45
EE 369 POWER SYSTEM ANALYSIS Lecture 14 Power Flow Tom Overbye and Ross Baldick 1

power system analysis PPT

Embed Size (px)

Citation preview

Page 1: power system analysis PPT

EE 369POWER SYSTEM ANALYSIS

Lecture 14Power Flow

Tom Overbye and Ross Baldick

1

Page 2: power system analysis PPT

AnnouncementsRead Chapter 12, concentrating on sections

12.4 and 12.5. Homework 12 is 6.43, 6.48, 6.59, 6.61,

12.19, 12.22, 12.20, 12.24, 12.26, 12.28, 12.29; due Tuesday Nov. 25.

2

Page 3: power system analysis PPT

400 MVA15 kV

400 MVA15/345 kV

T1

T2800 MVA345/15 kV

800 MVA15 kV

520 MVA

80 MW40 Mvar

280 MVAr 800 MW

Line 3 345 kV

Line

2

Line

1345 kV 100 mi

345 kV 200 mi

50 mi

1 4 3

2

5

Single-line diagram

The N-R Power Flow: 5-bus Example

3

Page 4: power system analysis PPT

Bus Type|V| per unit

θdegrees

PG

perunit

QG

perunit

PL

perunit

QL

perunit

QGmax

perunit

QGmin

perunit

1 Slack 1.0 0 0 0

2 Load 0 0 8.0 2.8

3 Constant voltage

1.05 5.2 0.8 0.4 4.0 -2.8

4 Load 0 0 0 0

5 Load 0 0 0 0

Table 1. Bus input data

Bus-to-Bus

Rper unit

Xper unit

Gper unit

Bper unit

MaximumMVA

per unit

2-4 0.0090 0.100 0 1.72 12.0

2-5 0.0045 0.050 0 0.88 12.0

4-5 0.00225 0.025 0 0.44 12.0

Table 2. Line input data

The N-R Power Flow: 5-bus Example

4

Page 5: power system analysis PPT

Bus-to-Bus

R perunit

Xperunit

Gc

perunit

Bm

perunit

MaximumMVA

per unit

MaximumTAP

Settingper unit

1-5 0.00150 0.02 0 0 6.0 —

3-4 0.00075 0.01 0 0 10.0 —

Table 3. Transformer input data

Bus Input Data Unknowns

1 |V1 |= 1.0, θ1 = 0 P1, Q1

2 P2 = PG2-PL2 = -8

Q2 = QG2-QL2 = -2.8

|V2|, θ2

3 |V3 |= 1.05

P3 = PG3-PL3 = 4.4

Q3, θ3

4 P4 = 0, Q4 = 0 |V4|, θ4

5 P5 = 0, Q5 = 0 |V5|, θ5

Table 4. Input data and unknowns

The N-R Power Flow: 5-bus Example

5

Page 6: power system analysis PPT

Let the Computer Do the Calculations! (Ybus Shown)

6

Page 7: power system analysis PPT

Ybus Details

02321 YY

2424 24

1 1 0.89276 9.919640.009 0.1

Y j per unitR jX j

2525 25

1 1 1.78552 19.839320.0045 0.05

Y j per unitR jX j

24 2522

24 24 25 25

1 12 2B BY j j

R jX R jX

288.0

272.1)83932.1978552.1()91964.989276.0( jjjj

unitperj 624.845847.284590.2867828.2

Elements of Ybus connected to bus 2

7

Page 8: power system analysis PPT

Here are the Initial Bus Mismatches

8

Page 9: power system analysis PPT

And the Initial Power Flow Jacobian

9

Page 10: power system analysis PPT

Five Bus Power System Solved

slack

One

Two

ThreeFourFiveA

MVA

A

MVA

A

MVA

A

MVA

A

MVA

1.000 pu 0.974 pu

0.834 pu

1.019 pu

1.050 pu 0.000 Deg -4.548 Deg

-22.406 Deg

-2.834 Deg

-0.597 Deg

395 MW 114 Mvar

520 MW 337 Mvar

800 MW 280 Mvar

80 MW 40 Mvar

10

Page 11: power system analysis PPT

37 Bus Example Design Case

slack

Metropolis Light and Power Electric Design Case 2SLACK345

SLACK138

RAY345

RAY138

RAY69

FERNA69A

MVA

DEMAR69

BLT69

BLT138

BOB138

BOB69

WOLEN69

SHI MKO69

ROGER69

UI UC69

PETE69HI SKY69

TI M69

TI M138

TI M345

PAI 69

GROSS69

HANNAH69

AMANDA69

HOMER69

LAUF69

MORO138

LAUF138

HALE69

PATTEN69

WEBER69

BUCKY138SAVOY69

SAVOY138

J O138 J O345

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

1.03 pu

1.02 pu

1.03 pu

1.03 pu

1.01 pu

1.00 pu1.01 pu

1.00 pu1.02 pu

1.01 pu

1.00 pu

1.01 pu1.01 pu

1.01 pu1.01 pu

1.02 pu

1.00 pu

1.00 pu

1.02 pu

0.99 pu

0.99 pu

1.00 pu

1.02 pu

1.00 pu1.01 pu

1.01 pu

1.00 pu 1.00 pu

1.01 pu

1.02 pu 1.02 pu

1.02 pu 1.03 pu

A

MVA

1.02 pu

A

MVA

A

MVA

LYNN138

A

MVA

1.02 pu

A

MVA

1.00 pu

A

MVA

System Losses: 10.70 MW 220 MW 52 Mvar

12 MW 3 Mvar

20 MW 12 Mvar

124 MW 45 Mvar

37 MW 13 Mvar

12 MW 5 Mvar

150 MW 0 Mvar

56 MW 13 Mvar

15 MW 5 Mvar

14 MW 2 Mvar

38 MW 3 Mvar

45 MW 0 Mvar

25 MW 36 Mvar

36 MW 10 Mvar

10 MW 5 Mvar

22 MW 15 Mvar

60 MW 12 Mvar

20 MW 28 Mvar

23 MW 7 Mvar

33 MW 13 Mvar 15.9 Mvar 18 MW

5 Mvar

58 MW 40 Mvar

60 MW 19 Mvar

14.2 Mvar

25 MW 10 Mvar

20 MW 3 Mvar

23 MW 6 Mvar 14 MW

3 Mvar

4.9 Mvar

7.3 Mvar

12.8 Mvar

28.9 Mvar

7.4 Mvar

0.0 Mvar

55 MW 25 Mvar

39 MW 13 Mvar

150 MW 0 Mvar

17 MW 3 Mvar

16 MW -14 Mvar

14 MW 4 Mvar

KYLE69A

MVA

11

Page 12: power system analysis PPT

Good Power System Operation• Good power system operation requires that there be

no “reliability” violations (needing to shed load, have cascading outages, or other unacceptable conditions) for either the current condition or in the event of statistically likely contingencies:• Reliability requires as a minimum that there be no

transmission line/transformer limit violations and that bus voltages be within acceptable limits (perhaps 0.95 to 1.08)

• Example contingencies are the loss of any single device. This is known as n-1 reliability.

12

Page 13: power system analysis PPT

Good Power System Operation

• North American Electric Reliability Corporation now has legal authority to enforce reliability standards (and there are now lots of them).

• See http://www.nerc.com for details (click on Standards)

13

Page 14: power system analysis PPT

Looking at the Impact of Line Outages

slack

Metropolis Light and Power Electric Design Case 2SLACK345

SLACK138

RAY345

RAY138

RAY69

FERNA69A

MVA

DEMAR69

BLT69

BLT138

BOB138

BOB69

WOLEN69

SHI MKO69

ROGER69

UI UC69

PETE69HI SKY69

TI M69

TI M138

TI M345

PAI 69

GROSS69

HANNAH69

AMANDA69

HOMER69

LAUF69

MORO138

LAUF138

HALE69

PATTEN69

WEBER69

BUCKY138SAVOY69

SAVOY138

J O138 J O345

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

1.03 pu

1.02 pu

1.03 pu

1.03 pu

1.01 pu

1.00 pu1.01 pu

1.00 pu1.02 pu

1.01 pu

1.00 pu

1.01 pu1.01 pu

1.01 pu1.01 pu

1.02 pu

1.01 pu

1.00 pu

1.02 pu

0.90 pu

0.90 pu

0.94 pu

1.01 pu

0.99 pu1.00 pu

1.00 pu

1.00 pu 1.00 pu

1.01 pu

1.01 pu 1.02 pu

1.02 pu 1.03 pu

A

MVA

1.02 pu

A

MVA

A

MVA

LYNN138

A

MVA

1.02 pu

A

MVA

1.00 pu

A

MVA

System Losses: 17.61 MW 227 MW 43 Mvar

12 MW 3 Mvar

20 MW 12 Mvar

124 MW 45 Mvar

37 MW 13 Mvar

12 MW 5 Mvar

150 MW 4 Mvar

56 MW 13 Mvar

15 MW 5 Mvar

14 MW 2 Mvar

38 MW 9 Mvar

45 MW 0 Mvar

25 MW 36 Mvar

36 MW 10 Mvar

10 MW 5 Mvar

22 MW 15 Mvar

60 MW 12 Mvar

20 MW 40 Mvar

23 MW 7 Mvar

33 MW 13 Mvar 16.0 Mvar 18 MW

5 Mvar

58 MW 40 Mvar

60 MW 19 Mvar

11.6 Mvar

25 MW 10 Mvar

20 MW 3 Mvar

23 MW 6 Mvar 14 MW

3 Mvar

4.9 Mvar

7.2 Mvar

12.8 Mvar

28.9 Mvar

7.3 Mvar

0.0 Mvar

55 MW 32 Mvar

39 MW 13 Mvar

150 MW 4 Mvar

17 MW 3 Mvar

16 MW -14 Mvar

14 MW 4 Mvar

KYLE69A

MVA

80%A

MVA

135%A

MVA

110%A

MVA

Opening one line (Tim69-Hannah69) causes overloads. This would not be Allowed.

14

Page 15: power system analysis PPT

Contingency Analysis

Contingencyanalysis providesan automaticway of lookingat all the statisticallylikely contingencies. Inthis example thecontingency setis all the single line/transformeroutages

15

Page 16: power system analysis PPT

Power Flow And Design• One common usage of the power flow is to determine

how the system should be modified to remove contingencies problems or serve new load• In an operational context this requires working with the

existing electric grid, typically involving re-dispatch of generation.

• In a planning context additions to the grid can be considered as well as re-dispatch.

• In the next example we look at how to remove the existing contingency violations while serving new load.

16

Page 17: power system analysis PPT

An Unreliable Solution:some line outages result in overloads

slack

Metropolis Light and Power Electric Design Case 2SLACK345

SLACK138

RAY345

RAY138

RAY69

FERNA69A

MVA

DEMAR69

BLT69

BLT138

BOB138

BOB69

WOLEN69

SHI MKO69

ROGER69

UI UC69

PETE69HI SKY69

TI M69

TI M138

TI M345

PAI 69

GROSS69

HANNAH69

AMANDA69HOMER69

LAUF69

MORO138

LAUF138

HALE69

PATTEN69

WEBER69

BUCKY138SAVOY69

SAVOY138

J O138 J O345

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

1.02 pu

1.01 pu

1.02 pu

1.03 pu

1.01 pu

1.00 pu1.01 pu

1.00 pu1.02 pu

1.01 pu

1.00 pu

1.01 pu1.01 pu

1.01 pu1.01 pu

1.02 pu

0.99 pu

1.00 pu

1.02 pu

0.97 pu

0.97 pu

0.99 pu

1.02 pu

1.00 pu1.01 pu

1.01 pu

1.00 pu 1.00 pu

1.01 pu

1.02 pu 1.02 pu

1.02 pu 1.03 pu

A

MVA

1.02 pu

A

MVA

A

MVA

LYNN138

A

MVA

1.02 pu

A

MVA

1.00 pu

A

MVA

System Losses: 14.49 MW 269 MW 67 Mvar

12 MW 3 Mvar

20 MW 12 Mvar

124 MW 45 Mvar

37 MW 13 Mvar

12 MW 5 Mvar

150 MW 1 Mvar

56 MW 13 Mvar

15 MW 5 Mvar

14 MW 2 Mvar

38 MW 4 Mvar

45 MW 0 Mvar

25 MW 36 Mvar

36 MW 10 Mvar

10 MW 5 Mvar

22 MW 15 Mvar

60 MW 12 Mvar

20 MW 40 Mvar

23 MW 7 Mvar

33 MW 13 Mvar 15.9 Mvar 18 MW

5 Mvar

58 MW 40 Mvar

60 MW 19 Mvar

13.6 Mvar

25 MW 10 Mvar

20 MW 3 Mvar

23 MW 6 Mvar 14 MW

3 Mvar

4.9 Mvar

7.3 Mvar

12.8 Mvar

28.9 Mvar

7.4 Mvar

0.0 Mvar

55 MW 28 Mvar

39 MW 13 Mvar

150 MW 1 Mvar

17 MW 3 Mvar

16 MW -14 Mvar

14 MW 4 Mvar

KYLE69A

MVA

96%A

MVA

Case now has nine separate contingencies having reliability violations(overloads in post-contingency system).

17

Page 18: power system analysis PPT

A Reliable Solution:no line outages result in overloads

slack

Metropolis Light and Power Electric Design Case 2SLACK345

SLACK138

RAY345

RAY138

RAY69

FERNA69A

MVA

DEMAR69

BLT69

BLT138

BOB138

BOB69

WOLEN69

SHI MKO69

ROGER69

UI UC69

PETE69HI SKY69

TI M69

TI M138

TI M345

PAI 69

GROSS69

HANNAH69

AMANDA69HOMER69

LAUF69

MORO138

LAUF138

HALE69

PATTEN69

WEBER69

BUCKY138SAVOY69

SAVOY138

J O138 J O345

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

1.03 pu

1.01 pu

1.02 pu

1.03 pu

1.01 pu

1.00 pu1.01 pu

1.00 pu1.02 pu

1.01 pu

1.00 pu

1.01 pu1.01 pu

1.01 pu1.01 pu

1.02 pu

1.00 pu

0.99 pu

1.02 pu

0.99 pu

0.99 pu

1.00 pu

1.02 pu

1.00 pu1.01 pu

1.01 pu

1.00 pu 1.00 pu

1.01 pu

1.02 pu 1.02 pu

1.02 pu 1.03 pu

A

MVA

1.02 pu

A

MVA

A

MVA

LYNN138

A

MVA

1.02 pu

A

MVA

A

MVA

System Losses: 11.66 MW 266 MW 59 Mvar

12 MW 3 Mvar

20 MW 12 Mvar

124 MW 45 Mvar

37 MW 13 Mvar

12 MW 5 Mvar

150 MW 1 Mvar

56 MW 13 Mvar

15 MW 5 Mvar

14 MW 2 Mvar

38 MW 4 Mvar

45 MW 0 Mvar

25 MW 36 Mvar

36 MW 10 Mvar

10 MW 5 Mvar

22 MW 15 Mvar

60 MW 12 Mvar

20 MW 38 Mvar

23 MW 7 Mvar

33 MW 13 Mvar 15.8 Mvar 18 MW

5 Mvar

58 MW 40 Mvar

60 MW 19 Mvar

14.1 Mvar

25 MW 10 Mvar

20 MW 3 Mvar

23 MW 6 Mvar 14 MW

3 Mvar

4.9 Mvar

7.3 Mvar

12.8 Mvar

28.9 Mvar

7.4 Mvar

0.0 Mvar

55 MW 29 Mvar

39 MW 13 Mvar

150 MW 1 Mvar

17 MW 3 Mvar

16 MW -14 Mvar

14 MW 4 Mvar

KYLE69A

MVA

Kyle138A

MVA

Previous case was augmented with the addition of a 138 kV Transmission Line

18

Page 19: power system analysis PPT

Generation Changes and The Slack Bus

• The power flow is a steady-state analysis tool, so the assumption is total load plus losses is always equal to total generation• Generation mismatch is made up at the slack bus

• When doing generation change power flow studies one always needs to be cognizant of where the generation is being made up• Common options include “distributed slack,” where the

mismatch is distributed across multiple generators by participation factors or by economics.

19

Page 20: power system analysis PPT

Generation Change Example 1

slack

SLACK345

SLACK138

RAY345

RAY138

RAY69

FERNA69

A

MVA

DEMAR69

BLT69

BLT138

BOB138

BOB69

WOLEN69

SHI MKO69

ROGER69

UI UC69

PETE69

HI SKY69

TI M69

TI M138

TI M345

PAI 69

GROSS69

HANNAH69

AMANDA69

HOMER69

LAUF69

MORO138

LAUF138

HALE69

PATTEN69

WEBER69

BUCKY138SAVOY69

SAVOY138

J O138 J O345

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

0.00 pu

-0.01 pu

0.00 pu

0.00 pu

0.00 pu

-0.03 pu-0.01 pu

0.00 pu0.00 pu

0.00 pu

-0.03 pu

-0.01 pu0.00 pu

0.00 pu0.00 pu

0.00 pu

0.00 pu

0.00 pu

0.00 pu

-0.002 pu0.00 pu

0.00 pu

0.00 pu

0.00 pu0.00 pu

0.00 pu

0.00 pu 0.00 pu

0.00 pu

0.00 pu 0.00 pu

0.00 pu 0.00 pu

A

MVA

-0.01 pu

A

MVA

A

MVA

LYNN138

A

MVA

0.00 pu

A

MVA

0.00 pu

A

MVA

162 MW 35 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

-157 MW -45 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 2 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW

0 Mvar

0 MW 3 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 4 Mvar

0 MW 0 Mvar

0 MW 0 Mvar -0.1 Mvar 0 MW

0 Mvar

0 MW 0 Mvar 0 MW

0 Mvar

-0.1 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar 0 MW

0 Mvar

-0.1 Mvar

0.0 Mvar

-0.1 Mvar

-0.2 Mvar

0.0 Mvar

0.0 Mvar

0 MW 51 Mvar

0 MW 0 Mvar

0 MW 2 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

Display shows “Difference Flows” between original 37 bus case, and case with a BLT138 generation outage; note all the power change is picked up at the slack

Slack bus

20

Page 21: power system analysis PPT

Generation Change Example 2

slack

SLACK345

SLACK138

RAY345

RAY138

RAY69

FERNA69

A

MVA

DEMAR69

BLT69

BLT138

BOB138

BOB69

WOLEN69

SHI MKO69

ROGER69

UI UC69

PETE69

HI SKY69

TI M69

TI M138

TI M345

PAI 69

GROSS69

HANNAH69

AMANDA69

HOMER69

LAUF69

MORO138

LAUF138

HALE69

PATTEN69

WEBER69

BUCKY138SAVOY69

SAVOY138

J O138 J O345

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

0.00 pu

-0.01 pu

0.00 pu

0.00 pu

0.00 pu

-0.03 pu0.00 pu

0.00 pu0.00 pu

0.00 pu

-0.03 pu

-0.01 pu-0.01 pu

0.00 pu0.00 pu

0.00 pu

0.00 pu

0.00 pu

0.00 pu

-0.003 pu0.00 pu

0.00 pu

0.00 pu

0.00 pu0.00 pu

0.00 pu

0.00 pu 0.00 pu

0.00 pu

0.00 pu 0.00 pu

0.00 pu 0.00 pu

A

MVA

0.00 pu

A

MVA

A

MVA

LYNN138

A

MVA

0.00 pu

A

MVA

0.00 pu

A

MVA

0 MW 37 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

-157 MW -45 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW

0 Mvar

42 MW -14 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

99 MW -20 Mvar

0 MW 0 Mvar

0 MW 0 Mvar -0.1 Mvar 0 MW

0 Mvar

0 MW 0 Mvar 0 MW

0 Mvar

-0.1 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar 0 MW

0 Mvar

0.0 Mvar

0.0 Mvar

-0.1 Mvar

-0.2 Mvar

-0.1 Mvar

0.0 Mvar

19 MW 51 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

0 MW 0 Mvar

Display repeats previous case except now the change in generation is picked up by other generators using a “participation factor” (change is shared amongst generators) approach.

21

Page 22: power system analysis PPT

Voltage Regulation Example: 37 Buses

Display shows voltage contour of the power system

slack

SLACK345

SLACK138

RAY345

RAY138

RAY69

FERNA69

A

MVA

DEMAR69

BLT69

BLT138

BOB138

BOB69

WOLEN69

SHI MKO69

ROGER69

UI UC69

PETE69

HI SKY69

TI M69

TI M138

TI M345

PAI69

GROSS69

HANNAH69

AMANDA69HOMER69

LAUF69

MORO138

LAUF138

HALE69

PATTEN69

WEBER69

BUCKY138SAVOY69

SAVOY138

J O138 J O345

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVAA

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

A

MVA

1.03 pu

1.01 pu

1.02 pu

1.03 pu

1.01 pu

1.00 pu1.00 pu

0.99 pu1.02 pu

1.01 pu

1.00 pu

1.01 pu1.01 pu

1.01 pu1.01 pu

1.02 pu

1.00 pu

1.00 pu

1.02 pu

0.997 pu0.99 pu

1.00 pu

1.02 pu

1.00 pu1.01 pu

1.00 pu

1.00 pu 1.00 pu

1.01 pu

1.02 pu 1.02 pu

1.02 pu 1.03 pu

A

MVA

1.02 pu

A

MVA

A

MVA

LYNN138

A

MVA

1.02 pu

A

MVA

1.00 pu

A

MVA

219 MW 52 Mvar

21 MW 7 Mvar

45 MW 12 Mvar

157 MW 45 Mvar

37 MW 13 Mvar

12 MW 5 Mvar

150 MW 0 Mvar

56 MW 13 Mvar

15 MW 5 Mvar

14 MW 2 Mvar

38 MW 3 Mvar

45 MW 0 Mvar

58 MW 36 Mvar

36 MW 10 Mvar

0 MW 0 Mvar

22 MW 15 Mvar

60 MW 12 Mvar

20 MW 9 Mvar

23 MW 7 Mvar

33 MW 13 Mvar 15.9 Mvar 18 MW

5 Mvar

58 MW 40 Mvar 51 MW

15 Mvar

14.3 Mvar

33 MW 10 Mvar

15 MW 3 Mvar

23 MW 6 Mvar 14 MW

3 Mvar

4.8 Mvar

7.2 Mvar

12.8 Mvar

29.0 Mvar

7.4 Mvar

20.8 Mvar

92 MW 10 Mvar

20 MW 8 Mvar

150 MW 0 Mvar

17 MW 3 Mvar

0 MW 0 Mvar

14 MW 4 Mvar

1.010 pu 0.0 Mvar

System Losses: 11.51 MW

22

Automatic voltage regulation system controls voltages.

Page 23: power system analysis PPT

Real-sized Power Flow Cases

• Real power flow studies are usually done with cases with many thousands of buses• Outside of ERCOT, buses are usually grouped into various

balancing authority areas, with each area doing its own interchange control.

• Cases also model a variety of different automatic control devices, such as generator reactive power limits, load tap changing transformers, phase shifting transformers, switched capacitors, HVDC transmission lines, and (potentially) FACTS devices.

23

Page 24: power system analysis PPT

Sparse Matrices and Large Systems

• Since for realistic power systems the model sizes are quite large, this means the Ybus and Jacobian matrices are also large.

• However, most elements in these matrices are zero, therefore special techniques, sparse matrix/vector methods, are used to store the values and solve the power flow: • Without these techniques large systems would be

essentially unsolvable.

24

Page 25: power system analysis PPT

Eastern Interconnect Example

Peoria

Rockford

Nor th Chi cago

Abbot t Labs Par kU. S. N Tr ai ni ng

O l d El m

Deerf i el d

Nor thbr ook

Lakehurst

Waukegan

Zi on

G urnee

Anti och

Pl easant

Round Lake

Zi on (138 kV)

Lake Zur i ch

Lesthon

Apt aki si c

Buf fal o G r oove

Wheel i ng

Pr ospect Hei ght sPal at i ne

Ar l i ngton

M ount Pr ospect

Pr ospect

G ol f M i l l

Des Pl ai nes

El mhurst

I t asca

Garfi el d

Tol l w ay

W407 ( Fer mi )

Wi l son

Bar ri ngt on

Dundee

Si l ver Lake

Cherry Val ley

Wempl eton

Nelson

H-471 (NW Steel )

Paddock

Ponti ac Mi dpoint

Br ai dw ood

State Li ne

Shefi el d

Chi ave

Munster

St. J ohn

El ect r i c Junct i on

Pl ano

La Sal le

Lombard

Li sle

Col li ns

Dresden

Lockport

East Frankfort

Goodi ngs Grove

Li ber tyvi l l e345 kV

Li ber tyvi l l e138 kV

Lake George

Dunacr

Green Acres

Schahfer

Tower Rd

Babcock

Hei ghts

Prairie

Racine

Mi chi gan City

El wood

Dequi ne

Loui sa

East Mol i ne

Sub 91

Walcott

Davenport

Sub 92

Rock Crk.

Salem

GI LMAN

WATSEKA 17GODLND

ELPASO T

MI NON K T

OGLESBY

1556A TPOTTAWA T

OGLSBY M

OGLES; T

HENNEPI N

ESK TAP

LTV TP NLTV TP E

HENNE; T

LTV STL

PRI NC TP

PRI NCTN

RI CHLAN D

KEWAN IP

S ST TAP

GALESBRG

NORMA; BNORMA; R

R FAL; R

MONMO UTH

GALESBR5

KEWAN;

HALLOCK

CAT MO SSFARGO

SPNG BAY

E PEORIA

RSW EAST

PI ONEERC

RADN OR

CAT TAP

CAT SUB1

SB 18 5

E MO LI NE

SB 43 5

SB 112 5

KPECKTP5

SO. SUB 5

SB 85 5

SB 31T 5

SB 28 5

SB 17 5

SB 49 5

SB 53 5

SB 47 5SB 48 5

SB A 5

SB 70 5

SB 79 5

SB 88 5

SB 71 5

BVR CH65 BVR CH 5 ALBAN Y 5

YO RK 5

SAVANNA5

GALEN A 5

8TH ST. 5

LO RE 5

SO .GVW.5

SALEM N 5

ALBAN Y 6

GARDE;

H71 ;BTH71 ; B

H71 ; R

R FAL; B

NELSO; R

NELSO;RT

STERL; B

D IXON;BT

MECCORD3

CO RD O;

Quad Ci ties

LEECO;BP

Byron

MARYL; B

MENDO; T

STI LL;RT

B427 ;1T

LANCA; R

PECAT; B

FREEP;

ELERO;BT ELERO;RT

LENA ; RLENA ; B

H440 ;RT

H440 ; R

STEWA; B

H445 ;3B

Roscoe

Pi erpont

S PEC; R

FO RD A; R

Harl em

Sand Park

NWT 138

BLK 138

RO R 138

JAN 138

ALB 138

NOM 138

DAR 138

HLM 138POT 138 MRE 138

COR 138 D IK 138

BCH 138

Sabrooke

Bl awkhawk

Al pine

E. Rockford

Charl es

Bel vi dere

B465

Marengo

WI B 138

WBT 138ELK 138

NLG 138

NLK GV T

SGR CK5

BRLGTN1

BRLGTN2

SGR CK4

UNI VRSTY

UN IV NEU

WHTWTR5

WHTWTR4

WHTWTR3

SUN 138

VI K 138

LBT 138

TI CHI GNPARIS WE

ALBERS-2

C434

El mw ood

Ni l es

Evanst on

Devon

Rose Hi l l

Skoki e

Nor thw est

Dr i ver

Ford City

Hayford

Sawyer

Nort hri dge

Hi ggi nsDes Pl ai nes

Fr ankl i n Par k

O ak Par k

Ri dgel and

D799

G al ew ood

Y450

Congr ess

Rockw el lCl ybour n

Quarry

Lasal l e

State

Cr osby

Ki ngsbur y

Jeff erson

Ohio

Taylor

Cl int

Dekov

Fi sk

Crawford

Uni versi ty

Ri ver

Z-494

Washi ngton ParkHarbor

Cal umet

Hegewi sch

Z-715

South Holl and

Evergreen

Damen

Wall ace

Beverl y

G3851

Z-524G3852

Wi ldwood

Harvey

Green Lake

Sand Ri dge

Chicago H ei ghts

Burnham

Lansi ng

F-575

F-503Glenw ood

Bl oomPark ForestMatteson

Country Club H i ll s

Al t G E

Natoma

Woodhil lU. Park

Moken

M cHenr y

Cr yst al Lake

Al gonqui n

Hunt l ey

P Val

Woodstock

Blue I sl and

G394

Al si p

Crestwood

K-319 #1

K-319 #2

Bradl ey

Kankakee

Davi s Creek

Wi lmington

Wi lton Center

Frankfort

N Len

Brigg

O akbr ook

Dow ners Groove

Woodri dge

W604

W603

Bol ingbrook

Sugar Grove

W. De Kal b G l i dden

N Aurora

El gi n

Hanover

Spaul di ngBar t l et t

Hof fm an Estat es

S. Schaumberg

Tonne

LandmBusse

Schaumber g

How ar d

Berkel ey

Bel l w ood

La G r ange

Chur ch

Addi son

Nor diG l endal e

G l en El l yn

But te

Yor k Cent er

D775

Bedford Park

Cl earning

Sayre

Bri dgevi ew

Ti nley Park

Roberts

Pal osRomeo

Wi l l ow

Bur r Ri dge

Jo456

J 322

South El gi n Wayne

West Chi cago

Aur or a

Warr envi l l e

W507

Montgomery

Oswego

Wolf Creek

Frontenac

W600 ( Naper vi l l e)

W602

W601J307

Sandw ich

Wat erman

J 323

Mason

J-371

J-375

J-339

Streator

Marseil l esLasal l e

N LASAL

Mendota

J370

Shore

Goose Lake

J-305

J-390J -326

Plainfi el d

J -332

Archer

Bell Road

Wi l l Co.

Hi ll crest Rockdale

Jol i et

Kendra

Crete

Upnor

LAKEVI EW

BAI N 4

Kenosha

SO MERS

ST RI TA

BI G BEN D

MUKWONGO

NED 138

NED 161

LAN 138

EEN 138

CASVI LL5

TRK RI V5

LIBERTY5

ASBURY 5

CN TRGRV5

JULIAN 5

MQO KETA5

E CALMS5

GR MND 5

DEWI TT 5

SBHYC5

SUB 77 5

SB 74 5SB 90 5

SB 78 5

DAVN PRT5

SB 76 5

SB 58 5

SB 52 5

SB 89 5

IPSCO 5

IPSCO 3

NEWPORT5

HWY61 5

WEST 5

9 SUB 5

TRI PP

Z-100Orlan

Kenda

MPWSPLI T

WYO MIN G5

MT VERN5

BERTRAM5

PCI 5

SB J I C 5

SB UI C 5

-0.40 deg

2.35 deg

-13. 3 deg -13. 4 deg

McCook

-1. 1 deg

1. 9 deg

0. 6 deg

93%B

MVA105%

B

MVA

Example, which models the Eastern Interconnectcontains about 43,000 buses. 25

Page 26: power system analysis PPT

Solution Log for 1200 MW OutageIn this example thelosss of a 1200 MWgenerator in NorthernIllinois was simulated. This caused a generation imbalancein the associated balancing authorityarea, which wascorrected by a redispatch of localgeneration.

26

Page 27: power system analysis PPT

Interconnected OperationPower systems are interconnected across

large distances. For example most of North America east of

the Rockies is one system, most of North America west of the Rockies is another.

Most of Texas and Quebec are each interconnected systems.

27

Page 28: power system analysis PPT

Balancing Authority AreasA “balancing authority area” (previously called a

“control area”) has traditionally represented the portion of the interconnected electric grid operated by a single utility or transmission entity.

Transmission lines that join two areas are known as tie-lines.

The net power out of an area is the sum of the flow on its tie-lines.

The flow out of an area is equal to total gen - total load - total losses = tie-line flow

28

Page 29: power system analysis PPT

Area Control Error (ACE)The area control error is a combination of:

the deviation of frequency from nominal, and the difference between the actual flow out of an area and

the scheduled (agreed) flow.That is, the area control error (ACE) is the difference

between the actual flow out of an area minus the scheduled flow, plus a frequency deviation component:

ACE provides a measure of whether an area is producing more or less than it should to satisfy schedules and to contribute to controlling frequency.

29

actual tie-line flow schedACE 10P P f

Page 30: power system analysis PPT

Area Control Error (ACE)The ideal is for ACE to be zero.Because the load is constantly changing, each

area must constantly change its generation to drive the ACE towards zero.

For ERCOT, the historical ten control areas were amalgamated into one in 2001, so the actual and scheduled interchange are essentially the same (both small compared to total demand in ERCOT).

In ERCOT, ACE is predominantly due to frequency deviations from nominal since there is very little scheduled flow to or from other areas.

30

Page 31: power system analysis PPT

Automatic Generation ControlMost systems use automatic generation

control (AGC) to automatically change generation to keep their ACE close to zero.

Usually the control center (either ISO or utility) calculates ACE based upon tie-line flows and frequency; then the AGC module sends control signals out to the generators every four seconds or so.

31

Page 32: power system analysis PPT

Power TransactionsPower transactions are contracts between

generators and (representatives of) loads.Contracts can be for any amount of time at any

price for any amount of power. Scheduled power transactions between balancing

areas are called “interchange” and implemented by setting the value of Psched used in the ACE calculation:ACE = Pactual tie-line flow – Psched + 10β Δf…and then controlling the generation to bring ACE

towards zero.32

Page 33: power system analysis PPT

“Physical” power Transactions

• For ERCOT, interchange is only relevant over asynchronous connections between ERCOT and Eastern Interconnection or Mexico.

• In Eastern and Western Interconnection, interchange occurs between areas connected by AC lines.

33

Page 34: power system analysis PPT

Three Bus Case on AGC:no interchange.Bus 2 Bus 1

Bus 3Home Area

266 MW133 MVR

150 MW

250 MW 34 MVR

166 MVR

133 MW 67 MVR

1.00 PU

-40 MW 8 MVR

40 MW -8 MVR

-77 MW 25 MVR

78 MW-21 MVR

39 MW-11 MVR

-39 MW 12 MVR

1.00 PU

1.00 PU

101 MW 5 MVR

100 MWAGC ONAVR ON

AGC ONAVR ON

Net tie-line flow is close to zero

Generationis automaticallychanged to matchchange in load

34

Page 35: power system analysis PPT

100 MW Transaction between areas in Eastern or Western

Bus 2 Bus 1

Bus 3Home Area

Scheduled Transactions

225 MW113 MVR

150 MW

291 MW 8 MVR

138 MVR

113 MW 56 MVR

1.00 PU

8 MW -2 MVR

-8 MW 2 MVR

-84 MW 27 MVR

85 MW-23 MVR

93 MW-25 MVR

-92 MW 30 MVR

1.00 PU

1.00 PU

0 MW 32 MVR

100 MWAGC ONAVR ON

AGC ONAVR ON

100.0 MW

Scheduled100 MWTransaction from Left to Right

Net tie-lineflow is now100 MW

35

Page 36: power system analysis PPT

PTDFsPower transfer distribution factors (PTDFs) show

the linearized impact of a transfer of power.PTDFs calculated using the fast decoupled

power flow B matrix:

1

Once we know we can derive the change in the transmission line flows to evaluate PTDFs.Note that we can modify several elements in ,in proportion to how the specified generators would par

θ B Pθ

P

ticipate in the power transfer. 36

Page 37: power system analysis PPT

Nine Bus PTDF Example

10%

60%

55% 64%

57%

11%

74%

24%

32%

A

G

B

C

D

E

I

F

H

300.0 MW 400.0 MW 300.0 MW

250.0 MW

250.0 MW

200.0 MW

250.0 MW

150.0 MW

150.0 MW

44%

71%

0.00 deg

71.1 MW

92%

Figure shows initial flows for a nine bus power system

37

Page 38: power system analysis PPT

Nine Bus PTDF Example, cont'd

43%

57% 13%

35% 20%

10%

2%

34%

34%

32%

A

G

B

C

D

E

I

F

H

300.0 MW 400.0 MW 300.0 MW

250.0 MW

250.0 MW

200.0 MW

250.0 MW

150.0 MW

150.0 MW

34%

30%

0.00 deg

71.1 MW

Figure now shows percentage PTDF flows for a change in transaction from A to I

38

Page 39: power system analysis PPT

Nine Bus PTDF Example, cont'd

6%

6% 12%

61% 12%

6%

19%

21%

21%

A

G

B

C

D

E

I

F

H

300.0 MW 400.0 MW 300.0 MW

250.0 MW

250.0 MW

200.0 MW

250.0 MW

150.0 MW

150.0 MW

20%

18%

0.00 deg

71.1 MW

Figure now shows percentage PTDF flows for a change in transaction from G to F

39

Page 40: power system analysis PPT

WE to TVA PTDFs

40

Page 41: power system analysis PPT

Line Outage Distribution Factors (LODFs)

• LODFs are used to approximate the change in the flow on one line caused by the outage of a second line– typically they are only used to determine the change

in the MW flow compared to the pre-contingency flow if a contingency were to occur,

– LODFs are used extensively in real-time operations,– LODFs are approximately independent of flows but

do depend on the assumed network topology.

41

Page 42: power system analysis PPT

Line Outage Distribution Factors (LODFs)

42

,

change in flow on line , due to outage of line .

pre-contingency flow on line ,

Estimates change in flow on line if outage on line were to occur.

l

k

l l k k

P lk

P kP LODF P

lk

Page 43: power system analysis PPT

Line Outage Distribution Factors (LODFs)

43

,

If line initially had 100 MW of flow on it,

and line initially had 50 MW flow on it,

and then there was an outage of line ,

if =0.1 then the increase in flow

on line after a continge

k

l

l k

k P

l P

k

LODF

l

,

ncy of line would be:

0.1 100 10 MW

from 50 MW to 60 MW.l l k k

k

P LODF P

Page 44: power system analysis PPT

Flowgates

• The real-time loading of the power grid can be assessed via “flowgates.”

• A flowgate “flow” is the real power flow on one or more transmission elements for either base case conditions or a single contingency– Flows in the event of a contingency are approximated

in terms of pre-contingency flows using LODFs.• Elements are chosen so that total flow has a

relation to an underlying physical limit.

44

Page 45: power system analysis PPT

Flowgates

• Limits due to voltage or stability limits are often represented by effective flowgate limits, which are acting as “proxies” for these other types of limits.

• Flowgate limits are also often used to represent thermal constraints on corridors of multiple lines between zones or areas.

• The inter-zonal constraints that were used in ERCOT until December 2010 are flowgates that represent inter-zonal corridors of lines.

45