectifiers?

How many rectifiers are installed in the system?

What is the status of the rectifiers’ input circuit breakers?

Are the rectifiers powered?

Are the rectifiers delivering power?

What is the status of the rectifier LEDs? Additional information:

NL= PL=

A

Specify:

ON / OFF

Specify:

YES / NO

Specify:

Specify: Ah

YES / NO

YES / NO

YES / NO

YES / NO

YES / NO

YES / NO

YES / NO

YES / NO

YES / NO