7
International Journ Internat ISSN No: 245 @ IJTSRD | Available Online @ www Analysis of Active P Transform Thandar O 1 ME S Electrical Powe The Republi ABSTRACT Nowadays, active power flow should because voltage fluctuation occurred on conditions. Phase shifting transformer to control the active power flow in electricity transmission network. It reliability and can serve as an altern investments in overhead lines. The con power flow is achieved by adjusting th of the voltages at the PST terminals. In t kV AC transmission line is chosen for flow control. Two conditions, m minimum load conditions are conside study for active power flow control per selected line. Simulation of active pow PST model is carried out by using Ma Finally, according to simulation re voltages and active power depend pha revealed in this paper. Keywords: phase shifting transformer, changer, transmission line, phase shift power flow control I. INTRODUCTION Electric power is transported betw voltage levels of the electric g interconnected transmission lines. O transmission line decreases the secur system. When power flows between tw is a voltage drop and a phase angle diff the sending end and receiving end. So, t needs to control in order to achieve utilization of transmission lines capac efficiency of transmission can be impro FACTS device. Phase Shifting Transfor the FACTS families which can be us nal of Trend in Scientific Research and De tional Open Access Journal | www.ijtsr 56 - 6470 | Volume - 2 | Issue – 6 | Sep w.ijtsrd.com | Volume – 2 | Issue – 6 | Sep-Oct Power Flow Control with Phas mer in AC Transmission Line Oo 1 , Su Mon Myint 2 , Aye Khaing Zin 3 Student, 2 Lecturer, 3 Assistant Lecturer wer Department, Pyay Technological University ic of the Union of Myanmar, Pyay, Myanmar be controlled n various load (PST) is used n three phase can increase native to new ntrol of active he phase angle this paper, 230 r active power maximum and ered as a case rformance in a wer flow with atlab software. esults, system ase angles are r, on load tap t angle, active ween different grid through Overloading in rity of power wo nodes, there ferent between the power flow e the optimal city. Operating oved by using rmer is one of sed for power control in a network. Theref transformer is the first cho active power flow between tw the less expensive than the performs satisfactorily under For example, the PST can be a power flow according to the this reason, the PSTs are interconnection lines [1]. In interconnected power transmission lines do not ha receiver ends since the activ these lines does not flow in t times. The polarity of phas voltages at two regions of a network is very important be direction of the active corresponding ac transmission the polarity of phase angle b using OLTC. PSTs compen inserting, between its sending series voltage in quadrature voltages. This quadrature vol the PSTs terminals, a phase varies with the magnitude of [3]. The purpose of PST is usual flow over transmission lines. the direction of the power flo varying the phase shift. Alth control of power flowing th itself is still a function of the power flow can only be “shift” evelopment (IJTSRD) rd.com p – Oct 2018 2018 Page: 666 se Shifting fore, the phase-shifting oice for controlling the wo system areas as it is e FACTS devices, and steady-state conditions. used in order to impose contractual amount. For e usually installed on networks, certain ac ave definite sender and ve power conveyed by the same direction at all se shift between the an interconnected power ecause it determines the power flow in the n line [4]. PST can alter between the voltages by nsates for the drop by and its receiving ends, a with the line-to-ground ltage produces, between shift whose magnitude f the quadrature voltage lly the control of power Both the magnitude and ow can be controlled by hough PSTs enable the hrough a line, the flow e grid situation, and the ” [9].

Analysis of Active Power Flow Control with Phase Shifting Transformer in AC Transmission Line

  • Upload
    ijtsrd

  • View
    7

  • Download
    0

Embed Size (px)

DESCRIPTION

Nowadays, active power flow should be controlled because voltage fluctuation occurred on various load conditions. Phase shifting transformer PST is used to control the active power flow in three phase electricity transmission network. It can increase reliability and can serve as an alternative to new investments in overhead lines. The control of active power flow is achieved by adjusting the phase angle of the voltages at the PST terminals. In this paper, 230 kV AC transmission line is chosen for active power flow control. Two conditions, maximum and minimum load conditions are considered as a case study for active power flow control performance in a selected line. Simulation of active power flow with PST model is carried out by using Matlab software. Finally, according to simulation results, system voltages and active power depend phase angles are revealed in this paper. Thandar Oo | Su Mon Myint | Aye Khaing Zin "Analysis of Active Power Flow Control with Phase Shifting Transformer in AC Transmission Line" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-2 | Issue-6 , October 2018, URL: https://www.ijtsrd.com/papers/ijtsrd18593.pdf Paper URL: http://www.ijtsrd.com/engineering/electrical-engineering/18593/analysis-of-active-power-flow-control-with-phase-shifting-transformer-in-ac-transmission-line/thandar-oo

Citation preview

Page 1: Analysis of Active Power Flow Control with Phase Shifting Transformer in AC Transmission Line

International Journal of Trend in International Open Access Journal

ISSN No: 2456

@ IJTSRD | Available Online @ www.ijtsrd.com

Analysis of Active Power Flow Control Transformer

Thandar Oo1ME Student,

Electrical Power Department, Pyay Technological The Republic of the Union of Myanmar

ABSTRACT Nowadays, active power flow should be controlled because voltage fluctuation occurred on various load conditions. Phase shifting transformer (PST) is to control the active power flow in three phase electricity transmission network. It can increase reliability and can serve as an alternative to new investments in overhead lines. The control of active power flow is achieved by adjusting the phase angof the voltages at the PST terminals. In this paper, 230 kV AC transmission line is chosen for active power flow control. Two conditions, maximum and minimum load conditions are considered as a case study for active power flow control performance in a selected line. Simulation of active power flow with PST model is carried out by using Matlab software. Finally, according to simulation results, system voltages and active power depend phase angles are revealed in this paper. Keywords: phase shifting transformer, on load tap changer, transmission line, phase shift angle, active power flow control I. INTRODUCTION Electric power is transported between different voltage levels of the electric grid through interconnected transmission lines. Overloading in transmission line decreases the security of power system. When power flows between two nodes, there is a voltage drop and a phase angle different between the sending end and receiving end. So, the power flow needs to control in order to achieve the optimal utilization of transmission lines capacity. Operating efficiency of transmission can be improved by using FACTS device. Phase Shifting Transformer is one of the FACTS families which can be used for power

International Journal of Trend in Scientific Research and Development (IJTSRD)International Open Access Journal | www.ijtsrd.com

ISSN No: 2456 - 6470 | Volume - 2 | Issue – 6 | Sep

www.ijtsrd.com | Volume – 2 | Issue – 6 | Sep-Oct 2018

Active Power Flow Control with Phase ShiftingTransformer in AC Transmission Line

Thandar Oo1, Su Mon Myint2, Aye Khaing Zin3 ME Student, 2Lecturer, 3Assistant Lecturer

Electrical Power Department, Pyay Technological University The Republic of the Union of Myanmar, Pyay, Myanmar

Nowadays, active power flow should be controlled because voltage fluctuation occurred on various load conditions. Phase shifting transformer (PST) is used to control the active power flow in three phase electricity transmission network. It can increase reliability and can serve as an alternative to new investments in overhead lines. The control of active power flow is achieved by adjusting the phase angle of the voltages at the PST terminals. In this paper, 230 kV AC transmission line is chosen for active power flow control. Two conditions, maximum and minimum load conditions are considered as a case study for active power flow control performance in a elected line. Simulation of active power flow with

PST model is carried out by using Matlab software. Finally, according to simulation results, system voltages and active power depend phase angles are

former, on load tap changer, transmission line, phase shift angle, active

Electric power is transported between different voltage levels of the electric grid through interconnected transmission lines. Overloading in transmission line decreases the security of power system. When power flows between two nodes, there

rop and a phase angle different between the sending end and receiving end. So, the power flow needs to control in order to achieve the optimal utilization of transmission lines capacity. Operating efficiency of transmission can be improved by using

evice. Phase Shifting Transformer is one of the FACTS families which can be used for power

control in a network. Therefore, the phasetransformer is the first choice for controlling the active power flow between two system areas as it is the less expensive than the FACTS devices, and performs satisfactorily under steadyFor example, the PST can be used in order to impose a power flow according to the contractual amount. For this reason, the PSTs are usually installed on interconnection lines [1]. In interconnected power networks, certain ac transmission lines do not have definite sender and receiver ends since the active power conveyed by these lines does not flow in the same direction at all times. The polarity of phase shift voltages at two regions of an interconnected power network is very important because it determines the direction of the active power flow in the corresponding ac transmission line [4]. PST can alter the polarity of phase angle between the vusing OLTC. PSTs compensates for the drop by inserting, between its sending and its receiving ends, a series voltage in quadrature with the linevoltages. This quadrature voltage produces, between the PSTs terminals, a phase shift whosvaries with the magnitude of the quadrature voltage [3]. The purpose of PST is usually the control of power flow over transmission lines. Both the magnitude and the direction of the power flow can be controlled by varying the phase shift. Althcontrol of power flowing through a line, the flow itself is still a function of the grid situation, and the power flow can only be “shift” [9].

Research and Development (IJTSRD) www.ijtsrd.com

6 | Sep – Oct 2018

Oct 2018 Page: 666

Phase Shifting

control in a network. Therefore, the phase-shifting transformer is the first choice for controlling the active power flow between two system areas as it is

ss expensive than the FACTS devices, and performs satisfactorily under steady-state conditions. For example, the PST can be used in order to impose a power flow according to the contractual amount. For this reason, the PSTs are usually installed on

In interconnected power networks, certain ac transmission lines do not have definite sender and receiver ends since the active power conveyed by these lines does not flow in the same direction at all times. The polarity of phase shift between the voltages at two regions of an interconnected power network is very important because it determines the direction of the active power flow in the corresponding ac transmission line [4]. PST can alter

between the voltages by using OLTC. PSTs compensates for the drop by inserting, between its sending and its receiving ends, a series voltage in quadrature with the line-to-ground voltages. This quadrature voltage produces, between the PSTs terminals, a phase shift whose magnitude varies with the magnitude of the quadrature voltage

The purpose of PST is usually the control of power flow over transmission lines. Both the magnitude and the direction of the power flow can be controlled by varying the phase shift. Although PSTs enable the control of power flowing through a line, the flow itself is still a function of the grid situation, and the power flow can only be “shift” [9].

Page 2: Analysis of Active Power Flow Control with Phase Shifting Transformer in AC Transmission Line

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

@ IJTSRD | Available Online @ www.ijtsrd.com

II. POWER FLOW CONTROL A. Controlling the power flow through a

transmission line A simplified relation between active power transported over a transmission line between sending and receiving nodes and the complex voltages at both nodes is:

)sin( X

VVP

Line

RSLine

Where sending node VS and receiving node Vphase angle between these voltages and Ximpedance. The active power is proportional to the voltages on the sending and the receiving ends and the phase angle between both ends; it is also inversely proportional to the line reactance. Therefore, the power flow through the line can be controlled by altering the voltage at a node, the impedance between nodes and the angle between terminal voltages. The line flow can also be altered by changing the line impedance. This can be done by inserting variable series impedance. Then, the active power flow can also be control by altering the phase angle between sending and receiving ends voltage with a series injected voltage in quadrature to the phase voltage. B. Phase Shifting Transformer The PST is installed as a series reactance with a phase shift in transmission line. The power flow through the line is increased by adding an angle angle. The phase shift is controllable within certain limits. The PST is a mechanically switched device which inserts a transformed, variable (using a tap changer) line voltage in series with the phase voltage. Figure 1(a) depicts this for direct symmetrical phaseshifting transformer and Figure 1(b) depicts its phasor diagram.

)sin( XX

VVP

PSTLine

RSLine

The state above can also be interpreted in another way: the active power is proportional to the phase angle between nodes. Altering the active power can be done by altering the phase angles. Although phase shifting transformers enable the control of power flowing through a line, the flow itself is still a function of the grid situation, and the power flow can only be “shifted” [9].

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

www.ijtsrd.com | Volume – 2 | Issue – 6 | Sep-Oct 2018

Controlling the power flow through a

simplified relation between active power transported over a transmission line between sending and receiving nodes and the complex voltages at both

(1)

and receiving node VR, the en these voltages and XLine the

impedance. The active power is proportional to the voltages on the sending and the receiving ends and the phase angle between both ends; it is also inversely proportional to the line reactance. Therefore, the

ugh the line can be controlled by altering the voltage at a node, the impedance between nodes and the angle between terminal voltages. The line flow can also be altered by changing the line impedance. This can be done by inserting variable

. Then, the active power flow can also be control by altering the phase angle between sending and receiving ends voltage with a series injected voltage in quadrature to the phase voltage.

The PST is installed as a series reactance with a phase shift in transmission line. The power flow through the

to the existing . The phase shift is controllable within certain

witched device which inserts a transformed, variable (using a tap changer) line voltage in series with the phase voltage. Figure 1(a) depicts this for direct symmetrical phase-shifting transformer and Figure 1(b) depicts its phasor

(2)

The state above can also be interpreted in another way: the active power is proportional to the phase angle between nodes. Altering the active power can be done by altering the phase angles. Although phase

ifting transformers enable the control of power flowing through a line, the flow itself is still a function of the grid situation, and the power flow can

L3

L1

S3

(a)

VL3

DV3

VL1

V

VS3

(b) Figure.1. Direct symmetrical PST (a) Circuit diagram

and (b) Phasor diagram III. PRINCIPLES OF PHASE SHIFTING

TRANSFORMER A. Basic Theory of Phase Shifting TransformerThe phase shifting transformer (PST) is a specialized form of transformer used to control the activeflow in three phase electricity transmission networks. The term Phase Shifter is more generally used to indicate a device which can inject a voltage with a controllable phase angle and/or magnitude under noload (off-load) and load (on-load) conditi Operation of a conventional phasecharacterized by: High response time as a result of inertia of moving

parts, and High level of maintenance due to mechanical

contacts and oil deterioration. The main power circuitry of the phase shifting transformer consists of Figure 2(a): the exciting transformer that provides input voltage to the phase shifter; the series transformer, that injects a controllable voltage Vα in the transmission line; and the converter or tap changer, which controls the magnitude and/or phase angle of the injected voltage. A converter is used in case of a power electronic based interface, and a tap changer is used in case of a

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470

Oct 2018 Page: 667

S1

L2

S2

V1D

V2D

VS1

VL2

VS2

Direct symmetrical PST (a) Circuit diagram and (b) Phasor diagram

PRINCIPLES OF PHASE SHIFTING

Basic Theory of Phase Shifting Transformer The phase shifting transformer (PST) is a specialized form of transformer used to control the active power flow in three phase electricity transmission networks. The term Phase Shifter is more generally used to indicate a device which can inject a voltage with a controllable phase angle and/or magnitude under no-

load) conditions.

Operation of a conventional phase-shifter is

High response time as a result of inertia of moving

High level of maintenance due to mechanical contacts and oil deterioration.

The main power circuitry of the phase shifting transformer consists of Figure 2(a): the exciting transformer that provides input voltage to the phase shifter; the series transformer, that injects a

in the transmission line; and the converter or tap changer, which controls the

gnitude and/or phase angle of the injected voltage. A converter is used in case of a power electronic based interface, and a tap changer is used in case of a

Page 3: Analysis of Active Power Flow Control with Phase Shifting Transformer in AC Transmission Line

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

@ IJTSRD | Available Online @ www.ijtsrd.com

mechanical controlled phase shifting transformer. The PST is a device that is used for power flowcontrol in order to relieve congestions in electrical grids. Figure 2(a) shows a schematic diagram of a phase shifter installed on a transmission line between buses a and b. The sending and receiving ends of the transmission line are represented by voltagVS and VR, and corresponding impedances Zrespectively.

ZSVa V

ConverterOr

OLTCExciting

Transformer

BoosterTransformer

∠SVS

V∠φ

(a)

Va

V

φ

Vb

A A'

B'

B

(b) (c) Figure.2. Diagrams of a phase-shifting transformer:

(a) Schematic diagram; (b) Phasor diagram; (c) Phase shift for advance [1]

Depending on the magnitude and phase angle of the injected voltage Vα, the magnitude and/or phaseof the system voltage Vb is varied Figure 2(b). With a flexible phase shifting transformer, the control range achieved is a circle with centre in the tip of the phasor Va and radius equal to the amplitude of Vvoltage of the phase shifting transformer is controlled by varying the amplitude and angle of the phasor Vthat is Vα and φ [1]. The active power flow on the transmission line that incorporates a PST is given by:

)-sin( X

VVP

Req

RS S

Where Xeq is the net equivalent reactance of the line and the sources, whereas δS and δR are phase angles of the phasors VS and VR, respectively. Based on equation (3) the angle α is the dominant variable for power flow control.

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

www.ijtsrd.com | Volume – 2 | Issue – 6 | Sep-Oct 2018

mechanical controlled phase shifting transformer.

The PST is a device that is used for power flow control in order to relieve congestions in electrical grids. Figure 2(a) shows a schematic diagram of a phase shifter installed on a transmission line between buses a and b. The sending and receiving ends of the transmission line are represented by voltage phasors

, and corresponding impedances ZS and ZR,

ZRVb

∠RVR

C'

C

shifting transformer: Schematic diagram; (b) Phasor diagram; (c) Phase

Depending on the magnitude and phase angle of the , the magnitude and/or phase-angle

is varied Figure 2(b). With a ransformer, the control range

achieved is a circle with centre in the tip of the phasor and radius equal to the amplitude of Vα. The output

voltage of the phase shifting transformer is controlled by varying the amplitude and angle of the phasor Vα,

The active power flow on the transmission line that incorporates a PST is given by:

(3)

is the net equivalent reactance of the line are phase angles of

, respectively. Based on equation (3) the angle α is the dominant variable for

B. Categories of Phase Shifting PST’s come in many different forms. They can be classified by these characteristics: Direct PST’s are based on one three

The phase shift is obtained by connecting the windings in an appropriate manner.

Indirect PST’s are based on a two separate transformers; one variable tap exciter to regulate the amplitude of the quadrature voltage and one series transformer to inject the quadrature voltage in the right phase.

Asymmetrical PST’s create an output voltage with an altered phase angle and amplitude compared to the input voltage.

Symmetrical PST’s create an output voltage with an altered phase angle compared to the input voltage, but with the same amplitude [7].

C. Delta-hexagonal Type Phase Shifting

Transformer In this paper, Delta-hexagonal type Phase Shifting Transformer is applied for active power flow control. This type of PST can be symmetrical with two tap changers, as shown in Figure 3, or nonwith only one tap changer. To maintain symmetry when two tap changers are used, the tap changers are often interlocked such that they take alternating steps from neutral to maintain no more than one step off of symmetry.

Figure.3. Delta-hexagonal type phase shifting transformer

An important advantage of this design is that only one tap variable transformer is need per phase. Deltahexagonal design PST has further advantage that the phase angle changes almost linearly with tapsetting. It is often used for lower voltage level.

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470

Oct 2018 Page: 668

Categories of Phase Shifting Transformer PST’s come in many different forms. They can be

fied by these characteristics: Direct PST’s are based on one three-phase core. The phase shift is obtained by connecting the windings in an appropriate manner. Indirect PST’s are based on a construction with two separate transformers; one variable tap exciter to regulate the amplitude of the quadrature voltage and one series transformer to inject the quadrature voltage in the right phase. Asymmetrical PST’s create an output voltage with

ltered phase angle and amplitude compared to

Symmetrical PST’s create an output voltage with an altered phase angle compared to the input voltage, but with the same amplitude [7].

hexagonal Type Phase Shifting

hexagonal type Phase Shifting Transformer is applied for active power flow control. This type of PST can be symmetrical with two tap changers, as shown in Figure 3, or non-symmetrical with only one tap changer. To maintain symmetry

wo tap changers are used, the tap changers are often interlocked such that they take alternating steps from neutral to maintain no more than one step off of

hexagonal type phase shifting transformer

this design is that only one tap variable transformer is need per phase. Delta-hexagonal design PST has further advantage that the phase angle changes almost linearly with tap-changer setting. It is often used for lower voltage level.

Page 4: Analysis of Active Power Flow Control with Phase Shifting Transformer in AC Transmission Line

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

@ IJTSRD | Available Online @ www.ijtsrd.com

IV. CASE STUDY 230 kV Toungoo-Tharyagone line is selected for active power flow control by using PST. This line is important since it is one of a power feeding line to lower Myanmar National Grid. This transmission line is connected to Kamarnet-Hlawga line that is one of a power carrying transmission line to Yangon City. The active power flow control becomes importance for the selected line because the power demand is varied on every time. For the control of active power flow, PST is installed in series with the selected linand line parameter of Toungootransmission line are shown in Table 1 and Table 2. The parameters of PST are shown in Table 3. In this case 200 MVA throughput power of PST is chosen depend on the maximum load condition in the selected line. For the active power flow performance 16 steps On-load Tap Changer and 30 degrees phase shift are selected. Thus, the tap is change from and the phase angle change for each tap is 3.75 degrees. Table1. Line Data of 230 kV Toungoo

Line

Months Pmax

(MW) Qmax

(MVAr) April(2017) 263.57 -15.54 July (2017) 274.92 3.62

December(2017) 290.95 9.80

Figure.4. Simulink model of with PST under maximum and minimum load condition

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

www.ijtsrd.com | Volume – 2 | Issue – 6 | Sep-Oct 2018

Tharyagone line is selected for active power flow control by using PST. This line is important since it is one of a power feeding line to lower Myanmar National Grid. This transmission line

Hlawga line that is one of a power carrying transmission line to Yangon City. The active power flow control becomes importance for the selected line because the power demand is varied on every time. For the control of active power flow, PST is installed in series with the selected line. Line data and line parameter of Toungoo-Tharyagone transmission line are shown in Table 1 and Table 2.

The parameters of PST are shown in Table 3. In this case 200 MVA throughput power of PST is chosen depend on the maximum load condition in the

ed line. For the active power flow performance 30 degrees phase

shift are selected. Thus, the tap is change from -8 to 8 and the phase angle change for each tap is 3.75

230 kV Toungoo-Tharyagone

Smax

(MVA) 264.03 274.94 291.11

Table2. Line Parameters of 230 kV ToungooTharyagone Line

System Voltage Line distance

Conductor size Frequency Resistance 0.0474 Reactance 0.31763

Table3. Parameters of Phase Shifting Transformer

Throughput PowerDesign Power

Phase Shift OLTC

Step Voltage System Current Rated Voltage

V. RESULTS AND DISCUSSIONA. Simulink Model with Phase Shifting

Transformer In this paper, AC 230 kV transmission line is connected from Toungoo Township to Tharyagone Township. Phase shifting transformer (PST) is inserted in series with the line to control power flow of network by adjusting the phase angles. The outgoing terminal of phase shifting transformer is connected with three phase RLC loads that is shown in Figure 4. The phase shift can be varied on loads by means of On Load Tap Changers (OLTC). In order to observe the operation of phase shifting transformer, one tap is 3.75 degree for each and the phase shift is increased from 0 to 30 degrees for leading (tap +8), then phase shift is reduced to 0 and increased again up to 30 degree lagging (tap -8).

Figure.4. Simulink model of with PST under maximum and minimum load condition

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470

Oct 2018 Page: 669

2. Line Parameters of 230 kV Toungoo-Tharyagone Line

230 kV 60.1 miles

2*605 MCM 50 Hz

0.0474 /km 0.31763 /km

3. Parameters of Phase Shifting Transformer Throughput Power 200 MVA

103.6 MVA 30 degree 16 steps 4296 V 502 A

230 kV

RESULTS AND DISCUSSION Simulink Model with Phase Shifting

In this paper, AC 230 kV transmission line is connected from Toungoo Township to Tharyagone

Phase shifting transformer (PST) is inserted in series with the line to control power flow of network by adjusting the phase angles. The outgoing terminal of phase shifting transformer is connected with three phase RLC loads that is shown

phase shift can be varied on loads by means of On Load Tap Changers (OLTC). In order to observe the operation of phase shifting transformer, one tap is 3.75 degree for each and the phase shift is increased from 0 to 30 degrees for leading (tap +8),

ase shift is reduced to 0 and increased again up

Figure.4. Simulink model of with PST under maximum and minimum load condition

Page 5: Analysis of Active Power Flow Control with Phase Shifting Transformer in AC Transmission Line

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

@ IJTSRD | Available Online @ www.ijtsrd.com

B. Simulink Model without Phase Shifting Transformer

Figure.5. Simulink model of without Figure 5 shows the Simulink model of without PST under maximum and minimum load conditions in 230 kV Toungoo-Tharyagone line. Before using PST, the active power flow on line is 264 MW from simulation the results. C. Simulations Results of Case StudyThe paper presents the analysis for active power flow control performance under maximum and minimum load conditions without and with PST in selected transmission line. From simulation results, the comparison under maximum and minimum conditions for phase angle difference between the voltages with related to tap positions, active power flow with related to tap positions, receiving end voltage with related to tap positions, and phase difference with related to power flow is shown inFigure 6, Figure 7, Figure 8 and Figure 9.

Figure.6. Comparison of result under maximum and minimum load conditions for the phase angle with

related to tap positions

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

www.ijtsrd.com | Volume – 2 | Issue – 6 | Sep-Oct 2018

Simulink Model without Phase Shifting Transformer

Figure.5. Simulink model of without PST under load condition

Figure 5 shows the Simulink model of without PST under maximum and minimum load conditions in 230

Tharyagone line. Before using PST, the active power flow on line is 264 MW from simulation

Results of Case Study The paper presents the analysis for active power flow control performance under maximum and minimum load conditions without and with PST in selected transmission line. From simulation results, the comparison under maximum and minimum load conditions for phase angle difference between the voltages with related to tap positions, active power flow with related to tap positions, receiving end voltage with related to tap positions, and phase difference with related to power flow is shown in Figure 6, Figure 7, Figure 8 and Figure 9.

Figure.6. Comparison of result under maximum and minimum load conditions for the phase angle with

Figure 6 presents the comparison of the phase angle with related to tap positions fromIn this figure, the phase angle on minimum load condition is lower than the maximum load condition. The phase angle is also increased by raising the tap positions.

In Figure 7, the active power flow on the line is different on various load conditions. From this result, it is clear that the active power flow on line is controlled by changing the tap positions.

Figure 8 shows the comparison result for the receiving end voltage with related to tap positions from simulation results. In this figure, the receiving end voltage for maximum load condition is lower than the minimum load condition. The receiving end voltage decreased due to the load growth. When the tap positions increased, the receiving end voltage decreased.

Figure.7. Comparison of active power flow with related to tap positions under maximum and minimum

load conditions

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470

Oct 2018 Page: 670

Figure 6 presents the comparison of the phase angle with related to tap positions from simulation results. In this figure, the phase angle on minimum load condition is lower than the maximum load condition. The phase angle is also increased by raising the tap

In Figure 7, the active power flow on the line is load conditions. From this result,

it is clear that the active power flow on line is controlled by changing the tap positions.

Figure 8 shows the comparison result for the receiving end voltage with related to tap positions from

is figure, the receiving end voltage for maximum load condition is lower than the minimum load condition. The receiving end voltage decreased due to the load growth. When the tap positions increased, the receiving end voltage

Comparison of active power flow with

related to tap positions under maximum and minimum load conditions

Page 6: Analysis of Active Power Flow Control with Phase Shifting Transformer in AC Transmission Line

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

@ IJTSRD | Available Online @ www.ijtsrd.com

Figure.8. Comparison of result under maximum and minimum load conditions for the receiving end

voltage with related to tap positions The comparison of the phase angle with related to active power flow from simulation result is illustrated in Figure 9. From the results, the phase angle on maximum load condition is larger than the minimum load condition and the improvement of active power flow on the line depends on the phase angle increasing in phase shifting transformer.

Figure.9. Comparison of result under maximum and minimum load conditions for the phase angle with

related to active power flow VI. CONCLUSION The active power flow on the line is increased by controlling the phase angles between sending and receiving end voltages. The phase angles are controlled by changing the tap position on the OLTC. In this paper, Direct Symmetrical Deltatype PST is chosen for the connections of transformer. Matlab software is applied for the simulation results. Two models for active power flow control with and without PST under load condition are described. In the result, before using PST the active power floline for maximum load condition is 264 MW and for minimum load condition is 2.26 MW. By using PST, the active power flow on the line is controlled from 67.27 MW to 450.89 MW for maximum load condition and -0.84 MW to 481.52 MW for minimum

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

www.ijtsrd.com | Volume – 2 | Issue – 6 | Sep-Oct 2018

Figure.8. Comparison of result under maximum and

minimum load conditions for the receiving end voltage with related to tap positions

f the phase angle with related to active power flow from simulation result is illustrated in Figure 9. From the results, the phase angle on maximum load condition is larger than the minimum load condition and the improvement of active power

e depends on the phase angle increasing in phase shifting transformer.

Figure.9. Comparison of result under maximum and minimum load conditions for the phase angle with

related to active power flow

The active power flow on the line is increased by controlling the phase angles between sending ends and receiving end voltages. The phase angles are controlled by changing the tap position on the OLTC. In this paper, Direct Symmetrical Delta-hexagonal

PST is chosen for the connections of transformer. Matlab software is applied for the simulation results. Two models for active power flow control with and without PST under load condition are described. In the result, before using PST the active power flow on line for maximum load condition is 264 MW and for

By using PST, the active power flow on the line is controlled from -67.27 MW to 450.89 MW for maximum load

0.84 MW to 481.52 MW for minimum

load condition. So, PST can control an active power flow in transmission lines. ACKNOWLEDGEMENTS First at all, the author would like to express her special thanks to Dr. Nyaunt Soe, Rector, Pyay Technological University for initiating the Master programme at the Pyay Technological University. The author is sincerely grateful to her teacher Dr. Soe Winn, Professor and Head, Department of Electrical Power Engineering, Pyay Technological University, for his patience, permissions and helpful suggestions. The author is deeply thankful to her supervisor, Dr. Su Mon Myint, Lecturer for her guidance, valuable advice and her co-supervisor, Daw Aye Khaing Zin, Assistant Lecturer for her worthy advice at Department of Electrical Power Engineering, Pyay Technological University. And, the author is deeply grateful to her teacher U Than Zaw Htwe, Lecturer, Department of Electrical Power Engineering, Yangon Technological University, for his valuable instructions. My heart-felt thanks to my family, friends and colleagues who have mcompletion of this paper. REFERENCES 1. Dorian O. SIDEA, Lucian TOMA, Mircea

EREMIA; “Sizing a phase shifting transformer for congestion management in high wind generation areas”, Department of Electrical Power Systems, University Politehnica of BuRomania: June 2017.

2. Michael Thompson; “Protection System for Phase-Shifting Transformers Improves Simplicity, Dependability, and Security”, Schweitzer Engineering Laboratories, Inc: Revised edition released May 2015.

3. J. M. Guzman, F. J. OregaJimenez, G. Tapia-Tinoco, L.A. ContrerasAugilar, “Implementation of PhaseTransformer model into an OPF formulation by Matlab optimization toolbox”, International Journal of Scientific and Research Publications, Volume 3, Issue 9, September 2013, ISSN 22503153.

4. FESTO, Electricity and New Energy, Lab Volt Series, “AC Transmission Lines”, 120V

5. Hingorani, N. G., Gyugyi, L; Understanding FACTS. New Youk: IEEE Press, 2000,432 s.

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470

Oct 2018 Page: 671

ion. So, PST can control an active power

First at all, the author would like to express her special thanks to Dr. Nyaunt Soe, Rector, Pyay Technological University for initiating the Master

Pyay Technological University. The author is sincerely grateful to her teacher Dr. Soe Winn, Professor and Head, Department of Electrical Power Engineering, Pyay Technological University, for his patience, permissions and helpful suggestions.

deeply thankful to her supervisor, Dr. Su Mon Myint, Lecturer for her guidance, valuable

supervisor, Daw Aye Khaing Zin, Assistant Lecturer for her worthy advice at Department of Electrical Power Engineering, Pyay

y. And, the author is deeply grateful to her teacher U Than Zaw Htwe, Lecturer, Department of Electrical Power Engineering, Yangon Technological University, for his valuable

felt thanks to my family, friends and colleagues who have me for the

Dorian O. SIDEA, Lucian TOMA, Mircea EREMIA; “Sizing a phase shifting transformer for congestion management in high wind generation areas”, Department of Electrical Power Systems, University Politehnica of Bucharest, Bucharest,

Michael Thompson; “Protection System for Shifting Transformers Improves Simplicity,

Dependability, and Security”, Schweitzer Engineering Laboratories, Inc: Revised edition

Orega-Herrera, J. Torres-Tinoco, L.A. Contreras-

Augilar, “Implementation of Phase-Shifting Transformer model into an OPF formulation by Matlab optimization toolbox”, International Journal of Scientific and Research Publications,

, Issue 9, September 2013, ISSN 2250-

FESTO, Electricity and New Energy, Lab Volt Series, “AC Transmission Lines”, 120V-60Hz

Hingorani, N. G., Gyugyi, L; Understanding FACTS. New Youk: IEEE Press, 2000,432 s.

Page 7: Analysis of Active Power Flow Control with Phase Shifting Transformer in AC Transmission Line

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

@ IJTSRD | Available Online @ www.ijtsrd.com

6. James H. Harlow. p. cm.-( The Electrical PEngineering Series; 9) Includes bibliographical references and index. ISBN 0(alk.paper). 1. Electric transformers. I . Harlow, James H. II. title. III Series.

7. Verboomen, J., Hertem, D. V., Schavemaker, P. H., Kling, W. L. and Belmans, R Transformers: Principles and Applications, IEEE Conf. on Future Power Systems, Amsterdam, November (2005)

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456

www.ijtsrd.com | Volume – 2 | Issue – 6 | Sep-Oct 2018

( The Electrical Power Engineering Series; 9) Includes bibliographical references and index. ISBN 0-8493-1704-5 (alk.paper). 1. Electric transformers. I . Harlow,

Verboomen, J., Hertem, D. V., Schavemaker, P. Phase Shifting

Transformers: Principles and Applications, IEEE Conf. on Future Power Systems, Amsterdam,

8. Jozef RUSNAK; POWER FLOW CONTROL BY USE OF PHASE-SHIFTING TRANSFORMER, Ph.D. Degree Programme, Dept. of Electric Power Engineering, FEI TU, Kosice.

9. Dirk Van Hertem*; Influence of phase shifting transformers and HVDC on power system losses. Graduate Student Menber, IEEEVerboomen, Member, IEEEGraduate Student Member, IEEE,Member, IEEE and Ronnie Belmans, IEEE *research group ELECTA, electrical engineering department, KU Leuven, Belgium.

International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470

Oct 2018 Page: 672

Jozef RUSNAK; POWER FLOW CONTROL BY SHIFTING TRANSFORMER,

Ph.D. Degree Programme, Dept. of Electric Power TU, Kosice.

Dirk Van Hertem*; Influence of phase shifting transformers and HVDC on power system losses. Graduate Student Menber, IEEE, Jody

Member, IEEE, Stijn Cole*, Graduate Student Member, IEEE, Wil Kling,

and Ronnie Belmans, Fellow, *research group ELECTA, electrical

engineering department, KU Leuven, Belgium.