27
Dr. Sarasij Das 1

Detecting Synchrophasors Computed Over Fault/Switching Transients

Embed Size (px)

DESCRIPTION

 

Citation preview

Page 1: Detecting Synchrophasors Computed Over Fault/Switching Transients

Dr. Sarasij Das

1

Page 2: Detecting Synchrophasors Computed Over Fault/Switching Transients

This Presentation is based on the paper

Sarasij Das, and Tarlochan Sidhu, "Detecting Synchrophasors

Computed Over Fault/Switching Transients", IET Generation,

Transmission & Distribution,

http://digital-library.theiet.org/content/journals/10.1049/iet-gtd.2013.0493

2

Page 3: Detecting Synchrophasors Computed Over Fault/Switching Transients

Brief overview of Wide Area Measurement

Systems (WAMS)

Proposed algorithm

Conclusions

3

Page 4: Detecting Synchrophasors Computed Over Fault/Switching Transients

4

Page 5: Detecting Synchrophasors Computed Over Fault/Switching Transients

Voltage/current waveforms sinusoid in nature

Phasor = representation of sinusoid in complex

plane

Phasors estimated by measuring

- magnitudes

- phase angles

Page 6: Detecting Synchrophasors Computed Over Fault/Switching Transients
Page 7: Detecting Synchrophasors Computed Over Fault/Switching Transients

Traditional SCADA monitoring slow

One complete SCADA polling may take 2-10 s

Measurements are not time synchronized

Phase angle measurement no possible

Not suitable for system dynamics monitoring

7

Page 8: Detecting Synchrophasors Computed Over Fault/Switching Transients

WAMS = PMU based monitoring systems

Synchrophasor = phasor + GPS time tagging

Synchrophasor = magnitude & phase angles

Synchrophasors used in system dynamics

monitoring

8

Page 9: Detecting Synchrophasors Computed Over Fault/Switching Transients

Control Center

Voltage, Current Synchrophasors

9

Page 10: Detecting Synchrophasors Computed Over Fault/Switching Transients

IEEE standard C37.118.1-2011[2] specifies

accuracy requirements for synchrophasors

IEEE standard C37.118.2-2011[3] specifies

message formats for communication data packets

IEEE standard C37.244-2013 [4] describes functional requirements for PDCs

10

Page 11: Detecting Synchrophasors Computed Over Fault/Switching Transients

11

Page 12: Detecting Synchrophasors Computed Over Fault/Switching Transients

12

Page 13: Detecting Synchrophasors Computed Over Fault/Switching Transients

Context Synchrophasor validations mostly happen in

PDCs

Validation often offline and time consuming

Lack of samples makes validation difficult in PDCs

Lack of algorithms to compute synchrophasor quality at PMU

13

Page 14: Detecting Synchrophasors Computed Over Fault/Switching Transients

Motivation

Fault/switching transient synchrophasors

computed over pre and post fault/switching

samples

Unusable in applications

Not easy to detect from values

1( ) 89.998

2

1.0045( 1) 90.1340

2

X k

X k

14

Page 15: Detecting Synchrophasors Computed Over Fault/Switching Transients

Motivation

No existing Algorithm

However, Algorithms [1][5] can be used

Existing Algorithms [1][5] make wrong detections in

presence of harmonics, decaying dc

15

Page 16: Detecting Synchrophasors Computed Over Fault/Switching Transients

Proposed low complexity algorithm to detect

fault/switching transient synchrophasor

16

Page 17: Detecting Synchrophasors Computed Over Fault/Switching Transients

17

Page 18: Detecting Synchrophasors Computed Over Fault/Switching Transients

Suggested to apply on current signals

Success Rate

18

X=Xm [1+ksx u(t-ts)]cos(ωot +ksa u(t-ts))

Page 19: Detecting Synchrophasors Computed Over Fault/Switching Transients

19

Performance

during

Oscillations

Page 20: Detecting Synchrophasors Computed Over Fault/Switching Transients

20

Performance

in presence of

missing samples

Page 21: Detecting Synchrophasors Computed Over Fault/Switching Transients

21

Page 22: Detecting Synchrophasors Computed Over Fault/Switching Transients

22

Page 23: Detecting Synchrophasors Computed Over Fault/Switching Transients

23

Page 24: Detecting Synchrophasors Computed Over Fault/Switching Transients

Proposed algorithm performs satisfactorily

- during nominal and off-nominal frequencies

- in presence of harmonics, decaying DC

- in presence of oscillations, ramping

- in presence of a number of missing samples

- for estimation windows 2.5 cycles or

greaterPlease see the paper for additional results

24

Page 25: Detecting Synchrophasors Computed Over Fault/Switching Transients

Algorithm has been proposed to tag fault/switching

transient synchrophasors

Proposed algorithm performs satisfactorily in various

scenarios

25

Page 26: Detecting Synchrophasors Computed Over Fault/Switching Transients

1. “Synchronized phasor measurements and their applications”, by Arun G. Phadke, John Samuel Thorp

2. “IEEE Standard for Synchrophasor Measurements for Power Systems”, IEEE C37.118.1-2011, (Revision of IEEE Std. C37.118-2005)

3. “IEEE Standard for Synchrophasor Data Transfer for Power Systems”, IEEE C37.118.2-2011

4. “IEEE Guide for Phasor Data Concentrator Requirements for Power System Protection, Control, and Monitoring”, IEEE Std C37.244-2013

5. Sodhi, Ranjana, S. C. Srivastava, and S. N. Singh. "A transient monitor to reflect the quality of synchrophasors." Power and Energy Society General Meeting, 2010 IEEE. IEEE, 2010.

26

Page 27: Detecting Synchrophasors Computed Over Fault/Switching Transients

27