13
Chapter 8 VOLTAGE STABILITY The small signal and transient angle stability was discussed in Chapter 6 and 7. Another stability issue which is important, other than angle stability, is voltage stability. Voltage stability can be defined as the ability of the system to retain system voltages within acceptable limits when subjected to disturbance. If the disturbance is large then it is called as large-disturbance voltage stability and if the disturbance is small it is called as small-signal voltage stability [1]-[2]. Voltage stability can be a local phenomenon where only a particular bus or buses in a particular region have voltage stability issue and this may not affect the entire system. Voltage stability can be a global phenomenon where many of the system buses experience voltage stability problems which can also trigger angle stability problems and hence can affect the entire system. Some of the voltage stability problems can start as a local problem and escalate to global stability problem. Voltage stability of a system can be analysed either by static analysis or dynamic analysis. In static analysis the system is assumed to be in steady state and hence instead of taking the DAE of the system only algebraic equations are considered. This type of analysis is suitable for small-disturbances in the system. For large disturbances the DAE are solved and the system response over a certain period of time is observed. It is important that for voltage stability the loads should be properly modelled as each type of load will affect the system voltage stability in a different way. Similarly the tap changing transformers, shunt or series reactive power compensators, generator reactive power limits, line charging capacitance should be included in the system representation to get an accurate picture of voltage stability. 8.1 Basic Concept of Voltage Stability To understand the concept of voltage stability let there be a two bus system with one end being sending end and the other being receiving end as shown in Fig. 8.1. Let the voltage of sending end be S V and that of receiving end be R V . The transmission 8.1

Chapter8

Embed Size (px)

Citation preview

Page 1: Chapter8

Chapter 8 VOLTAGE STABILITY

The small signal and transient angle stability was discussed in Chapter 6 and 7.

Another stability issue which is important, other than angle stability, is voltage

stability. Voltage stability can be defined as the ability of the system to retain system

voltages within acceptable limits when subjected to disturbance. If the disturbance is

large then it is called as large-disturbance voltage stability and if the disturbance is

small it is called as small-signal voltage stability [1]-[2]. Voltage stability can be a

local phenomenon where only a particular bus or buses in a particular region have

voltage stability issue and this may not affect the entire system. Voltage stability can

be a global phenomenon where many of the system buses experience voltage stability

problems which can also trigger angle stability problems and hence can affect the

entire system. Some of the voltage stability problems can start as a local problem and

escalate to global stability problem.

Voltage stability of a system can be analysed either by static analysis or

dynamic analysis. In static analysis the system is assumed to be in steady state and

hence instead of taking the DAE of the system only algebraic equations are

considered. This type of analysis is suitable for small-disturbances in the system. For

large disturbances the DAE are solved and the system response over a certain period

of time is observed. It is important that for voltage stability the loads should be

properly modelled as each type of load will affect the system voltage stability in a

different way. Similarly the tap changing transformers, shunt or series reactive power

compensators, generator reactive power limits, line charging capacitance should be

included in the system representation to get an accurate picture of voltage stability.

8.1 Basic Concept of Voltage Stability

To understand the concept of voltage stability let there be a two bus system with

one end being sending end and the other being receiving end as shown in Fig. 8.1. Let

the voltage of sending end be SV and that of receiving end be RV . The transmission

8.1

Page 2: Chapter8

line is represented by a short line mode with impedance TZ T . If a load of

impedance LZ L is connected at the receiving end.

Fig. 8.1: Single line diagram of two bus system

The magnitude of current in the transmission line is given as, taking the sending end

voltage as reference,

2 2

0

T T LZ Z 2 cosS S

L T L T L T L

V VI

Z Z Z Z

(8.1)

The receiving end voltage magnitude is then defined as

2 2T LZ Z 2 cos

S LR

T L T L

V ZV

Z Z

(8.2)

The real and reactive power consumed by the load is given as

2

2 2

S L

T L

V Z

Z Z

cos

2 cos

LL

T L T L

PZ Z

(8.3)

2

2 2

S L

T L

V Z

Z Z

sin

2 cos

LL

T L T L

QZ Z

(8.4)

SV TZ

RV

LZ

I

8.2

Page 3: Chapter8

Let the transmission line impedance be taken as 0.25TZ pu , neglecting

resistance as usually the reactance to resistance ratio is quite high in a transmission

network. Let the sending end voltage be 1 pu . The real and reactive power of the load

can be increased by decreasing the load impedance LZ maintaining a constant power

factor say 0.8. The receiving end voltage is plotted in Fig. 8.2 with varying real power

consumed by the load, with the parameters mentioned above. This curve is called as

P-V curve.

Knee Point

Fig. 8.2: P-V curve

It can be observed from P-V curve that as the load increases from no load

condition the receiving voltage starts dropping form initial no load voltage of 1 pu .

The increase in the current I due to decrease in the load impedance LZ is more than

the drop in the receiving end voltage magnitude and hence the real power

consumed by the load will increase. The maximum real power, 1

RV

pu , will be delivered

to the load when L TZ Z . Once operating point reaches the maximum power point or

critical point or knee point of the curve any further decrease in load impedance, to

8.3

Page 4: Chapter8

increase the load, will result in further drop in the receiving end voltage and

simultaneously the real power consumed by the load will also decrease. This is

because after knee point the drop in the voltage is more than the increase in the line

current leading to a decrease in the real power consumed by the load.

8.1.1 Effect of load type on voltage stability

Fig. 8.3: P-V curve with stable and unstable operating points

Consider the P-V curve shown in Fig. 8.3. For a given real power consumed by

the load there are two possible receiving end voltages. As can be seen from operating

points A and B from Fig. 8.3, for a real power of 0.6 pu there are two receiving end

voltages of 0.85 pu and 0.20 pu , approximately. If the load is a constant MVA load

then the operating point A is stable where as the operating point B is unstable. In fact

for a constant MVA load any operating point below the knee point is unstable. This

phenomenon can be understood from the Fig. 8.3. Suppose due to some disturbance

the operating point moves from point A to C. At the operating point C the real power

is more than the real power at operating point A. Since, the load is constant MVA

8.4

Page 5: Chapter8

load the current will decrease and therefore the operating point move back from C to

A. The operating point may not stop immediately at operating point A but may

oscillate around it and will settle down with enough damping. Hence, the operating

point A is a stable operating point. Now consider the operating point B. Again let the

operating point move to point D due to disturbance. At operating point D the real

power is less than that at operating point B. Since the load is a constant MVA load at

operating point D the current increases, as compared to operating point B, which leads

to a further voltage drop and further increase in the line current. This phenomenon

continues till the voltage at the receiving end becomes zero and hence called as

voltage collapse. Therefore, the operating point B is unstable operating point. It can

be observed from P-V curve that the curve above knee point has negative

that is the change in real power and voltage are in opposite direction, for a increase in

power voltage decreases and for a decrease in power voltage increases. The curve

below the knee point has positive and at the knee point is zero.

/RdV dP

/R LdV dP

L

L/RdV dP

Fig. 8.4: P-V curve for different power factor loads

8.5

Page 6: Chapter8

Figure 8.4 show the P-V curves for loads with different power factors. It can be

observed from the figure that as the load power factor moves from lagging to leading

the knee point is shifted towards higher real power and higher voltage. This shows

that the voltage stability improves as the power factor moves from lagging to leading

loads.

Fig. 8.5: Q-V curve for different load real powers

Just as the load real power was plotted with respect to the receiving end voltage

for varying load impedances, the load reactive power variation with respect to the

receiving end voltage, with load real power being constant, can also be plotted.

Figure 8.5 shows the variation of receiving end voltage with variation in load reactive

power for three different real power loads. Again the locus of knee point is marked.

On the curve left of the locus of the knee point the reactive power and the voltage

move in opposite directions that is is negative and this region is unstable.

The curve on the right of the locus of the knee point the reactive power and the

voltage move in the same direction and hence is positive and this region is

stable. In the unstable region even if reactive power compensation is done through

shunt capacitance at the receiving end bus, the voltage of the receiving end bus will

/ RdQ dV

/ RdQ dV

8.6

Page 7: Chapter8

not improve. One way of finding the voltage stability is to check the sensitivity of

each bus voltage with respect to the reactive power injected at that bus and if the

sensitivity is positive then it means the operating point is stable and is on the right

side of the locus of the knee points in Fig. 8.4 and if it is negative then it is on the left

side. This stable region and unstable region are only applicable to constant MVA

loads. In case of constant impedance and constant current loads the loads interact with

the system and settle at a new operating point as there is no requirement of constant

MVA.

8.2 Static Analysis

In static analysis [3] of voltage stability the snapshots of the entire system at

different instants is considered and at each instant the system is assumed to be in

steady state that the rates of changes of the dynamic variables are zero. Hence, instead

of considering all the differential algebraic equations only algebraic power balance

equations are considering assuming that the system is in steady state. At each instant

whether the system is voltage stable or not and also how far the system is from

instability can be assessed. There are two methods for assessing whether system is

voltage stable or not. They are sensitivity analysis [4] and modal analysis [5].

8.2.1 Sensitivity analysis

The power balance equations are taken assuming that the system is in steady

state. For, , assuming bus number 1 is a slack bus, the real power balance

equation is given as

2,......,i n

1

( ) cos 0n

Gi Di i i j ij i j ijj

P P V VV Y

(8.5)

The reactive power balance equations are taken at the load buses, for

1, 2,......,g gi n n n

8.7

Page 8: Chapter8

(8.6) 1

( ) sin 0n

Di i i j ij i j ijj

Q V VV Y

The linearized form of equations (8.5) and (8.6) is given as

2 2

1 1g g

n nP PV

n nQ QV

n n

P

P J J

Q VJ J

Q V

or

PJ

Q V

(8.7)

The matrix is the Jacobian matrix used in Newton-Raphson load flow analysis. For

constant real power is zero hence from equation (8.7)

J

P

1

P PVJ J V

(8.8)

Substituting (8.8) in (8.7) an simplifying leads to

(8.9) 1

QV P PV QQ J J J J V

Let, 1

R QV P PV QJ J J J J , then

1RV J Q (8.10)

The diagonal elements of the matrix 1RJ represents the sensitivity of the voltage

with respect to the reactive power injected at that bus. This is nothing but the slope of

8.8

Page 9: Chapter8

Q-V curve given in Fig. 8.4. Hence, if the V-Q sensitivity of an ith bus is positive then

the system is voltage stable and if it is negative then the system is voltage unstable. A

small positive value of sensitivity indicates that the system is more voltage stable and

if the sensitivity is small with negative value then the system is highly voltage

unstable.

8.2.2 Modal Analysis

Voltage stability can also be estimated by the eigen values and eigen vectors of

the matrix . The matrix can be expressed in terms of right and left eigen vector

matrices as

1RJ

,

RJ

RJ (8.11)

1RJ 1 (8.12)

Where, is a diagonal matrix with eigen values along its diagonal. Substituting

(8.12) in (8.10) lead to, noting that

I

1 1RV J Q Q (8.13)

1V Q

Q

(8.14)

Let, v V and , then or q 1v q

1i

i

v iq

(8.15)

Where, is the ith bus modal voltage and is the modal reactive power. If the

eigen value is positive then the system is voltage stable. The larger the eigen value

with positive sign the better the stability and if the eigen value has very small positive

value then it is very close to

iv iq

0i , that is the critical point or knee point, and hence

8.9

Page 10: Chapter8

very close to instability. If the eigen value is negative then the system is voltage

unstable.

8.3 Dynamic Analysis

The voltage stability of a system can also be assessed by the transient simulation

over a period of time [3]. The differential algebraic equations, given in (8.16), of the

system should be solved through numerical methods and the transient simulation

should be carried out for few minutes to completely observer the interaction of

generators, static loads, dynamic loads, tap changing transformer etc.

( , , , )

( , )

0 ( , , )

d q

d q

d q

x f x I V u

I h x V

g x I V

-

-

-

=

=

=

(8.16)

The transient simulation should be done for different fault scenarios and the

system behaviour should be observed. If the system voltages are restored to

acceptable values after fault clearing then the system is voltage stable if not the

system is voltage unstable. The simulations needs to be done for few minutes because

the time constant involved can be very small like generator exciter or very large like

induction motors or tap changing transformers. For voltage stability assessment load

modelling is important hence both static and dynamic loads should be modelled. The

reactive power compensating devices like series / shunt capacitor and static VAr

compensator should also be included in the system model.

8.3.1 Small-disturbance analysis

Small-disturbance (signal) analysis can also be used for voltage stability

analysis. The DAE given in equation (8.16) can be represented as

( , ( , ), , )

0 ( , ( , ), , )

x f x h x V V u

g x h x V V l

=

= (8.17)

8.10

Page 11: Chapter8

Where, in (8.17) is a constant representing the loading of the system, as given in

(8.18)

0

0

1

1

D D

D D

P P

Q Q

(8.18)

0 , 0D DP Q are the real and reactive power loads at all the load buses for base case.

The idea is to increase the loading factor in steps and at each step find the eigen

values of the linearized system given in (8.17). The linearized form of the system

given in (8.17) is given as

0

Vf f f fx x u

x V u

Vg g gx

x V

qq

qq

é ùDé ù¶ ¶ ¶ ¶ê úê úD = D + + Dê úê ú D¶ ¶ ¶ ¶ë û ë ûé ùDé ù¶ ¶ ¶ ê úê ú= D + ê úê ú D¶ ¶ ¶ë û ë û

(8.19)

Here, 1 1 1

T T

nV V V V V n n hence the linearized form shown in

(8.19). On further simplification of (8.19) the following expression can be derived

1

sysJ

sys

f f f g g g fx x u

x V V x u

fJ x u

u

q q

-é ùé ù é ù é ù é ù é ù¶ ¶ ¶ ¶ ¶ ¶ ¶ê úê ú ê ú ê ú ê ú ê úD = - D + Dê úê ú ê ú ê ú ê ú ê ú¶ ¶ ¶ ¶ ¶ ¶ ¶ë û ë û ë û ë û ë ûê úë ûé ù¶ê ú= D + Dê ú¶ë û

(8.20)

The matrix sysJ is called as the system Jacobian and is different from the load

flow Jacobian. The eigen value of the system Jacobian sysJ for different loading

conditions, obtained by varying the loading factor , are computed. If a one of the

eigen value becomes zero or a pair of complex conjugate eigen values are on the

imaginary axis for a particular loading factor then the load corresponding to the

8.11

Page 12: Chapter8

loading factor is a critical load at which the system becomes voltage unstable. If a

complex conjugate pair of eigen values are on imaginary axis then that operating

point is called as Hopf-bifurcation point. If one of the eigen value is on the origin then

that operating point is called as saddle node point. The saddle node bifurcation point

represents the knee point. Hopf-bifurcation point occurs at a load which is less than

the load at which the saddle node bifurcation point occurs. Hence, due to the

dynamics involved the system can become voltage unstable even before the operating

point reaches the knee point.

8.12

Page 13: Chapter8

8.13

References

1. IEEE, Special publication 90TH0358-2-PWR, Voltage stability of power

systems: concepts, analytical tools, and industry experience, 1990.

2. CIGE task force 38-02-10, Modelling of voltage collapse including dynamic

phenomena, 1993.

3. G. K. Morison, B. Gao, and P. Kundur, “Voltage stability evaluation using

static and dynamic approaches,” IEEE PES summer meeting, July 2-16, 1992,

Seattle, Washington.

4. N. Flatabo, R. Ognedal and T. Carlsen, “Voltage stability conditions in a

power transmission system calculated by sensitivity methods,” IEEE Trans.,

Vol. PWRS-5, No. 4, pp. 1286-1293, November.

5. 1990G. K. Morison, B. Gao, and P. Kundur, “Voltage stability evaluation

using modal analysis,” IEEE Trans., Vol. PWRS-7, No. 4, pp. 1529-1542,

November 1992.