TR series Expandable Multifunction touch panel monitor unit User’s manual 2011. 07. 01 TOSHIBA Industrial Product Sales Corp.

Pmiu manual 12.06

Embed Size (px)

Citation preview

  • TR series Expandable

    Multifunction touch panel monitor unit

    Users manual

    2011. 07. 01

    TOSHIBA Industrial Product Sales Corp.

  • Safety precautions

    This section contains important information to operate this product safely, and avoid bodily injury and property

    damage. Please read before use this product well, and understand content.

    Hazard classifications

    DANGERDANGERDANGERDANGER ! ! ! !

    If the content is not observed, as a result of a breakdown

    and malfunction of TR series, there is a possibility of

    serious injury or death, and large scale damage for

    property.

    WARNINGWARNINGWARNINGWARNING ! ! ! !

    If the content is not observed, as a result of a breakdown

    and malfunction of TR series, there is a possibility of

    injury and damage for property.

    Serious injury means loss of sight, injury, burns (high temperature, low temperature), electrical shock,

    fracture, or intoxication which leaves aftereffects or requires hospitalization or need to go to the hospital

    for a long time.

    Injury means hurt, burn, or electrical shock which does not require hospitalization or going to the hospital

    for a long time. Property damage means extended breakdown of assets and materials.

    Meanings of markings

    PROHIBITED

    Indicates "You must not do it".

    The concrete forbiddance is indicated with a pictograph

    or wording.

    COMPULSION

    Indicates You must do it.

    The concrete content is indicated inside or near the

    circle with a pictograph or wording

    CAUTION

    Indicates a caution.

    The concrete content is indicated inside or near the

    triangle.

    The description of prohibited, compulsion, and caution marks are subject to change, depending on the labels

    on the case of unit.

  • PROHIBITED

    Do notDo notDo notDo not DDDDismantleismantleismantleismantle, , , , MMMModifyodifyodifyodify ! ! ! !

    Do not dismantle or modify any part of hardware,

    software, and the firmware.

    There is no part that the user should dismantle.

    PROHIBITED

    Do not Do not Do not Do not use in use in use in use in GGGGasasasas or or or or DDDDust !ust !ust !ust !

    Do not use or storage TR series in corrosive/explosive/

    flammable gas or vapors, water or oil splash/mist, dust,

    dewy place, etc. TR series is not protected for them. A

    clean, a little moist air is the best.

    COMPULSION

    ReadReadReadRead,,,, observe observe observe observe, keep, keep, keep, keep manuals manuals manuals manuals !!!!

    Read, understand, and observe the content of the

    manual and the safety labels before use TR series. Keep

    the manual while being using TR series.

    COMPULSION

    Be sure to do Be sure to do Be sure to do Be sure to do EEEEartharthartharth !!!!

    Earth TR series surely. Earth wire must use fat wire as

    much as possible and wire shortest distance. This not

    only prevents the accident but also there is an effect of

    controlling the breakdown.

    COMPULSION

    ComposeComposeComposeCompose SSSSafety afety afety afety systemsystemsystemsystem ! ! ! !

    Compose safety system (such as emergency stop

    circuit, interlock circuit etc.) outside of TR series by

    enough reliable method. If the TR series breaks down,

    there is a possibility that it becomes impossible to stop

    the system.

    COMPULSION

    Use Use Use Use SSSSuitable uitable uitable uitable ppppower supply !ower supply !ower supply !ower supply !

    Do not connect a power supply different from the

    specification. Power source of TR series are DC24V

    only.

    DC power supply of a different voltage and the AC

    power supply causes the damage that cannot be

    recovered.

    COMPULSION

    Use Use Use Use CCCCorrect orrect orrect orrect bbbbattery !attery !attery !attery !

    For the model equipped with the battery, use correct

    battery. Dispose of a used battery by the proper

    procedure.

    Do not charge this battery. It causes the explosion and

    fire.

    DANGERDANGERDANGERDANGER ! ! ! !

  • PROHIBITED

    Do not Do not Do not Do not add add add add SSSShock, hock, hock, hock, VVVVibration !ibration !ibration !ibration !

    Do not beat, vibrate the unit. Do not install it in the place

    where the vibration and shock are applied. Do not apply

    physical stress to unit. This product is a precise

    electronic equipment.

    COMPULSION

    Be Be Be Be carefulcarefulcarefulcareful to to to to CCCCooling !ooling !ooling !ooling !

    Unit generates heat, so note heat radiation. Do not close

    the heat radiation hole of the unit case. Do not set it up

    with the case tilted. These obstruct cooling the inside of

    the case by air. Put the surrounding temperature within

    the range of specification.

    COMPULSION

    Note Note Note Note LLLLife times of parts !ife times of parts !ife times of parts !ife times of parts !

    Some of parts used for the TR series have life times

    (relays, battery etc). Please confirm the life times that

    has been described this manual, and use them within

    their life times.

    COMPULSION

    Be Be Be Be carefulcarefulcarefulcareful to to to to IIIInstallationnstallationnstallationnstallation ! ! ! !

    The specialist of electrical work must do the installation

    construction. Do not apply any stress to unit. Do not put

    or insert garbage, dust, wire etc. into unit. Install surely

    in the place where the weight of unit can be endured.

    COMPULSION

    Use Use Use Use SSSSafetyafetyafetyafety equipments ! equipments ! equipments ! equipments !

    When you work, use necessary safety equipment (such

    as safety shoes, rubber gloves, hard hats, safety glasses,

    face shields, flash clothing) in accordance with

    established safety practices.

    COMPULSION

    Be Be Be Be carefulcarefulcarefulcareful to to to to SSSStatic electricitytatic electricitytatic electricitytatic electricity ! ! ! !

    Sensitive electric devices (LSI, IC, etc) are destroyed by

    electrostatic discharge easily. Do not touch connector

    electrode of TR series. Use electrostatic hazard shoes,

    ESD wristband.

    WARNINGWARNINGWARNINGWARNING ! ! ! !

  • General precautions

    Purpose that TR series can be used

    All TR series are a general-purpose industrial products. It is a system component and is used in conjunction

    with other items of industrial equipment such as PLCs, Adjustable Speed Drives (such as inverter), etc. TR

    series are designed and produced carefully enough, but it is necessary to note it when using it for the following

    usages.

    TR series is not designed to be used for the systems which can endanger human life (equipment used to

    medical treatments, such as life-support system, surgical equipment, etc). Do not use TR series for those

    usages.

    If you intend to use TR series for a special application which involves human life or has great influence on

    the public function (the system that needs very advanced reliability or safety-critical system such as

    control/safety system of nuclear power plant or nuclear facility, the operation control system of mass

    transportation system, the equipment/ system related to aerospace, the equipment/system used in very

    severe environment), please consult us.

    These system needs special consideration (fail safe design, fool proof design, redundant design, etc.) for the

    design, operation, and the maintenance.

    For the safety design of your system/machine

    Safety is the most important for all systems/machine. Even if it is used on the assumed worst condition, it is

    necessary to prevent the system/machine from endangering the person. To protect the user, the third party,

    and the property, please note following items at the system design.

    Protect user and third party from a hazardous locations and the part (movable part, sharp part, where

    voltage or heat is applied, etc.) as much as possible with cover and safety devices.

    When carelessly resetting systems/machine after emergency stops, movable part might begin to move

    suddenly. When network communications is used, there is a possibility that data and the command become

    improper because of a noise and an incorrect operation, or the communication is not done for some

    reasons. Measures not to become a hazardous situation are necessary even if these occur. It is necessary

    to design interlock that all the movable parts are locked until safety is confirmed, and control shifts to a

    local mode when communication device is not possible to communicate, etc.

    Never use TR units to perform emergency stop mechanism. Compose the safety system of not relying on

    TR series. Even if TR series or a part of the system/device break down, system/machine should be able to

    be stopped safely.

    Even if the system/machine has the improvement and modification, do not let the above-mentioned

    function be lost.

  • Disposal

    Never dispose of electrical components (including TR series) via incineration. It generates a poisonous gas, and

    there is danger to which the fire and the explosion. And, this deteriorations the law in many cases, pollutes the

    global environment.

    When you dispose TR series, handle TR series as industrial waste. Contact environmental agency for details on

    disposal of electrical components and packaging in your area.

    Exemption matters

    We do not assume the responsibility of the following damage at all.

    Damage caused because natural disasters such as fires, earthquakes, and other accidents.

    Damage due to fault and misuse of user or third party, use on abnormal condition.

    Damage because of use or being not able use of TR (such as loss at business profit and chance),

    interruption of business, change and disappearance etc. of memory content.

    Damage caused by having combined with other equipment such as malfunction etc.

    Damage caused by not having observed content of this manual.

    Damage caused by combination with project that customer made, sample program described in this manual,

    or program that modifies it.

    About this manual

    This manual is described about TR SPUX series logic controller and TR PGMS01 programming software. Please

    read well before using. When you use sample program described in this manual, confirm safety enough. We do

    not take responsibility for the result that executed a sample program listed in this manual at all.

    Content of this manual can use only for purpose of obtaining method of technology necessary for using of TR

    series. This manual is protected by the copyright, and the reproduction, reprint, etc. of the content without

    permission are prohibited. The content might be changed without a previous notice for the improvement.

    TR series product and this manual is designed for the person that has the skills and knowledge relating to the

    construction, installation, operation, and maintenance of the electrical equipment and has received safety

    training on the hazards involved (Refer to the latest edition for additional safety requirements).

  • TOC

    Chapter 1. IntroductionChapter 1. IntroductionChapter 1. IntroductionChapter 1. Introduction 1

    Chapter 2. Chapter 2. Chapter 2. Chapter 2. HardwareHardwareHardwareHardware5

    2.12.12.12.1 Series lineupSeries lineupSeries lineupSeries lineup 6

    2.22.22.22.2 TR PMIU series touch panel monitor unit specificationTR PMIU series touch panel monitor unit specificationTR PMIU series touch panel monitor unit specificationTR PMIU series touch panel monitor unit specification 7

    2.2.1

    2.2.12.2.1

    2.2.1 TR PMIU0300L 7

    2.2.2

    2.2.22.2.2

    2.2.2 TR PMIU0300A 8

    2.2.3

    2.2.32.2.3

    2.2.3 TR PMIU0500L 9

    2.2.4

    2.2.42.2.4

    2.2.4 TR PMIU0500A10

    2.2.5

    2.2.52.2.5

    2.2.5 Wiring for PMIU unit11

    2.32.32.32.3 Expansion I/O unit specificationExpansion I/O unit specificationExpansion I/O unit specificationExpansion I/O unit specification 12

    2.3.1

    2.3.12.3.1

    2.3.1 TR PDIO0808P/N12

    2.3.2

    2.3.22.3.2

    2.3.2 TR PDIX160015

    2.3.3

    2.3.32.3.3

    2.3.3 TR PROX001217

    2.42.42.42.4 Unpacking and Installation of unitUnpacking and Installation of unitUnpacking and Installation of unitUnpacking and Installation of unit19

    2.4.1

    2.4.12.4.1

    2.4.1 Unpacking and accessory19

    2.4.2

    2.4.22.4.2

    2.4.2 Attention of installation location 19

    2.4.3

    2.4.32.4.3

    2.4.3 Installation of PMIU unit 20

    2.4.4

    2.4.42.4.4

    2.4.4 Installation of Expansion I/O unit 22

    2.52.52.52.5 PMIU unit operation modePMIU unit operation modePMIU unit operation modePMIU unit operation mode23

    2.5.1

    2.5.12.5.1

    2.5.1 Kind of operation mode 23

    2.

    2.2.

    2.5.2

    5.25.2

    5.2 When any error is detected24

    2.62.62.62.6 Operation and maintenanceOperation and maintenanceOperation and maintenanceOperation and maintenance25

    2.6.1

    2.6.12.6.1

    2.6.1 Maintenance items 25

    2.6.2

    2.6.22.6.2

    2.6.2 Trouble shooting 26

    2.72.72.72.7 RTCRTCRTCRTC 28

    Chapter 3. TR PGMSChapter 3. TR PGMSChapter 3. TR PGMSChapter 3. TR PGMS 29

    3.13.13.13.1 User interface of TR PGMS01User interface of TR PGMS01User interface of TR PGMS01User interface of TR PGMS01 30

    3.1.1

    3.1.13.1.1

    3.1.1 Overview of window30

    3.1.2

    3.1.23.1.2

    3.1.2 Menu bar 32

    3.1.3

    3.1.33.1.3

    3.1.3 Tool bar 38

    3.23.23.23.2 Operation of TR PGMSOperation of TR PGMSOperation of TR PGMSOperation of TR PGMS41

    3.2.1

    3.2.13.2.1

    3.2.1 Creating of new project 41

    3.2.2

    3.2.23.2.2

    3.2.2 Project Configuration42

  • 3.2.3

    3.2.33.2.3

    3.2.3 Print project45

    3.2.4

    3.2.43.2.4

    3.2.4 Download/Upload/Online 46

    3.2.5

    3.2.53.2.5

    3.2.5 Application Memory Status 50

    3.2.6

    3.2.63.2.6

    3.2.6 Convert Application50

    3.2.7

    3.2.73.2.7

    3.2.7 Preference (Color settings)51

    3.2.8

    3.2.83.2.8

    3.2.8 Preference (Project global settings)51

    3.2.9

    3.2.93.2.9

    3.2.9 Device Information 51

    3.33.33.33.3 Ladder logicLadder logicLadder logicLadder logic 52

    3.3.1

    3.3.13.3.1

    3.3.1 Overview 52

    3.3.2

    3.3.23.3.2

    3.3.2 Kinds of Ladder block 53

    3.3.3

    3.3.33.3.3

    3.3.3 Ladder edit area54

    3.3.4

    3.3.43.3.4

    3.3.4 Input ladder circuit55

    3.3.5

    3.3.53.3.5

    3.3.5 Execution order of instruction56

    3.3.6

    3.3.63.3.6

    3.3.6 Index modification57

    3.43.43.43.4 Data MonitorData MonitorData MonitorData Monitor 58

    3.53.53.53.5 System ParameterSystem ParameterSystem ParameterSystem Parameter 59

    3.63.63.63.6 Multi LanguageMulti LanguageMulti LanguageMulti Language 60

    3.7.1

    3.7.13.7.1

    3.7.1 Overview 60

    3.7.2

    3.7.23.7.2

    3.7.2 Setting61

    3.7.3

    3.7.33.7.3

    3.7.3 Import/Export Text data 64

    Chapter 4. CommunicationChapter 4. CommunicationChapter 4. CommunicationChapter 4. Communication 66

    4.14.14.14.1 OverviewOverviewOverviewOverview 67

    4.24.24.24.2 COM port settingsCOM port settingsCOM port settingsCOM port settings 68

    4.2.1

    4.2.14.2.1

    4.2.1 Node information window 68

    4.2.2

    4.2.24.2.2

    4.2.2 Setting procedure(Add/Edit node) 69

    4.34.34.34.3 Communication protocolCommunication protocolCommunication protocolCommunication protocol 70

    4.3.1

    4.3.14.3.1

    4.3.1 None70

    4.3.2

    4.3.24.3.2

    4.3.2 Serial printer70

    4.3.3

    4.3.34.3.3

    4.3.3 Modbus RTU (Unit as Master)70

    4.

    4.4.

    4.3.4

    3.43.4

    3.4 Modbus RTU (Unit as Slave)71

    4.3.5

    4.3.54.3.5

    4.3.5 TOSHIBA Inverter/T series 71

    4.44.44.44.4 Monitoring of communicationMonitoring of communicationMonitoring of communicationMonitoring of communication72

    4.3.1

    4.3.14.3.1

    4.3.1 POWER LED 72

    4.3.2

    4.3.24.3.2

    4.3.2 System tags72

    Chapter 5. TagChapter 5. TagChapter 5. TagChapter 5. Tag 73

    5.15.15.15.1 About TagAbout TagAbout TagAbout Tag74

  • 5.1.1

    5.1.15.1.1

    5.1.1 Relation between Coli/Bit and Register74

    5.1.2

    5.1.25.1.2

    5.1.2 Register length75

    5.25.25.25.2 Tag databaseTag databaseTag databaseTag database 76

    5.2.1

    5.2.15.2.1

    5.2.1 Overview 76

    5.2.2

    5.2.25.2.2

    5.2.2 Add Tag window 77

    5.2.3

    5.2.35.2.3

    5.2.3 Import/Export tag79

    5.35.35.35.3 Various tagsVarious tagsVarious tagsVarious tags 80

    5.3.1

    5.3.15.3.1

    5.3.1 System tags80

    5.3.2

    5.3.25.3.2

    5.3.2 Other tags in PMIU unit 83

    5.3.3

    5.3.35.3.3

    5.3.3 Modbus Tags 84

    5.3.4

    5.3.45.3.4

    5.3.4 Toshiba Inverter Tags85

    5.3.5

    5.3.55.3.5

    5.3.5 The tags of Toshiba T series, Toshiba (Link port) series PLCs87

    Chapter 6. TaskChapter 6. TaskChapter 6. TaskChapter 6. Task 88

    6.16.16.16.1 Task and Task listTask and Task listTask and Task listTask and Task list 89

    6.1.1

    6.1.16.1.1

    6.1.1 Overview 89

    6.1.2

    6.1.26.1.2

    6.1.2 Task list90

    6.1.3

    6.1.36.1.3

    6.1.3 Power-On/Global Task list 92

    6.1.4

    6.1.46.1.4

    6.1.4 Screen Task list 93

    6.1.5

    6.1.56.1.5

    6.1.5 Key Task list94

    6.26.26.26.2 Various tasksVarious tasksVarious tasksVarious tasks 95

    6.2.1

    6.2.16.2.1

    6.2.1 Bit Tag operation95

    6.2.2

    6.2.26.2.2

    6.2.2 Register Tag operation96

    6.2.3

    6.2.36.2.3

    6.2.3 Screen task 100

    6.2.4

    6.2.46.2.4

    6.2.4 Extra task 102

    ChaptChaptChaptChapter 7. Expansion I/O uniter 7. Expansion I/O uniter 7. Expansion I/O uniter 7. Expansion I/O unit109

    7.17.17.17.1 Allocation of Expansion I/O unitsAllocation of Expansion I/O unitsAllocation of Expansion I/O unitsAllocation of Expansion I/O units 110

    7.27.27.27.2 Tag numbering rule of Expansion I/O unitsTag numbering rule of Expansion I/O unitsTag numbering rule of Expansion I/O unitsTag numbering rule of Expansion I/O units 112

    7.37.37.37.3 Usage of Digital I/O unitUsage of Digital I/O unitUsage of Digital I/O unitUsage of Digital I/O unit 113

    Chapter 8. ScreenChapter 8. ScreenChapter 8. ScreenChapter 8. Screen114

    8.18.18.18.1 About screeAbout screeAbout screeAbout screennnn 115

    8.1.1

    8.1.18.1.1

    8.1.1 Overview 115

    8.1.2

    8.1.28.1.2

    8.1.2 Screen structure 116

    8.1.3

    8.1.38.1.3

    8.1.3 Type and properties of screen 117

    8.28.28.28.2 Screen objectScreen objectScreen objectScreen object 121

    8.2.1.

    8.2.1.8.2.1.

    8.2.1. Common properties 121

  • 8.2.2.

    8.2.2.8.2.2.

    8.2.2. Drawing tools 122

    8.2.3.

    8.2.3.8.2.3.

    8.2.3. Quick buttons 124

    8.2.4.

    8.2.4.8.2.4.

    8.2.4. Show Data 129

    8.2.5.

    8.2.5.8.2.5.

    8.2.5. Edit Data 131

    8.2.6.

    8.2.6.8.2.6.

    8.2.6. Advanced Objects 132

    8.2.7.

    8.2.7.8.2.7.

    8.2.7. Clock objects 143

    8.2.8.

    8.2.8.8.2.8.

    8.2.8. Alarm Buttons 144

    8.38.38.38.3 Draw screenDraw screenDraw screenDraw screen 145

    8.3.1

    8.3.18.3.1

    8.3.1 About screen number 146

    8.3.2

    8.3.28.3.2

    8.3.2 State simulation 147

    8.3.3

    8.3.38.3.3

    8.3.3 Bookmark 148

    Chapter 9. Special function for TR PMIUChapter 9. Special function for TR PMIUChapter 9. Special function for TR PMIUChapter 9. Special function for TR PMIU 149

    9.19.19.19.1 USB Host functionUSB Host functionUSB Host functionUSB Host function 150

    9.1.1

    9.1.19.1.1

    9.1.1 Overview 150

    9.1.2

    9.1.29.1.2

    9.1.2 USB Upload (From PMIU unit to USB memory) 151

    9.1.3

    9.1.39.1.3

    9.1.3 USB Data Log Upload task (From USB memory to PMIU unit) 152

    9.1.4

    9.1.49.1.4

    9.1.4 USB Download (From USB memory to PMIU unit) 152

    9.29.29.29.2 Function key and Function key LEDFunction key and Function key LEDFunction key and Function key LEDFunction key and Function key LED 153

    9.39.39.39.3 Brightness controlBrightness controlBrightness controlBrightness control 153

    9.49.49.49.4 Alarm functionAlarm functionAlarm functionAlarm function 154

    9.4.1

    9.4.19.4.1

    9.4.1 Overview 154

    9.4.2

    9.4.29.4.2

    9.4.2 Setting 155

    9.59.59.59.5 Data loggerData loggerData loggerData logger 161

    9.5.1

    9.5.19.5.1

    9.5.1 Overview 161

    9.5.2

    9.5.29.5.2

    9.5.2 Setting 162

    9.5.3

    9.5.39.5.3

    9.5.3 Uploaded data 165

    AppendixAppendixAppendixAppendix 166

    Append. AAppend. AAppend. AAppend. A Battery replaceBattery replaceBattery replaceBattery replace 167

    Append. BAppend. BAppend. BAppend. B Erase modeErase modeErase modeErase mode 168

    Append. CAppend. CAppend. CAppend. C Serial communication cableSerial communication cableSerial communication cableSerial communication cable 169

    Append. DAppend. DAppend. DAppend. D System work flowSystem work flowSystem work flowSystem work flow 170

  • 1

    Chapter Chapter Chapter Chapter 1111....

    IntroductionIntroductionIntroductionIntroduction

  • 2

    What is TR PMIU series?

    Thank you for purchasing TR PMIU series. TR PMIU series is graphical color touch panel unit that ladder logic

    function is built into. All models have serial communication port, and some models has Expansion slot for IO unit.

    Moreover, they have data logger and alarm function. The display, the operation, and the control of a small-scale

    machine can be handled with this one. This will replace many switches, timers, and relays used of your

    machine/system.

    Requirement

    Following things are necessary for developing TR series.

    Personal computer (PC)

    TR PGMS01 programming software requires IBM PC/AT Compatible system that has Pentium

    800MHz or equivalent CPU, 256MB of RAM, 800MB of HDD free space, Windows OS (Windows

    2000

    SP4, Windows

    XP Professional SP2 or Home edition SP2) , Display (800x600 High-color 16bit),

    Keyboard and mouse, one USB or RS232C Serial port (We recommend USB port).

    TR PGMS01 software

    You must install this software before start development. All settings of the TR series are done from this.

    DC 24V Power supply

    Power source of all TR series. The power of most digital Expansion I/O unit is supplied from PMIU unit,

    but the Expansion I/O units that has relay output or analog I/O requires specially power supply for relay

    coil/AD converter. Protect the power supply with the circuit breaker for safety.

    USB cable (type A male/type B male) or Serial cable

    USB connection is recommended. Serial communication (RS233C) is more low-speed than USB, and the

    function is limited. If you want to connect by serial communication, refer Append. C.

    Device necessary for debugging or check of operation

    Expansion I/O unit, Tools, wiring material, device connected with TR unit, etc. Developing as much as

    possible in a near environment facilitates developing, and decreases the trouble. The device actually

    used is recommended to be prepared as much as possible.

    About TR PGMS01

    TR PGMS01 is setting and programming software for the all TR series. This can use all TR series including TR

    PMIU series touch panel monitor and Expansion I/O unit for it.

    Installation and uninstallation of TR PGMS is similar to general Windows software. To start setup, click

    setup.exe in program folder, then set up wizard is started. When the installation is completed, reboot your PC.

    To remove TR PGMS from your computer, open the control panel of Windows, and select "Add or remove

    programs", "Change or remove programs".

    We recommend this software to be used in an English environment. Some functions (function related to display

    and language) might not be able to be used normally under 2bytes character (language chiefly used in east Asia,

    Middle East, etc) environment.

  • 3

    Important term of operation

    About detail of each term, refer later chapter.

    Tag Tag is all registers or devices addressed in all TR series unit or other devices communicating with

    PMIU unit. There are much kind of tags corresponding to data type (Bit, numerical data, retentive

    area, system setting, etc). All the tags of a current project are registered in Tag Database. You can

    refer/add/edit/remove tag from here. Refer 5.1.

    Task Task is defined operation and is executed specific timing. All the tasks of a current project is

    registered in Task list corresponding to execution timing. Refer 6.1.

    Download/Upload/Online

    The transfer of project data from your PC to PMIU unit is called Download, the transfer from PMIU

    unit to your PC is called Upload. You can monitor edit tags of PMIU unit in RUN mode, it is called

    ONLINE mode. Refer 3.2.4.

    PMIU unit/Expansion I/O unit

    PMIU unit mean TR PMIU0300L/A or TR PMIU0500L/A. The color of case is black. You can connect

    Expansion I/O unit to PMIU unit up to 3 (in PMIU0300A) or 5 (in PMIU0500A) units. Expansion I/O

    unit cannot use alone, you must use it with PMIU unit. The color of case is red.

    Node The device which it is connected to the COM port, and communicates. For example, if 3 inverters

    and 1 touch panel is connected, there is 4 nodes. The table of all nodes is called node list. Refer 4.1.

    Project Minimum unit of files edited with TR PGMS. All data necessary to operate PMIU unit and Expansion

    I/O unit (such as unit settings, communication setting, node list, firmware, ladder program, screen

    data, etc) are contained.

    Key All TR PMIU unit has 6 Function keys with red LED (Function key LED) in right side of the screen.

    You can assign various usage for these keys and LEDs. Refer 9.2.

    Object All things that is put on screen. Some objects can display the data, or can control tags. Such as line,

    rectangle, display data, trend graph, etc

  • 4

    How to development

    The development order is roughly as follows.

    Step 1. Prepare the environment for development. Create New project in PGMS.

    Step 2. Set COM port of unit, and define communication node.

    Step 3. Define and register tag.

    Step 4. Define tasks, create ladder block. To define task, it is necessary to define tag beforehand.

    Step 5. Set unit function.

    Step 6. Design screen.

    Step 7. Download project to PMIU unit, check operation and debug project.

    The order of each step might change places and go back. Advance development by the method it is easy for you.

    But, note the following relations. An extra going back happens when it makes a mistake in these orders.

    Tag is necessary to define Task.

    Registration of Node is necessary to add tags of the communication device.

    Therefore, when you add the task that uses tag of communication device, the order "Add Node ", "Register Tag

    ", and "Define Task" should not be replaced.

  • 5

    Chapter 2.Chapter 2.Chapter 2.Chapter 2.

    HardwareHardwareHardwareHardware

  • 6

    2.12.12.12.1 SSSSeries lineuperies lineuperies lineuperies lineup

    PMIU unit

    Model Screen Expansion slots RTC Serial port USB port

    TRPMIU0300L - No 1 1

    TRPMIU0300A

    3.5in

    3 Yes 1 2

    TRPMIU0500L - No 1 1

    TRPMIU0500A

    5.7in

    5 Yes 1 2

    Expansion I/O unit

    Model Type Ch

    TRPDIO0808P Transistor Input & PNP type Transistor Output 8/8

    TRPDIO0808N Transistor Input & NPN type Transistor Output 8/8

    TRPDIX1600 Transistor Input 16

    TRPDOX0016P PNP type Transistor Output 16

    TRPDOX0016N NPN type Transistor Output 16

    TRPROX0012 Relay Output 12

  • 7

    2.22.22.22.2 TR TR TR TR PMIU series PMIU series PMIU series PMIU series touchtouchtouchtouch panel monitor unit panel monitor unit panel monitor unit panel monitor unit specificationspecificationspecificationspecification

    2.2.12.2.12.2.12.2.1 TR PMIU0300L

    General Specification

    Power supply DC24V +/-15% External dimension (mm) 128.0 x 102.0 x 44.5

    Power rating 5Watt Installation Panel mounting

    Total 8MB Front Bezel protection IP65 (If mounted correctly)

    Application Max 6MB Operating Temperature 0 - 50

    Ladder 170kSteps (1MB) Operating Humidity 0 90%RH (Non condensing)

    Data register 4096 Words ESD immunity IEC61000-4-2

    Retentive

    Register

    1400 Words Fast/Burst IEC61000-4-4

    Internal Register 256 Words Radiated RF IEC61000-4-3

    Input Register 400 Words (Max) Conducting noise IEC61000-4-6

    Output Register 400 Words (Max) Emission EN61000-6-4

    Timer Register 256 Words

    Timer Coil 256 points

    Counter Register 256 Words

    Sweep vibration test

    10 57Hz, +/- 0.075mm

    5 min/octave

    10 sweeps

    each X/ Y/ Z axis

    Counter Coil 256 points

    Configuration

    Register

    1600 Words (Max)

    System Register 256 Words

    Shock test

    57 150Hz 1G

    168 Sec/octave

    10 sweeps

    each X/ Y/ Z axis

    Memory

    System Coil 100 points

    Com1 RS232C/485/422

    Com2 -

    Com

    port

    USB 1(Device)

    Expansion slot -

    Type TFT Color LCD

    Resolution 320 x 240 pixel

    Monitor

    Touch screen Analog resistive

    This is detachable terminal block.

    Connecting of power supply connector is shown right.

  • 8

    2.2.22.2.22.2.22.2.2 TR PMIU0300A

    General Specification

    Power supply DC24V +/-15% External dimension (mm) 128.0 x 102.0 x 44.5

    Power rating 5Watt Installation Panel mounting

    Total 8MB Front Bezel protection IP65 (If mounted correctly)

    Application Max 6MB Operating Temperature 0 - 50

    Ladder 170kSteps (1MB) Operating Humidity 0 90%RH (Non condensing)

    Data register 4096 Words ESD immunity IEC61000-4-2

    Retentive

    Register

    1400 Words Fast/Burst IEC61000-4-4

    Internal Register 256 Words Radiated RF IEC61000-4-3

    Input Register 400 Words (Max) Conducting noise IEC61000-4-6

    Output Register 400 Words (Max) Emission EN61000-6-4

    Timer Register 256 Words

    Timer Coil 256 points

    Counter Register 256 Words

    Sweep vibration test

    10 57Hz, +/- 0.075mm

    5 min/octave

    10 sweeps

    each X/ Y/ Z axis

    Counter Coil 256 points

    Configuration

    Register

    1600 Words (Max)

    System Register 256 Words

    Shock test

    57 150Hz 1G

    168 Sec/octave

    10 sweeps

    each X/ Y/ Z axis

    Memory

    System Coil 100 points

    Com1 RS232C/485/422

    Com2 -

    Com

    port

    USB 2 (Device & Host)

    Expansion slot 3

    Type TFT Color LCD

    Resolution 320 x 240 pixel

    Monitor

    Touch screen Analog resistive

  • 9

    2.2.32.2.32.2.32.2.3 TR PMIU0500L

    General Specification

    Power supply DC24V +/-15% External dimension (mm) 195.0 x 142.0 x 50.0

    Power rating 5Watt Installation Panel mounting

    Total 8MB Front Bezel protection IP65 (If mounted correctly)

    Application Max 6MB Operating Temperature 0 - 50

    Ladder 170kSteps (1MB) Operating Humidity 0 90%RH (Non condensing)

    Data register 4096 Words ESD immunity IEC61000-4-2

    Retentive

    Register

    1400 Words Fast/Burst IEC61000-4-4

    Internal Register 256 Words Radiated RF IEC61000-4-3

    Input Register 400 Words (Max) Conducting noise IEC61000-4-6

    Output Register 400 Words (Max) Emission EN61000-6-4

    Timer Register 256 Words

    Timer Coil 256 points

    Counter Register 256 Words

    Sweep vibration test

    10 57Hz, +/- 0.075mm

    5 min/octave

    10 sweeps

    each X/ Y/ Z axis

    Counter Coil 256 points

    Configuration

    Register

    1600 Words (Max)

    System Register 256 Words

    Shock test

    57 150Hz 1G

    168 Sec/octave

    10 sweeps

    each X/ Y/ Z axis

    Memory

    System Coil 100 points

    Com1 RS232C/485/422

    Com2 RS232C

    Com

    port

    USB 1 (Device)

    Expansion slot -

    Type TFT Color LCD

    Resolution 320 x 240 pixel

    Monitor

    Touch screen Analog resistive

  • 10

    2.2.42.2.42.2.42.2.4 TR PMIU0500A

    General Specification

    Power supply DC24V +/-15% External dimension (mm) 195.0 x 142.0 x 50.0

    Power rating 5Watt Installation Panel mounting

    Total 8MB Front Bezel protection IP65 (If mounted correctly)

    Application Max 6MB Operating Temperature 0 - 50

    Ladder 170kSteps (1MB) Operating Humidity 0 90%RH (Non condensing)

    Data register 4096 Words ESD immunity IEC61000-4-2

    Retentive

    Register

    1400 Words Fast/Burst IEC61000-4-4

    Internal Register 256 Words Radiated RF IEC61000-4-3

    Input Register 400 Words (Max) Conducting noise IEC61000-4-6

    Output Register 400 Words (Max) Emission EN61000-6-4

    Timer Register 256 Words

    Timer Coil 256 points

    Counter Register 256 Words

    Sweep vibration test

    10 57Hz, +/- 0.075mm

    5 min/octave

    10 sweeps

    each X/ Y/ Z axis

    Counter Coil 256 points

    Configuration

    Register

    1600 Words (Max)

    System Register 256 Words

    Shock test

    57 150Hz 1G

    168 Sec/octave

    10 sweeps

    each X/ Y/ Z axis

    Memory

    System Coil 100 points

    Com1 RS232C/485/422

    Com2 RS232C

    Com

    port

    USB 1 (Device)

    Expansion slot 5

    Type TFT Color LCD

    Resolution 320 x 240 pixel

    Monitor

    Touch screen Analog resistive

  • 11

    2.2.52.2.52.2.52.2.5 Wiring for PMIU unit

    This section is common to all PMIU unit.

    Power supply cable connector

    This is detachable terminal block.

    Connecting of power supply connector is shown right.

    Insert and pull out connector straight. When force is

    diagonally applied, connector is damaged.

    COM1 port DB9pin female connector. If you use RS485 of this port as 2 wire connection, short 4pin & 5pin

    and connect to A line (or +, positive), short 6pin & 7pin and connect to B line (or -, negative) .

    All models has this port.

    COM2 port DB9pin female connector. This port supports only RS232C communication.

    TR PMIU0300L/A has not this port.

    USB SLAVE port USB Standard B type female connector. This is used to connect PMIU unit to your PC

    for programming and monitoring. All models have this port.

    USB HOST port USB Standard A type female connector. This is used for USB Host function and USB

    logged data upload. TR PMIU0300L/0500L has not this port. Refer 9.1, 9.5.

    P24V

    0V

    Earth

    Insert

  • 12

    2.32.32.32.3 Expansion I/O unitExpansion I/O unitExpansion I/O unitExpansion I/O unit specificationspecificationspecificationspecification

    2.3.12.3.12.3.12.3.1 TR PDIO0808P/N

    Specifications

    Common to TR PDIO0808P and N

    Unit type

    Digital Input x 8

    Digital Output x 8

    Type Bidirectional Transistor

    Rated Voltage DC 24V

    Rated Current 5 mA (Max)

    Impedance 4.9 kOhm

    Minimum ON DC 15.0V

    Maximum OFF DC 5.0V

    Turn ON/OFF time 10 mSec

    Input

    Isolation

    from internal circuit

    Photo coupler

    Type

    Transistor

    PNP type (DIO0808P)

    NPN type (DIO0808N)

    Rated Voltage DC 24V

    Output

    Rated Current 500 mA (Max)

    Rated power consumption DC3.9V 0.3W (Max)

    Supply of power From PMIU unit

    Operating Temperature 0 50

    Operating Humidity

    0 90%RH

    (Non condensing)

    External dimension (mm) 30.0 x 79.0 x 36.0

    Approximately weight 85 gm

  • 13

    Input

    Wiring for TR PDIO0808 P

    Output

  • 14

    Wiring for TR PDIO0808 N

    Input

    Output

  • 15

    2.3.22.3.22.3.22.3.2 TR PDIX1600

    Specifications

    Unit type Digital Input x 16

    Type Bidirectional Transistor

    Rated Voltage DC 24V

    Rated Current 5 mA (Max)

    Impedance 4.9 kOhm

    Minimum ON DC 15.0V

    Maximum OFF DC 5.0V

    Turn ON/OFF time 10 mSec

    Input

    Isolation

    from internal circuit

    Photo coupler

    Rated power consumption DC3.9V 0.3W (Max)

    Supply of power From PMIU unit

    Operating Temperature 0 50

    Operating Humidity

    0 90%RH

    (Non condensing)

    External dimension (mm) 30.0 x 79.0 x 36.0

    Approximately weight 85 gm

  • 16

    Input

    Input

    Wiring for TR PDIX1600

  • 17

    2.3.32.3.32.3.32.3.3 TR PROX0012

    Specifications

    Unit type Digital Output x 12

    Type Mechanical relay

    Common 3 points per common

    Rated Voltage DC 24V/AC 230V

    Rated Current 2 A/point (Max)

    Turn ON/OFF time 10/5 mSec

    Output

    Isolation

    from internal circuit

    Photo coupler

    Rated power consumption DC3.9V 0.3W (Max)

    Supply of power From PMIU unit

    Operating Temperature 0 50

    Operating Humidity

    0 90%RH

    (Non condensing)

    External dimension (mm) 30.0 x 79.0 x 36.0

    Approximately weight 85 gm

  • 18

    Output

    Wiring for TRSDOX0016N

  • 19

    Power supply

    connector

    Silica gel

    bag

    Mounting

    clamp x4

    2.42.42.42.4 Unpacking and Unpacking and Unpacking and Unpacking and InstallationInstallationInstallationInstallation of unit of unit of unit of unit

    2.4.12.4.12.4.12.4.1 Unpacking and accessory

    When you open package, check the type and the number of the

    contents. Unit is wrapped by vinyl bag, and Mounting clamps (4pcs),

    Power supply connector (1pcs), a silica gel bag (this is a desiccant and

    is protecting unit from moisture while transporting it) are attached in

    box (Power supply connector is not attached to some Expansion I/O

    unit). If the type or the number is different from your order, or if

    damage/trouble is found, please report to us immediately except the

    case that is clear that it is an accident under transportation.

    When unit is breaks down, it is necessary to send back unit to us. We

    recommend package to be kept.

    2.4.22.4.22.4.22.4.2 Attention of installation location

    Before installation of units, consider the following matters.

    Location that unit must not be installed

    There is corrosive/explosive/flammable gas, vapors or dust, oil/water mist.

    Where water, oil, or chemical are sprayed to, or dropped on unit.

    Only when the PMIU unit is appropriately set in the panel that endures water, front side of the unit

    endures a weak spray of water. However, a strong jet flow cannot be endured. Note that the back of unit

    has no protection.

    Place where fast temperatures fluctuate or high humidity exists.

    Place where vibration, shock, or stress might be applied to unit. (Note that connected wires not be pulled.)

    Place with strong electromagnetic noise (near adjustable speed drive, servo drive, motor driven by them,

    switching power supply, contactor, high frequency heating furnace, electric furnace, etc).

    Note for installation

    When front seat (it is a thin plastic sheet put on the front surface of touch panel) is damaged, dust, water

    etc. are infiltrated into inside of unit case. Do not touch, press or throw touch panel with hard and sharp

    pointed things (such as pen point, screwdriver, etc), high temperature things, things with pointed corner. Do

    not touch the chemical that might be deteriorated or dissolve the plastic.

    There is no protection in the back of unit (part that becomes the other side of the panel at the mount), the

    heat radiation hole is open in this part. Never wet or dirty, protect from dust, vapor, etc.

    It is necessary to radiate heat of unit. Note ventilation around the unit. Moreover, it is necessary to avoid

    that the device that generates heat or blows up hot wind is right under the unit. When you install unit in

    cubicle, note that cubicle doesn't become a high temperature because of sunlight etc.

    Enough space is necessary to handle wiring. Consider height of terminal block and the space of wiring. Give

    wires appropriate slack. Do not apply any stress to the PMIU unit, Expansion I/O unit, connector, terminal

    block and cable.

  • 20

    If you try to set up unit in the place with strong electromagnetic noise, give measures carefully. Earth wire

    must use fat wire as much as possible and wire shortest distance. Independent earth, cubicle earth, shield

    (earthed metal plate that blocks off noise), shielded twist pare cable, insulation transformer, insertion of

    ferrite core are effective to prevent noise. For some cases, isolation from the ground may lead to the stable

    operation.

    Unit cannot be used in outdoor. When exposed to strong sunlight for a long term, plastics used in exterior

    might be deteriorated by UV rays of sunlight, or rain water might be infiltrated in the unit. When using TR

    series in outdoor, install unit in cubicle.

    2.4.32.4.32.4.32.4.3 Installation of PMIU unit

    Step 1. Cut-out panel

    The size of the panel is shown below. These do not contain the size necessary for handling the wire.

    Panel cut-out Depth of unit (Without front bezel thickness)

    Item

    Vertical Horizontal

    Without

    Expansion I/O unit

    Include

    Expansion I/O unit

    Maximum

    Panel

    thickness

    TR PMIU

    0300L/A

    94 mm 120 mm 50 mm 85 mm

    TR PMIU

    0500L/A

    132 mm 185 mm 55 mm 90 mm

    6.5 mm

    TR PMIU0300L/A TR PMIU0500L/A

  • 21

    Step 2. Check gasket and clamp mount hole

    If the gasket protrudes beyond the ditch, push it into the ditch. Check clamp mount hole.

    There is 4 places clamp mount hole in

    TR PMIU0300L/A : right & left surface

    TR PMIU0500L/A : upper & bottom surface

    Step 3. Insert unit to panel cut-out

    Before unit inserts, remove the power supply

    connector, communications cable, and USB

    cable (Remove of Expansion I/O unit is not

    necessary).

    After unit inserts, it is necessary support the

    unit by someone or to be fixed temporary. Do

    not drop the PMIU unit!

    Step 4. Set mounting clamp

    Insert and hang mounting clamp on the clamp mount hall. Tighten the screw of mounting clamp.

    At first, screw must tighten loosely. Afterwards, tighten 4 screws evenly. Note that tightening of screw not

    even, and tightening of screw too much cause damages unit case

    (appropriate tightening torque is 0.6 - 0.7Nm). Wire when you

    confirm the unit was firmly fixed.

    Panel

    Screw

    Hang to

    here.

    This part

    TR PMIU0500L/A

    Clamp mount hole

    2 places are in 1 side.

    Clamp mount hole

    2 places are in 1 side.

    TR PMIU0300L/A

    Clamp mount

    hole

    2 places are in 1 side.

    Clamp mount

    hole

    2 places are in 1 side.

  • 22

    Lock Lock

    2.4.42.4.42.4.42.4.4 Installation of Expansion I/O unit

    Installation method is common to all expansion I/O units. Installation slot position of the expansion I/O unit is

    free. You can install expansion I/O unit in an arbitrary slot.

    Before installing expansion I/O unit, turn off power supply of the unit. To prevent accident, attach slot cover to

    the connector of the extended slot not used.

    Step 1. Slide lock

    All Expansion I/O units have 2 locks and 2 positioning

    pins. At first, slide locks to outside.

    Step 2. Install Expansion I/O unit to TR PMIU unit

    Remove slot cover of PMIU unit, then the expansion connector appears. Check connector position of

    expansion I/O unit, fit unit to position with the connector and positioning pin, push into expansion I/O unit,

    then slide lock to inside.

    Do not push expansion I/O unit forcibly, note that the connector is correctly connected.

    Lock

    1111. Remove

    Slot cover

    3

    33

    3. Insert Expansion unit

    2

    22

    2. Check Connector

    4

    44

    4. Lock

    4

    44

    4. Lock

  • 23

    2.52.52.52.5 PMIU PMIU PMIU PMIU unitunitunitunit operation mode operation mode operation mode operation mode

    2.5.12.5.12.5.12.5.1 Kind of operation mode

    You can change the mode of the PMIU unit by the operation from TR PGMS (Online mode only).

    RUN

    All input is detected, self diagnosis, task, ladder logic and communication services are executed, all output is

    controlled according to project. If error is detected at self diagnosis, change to HALT mode.

    Note that if any Expansion I/O unit is not allocated in project, PMIU unit not detects Expansion I/O unit

    even if Expansion I/O unit is attached.

    HALT

    Execution of program (task and ladder) is stopped, all output is turned OFF. If any error is detected, PMIU

    unit switches to this mode. When any error is detected, or project is downloaded, PMIU unit is switched to

    this mode.

    In this mode, operation information is displayed in screen.

    HOLD

    Execution of program (task and ladder) is suspended, all the outputs are held in the state when switched to

    this mode. Refresh of input and output is executed, so you can edit ON/OFF state of output. This mode is

    provided mainly for checking the external I/O signals.

    In this mode, operation information is displayed in screen.

  • 24

    2.5.22.5.22.5.22.5.2 When any error is detected

    PMIU unit has self diagnosis function and checking itself every scanning. If any error is detected and cannot

    recover the error by retries, PMIU unit switches to HALT mode. You can refer history and detail of error by

    Event history, and current status can referred by system tags.

    There is a kind of error shown below.

    Unit Error

    Watchdog timer error of micro processor built in PMIU unit. System coil M0016 (CPU error) and M0027

    (Watchdog timer error) changes to ON.

    I/O mismatch

    The allocation (installed slot number) or the type of Expansion I/O unit is different from project. System coil

    M0017 (I/O error) and M0029 (I/O mismatch error) changes to ON.

    When this error is detected in power ON, PMIU unit becomes HALT mode. To switch the unit to RUN mode

    forcibly, press F1 key twice, or connect USB cable to unit, switch ONLINE mode and select RUN from

    PLC Control from Mode menu of menu bar. Then the PMIU unit becomes to Forced RUN mode. In this

    mode, ladder and application of project is executed even if I/O unit is different from project or not attached,

    but I/O scan and refresh is not done. POWER LED is blinking.

    I/O bcc error

    Parity error is detected at Expansion I/O unit or data bus of Expansion port. System coil M0017 (I/O error)

    and M0031 (I/O communication error) changes to ON.

    Program Error

    Scan time is exceeds 200mSec (in default. You can extend it to 350mSec by using WDT reset instruction in

    ladder block). System coil M0018 (Program error) and M0031 (Ladder scan time over) changes to ON.

    Clock calendar error

    The data of built-in RTC is invalid. System coil M0021 (Clock/calendar illegal value warning) changes to ON.

    Retentive data loss

    The data of retentive memory area is invalid. If this error is detected, data validity of retentive area is not

    guaranteed. System coil M0022 (Clock/calendar illegal value warning) changes to ON.

    When the power of PMIU unit is ON, this item is checked at only once.

  • 25

    2.62.62.62.6 Operation and maintenanceOperation and maintenanceOperation and maintenanceOperation and maintenance

    All units require periodically check and maintenance. When you check, be careful about the following matters.

    Note for Electrostatic discharge

    Static electricity is accumulated in human body. It causes electrostatic discharge and destroys sensitive

    electric devices (LSI, IC, etc) easily. To discharge static electricity, before touching unit, touch the metal

    connected with earth. Use electrostatic hazard shoes, ESD wristband. Do not touch any electrode or metal

    part of unit. Especially, be careful when you connect/disconnect programming cable.

    Do not install/remove Expansion I/O unit while unit power is ON

    When you install/remove Expansion I/O unit, turn OFF power supply of the PMIU unit.

    Do not insert finger, wire, tool tip etc. into unit case

    Unit case has heat radiation hole, connector hole etc. The invasion of these may cause malfunction of unit,

    fire or electrical shock.

    2.6.12.6.12.6.12.6.1 Maintenance items

    LED status

    When PMIU unit is operating normally, POWER LED is lit.

    Screen

    Screen of PMIU unit should be clean. If there is dirt, wipe with clean closes.

    Installation state

    PMIU unit should be fixed to panel surely, and Expansion I/O units should be attached to PMIU unit surely.

    There must not be loosening in the installation.

    Connected wires and wire terminals

    All connectors and terminal blocks should be installed surely, all wire should be appropriate slack. Wire

    covering, connector or terminal block must not be discoloration or damage, wire terminal must not be dirt or

    discoloration.

    The discoloration of the metal might have been caused because of an abnormal current/voltage or

    overheating. The dirt/scorching of connector, wiring terminal and of surroundings might cause the

    short-circuit accident. Note that wire covering that passes a long term becomes hard and is damaged easily.

    Project (software) backup

    We recommend periodically backup of project for an unexpected memory loss (it may be caused by strong

    EMC noise, lightning accident, etc). You can Online or Upload project freely while unit power is ON and unit

    mode is RUN mode.

  • 26

    2.6.22.6.22.6.22.6.2 Trouble shooting

    If PMIU unit causes malfunction, or any unit emits smoke or odor, shut OFF all power of your system/machine

    immediately and safely.

    When you check the system/machine, give measures carefully so that harmful operation should not happen.

    Make sure enough safety when you turn ON the power when investigate the failure cause.

    If the problem is found in the TR unit, check the following points;

    1. Supply of power

    2. PMIU unit

    3. Input and output of Expansion I/O unit

    4. Remove all Expansion I/O units and check PMIU unit alone. If PMIU unit operates normally, connect each

    Expansion I/O unit one by one. There is possibility that breakdown of some unit causes overall

    malfunction.

    5. Check operation of unit in the place where a trouble happened. If the unit operates normally, some

    environmental factor may causes trouble. If unit causes malfunction synchronously with other

    device/machine/equipment, they might cause trouble.

    Supply of power

    POWER LED

    POWER LED is lit or blinking when power is supplied to the unit regardless of unit mode. If not lit, power

    is not supplied to PMIU unit.

    Wiring of power supply

    Check connection of wire and terminal block. Screws of terminal block should be tighten surely, and

    terminal block should be inserted to connector of unit surely.

    The core wire which came loose may short-circuit with the next terminal.

    Input voltage

    Check polarity and voltage (DC24V +/- 15%) at power supply connector of unit. Do not connect AC to

    the unit. Electromagnetic noise, voltage fluctuations, surge of voltage must not superimpose to power line.

    If the capacity of the power supply is extremely small, when the input/output circuit operates, or supply

    voltage is dropped by inrush current of unit, unit might not be able to be booted.

    Cable

    If POWER LED become lit when remove cable (communication cable or programming cable), the there is

    short-circuit in the external connections of the port. Check USB or serial cable, or USB/COM port of

    your PC.

  • 27

    PMIU unit

    LED status

    PMIU unit has POWER LED in top left of case. If it is blinking, there may be some error. There are 2 cases,

    communication error and RUN-force mode.

    Operation mode

    Connect PC to PMIU unit and check operation mode of PMIU. If PMIU mode is RUN-F mode, unit

    operates normally even if Expansion I/O unit attached to PMIU unit is different from project, and the I/O

    status of Expansion I/O unit is not updated.

    Input

    Input signal status

    Check signals at the terminal of Expansion I/O unit. If the screw of signal terminal is loosen, the signal

    may repeat unstable chattering. And, the core wire which came loose may short-circuit with the next

    terminal.

    If input signal is OK, unit may be faulty. Replace the unit with new one.

    Usage of input device/register

    Connect PC and monitor the input register/device in RUN mode. If the monitored device is changed

    corresponding to the external signal, the cause might be in the project.

    Check usage of the device/register in project. Note that unit is operation normally in RUN-F mode even

    if Expansion I/O unit is mismatch.

    Output

    Output status of unit

    Output changes according to the execution of the program. If no, check IO allocation and usage of the

    device/register in project. Note that unit is operation normally in RUN-F mode even if Expansion I/O unit

    is mismatch.

    The core wire which came loose may short-circuit with the next terminal.

    External device connected to output

    If I/O of unit is operates normally, check input specification of external devices connected to the unit.

    Environmental factors

    Troubles may caused by severe electromagnetic noise, difference of grounding potentials between unit and

    external circuit, mechanical shock/vibration, high/low temperature, dewfall, oil mist, water drop, dust, etc.

    Only when appropriately set up in the panel that endures water, front side of unit endures a weak spray of water.

    However, a strong jet flow cannot be endured. The material of the front seat cannot endures some kind of oil,

    chemicals etc. Note that back of unit has no protection.

    Moreover these factors shorten the life of the unit. Avoid these factors or give measures at installation.

    Noise might enter to unit via wires. Isolation of I/O signal, or earth line may lead to the stable operation in some

  • 28

    cases. Check the unit in the different location (There is no factor which gives harmful influence to the unit).

    If the unit operates normally, there is a possibility the installation environment has some problem.

    Timing of the trouble may become an important factor for a specific cause. If trouble occurs synchronously with

    the operation of external device/machine/equipment etc, they might cause the trouble.

    If the improper operation occurs when specific time/time zone, check installation environment of unit. There is

    a possibility of becoming dewfall or severe high/low temperature in control panel because of the ambient

    temperature, sunlight, the heat generated by equipment of control panel or close to the control panel, etc.

    Check that no garbage or water drop or oil mist has been entered into the unit. Consider climatic conditions.

    2.72.72.72.7 RTCRTCRTCRTC

    TR PMIU0300A/0500A has battery back upped built-in RTC. Current date and time is stored in system register

    from SW0010 to SW0016. Refer below table. It can change by only using of set RTC instruction or Set RTC

    task.

    Address Item Description

    SW 0010 Day Valid data range is from 01 to 31.

    SW 0011 Month Valid data range is from 01 to 12.

    SW 0012 Year Valid data range is from 00 to 99. 00 means A.D.2000.

    SW 0013 Hour Valid data range is from 00 to 23.

    SW 0014 Minute Valid data range is from 00 to 59.

    SW 0015 Second Valid data range is from 00 to 59.

    SW 0016

    Day of

    week

    Valid data range is from 1 to 7.

    1is Sunday, 2 is Monday, 3 is Tuesday 7 is Saturday

  • 29

    Chapter Chapter Chapter Chapter 3333....

    TR PGMSTR PGMSTR PGMSTR PGMS

  • 30

    3.13.13.13.1 User interface of TR PGMS01User interface of TR PGMS01User interface of TR PGMS01User interface of TR PGMS01

    In this chapter, item of screen and menu bar of TR PGMS software is explained. The items of menu bar, toolbar

    changes according to the situation.

    3.1.13.1.13.1.13.1.1 Overview of window

    When you launch TR PGMS, the application window opens with standard toolbars and working platform.

    Menu bar The area containing pull-down menu options.

    Tool bar This contains shortcuts of commands. There are 3 kinds (Project, Layout, and Global).

    Project information

    Elements that composes the current project is displayed by the tree view form. If each folder ( ) is click,

    you can access the item. Current access folder is displayed while having opened ( ).

    Folder displayed like contains some items. The content can be progressed by clicking ( ).

    Property section (This is not displayed in above example)

    A detailed attribute of current object or instruction is displayed.

    Menu bar Project tool bar

    Project

    information

    Workspace

    area

    Property

    section

    Global

    tool bar

    Layout

    tool bar

  • 31

    If you want to display/hide toolbar arbitrary, right-click on the menu

    bar, then menu shown left is displayed. Check item to display

    corresponding toolbar.

    When some list(Node list, Tag list, etc.) is displayed, you can change uppermost column as spread-seat

    software.

    When you bring cursor to botder of item of uppermost

    column, shape of cursor is changes like spread-sheet soft.

    Then you can change the width of item by dragging a cursor

    in this state.

    Right click to change displayed item of column.

    Drag to change width of item column.

    Each item can be

    Display/hide.

    Right click

    On column

    Drag on

    border

  • 32

    3.1.23.1.23.1.23.1.2 Menu bar

    The order of the item changes by the situation.

    Project

    New Create new project.

    Open Open existing project.

    Close Close current project.

    Save Save current project by overwriting.

    Save as Save current project by another name.

    Properties Open Project configuration window. Refer 3.2.2.

    Import Text Objects

    Import text data associated with the object (on/off text, labels etc.).

    Refer 3.7.3.

    Export Text Objects

    Export data from projects and put it into a user specified file. Refer 3.7.3.

    Transfer Download/Upload project. Refer 3.2.4.

    Print Print information of current project. Refer 3.2.3.

    Compile Compile current project. If there is error, message is displayed.

    RUN Start simulation. You can check the operation of PMIU unit

    without the unit. Note that some function cannot simulate such

    as trend, ladder, etc.

    Exit Quite from TR PGMS.

    Draw

    Graphical Objects , Buttons, Input Objects, Display Object

    Corresponding object is put on screen.

    Alphanumeric Grid Display grid to screen. This can be used as a standard

    when arranging object.

    Touch Grid Display grid that shows touch position resolution of the

    touch panel. Touch panel cannot detect the touch

    position in detail more than this grid.

    Snap To Grid Snap object to Alphanumeric Grid. It is useful when you

    arrange some objects.

    Configure Grid Change interval between grid and grid. 40 pixel or less.

  • 33

    Edit

    Undo Cancel operation done just before.

    Redo Repeat operation done just before.

    Cut Cut current selected object to clipboard.

    Copy Copy current selected object to clipboard.

    Paste Paste object of clipboard to screen.

    Select All object of current screen is selected.

    Make Group Make 2 or more objects to single group object.

    Break Group Break group object to 2 or more objects.

    Bookmarks Set bookmark to current screen. Refer 8.3.3.

    Tools

    Application Memory Status

    Details of the memory capacity are displayed. Refer 3.2.5.

    Display Logged data

    Uploaded logged data is displayed by using spread-sheet software.

    This function is available when logged data is uploaded. Refer 3.2.4.

    Display Historical Alarm Data

    Display the data of Historical Alarm. Refer 3.2.4.

    Convert Application

    Current project is converted for another model. Refer 3.2.6.

    Preferences

    Colors Set color of Online ladder monitor and ladder editing

    mode. Refer 3.2.7

    Online communication

    Set communication method between PMIU unit and PC.

    Others Set display of ladder editing mode and ladder editing

    mode. Refer 3.2.8.

  • 34

    View

    Data Monitor Window

    Display the value of register. If this item is chose in

    Online, the real time value is displayed. Refer 3.4.

    Device information

    Display information of the unit connected to your PC by

    USB. Refer 3.2.9.

    Icons The display of the item is switched to the icon display.

    Lists The display of the item is switched to the simple list.

    Details The display of the item is switched to the detail list.

    Arrange by Icon or item of list is arranged by

    Number/Name/Destination/Type/Task/Description.

    Zoom To Zoom workspace area.

    Errors and Warnings

    Show ladder block syntax error and project compile error

    of current opened project.

    Refresh Refresh display of workspace area.

    Screen Information

    Show/hide information of current screen in bottom of

    workspace area.

    Screen/Object Properties

    Show/Hide of Property section in bottom of workspace

    area.

    Projects Information

    Show/Hide Project information in left side of workspace

    area.

  • 35

    Screen

    New Base Screen Create new Base Screen.

    New Popup Screen Create new Popup Screen.

    New Template Screen Create new Template Screen

    Open Screen Open existing screen.

    Open Template Screen Open existing Template screen.

    Apply Template Screen Apply Template Screen to current screen.

    Close Close Current screen.

    Delete Delete Current screen.

    Duplicate The same screen as Current screen is made.

    First Screen Open first screen in project

    (Screen number is lowest in current project)

    Next Screen Open next screen.

    Previous Screen Open previous screen.

    Last screen Open the screen in project

    (Screen number is largest in current project)

    Mode

    Edit Switch to project edit mode. In this mode, TR PGMS switches

    to OFFLINE mode and you can edit uploaded project, but it is

    necessary to save edited project and download again. You can

    switch this option by F7 key.

    Online/Offline Change mode when you connect PMIU unit to PC. Refer 3.2.4.

    PLC Control Switch mode of PMIU unit. Refer 2.5.

  • 36

    Layout

    Pattern Set painting out pattern of object.

    Line Color Set color of profile line

    Fill Color Set fill color of object.

    Text Color Set color of text

    Pattern Color Set color of painting out pattern

    Bring To Front Bring overlapped object to front side (forward of other objects).

    Bring To Back Bring overlapped object to rear side (behind of other objects).

    Align To Left/Right/Top/Bottom

    2 or more selected objects are placed to line based on a

    left/right/top/bottom edge.

    Align Middle

    Horizontal/Vertical Align object to a horizontal/vertical center of screen.

    Horizontal Shape Arrange horizontal center point of 2 or more objects.

    Vertical Shape Arrange vertical center point of 2 or more objects.

    Place Equal Horizontal/Vertical

    Arrange 2 or more objects vertically/horizontally equal intervals.

    Make Equal Height/Width/Size

    Arrange 2 or more objects in the same height/width/size.

    Define

    Data Logger Open Data Logger setting screen. Refer 9.5.

    Global Keys Open Global Key Task setting screen. Refer 6.1.4.

    Nodes Open Node list. Refer 4.1.

    Tag Database Open Tag Database screen. Refer 5.2.

    System Parameters

    Set interrupt timer and Retentive memory area. Refer 3.5.

  • 37

    Window

    Cascade All opened window is piled up to the vertical direction.

    Tile Horizontally All opened window is horizontally arranged.

    Tile Vertically All opened window is vertically arranged.

    Close All All opened window are closed.

    Help

    Contents/Index/Search Start Help.

    About Display version information of TR PGMS.

    List of block that is opening now

    When you click, block is opened.

    Click to open the list of available block.

  • 38

    3.1.33.1.33.1.33.1.3 Tool bar

    Item and activities change by the situation.

    Project toolbar

    Create new project.

    Open existing project.

    Save current project.

    Close current project.

    Upload project from PMIU unit to your PC. Refer 3.2.4.

    Download project from your PC to PMIU unit. Refer 3.2.4.

    Display/hide Property section.

    Zoom up workspace area.

    Zoom down workspace area.

    Set zoom of workspace area.

    Toggle Online/Offline mode. Refer 3.2.4.

    Start simulation. You can check the operation of PMIU unit without the unit.

    Note that some function cannot simulate such as trend, ladder, etc.

    Open Data monitor window. Refer 3.4.

    Compile current project.

    Start help.

    Cut selected instruction.

    Copy selected instruction.

    Paste instruction of clipboard.

    This function is not available.

    / Redo/Undo operation.

    Switch display of screen list to large icon with preview.

    Switch display of screen list to small icon.

    Switch display of screen list to simple list.

    Switch display of screen list to detail list.

    Show/hide system tags in Tag Database.

  • 39

    Layout toolbar

    The button that gray out is not used

    Create new Base Screen.

    Create new Template Screen.

    Create new Popup Screen.

    Delete Current screen.

    Open existing screen.

    Switch screen edit mode from other mode.

    Open Node list screen. Refer 4.1.

    Open Tag Database screen. Refer 5.2.

    Open Alarm Database screen. Refer 5.2.

    Apply bookmark to current screen. Refer 8.3.3.

    Clear bookmark of current screen. Refer 8.3.3.

    Clear all bookmark. Refer 8.3.3.

    Jump to Next bookmark screen. Refer 8.3.3.

    Jump to Previous bookmark screen. Refer 8.3.3.

    Move to Previous screen/block.

    Move to Next screen/block

    Jump to First screen/block

    Jump to Last screen/block

    / Bring overlapped object to front/back side (upper/lower side of other objects).

    / / / Line up 2 or more selected objects based on a left/right/top/bottom edge.

    / Align object to a horizontal/vertical center of screen.

    / Arrange horizontal/vertical center point of 2 or more objects.

    / Arrange 2 or more objects vertically/horizontally equal intervals.

    / / Make 2 or more objects in the same height/width/size.

    Make 2 or more objects to single group object.

    Break group object to 2 or more objects.

    Cancel previous instruction.

    Arrange horizontal blanch.

    Arrange vertical blanch.

    Arrange NO contact.

    Arrange NC contact.

    Arrange Coil instruction.

    Arrange ON timer instruction.

  • 40

    Arrange Counter instruction.

    Arrange END instruction.

    Search instruction from ladder block.

    Global toolbar/Font toolbar

    Change object display of current screen to ON state.

    Change object display of current screen to OFF state.

    Change object display of current screen to previous state.

    Change object display of current screen to next state.

    Change object display of current screen to specify state.

    Switch the language of the displayed screen.

    Change font of selected object.

    Change size of selected object.

    Change font of selected object to Bold-face.

    Change font of selected object to italic style.

    Add under bar to font of selected object.

    Change border line color of selected object. If clicked, color palette is displayed.

    Change background color of selected object. If clicked, color palette is displayed.

    Change text color of selected object. If clicked, color palette is displayed.

    Change background pattern of selected object. If clicked, palette is displayed.

    Change background pattern color of selected object. If clicked, color palette is displayed.

  • 41

    3.23.23.23.2 Operation of TR PGMSOperation of TR PGMSOperation of TR PGMSOperation of TR PGMS

    3.2.13.2.13.2.13.2.1 Creating of new project

    To create new project, select Project of project tool bar

    and click Create New Project, or click of Project

    menu bar. Then Select product window shown right is

    displayed.

    Select type and model of PMIU unit, then Project

    Configuration is displayed.

    or

    1

    11

    1. Choice unit type

    2

    22

    2. Choice unit model

    Setting items

    (4 or 5 tabs)

    Click OK

    Click OK

    New Project is

    made

    Model information

  • 42

    3.2.23.2.23.2.23.2.2 Project Configuration

    You can change these settings later.

    Project Information

    Project Title Title of this project.

    Save in Directory Set folder pass to save this project.

    Description This is memo space. You can use this space to comment, note, etc. of project.

    Author You can input author name of this project. Up to 45 characters.

    Password You can set password of this project. If you set password, this project cannot open

    without inputting password. Up to 8 characters.

    COM port (This section is common to COM 1 and COM 2 port. Refer 4.1)

    Protocol Select communication protocol.

    Model Select model to communicate.

    Communication Settings Select option. You can change these settings later.

    Add Node Add node in default node name. The number of nodes that you clicked are added.

  • 43

    Alarm

    For detail setting, refer 9.4.

    Alarm type

    16 consecutive words Alarm register is defined consecutive 16 words. You must prepare 16 register tags

    (2bytes) where the address is consecutive.

    16 random words Alarm register is defined random 16 words. Address of register may be not

    consecutive.

    Auto Acknowledge

    Acknowledge All All alarms are acknowledged at same acknowledge bit.

    Selectable Acknowledge bit of each alarm bit is defined.

    Memory Full operation

    Maximum capacity of alarm memory is 600 alarms. If alarm memory is full, alarm operates as follows.

    Erase previous Alarms and starts logging from beginning (Old alarm is overwritten.)

    Stop logging (Alarm logging is stopped)

    Alarm type

    Auto Acknowledge

    Memory Full

    operation

  • 44

    Settings

    Screen Saver Enable If you check and set time, enabled. If it doesn't touch the screen during waiting

    time, the backlight of LCD is turned off. Backlight lights again when touching

    screen.

    Erase Data Logger Memory If checked, Data logger memory of unit is cleared before download project.

    Download Tag names If checked, Tag name of project is download to unit. If it is not checked, All the

    displays of the online ladder monitor become the default tag names.

  • 45

    3.2.33.2.33.2.33.2.3 Print project

    When you print documents of project, Select Project of menu bar, and click Print. Select data for print

    (HMI data or Ladder data). If you click Preview, print preview is displayed.

    HMI data

    Ladder data

    Select block

    for print

    Select item

    for print

    Select screen for

    print

  • 46

    3.2.43.2.43.2.43.2.4 Download/Upload/Online

    Download is operation that transfers project edited on your PC to PMIU unit. Upload is operation that

    transfers project and data of PMIU unit to your PC. Online is operation that monitors ladder circuit and data

    in PMIU unit from your PC.

    Note that during Download operation, all functions (task, ladder, operation of expansion I/O unit, data logger and

    alarm) of the PMIU unit stop.

    Upload

    Download

    Open Data monitor window.

    Toggle Online/Offline

    If you transfer edited data and project at the same time, edit data of tags in data monitor (refer 3.4), then

    download project with Data option in download option. Refer following chapter.

    When you connect PC and PMIU unit by USB for the first time, Windows might requests device driver. The

    driver file exists in USB driver folder in PGMS installation folder. Select driver file according to OS installed

    to your PC.

    If unit not reply in these operation (the message Unit not responding is displayed), open device manager of

    windows, delete the unit (unit is existing in USB controller as the name HMI USB device if unit is installed),

    disconnect USB cable. Reboot your PC and install unit again.

    If you use serial communication, Serial communication cable is required. Refer Append. A. Note that RS232C

    straight cable on the market cannot be used as it is, and you cannot use "Online" by serial communication.

    Download

    Upload

  • 47

    Download

    Step 1. Connect PMIU unit to your PC with USB cable or Serial cable. If you use serial port, serial cable

    should be connected between COM1 port of PMIU unit and RS232C port of your PC.

    Step 2. Click of project toolbar, or click Project of menu bar, Select Transfer, click Download.

    Then following window is displayed. Set options.

    Mode Select USB or serial. If you select serial, Select COM port and set communication

    settings of your PC.

    Download options Check the item that you transfer to PMIU unit.

    Firmware When you use new unit for the first time, or edit communication, alarm or data

    logger settings

    Application When you edit unit settings excluding ladder

    Ladder When you edit Ladder logic block

    Data You can download edited data by Data monitor. Refer 3.4.

    Device settings

    Automatically put unit in halt mode before download

    The mode of PMIU unit is changed to HALT mode before downloading project automatically.

    Automatically put unit in run mode before download

    The mode of PMIU unit is changed to RUN mode after downloading project automatically.

    If check is removed, unit become HALT mode after downloading even if RUN/HALT switch is

    RUN position.

    Initialize keep memory area after download

    Back up memory area of PMIU unit is initialized after downloading (data of there is cleared).

    Initialize all device register except keep memory area after download

    All registers and devices of PMIU unit is cleared except back up memory area.

  • 48

    Step 3. Check option and Click Download, then downloading is starts. When project is existing in PMIU unit,

    or the data of data logger is existing, confirmation window of overwriting project is displayed.

    Upload

    Step 1. Connect PMIU unit to your PC with USB cable or Serial cable. If you use serial port, serial cable

    should be connected between COM1 port of PMIU unit and RS232C port of your PC.

    Step 2. Click of project toolbar, or click Project of menu bar, Select Transfer, click Upload.

    Then following window is displayed. Set options.

    Mode Select USB or serial. If you select serial, Select COM port and set communication

    settings of your PC.

    Upload options Check the item that you transfer to your PC.

    Application Upload project data except ladder logic block.

    Application + Ladder Upload project data and ladder logic block.

    Logged Data Upload logged data of Data Logger (if checked, unit reboots after

    uploading).

    Historical Alarm Data Upload alarm data of Historical Alarm.

  • 49

    Step 3. Check option and Click Upload, then upload is starts.

    When finished, uploaded project is opened by PGMS, and saved as UPLD.pzm.

    When you check Logged Data or Historical Alarm Data, uploaded data is stored as Logg.csv or

    HistAlarm.csv in PGMS installation folder. In this case, note that the unit reboots after uploading

    project.

    Online (This can only USB connection.)

    Step 1. Connect PMIU unit to your PC with USB cable.

    Step 2. Click of project toolbar, or click Mode of menu bar, select Online, select With Upload or

    Without Upload.

    When you select With Upload, PGMS closes current project, and uploads the project that exists in

    the PMIU unit automatically. You can switch to this mode by pressing F8 key of your PC.

    When you select Without upload, PGMS not uploads project. Online monitoring is done by current

    opened project.

    Step 3. Switch to Online mode automatically, and the window of ladder logic block 1 is opened.

    Step 4. When you monitor another ladder block, click Block of menu bar, Click Open and select block

    you open. When you monitor data of tags, click to open Data monitor window (Refer 3.4).

    Step 5. When you edit project, press F7 key of your PC, or click Mode of menu bar, select edit.

    TR PGMS switches to OFFLINE mode, and you can edit current project. When you finish editing,

    download project again. When you switch offline, click again, or click Mode of menu bar, select

    Offline. Then you can disconnect USB cable.

  • 50

    3.2.53.2.53.2.53.2.5 Application Memory Status

    Number of items that compose current project, current used/free memory capacity, are shown. This shows the

    status when the project was saved last. To know latest status, save project and open this window.

    3.2.63.2.63.2.63.2.6 Convert Application

    Convert current project to other model. Available conversion is as follows.

    TRPMIU0300L/A/E to TRPMIU0300L/A/E

    TRPMIU0500L/A/E to TRPMIU0500L/A/E

    Conversions other than showing here cannot be done.

  • 51

    3.2.73.2.73.2.73.2.7 Preference (Color settings)

    Color settings

    Contact ON Color of contact that has been turned ON.

    Contact OFF Color of contact that has been turned OFF.

    Function block Color of function block such as transfer

    instruction, etc

    Operand value Color of operand character.

    Editor

    Block background

    Background of function block such as transfer instruction, etc.

    Active Rung Color of current selected rung.

    Left Margin Rung 1 Color of line number (odd number)

    Left Margin Rung 2 Color of line number (even number)

    Set all default All settings are change to default setting.

    3.2.83.2.83.2.83.2.8 Preference (Project global settings)

    Ladder instruction tag name length

    Length of Tag name displayed in ladder editing screen.

    Settings

    Show default tag name definition screen

    Whenever new tag is input, Define tag name window is

    displayed.

    Show overlapping Message Screen

    This function is not available.

    3.2.93.2.93.2.93.2.9 Device Information

    If PMIU unit is connected to PC by USB, you can check the

    Boot block version/Hardware version/Firmware version of

    the PMIU unit, and Expansion I/O unit which is connected

    to the PMIU unit (ONLINE mode is not needed).

    Upgrade Firmware button and check box options in the

    bottom of window are used for change Firmware.

    The latest version firmware is installed in an all shipped unit.

    Do not operate these functions without our instruction.

  • 52

    3.33.33.33.3 LLLLadder logicadder logicadder logicadder logic

    3.3.13.3.13.3.13.3.1 Overview

    PMIU unit can execute ladder logic.

    Ladder circuit is described in the Ladder

    logic block (ladder block).

    There are 4 kinds of ladder block. All

    ladder blocks exist in one of these 4

    folders. When you click Logic Blocks

    folder, list of the screen that exists in

    current project is displayed in the

    workspace area.

    There are 6 folders in Logic Blocks folder.

    Each folder has corresponding ladder block. Program

    capacity of each ladder logic block has no limitation.

    Total capacity for ladder blocks is 48KB, 8192 steps. You

    can refer current ladder capacity in Application Memory

    Status (refer 3.2.5).

    Maximum number of block is 256, block number need not

    be consecutive.

    You can compile project while editing, for checking syntax error of ladder. Click button of Global tool bar

    or press F9 key of your PC, then project is compiled. If there is an error, error message is displayed under

    workspace area.

    When you right click on each folder, following menus are displayed.

    New Logic Block Create new ladder logic block in clicked folder.

    Ladder logic

    block

    List of blocks

  • 53

    3.3.23.3.23.3.23.3.2 Kinds of Ladder block

    Power Up Logic block

    This block is executed only once when unit power is turned ON, and it is not executed afterwards.

    Main logic block

    This block is started after Power Up logic block and executed every scanning while PMIU unit is RUN or RUN-F

    mode. You can refer Ladder scan time at SW 0048 (Ladder scan time).

    Operation image of Power-Up and Main logic blocks is shown as follow.

    Timer Interrupt

    When interrupt timer is turned ON, other operation (execution of Main logic block, tasks etc) is suspended and

    this block is executed. If execution of this block is completed, execution of Main logic block is resumed. Priority

    is highest in all tasks/logic blocks. Interrupt interval can set by System parameter. Refer 3.5.

    Subroutine

    This block is executed only when Subroutine call instruction is executed. While executing the subroutine block,

    processing of main block is stopped. If execution of this block is completed, execution of Main logic block is

    resumed. About detail, refer Subroutine call instruction of Ladder reference manual.

    I/O interrupt #1, #2

    This function is not available.

  • 54

    3.3.33.3.33.3.33.3.3 Ladder edit area

    To edit/refer existing ladder block, open Logic Blocks folder and click the block, then edit window is opened.

    You can edit 2 or more ladder blocks at same time. Click to display current block as window, click to

    minimize current window, click to close current window, and you can also use Window menu of menu bar.

    On ladder edit area, the row in the vertical direction that the number is putted is called "Rung", each row when

    2 or more rows are occupied with same rung number is called "Line", right and left squares are called "Column".

    1 Rung/Line is composed of 11 columns, and 1 Rung can contain up to 50 lines. Rung and Line can be added/

    inserted/deleted from the right-clicking menu.

    Please note that any instructions except the NO/NC contact cannot be arranged in the left edge of

    column/line (including Rising/Falling edge contact), and any contact cannot be arranged in the right edge of

    column. It is necessary to arrange Coil instruction on a right edge of the line.

    Ladder edit

    area

    1 Rung

    (2 Line)

    1 Rung

    (1 Line)

    Rung

    number

    Column

    Rung

    or

    Line

    Selected

    instruction

    Select block

    Instruction menu bar

    Instruction

    properties

  • 55

    1

    11

    1. Select Menu

    2

    22

    2. Select instruction

    3

    33

    3. Click to arrange

    3.3.43.3.43.3.43.3.4 Input ladder circuit

    To arrange instruction, select instruction from

    menu, and click place in ladder edit area where

    you arrange instruction. If there is no enough

    space, you cannot arrange the instruction.

    Delete existing instruction to make space

    enough to arrange the instruction.

    When you select ladder instruction, Instruction

    properties is displayed the right side of ladder

    editing area. You can set detail of instruction.

    When you right click in ladder editing area, following menu is displayed.

    Duplicate Block The same block as a current block is created.

    Delete Block Delete current block.

    Close Block Close window of current block.

    Copy All Instructions Copy all the instruction in each Rung/Line.

    Paste Paste object of clipboard.

    Select All Objects Select all instructions of current block.

    Show Rung Comm