1
1 General
FCS/W portable test kit is used to test main characteristic of BT2 & BT3 series air circuit breaker. It
tests tripping characteristic of breaker by simulating signal to intelligent controller of breaker. It has
many testing functions, for example three class protection.
2 Attentions
Read this manual carefully before using and maintenance, in order to use this test kit safely.
Warning
——This kit must operated and maintained by specialized staff.
——Cut off the power before moving or breaking the wire.
——Do not use the power that exceed the rated value (this test kit's rated voltage is AC230V),
otherwise it will burnt down.
——Connect the test wire correctly before testing, do not hot swapping.
——Move this test kit carefully.
2
3 Group Part
Connecting line
Supply line Testing line B
Testing line A1 Testing line A2 Testing line A3
Suitable for BT2-2000-6300 Suitable for BT2-1600 Suitable for BT3
Upper cover (Internally putting testing accessories)
Touch screen man-machine
Supply switch
Testing interface1
Testing interface2
USB interface
3
4 Technical Parameter
Auxiliary Supply
Work Voltage AC230V±10%
Frequency 50Hz
Maximum Power Loss 30W
Test kit output
Supply
Controller Work Voltage DC24V±5%
Maximum Output Current 200mA
Analog Signal
Accuracy ±3%
Frequency 50Hz
Range 20mV ~ 9V(RMS)
Tripping time measuring
Accuracy
≤0.5s ±5ms
>0.5s ±1%
Resolution Ratio 1ms
Range 0 ~ 3000s
Work Temperature -10℃ ~ +50℃
Storage Temperature -20℃ ~ +60℃
Dimension 327mm(L)×282mm(W)×218mm(H)
4
5 Testing Function
Breaker Type BT2 BT3
Controller Type L25 M25 P25 M26 H26
P26
EA35 EP35 EQ35 EG35 EN35
EA36 EP36 EQ36 EG36 EN36
Senior Testing
Automatic Testing
Long Time Delay
√ √ √ √ √ √ √
Short Time Delay
√ √ √ √ √ √ √
Instantaneous √ √ √ √ √ √ √
Manual Testing
Long Time Delay
√ √ √ √ √ √ √
Short Time Delay
√ √ √ √ √ √ √
Instantaneous √ √ √ √ √ √ √
Grounding Fault
× × × √ √ × √
Current -Unbalance
× × ○ × ○ ○ ○
MCR √ √ √ √ √ √ √
ZSI × ○ ○ ○ ○ ○ ○
Simple Testing
Long Time Delay
√ √ √ √ √ √ √
Short Time Delay
√ √ √ √ √ √ √
Instantaneous √ √ √ √ √ √ √
Grounding Fault
× × × √ √ × √
Supply Testing √ √ √ √ √ √ √
Note:
"√": Controller has this function; test kit can test this item.
"○": Only the controller having this function is tested by test kit.
"×": Controller haven't this function, don't be tested by test kit.
5
6 Connecting
Testing line and connecting type are determined by controller type. Testing interface and position are
different from controller type. Please connect by the following.
6.1 BT2-1600 Connecting Way
Fig 6.1
10
7 Operation & Use
7.1 Start & Close
When the test wire is correctly connected, switch on the
AC230V power; turn on the test kit switch, man-machine
interface light on, and welcome interface shows after a
few seconds.
After the test, cut off the power first, and then disconnect
the test wire.
Fig 7.1 Welcome Screen
7.2 Function Menu
Click the "NEXT" button in the welcome screen and the
function menu shows, and showing the following options:
—— FUNCTION TEST: various function tests including the three
section protection
—— POWER TEST: self-power supply test
—— COPY SETTING VALUE: Copy the setting value from one
controller to another
—— SAVE RECORD TO U DISK: transfer the test record into
USB Disk
—— UPDATE FROM U DISK:Update software From U Disk
Fig 7.2 Function Menu
7.3 Function Test
Click the function test at function menu, the test kit will
reads and shows the intelligent controller parameter (Fig
7.3). Then click the "NEXT" button to start test (Fig 7.4):
—— SIMPLE TEST: test the long-time-delay,
short-time-delay, instantaneous and ground fault by controller test interface
—— SENIOR TEST: input the simulate signal from the controller
transformer input terminal for the various function tests including the three section protection, there are two test ways: automatic test and manual test (Fig 7.5)
Fig 7.5 Automatic/Manual Test
Fig 7.3 Circuit Breaker Parameters
Fig 7.4 Test Mode
11
7.3.1 Simple Test
Select "SIMPLE TEST" to enter the "CONFIGURE
SIMPLE TEST PARAMETERS" screen (Fig 7.6); Select
the test phase: A, B, C, N, G; Then select the type of trip:
TRIP, NOT TRIP.
In the "CONFIGURE SIMPLE TEST PARAMETERS"
screen, click "NEXT" to enter simple test screen(Fig 7.7),
to set the size of the test current by clicking △ ▽, click
"START" to perform a simple test, the test results and
test status will real-time display on the screen (Fig 7.8).
After the test is complete, click "NEXT" to save this test
result, click "SAVE" to complete this test to save the txt
file. Test file name with the date of the test, the test
results on the same day will be saved in the same file,
and different tests to distinguish specific test time (Fig
7.9).
Note: After exiting the test or the end of the test, press
the clear light button on the controller of the circuit
breaker.
Fig 7.6 Configure Simple Test
Parameters
Fig 7.7 Simple Test Screen
Fig 7.8 Simple Test Result
Fig 7.9 Test File Save
12
7.3.2 Senior Test
7.3.2.1 Automatic Test
Select the "SENIOR TEST" to enter automatic test and
manual test selection interface (Fig 7.5), select the
"AUTOMATIC TEST" to enter "CONFIGURE
PROTECTION PARAMETERS" interface (Fig 7.10)
Attention: automatic test is available for the controller
with test interface, and the protection parameters are
special designed. It may different from the tested
controller; the parameter will be return to original after the
test.
Click the "NEXT" button at "CONFIGURE PROTECTION
PARAMETERS" interface (Fig 7.11), click the needed
protection type, Fig 7.12 is the situation that three section
protection test function put in.
After configured the protection type, click "NEXT" button
to enter the test alert interface (Fig 7.13), test interface
shows and test begins after confirming (Fig 7.14).
Automatic test interface shows test current, time and
status of each protection, tests are separated by the
selected protection type, if the status bar shows the
following status:
—— INITIALIZING :simulating the test signal
—— TESTING :Simulated test signal send to controller, begins
test
—— PASSED:This kind of protection be in good condition
—— FAILED:This kind of protection function failed
Click the "NEXT" button to show file name of the test (Fig
7.15), click "SAVE" button to save the file.
Attention: the test date is the test file name, the same
test result saved in the same txt file, differentiated by
specific test time.
Fig 7.15 Save File
Fig 7.10 Configure Protection
Parameters
Fig 7.11 Configure Protection Type
Fig 7.12 Configure Protection Type
Fig 7.13 Alert Screen
Fig 7.14 Automatic Test Screen
13
7.3.2.2 Manual Test
Click "SENIOR TEST" button to enter the manual test,
automatic test selection (Fig 7.5), click "MANUAL TEST"
into "CONFIGURE MANUAL TEST PARAMETERS" (Fig
7.16).
Click the symbol ▽ behind the "PROTECTION TYPE"
at "CONFIGURE MANUAL TEST PARAMETERS"
selection interface, and protection type selection shows
(Fig 7.17), click the type to be tested.
Attention: for manual test, there are two conditions for
the controller that with test interfaces or not.
1) For the controller with test interface, the test kit will
close other protection functions that may affect the test
for certain functions, other protection functions will
resume after the test finished and quit.
2) For the controller without test interface, set the
controller function parameters correctly before the test.
Click "CURRENT" button, input the suitable current
according to the tested controller protection parameters
(Fig 7.18). Click "CONFIRM" finish the input.
Attention: for the controller with test interface, there is
"MINIMUM CURRENT" limitation, the current input
should not less than the minimum current. The minimum
current limitation differs from the controller type and test
protection type. There is no limitation for the controller
without interface. Besides, correct result can only gained
through inputting suitable current for manual test.
Click the symbol ▽ behind "PHASE SELECTION" and
shows phase selection menu (Fig 7.19), select the phase
to be tested.
Fig 7.16 Configure Manual Test
Parameters
Fig 7.17 Protection Type
Fig 7.18 Current Setting
Fig 7.19 Phase Selection
14
Click the "NEXT" button to enter alert interface (Fig 7.20)
after inputting the parameters, and test begins after
confirming (Fig 7.21).
Manual test interface shows the protection type of the
test, test current, time and status, if the status bar shows
the following status in the test:
—— INITIALIZING: simulating the test signal
—— TESTING: Simulated test signal send to controller, begins
test
—— STOPPED: Test finished
—— SIGNAL UPLOAD PASSED: ZSI function test normal
—— SIGNAL UPLOAD FAILED: ZSI function test abnormal
Click the "NEXT" button to show file name of the test (Fig
7.15), click "SAVE" button to save the file.
Attention: the test date is the test file name, the same
test result saved in the same txt file, differentiated by
specific test time.
ZSI function test instruction:
The tested controller sends the ZSI signal from the lower
grade to the upper grade. This test simulates the
situation that breaker's short-time delay fault occurs, user
should input a current that make the controller's
short-time delay acts to the test kit for ZSI test, when the
controller checked the fault current reaches the
short-time delay action value, instantaneous protection
will take the place of short-time delay protection, and
sends the ZSI signal to the test kit. If the ZSI functions
well, test kit shows "SIGNAL UPLOAD PASSED",
otherwise shows "SIGNAL UPLOAD FAILED"
Attention: the result will also shows "SIGNAL UPLOAD
FAILED" if the ZSI current input is less than the
short-time delay act value of the controller. This should
not be seen as ZSI abnormal; user should input the
correct current value to test again according to the
instruction before.
Fig 7.20 Alert Screen
Fig 7.21 Long-time Manual Test
15
7.4 Power Test
Click the "POWER TEST" button to enter power test alert
interface (Fig 7.22), and power test interface (Fig 7.23)
shows after confirming, if the status bar shows the
following status in the test:
—— TESTING: Power input the controller, start power test.
—— PASSED: Controller's self-power supply functions well.
—— FAILED: Controller's self-power supply test failed.
Click the "NEXT" button to show file name of the test (Fig 7.15),
click "SAVE" button to save the file.
Attention: the test date is the test file name, the same
test result saved in the same txt file, differentiated by
specific test time.
Fig 7.22 Alert Screen
Fig 7.23 Power Test
7.5 Save File
Click the "SAVE FILE" button at function menu to enter
alert interface (Fig 7.24), make sure the U DISK is
correctly plugged into the test board before saving the
test file into U DISK.
Attention: user should bring your own U DISK.
Fig 7.24 Alert Screen
7.6 Copy Setting Value
When copy setting value, just connect the test line B, test
line A1, A2, A3 can be disconnected. Click the "copy
setting value" button at function menu to enter setting
value read/write interface, this function can perform
read/write operation of the setting value of controller.
——READ SETTING VALUE: Click "READ SETTING
VALUE" button to read the setting value of long time
delay, short time delay, instantaneous and grounding of a
controller. "WRITE SYNCH.IN FILE SUCCEED" appears
if it read successfully, the test kit will save the setting
value till the next reading operation, setting value which
correspond to the specification of the controller saved in
the test kit will be displayed on upside of the
interface.(Fig 7.25)
——WRITE SETTING VALUE: Click "WRITE SETTING
VALUE" button, the test kit will write the setting value
Fig 7.25 Write Synch.ini File Succeed
Fig 7.26 Write Setting Value Succeed
16
saved into the controller connected at present. "WRITE
SETTING VALUE SECCEED" appears on the downside
of the interface if write successfully.(Fig 7.26)
NOTE: The controller performing copy setting value
operation should be the same specification; otherwise it
cannot run properly.
8 Maintenance
8.1 Replace the Fuse
1. Turn off the power switch, pluck the plug.
2. Pry upward of the fuse stand in power switch module with screwdriver (Fig 8.1), take out
the fuse stand.
3. Replace the fuse in fuse stand with suitable fuse (3A).
4. Push the fuse stand into the groove of the power switch slightly.
5. Confirm the installation is reliable, connect the power, turn on the power switch, and touch
screen light on normally.
Fig 8.1
8.2 Clean the touch screen
1. Turn off the power switch, pull the plug and test wire.
2. Wipe the touch screen softly with special LCD cleaner.
17
8.3 Change the test wire
The test wire is for the test kit's exclusive use, prohibit user privately restructure and
manufacture, contact with us if necessary.
8.4 Maintain
Do not dismount this product optionally, contact with us if any fault occurs.
8.5 Software Update
Insert U disk, then select "UPDATE FROM U DISK" to update test kit's software in the
"FUNCTION MENU" screen.