ELECTRICAL SYSTEM
DESIGN OF GARDEN
PROJECT AT BELHAVEN,
KOWDIAR
Presented by:
Nithya Susan Varghese
Guided by:
Prof M.K. Giridharan
Overview
Introduction
Proposed project
Connected Load
Calculation of Connected Load
Design of Distribution Board
Current Status and Work to be completed.
2
Electrical System Design
• Electrical system design is the design of electrical systems.
• Simple systems can be created by one person. Large systems require
large teams of people, simulation software and many paper and
electronic records.
• The design should assure proper functioning of the installation.
• The design should provide safety.
3
Electrical System Design For
High Rise Buildings
• High – rise buildings are buildings having 5 floors and above, or
having a height of 15m and above.
• They normally refer to occupancy for:
General offices
Commercial establishments
Hotels /Condominiums
4
Design Concept
• For all building construction the owner must first have a
concept for the new design, and then the architect or
designer can produce a set of building plans.
• An electrical design goes through several important stages
or development.
• Every electrical design has unique requirements,
depending upon the scope of the project. The project
scope is determined by the customers’ requirements and
the type of structure.
5
HIGH RISE BUILDING POWER SUPPLY
REQUIREMENTS:
1. General Lighting & Power
light for general illumination, seeing tasks, decorative features, hallways and stairways, others
power for appliances and office machines
2. Heating, Ventilation & Air-conditioning (HVAC) System
air-conditioning for temperature control
blowers and fans ventilation
heaters for humidity control
3. Transport System
elevators and escalators
conveyors, dumbwaiters, others
4. Water Pumps
potable and non-potable water supply
water sprinkle (fire suppression)
pumps / drainage
sewage ejectors
5. Communication System
PABX telephone system
Intercom
6
6. Automatic Doors
entrance and exit for pedestrians
garage and freight
7. Central Computer System
CPU and peripherals
Terminals
8. Auxiliaries
intrusion and hold-up control system
fire fighting & alarm system
background music and paging
sound reinforcement and video facilities
noise masking and acoustics, others
7
Proposed Project
• The proposed building “Garden Project” at Belhaven Road, Kowdiar is a 10 storeyed building. It includes a cellar for parking purpose, and 10 floors of which 2 floors are for commercial purpose, 1 for parking and the remaining for residential purpose. It has a total plinth area of 4948.34 sq. m.
8
Site Plan
9
Section
10
Cellar
11
Ground
12
First Floor
13
Second Floor
14
Third Floor
15
Fourth Floor
16
Fifth Floor
17
Terrace Floor
18
Mezzanine
19
Machine Room
20
Connected Load
DEFINITION :The sum of the continuous power
ratings of all load-consuming apparatus connected
to an electric power distribution system or any part
thereof.
Connected load for electricity is the maximum
amount of wattage that is allocated to a building.
Calculation of Connected Load is done by
engineers from the utility from which the
connection is taken.
21
Description Area of the residential building (sq-m)
35 45 55 85 140
Light points 7 8 10 12 17
Ceiling fan 2-2 3-2 4-3 5-4 7-5
6A sockets 2 3 4 5 7
16A sockets - 1 2 3 4
Call Bell - - 1 1 1
Description Socket Outlets
6A 16A
Bed rooms 2-3 1
Living rooms 2-3 2
Kitchen 1 2
Dining room 2 1
Garage 1 1
For Refrigerator - 1
For Air Conditioner - 1
Verandah 1 for every 10 sq m -
Bathrooms 1 1 22
Min no. of socket outlets
Min no. of points to be provided on the basis of plinth area
Units of Electrical Energy Consumed
by common Domestic
Appliances/Equipment
ELECTRICAL APPLIANCES WATTAGE RATING
Incandescent Bulb 25W,60W,100W
Fluorescent Tube light (4feet) 40W
Fan 60W
Air Conditioner (1-1.5 ton) 1500-2500W
Refrigerator 100W
Mixer/Blender/Juicer 450W
Toaster 800W
Oven 450-700W
Electric kettle 1000/2000W
Iron 450/700W
Geyser(1.5-2 litre) 3000W
Vacuum Cleaner 700-750W
23
ELECTRICAL APPLIANCES WATTAGE RATING
Washing Machine 325W
Television 60-120W
Computer 120-600W
Radio 15W
Stereo System 50W
CFL 15W
24
Fifth floor
25
Electrical Notations
26
Calculation of Connected Load
(Fifth Floor)
Sl
No
Room Space FL
Tube
4 feet
(40W)
CFL
light
(15W)
6A
socket
(60W)
16A
socket
(500W
)
25A
Socket
(2500
W)
Exhaust
Fan
(60W)
Ceiling
Fan
(60W)
Chandelier
(200W)
Total
CL of
room
space
1 Living Room +
Balcony 2 4 1 2 2 1 1520
2 Dining Room
+Balcony 1 4 2 2 2 1340
3 a Bedroom 1 +
Balcony 1 4 3 2 1 1 3840
b Dressing Room 1 2 1 90
c Toilet 1 2 1 1 590
4a Bedroom 2 1 4 3 2 1 1 3840
b Toilet 2 2 1 1 590
5a Bedroom 3 1 3 3 2 1 1 3825
b Toilet 3 2 1 1 590
6a Kitchen+ Work
Area 1 3 2 3 1 1 1825
b Toilet 1 1 75
7 Foyer 2 30
TOTAL=18155W 27
Distribution Board
• Total No: of light points= 66
(No. of light points= light+fan+6A socket+exhaust fan)
• No: of light circuits= 66/8 = 8.25 ~9
• Total No: of power points = 19
• No: of power circuits = 19/2 = 9.5~ 10
• Total No: of sub-circuits = 10+9 = 19
• Therefore we choose 8 way 3 phase DB which has 24 (i.e. 3x8) sub-circuits.
28
Calculation of Connected Load
(Third Floor) Sl
No
Room Space FL
Tube
4 feet
(40W)
CFL
light
(15W)
6A
socket
(60W)
16A
socket
(500W)
25A
Socket
(2500
W)
Exhaust
Fan
(60W)
Ceiling
Fan
(60W)
Chandelier
(200W)
Total
CL of
room
space
1 Living Room+ Balcony 1 10 3 1 1 2 1 3690
2 Toilet 4 3 1 168
3 Hall 1 4 6 1 1 2 1 3920
4 Family Living+Dining 1 7 3 1 1 2 3445
5 Foyer 4 60
6 Kitchen 2 2 5 3 1 1 1 4530
7 Work Area 1 2 2 1 1 750
8 Store 1 1 55
9 Serva t’s Roo 1 2 1 195
10 Serva t’s Toilet 1 1 75
11a Bedroom +Balcony 1 5 2 5 1 1 5295
b Dressing Room 1 1 75
c Toilet 2 1 1 1 650
TOTAL=22908W 29
Calculation of Connected Load
(Fourth Floor) Sl
N
o
Room Space FL
Tube
4 feet
(40W)
Bell
(60W)
CFL
light
(15W
)
6A
socket
(60W)
16A
socket
(500W
)
25A
Socket
(2500
W)
Exhaust
Fan
(60W)
Ceiling
Fan
(60W)
Chandelier
(200W)
Total
CL of
room
space
1 Family Living Room 3 1 9 1 6 1 2 1 6195
2a Bedroom1 +Balcony 1 5 1 6 1 2 5795
b Dressing Room 1 15
c Toilet 2 2 1 1090
3a Bedroom 2 1 1 6 1 2 5720
b Dressing Room 2 30
c Bathroom 2 2 1 1090
4a Bedroom 3 1 7 1 3 1 2 4325
b Dressing 3 45
c Toilet 3 2 1 1105
5a Bedroom 4 1 3 1 8 1 2 6765
b Dressing Room 2 30
c Toilet 2 2 1 1090 30
Sl
N
o
Room Space FL
Tube
4 feet
(40W)
Bell
(60W)
CFL
light
(15W)
6A
socket
(60W)
16A
socket
(500W)
25A
Socket
(2500
W)
Exhaust
Fan
(60W)
Ceiling
Fan
(60W)
Chandelier
(200W)
Total CL
of room
space
6 Yoga Room 2 4 2 2 1260
7 Internal stairs 1 15
8 Lift(10) 10000
TOTAL=34555W
31
Calculation Of Common
Connected Load
Sl.no Room Space FL light 4 ft
(40W)
CFL light
(15W)
Total connected
load
1 Parking (Second floor) 55 825
2 Lobby 24(6 floors)
360
3 Stairway 12(7 floors) 480
4 Terrace floor 12 180
5 Mezzanine 6 90
6 Machine room 4 60
7 Lift(10) 10000
8 Stretcher lift(18) 15000
8 External lights 20 300
9 Water lifting pump 5000
32
Current Status
• Connected Load of all floors (except commercial) has been calculated.
• Distribution Board of one apartment has been decided.
• Supplementary drawings were completed.
Work to be Completed
DB of commercial floors and Common CL, Cabling, Metering Panel
Design, Transformer Design, Emergency Power Supply, Earthing and
extensive electrical drawings have to be completed.
33
References
• Electrical Systems Design by M.K. Giridharan