1. PURPOSE AND GENERAL CLASSIFICATION A substation is a
high-voltage electric system facility. It is used to switch
generators, equipment, and circuits or lines in and out of a
system. It also is used to change AC voltages from one level to
another, and/or change alternating current to direct current or
direct current to alternating current. Some substations are small
with little more than a transformer and associated switches. Others
are very large with several transformers and dozens of switches and
other equipment.
2. SUBSTASTION can classified according to: Service Alternating
current Alternating to direct current Mounting Indoor Outdoor
3. Function Tap Distributing Industrial Sectionalizing
Transmission-line supply Power- factor correction Frequency changer
Railway, portable Direct current for light and power
4. Type of apparatus Transformer Rotary converter Motor
generator Frequency changer Synchronous condenser Power rectifier
Control Manual Semiautomatic Automatic Supervisory
5. High voltage (HV) ac: 69 kV, 115 kV, 138 kV, 161 kV, 230 kV
Extra-high voltage (EHV) ac: 345 kV, 500 kV, 765 kV Ultra-high
voltage (UHV) ac: 1100 kV, 1500 kV Direct-current high voltage (dc
HV): 250 kV, 400 kV, 500 kV
6. to be economical, transmission of large amounts of power
over long distances must be done at voltages above 110,000 volts.
Such substation between the 110- and 44-kv. Lines is known as a tap
sub-station. -Equipment may comprise high and low tension switching
equipment, transformers, and lightning arresters. A. TAP
7. B. Distribution Any substation that is used to transform
electrical energy to a potential that is low enough for general
distribution and utilization is a distributing substation for local
dist, 2 400 volts has been recognized as a standard voltage;
Distribution at 6 600, 13 200 and 22 000 volts is used for longer
distances and larger blocks of power.
8. DISTRIBUTION SUBSTATION
9. C. Industrial Large blocks of power are required by
industrial plants, it often becomes necessary and advisable to
install an individual substation to supply such a load direct from
the main high-voltage line or secondary line of lower voltage.
Equipment may comprise only switching equip, in most cases a
voltage transformation is probably needed
10. D. Sectionalizing In very long high-voltage large capacity
lines, particularly when several circuits are run in parallel, it
is often necessary to split the lines into sections, in order that
proper protection to the line and service be obtained. Equipment
comprise only switching equipment. In long lines it may also serve
to supply power factor correcting equipment
11. E. Transmission-line supply It is becoming more and more
common to install the high-tension equipment of a power plant
outdoors, the installation becoming nothing more than a step- up
substation receiving its power at generator voltage, then stepping
up its voltage and finally sending it out over high-voltage
transmission lines.
12. F. Power factor Correction Long transmission lines will
reveal the fact that the voltage at the end of the line tends to
increase as the load supplied is decreased, while on the other hand
it tends to decrease as the load is increased. It is necessary to
use synchronous condensers, so to control it power factor and
voltage regulation may be had at the end of a long transmission
line.
13. Synchronous Condensers synchronous condenser is a
synchronous machine running without mechanical load and supplying
or absorbing reactive power to or from a power system. Also called
a synchronous capacitor, synchronous compensator or rotating
machinery.
14. G. Frequency Changer To interconnect two systems of
different frequencies it is absolutely necessary that the frequency
changers be used. This type will necessitate transformers to step-
down or step up the voltage supplied to or delivered from the
frequency changer.
15. H. Railway Substations supplying railways may be generally
classified under two heads, namely, as Alternating current and
Direct current Alternating current power can be more economically
generated and controlled from the three phase units than single
phase generators. Direct current is has been generally recognized
that direct current is better suited to city railway service. the
substation are generally supplied with 3-phase power and converted
to direct current by means of rotary converters, motor generator
sets, or power arc rectifiers.
16. I. Direct Current for Light and Power There are still a few
sections in some of our large cities which are supplied with direct
current three wire systems. Such a supply is invariably obtained
from synchronous converters. E.g.; certain types of motor loads in
industrial plants, for electrolytic work, low voltage DC is
absolutely essential.
17. Outdoor Substation The necessary clearances b/w conductors
and the space required for switches, circuit breakers,
transformers, and other equipment become so great for voltages
above 22 000 volts that it is generally more economical to install
all such equipment outdoors.
18. Indoor Substation Indoor Electrical Power Substation: In
Indoor Substations is installed within the substation building.
Such substations are usually for the rating of 22 kV below . Indoor
Substations are preferred in heavily polluted areas and Power
Substations situated near the seas (saline atmosphere causes
Insulator Failures results in Flashovers)
19. Indoor substation
20. Transformer Power transformers raise or lower the voltage
as needed to serve the transmission or distribution circuits.
21. Potential transformers Potential transformers are required
to provide accurate voltages for meters used for billing industrial
customers or utility companies.
22. Current transformers Current transformers can be used to
supply information for measuring power flows and the electrical
inputs for the operation of protective relays associated with the
transmission and distribution circuits or for power
transformers.
23. These current transformers have the primary winding
connected in series with the conductor carrying the current to be
measured or controlled. The secondary winding is thus insulated
from the high voltage and can then be connected to low-voltage
metering circuits.
24. Grounding Transformer A grounding transformer is intended
primarily to provide a neutral point for grounding purposes. It may
be provided with a delta winding in which resistors or reactors are
connected.
25. Rectifier A rectifier is a device used to convert
alternating current to direct current.
26. Rotary Converter A rotary converter is a type of electrical
machine which acts as a mechanical rectifier or inverter. It was
used to convert alternating current (AC) to direct current (DC), or
DC to AC power, before the advent of chemical or solid state power
rectification. They were commonly used to provide DC power for
commercial, industrial and railway electrification from an AC power
source.
27. Frequency Changer A frequency changer is a motor-generator
set that changes power of an alternating current system from one
frequency to one or more different frequencies, with or without a
change in the number of phases, or in voltage. Sometimes a
converter is used to accomplish this.
28. Lightning Arresters Lightning arresters are protective
devices for limiting surge voltages due to lightning strikes or
equipment faults or other events, to prevent damage to equipment
and disruption of service. Also called surge arresters.
29. A. Manual This type of control is applicable only to small-
capacity substations. All the disconnecting switches, circuit
breakers, and other equipment are manually controlled.
30. B. Semi-automatic The majority of stations fall under this
class. Control is obtained from a switchboard through mechanically
or electrically remote methods, but all control is dependent upon
the operator in charge at the substation.
31. C. Automatic Full automatic substations have obtained a
considerable favor for various purposed, particularly among railway
engineers. Such substations are entirely unattended; they are
started up automatically when a train comes into the range of the
particular station and stopped when the train passed out of the
range of the station.
32. D. Supervisory In a many good cases it is desirable that
the operation of a substation be under the direct control of an
operator located at a considerable distance away. This can be
accomplished by what us known supervisory control. By means of only
three or four control wires running b/w the operator and the
substation , it is possible to operate the substation very
satisfactorily.