ZXD800 15A switch rectifier User's manual

   

Data version 20051229-R1. 2

Product version V1. 0

   

 INFORMATION Copyright ZTE CORPORATION. Without the

written permission of the copyright holder, no unit or individual

shall not in any way abstracted, reproduced or translated.

All Rights Reserved.

Copyright © ZTE Corporation

All rights reserved.

No part of this documentation may be excerpted, reproduced, translated, annotated or

duplicated, in any form or by any means without the prior written permission of ZTE Corporation.

 

 

 

Market Center Engineering Planning Division, with headquarters Hattori

Edited by Li Lin

Editor Bo Young

****

ZTE Corporation

Address: Shenzhen Hi-Tech Industrial Park, ZTE Plaza, Keji Road South

Postal Code: 518057

Technical Support Web site: http://support.zte.com.cn

Customer Support Center Hotline: (+ 86 755) 26770800 800 - 830 - 1118

Fax: (+ 86 755) 26770801

E-mail: [email protected] n

**** ID: S jzl1999174

Page 3: ZX D800 15A Switching Rectifier

Feedback Form

To improve the quality of ZTE user information to better serve you and hope

you make your suggestions and comments in his busy schedule, and please fax to:

0755-26770160, or mail to: ZTE Corporation, Shenzhen Science and Technology Park

Building Engineering Department, Market Center, Zip: 518057. We will send your a

beautiful gift.

Title ZXD800 15A switch rectifier User Manual Product

Version V1. 0 Data release 200 51229-R1.2

Time to install the device in

your organization  

To be able to contact you, please fill in the following information about your Full name   Name  

Zip Code   Address  

Phone   E-mail  

Your use of

this

information Evaluation

  Good Better General Poor Poor Overall

satisfaction          

Guiding          

Easy access          

Is correct          

Content

Complete          

Reasonable

structure          

Chart

description          

Straightaway          

Your use of

this

information Recommendat

ions for

improvement

  Details Content

Structure  

Detailed  

Content

Depth  

Concise

expression  

Increase in

graphics  

Increased

instances  

Increase FAQ  

Others  

You ZTE User

 

 

Page 4: ZX D800 15A Switching Rectifier

information Other

suggestions

 

 

 

Page 5: ZX D800 15A Switching Rectifier

 

Foreword

Manual instructions

ZXD800 15A switch rectifier is independently developed by ZTE

communication power switch rectifier. "ZXD800 15A Switching

Rectifier user manual" to guide ZXD800 15A rectifier switch installation,

use and maintenance.

 

Notice: Due to product and technology constantly updated, improved,

the contents of this document may not exactly match the actual

product, please understand. For inquiries updates of products, please

contact your local office.

 

Page 6: ZX D800 15A Switching Rectifier

 

Table of Contents

Chapter 1 Overview

1.1 Brief introduction

1.2 Model Description

1.3 The main features

Chapter 2 Performance Parameters

2.1 AC input parameters

2.2 DC output parameters

2.3 Internal protection

2.3.1 AC input voltage protection

2.3.2 AC input voltage protection

2.3.3 DC output protection

2.3.4 Other protection

2.4 HMI

2.5 Battery Protection

2.5.1 RS-232 version ZXD800 15A switching regulator

2.5.2 RS-485 version ZXD800 15A switching regulator

2.6 Three remote interfaces

2.7 Fan Control

2.8 Electromagnetic compatibility

2.9 Reliability

2.10 Work Environment

2.11 Dimensions and weight

2.12 Standard

Chapter 3 works

Chapter 4 Monitoring and Display

4.1 Indicator

4.2 LCD

Page 7: ZX D800 15A Switching Rectifier

4.2.1 RS-232 version ZXD800 15A switching regulator

4.2.2 RS-485 version ZXD800 15A switching regulator

4.3 Keyboard and control menu

Chapter 5 Installation and Use

5.1 Installation

5.2 Input and output

5.2.1 AC input

5.2.2 DC output

5.2.3 Communication Interface

5.2.4 Current sharing bus interface

5.3 The installation process

Chapter 6 Maintenance and Repair

6.1 Daily use

6.2 Troubleshooting

Appendix A packaging, transport and storage

A.1 Package

A.2 Transport

A.3 Store

A.4 Random packing accessories

 

- 1 -  

Page 8: ZX D800 15A Switching Rectifier

Chapter 1    Outline

1.1   Brief introduction ZXD800 15A switch rectifier is independently developed by ZTE communication power

switch rectifier. It uses the international advanced switching regulator technology

can be widely used in a variety of communications switching equipment, microwave

communications and fiber optic transmission medium.

ZXD800 15A rectifier switch sets the input AC power distribution, AC / DC power

conversion, DC power distribution, battery protection, monitoring systems, flow

control all in one, both suitable for use alone or can be easily combined into a

system of 100 A or less.

ZXD800 15A switching regulator is divided into two different versions according to the

communication protocol: RS-232 and RS-485 version version, two versions of the fully

compatible ZXD800 15A rectifier switch hardware. .

ZXD800 15A switch rectifier shape shown in Figure 1-1.

Figure 1-1 Schematic outline switch rectifier

1.2   Model Description ZXD800 15A in:

"ZX" stands for "ZTE products"

"D" stands for "Power Module"

"800" stands for "output"

"15A" on behalf of "Output current"

Page 9: ZX D800 15A Switching Rectifier

1.3  

The main features

1.               The use of advanced technology zero voltage resonant phase shift, reducing

the switching losses and electromagnetic interference;

2.               Advanced modular design, multiple parallel automatic current;

3.               Built-in CPU and LCD module can display real-time parameters of the rectifier;

4.               Protection alarm parameters can be set via the keyboard, set the output

voltage, current limit set point;

5.               Perfect three remote interface functions provide RS-232 and RS-485

communication interface, can achieve centralized monitoring;

6.               The output has a DC float, are charged in two modes can be set via the

keyboard;

7.               Fan thermostat work to improve the reliability of the system;

8.               Applicable volatile region in the grid voltage;

9.               Input and output sound reasonable protective measures, both to improve the

reliability of the rectifier, but also to protect the electrical equipment;

10.               Improved battery management, can be used alone, suitable for small

decentralized power supply capacity occasions (only ZXD800 15A Switching Rectifier

RS-232 communication interface has this feature);

11. Sound limiting, both current performance, the use of multiple parallel

straightforward;

12.               Professional input, output filter circuit and shielding insulation design it has

a good electromagnetic compatibility and minimal electromagnetic radiation.

 

 

 

1  

Page 10: ZX D800 15A Switching Rectifier

Chapter 2   Performance Parameters

Page 11: ZX D800 15A Switching Rectifier

Chapter 2    Performance Parameters

2.1   AC input parameters Voltage: 220V single-phase three-wire system

Current: 6A (output load)

Frequency: 45 H z ~ 65Hz

Inrush current: less than the normal operating current

Slow start time: more than 3 s, the output no overshoot

≥ 85 (under full load).

2.2   DC output parameters Output power: Max 870W

Voltage: 48V (42V ~ 58V continuously adjustable)

Float: 53.5V (adjustable)

BC: 56.4V (adjustable)

Current: Maximum output 1 6 A

Limiting values: 3A ~ 16A continuously adjustable

Regulation ≤ ± 0.6

Phone Scale noise: ≤ 2 mV

Broadband noise voltage:

≤ 50mV (within 3.4kHz ~ 150kHz range)

≤ 15 mV (the 0.15MHz ~ 30MHz range)

Discrete frequency noise voltage:

≤ 5mV (within 3.4kHz ~ 150kHz range)

≤ 3mV (within the range of 150kHz ~ 200kHz)

≤ 2mV (within the range of 200kHz ~ 500kHz)

Page 12: ZX D800 15A Switching Rectifier

≤ 1mV (within 0.5MHz ~ 30MHz range)

Peak - peak noise voltage: ≤ 2 00mV (20MHz bandwidth)

Between modules flow <± 5 (50% load or more)

2.3   Internal protection

2.3.1   AC input voltage protection

When the AC input voltage is higher than 286 V ± 5 V, rectifier stop and

alarm when the AC voltage is reduced to 270V ± 5V, the rectifier

automatically resume normal operation.

2.3.2   AC input voltage protection

When the AC input voltage is below 154V ± 5V, the rectifier will

automatically reduce the current limit, limit the maximum output

power. When the AC input voltage is below 140 V ± 5 V, rectifier

shutdown and alarm. When the AC input rises back to 1 7 0V ± 5V, the

rectifier automatically resume normal operation.

2.3.3   DC output protection

Sustained high output voltage, shutdown and alarm. Instantaneous

output short circuit, the system automatically retrace current limit, the

voltage is maintained at a smaller value. The short is removed

automatically resume normal operation.

2.3.4   Other protection

The rectifier main radiator temperature (can be software settings, the

range is 70 ℃ ~ 80 ℃), the shutdown and alarm. At the same hardware

over-temperature protection (> 80 ℃). Rectifier with internal lightning

and surge current limiting circuit.

When a fan failure alarm.

2.4   HMI 1.               LCD module parameters, alarms and control menu.

Page 13: ZX D800 15A Switching Rectifier

2.               You can set the keyboard rectifier alarm threshold protection

parameters.

3.               Regulate the output voltage and output current limit and fan

working condition temperature points.

4.               Keyboard control are floating, the switch machine.

5.               Keyboard control battery breaker off (only RS-232 communication

interface ZXD800 15A switch rectifier has this feature).

2.5   Battery Protection

2.5.1   RS-232 version ZXD800 15A switching regulator

1.               Detecting the battery current, voltage

2.               Detect the battery circuit breakers, fuses state

Two battery undervoltage protection:

When the battery voltage is between 42V ± 2V ~ 46V ± 2V, there BL (low

battery) warning; below 42V ± 2V, battery tripping protection, while

BLL (battery voltage is too low) alarms; battery voltage is above 47V ±

2V, the alarm disappears.

2.5.2   RS-485 version ZXD800 15A switching regulator

When the battery voltage is less than 41V ± 2V, the battery protection

trip; when the battery voltage is higher than 47V ± 2V, returned to

normal.

2.6   Three remote interfaces 1.               Independent internal microprocessor

2.               RS-232 interface for communication with superiors monitoring

module

3.               RS-485 interface for communication with superiors monitoring

module

Page 14: ZX D800 15A Switching Rectifier

4.               With a perfect three remote (telemetry, remote control and

remote communication) function

2.7   Fan Control According Rectifier main radiator temperature control fan stopped,

half turn, full turn. Each temperature control point can be set via the

keyboard, the default value (recommended setting) as shown in Table

2-1 and Table 2-2.

1.               RS-232 version ZXD800 15A switching regulator

Table 2-1 Fan Status Table

Temperature Range Fan Status T ≤ 3 0 ℃ Fan does not turn 3 0 ℃ <T ≤ 4 0 ℃ Fan half turn 40 ℃ <T ≤ 70 ℃ Fans full turn 70 ℃ <T ≤ 80 ℃ Half load output T> 80 ℃ Rectifier shutdown

2.               RS-485 version ZXD800 15A switching regulator

Table 2-2 Fan Status Table

Temperature Range Fan Status T ≤ 3 5 ℃ Fan does not turn 3 5 ℃ <T ≤ 5 0 ℃ Fan half turn 5 0 ℃ <T ≤ 65 ℃ Fans full turn 65 ℃ <T ≤ 75 ℃ Half load output T> 75 ℃ Rectifier shutdown

2.8   Electromagnetic compatibility 1.               Meets VDE0 871 A-level standards

2.               Audible noise: <55dBa (1m)

2.9   Reliability MTBF: ≥ 10 5 h

Page 15: ZX D800 15A Switching Rectifier

2.10   Work Environment 1.               Ambient temperature: - 10 ℃ ~ +40 ℃

2.               Storage temperature: - 40 ℃ ~ +85 ℃

3.               Relative Humidity: 10% ~ 90% RH (temperature of 40 ℃ ± 2 ℃)

2.11   Dimensions and weight 1.               Dimensions: 88mm × 483mm × 330mm (excluding the handle) (H ×

W × D)

2.               Weight: 5 kg

2.12   Standard YD/T731-2002 communication with high-frequency switching rectifier

1  

Page 16: ZX D800 15A Switching Rectifier

Chapter 3    Works

ZXD800 15A rectifier zero voltage switching resonant phase shift

technology, and features a built-in intelligent power monitoring and

control. The circuit schematic diagram shown in Figure 3-1.

Figure 3-1 ZXD800 15A rectifier circuit schematic block diagram of a switch

ZXD800 15A switch rectifier is divided into four parts:

1.               AC input rectifier and start the auxiliary power supply section

2.               Power conversion and output rectifier filter section

3.               Phase shift control circuit

4.               The microprocessor section (MPU)

First phase AC input via the input switch, and then after EMI filter

circuit into rectifier circuit, the input rectifier circuit has a circuit to

limit the inrush current, making the rectifier input power with a

smaller surge current. Under the rectified DC voltage is normally about

310 V, the supply stage power conversion circuits.

Phase shift control circuit is a phase shift oscillator power generation

and closed-loop feedback regulation section. DC voltage and current

feedback signals respectively compared with the set value, closed-loop

Page 17: ZX D800 15A Switching Rectifier

regulation constitutes a specific frequency response, a group of

converted PWM pulse width modulation signal having a phase shift of

the main circuit is provided to enable the power supply to achieve the

specified voltage and current limit Flow characteristics and dynamic

characteristics of external requirements. Also on the main circuit of the

primary current, output current over-current protection, over-voltage

on the output voltage and short circuit protection.

Microcontroller circuit parameters real-time acquisition of power and

control the normal operation of the power supply; accept keyboard

commands; using LCD display real-time data and power control menu;

transmit power and data, and receive the alarm information to the

monitoring module via RS-232 or RS-485 keypad or the upper system

monitoring module set command.

Auxiliary power supply rectifier control circuitry required for a variety

of internal power.

Start auxiliary power supply is used to provide power needed to start

the auxiliary power input voltage, load after starting its work.

Temperature detection circuit detects the temperature of the main

radiator, gave the SCM system, SCM system based on temperature

through the main radiator fan control circuit controls the fan working

condition.

Relevant parameters to detect the battery, the battery management

(only RS-232 communication interface ZXD800 15A switch rectifier has

this feature).

 

1  

Page 18: ZX D800 15A Switching Rectifier

Chapter 4    Monitor and Display

There is a small LCD display, 4 LEDs and control keyboard on the

rectifier panel. LCD display shows the rectifier operating parameters,

alarms and control menu. LED indicates the operating status of the

rectifier, control the keyboard is used to set various protection alarm

parameters, adjust the output voltage.

Rectifier front panel shown in Figure 4-1 .

Figure 4-1 ZXD800 15A rectifier switch front panel Figure

4.1   Indicator On the rectifier panel were four lights: green, green, yellow, red,

respectively, indicating rectifier for AC input and DC output, output

current limiting, alarm status. Normal AC input and DC output

indicator light, output current limiting and warning lights off, output

current limiting occurs when the output current limiting lights. When

there is an alarm message warning lights. You should make the

appropriate treatment based on the liquid crystal display of alarm

information.

4.2   LCD

4.2.1   RS-232 version ZXD800 15A switching regulator

Figure 4-2 is a real-time data display, in the normal state, the LCD

display will show the rectifier and battery voltage and current, the

Page 19: ZX D800 15A Switching Rectifier

temperature of the main radiator, battery charging. Are there warning

and other information.

  53.5V 14.3A T = 26 53.5V 10.2A FL A

Figure 4-2 Real-time data display

The first line shows a total of three messages: the first one for the

rectifier voltage (53.5V); second is the current value of the rectifier

(14.3A); temperature value of the third main radiator (26 C) . The second

line shows four messages: the first one is the battery voltage (53.5V);

second is the current value of the battery (10.2A); third battery charging

method ("FL" said float; For "EQ", it means that both charge); fourth of

alarm information (if "A" blinking, an alarm is generated; If "A" is not

flashing, it means that no alarm). If there is an alarm, then press the

"Enter", the alarm message will be displayed as shown in Figure 4-3:

 

  ON ON OFF OFF BLL FF

Figure 4-3 alarms

Displayed on the first line of the display status information rectifier

module, there are four: the first is the output state ("ON" indicates that

the output of normal; "OFF" indicates that the output off); second AC

switch status ( "ON" said AC switch is turned on; "OFF" said AC switch

off); third relay for the state of the battery ("ON" indicates that the

battery relay switches; "OFF" indicates that the battery relay shut off);

fourth a fuse for the battery status ("ON" indicates that the battery fuse

turn; "OFF" indicates that the battery fuse disconnect). Alarm

information is displayed on the second line of the display include: AC

voltage is too high (AH) or too low (AL), the battery voltage is low (BL)

or too low (BLL), the main radiator high temperature (TH) or too High

(TV), direct current high voltage (HV) or short circuit (SC), fan failure

Page 20: ZX D800 15A Switching Rectifier

(FF). The second line on the map display system battery voltage is too

low (BLL) and fan failure (FF) alarms.

The code corresponding to the displayed alarm information as shown

in Table 4-1.

Table 4-1 and the alarm code table

Code Meaning Code Meaning AL AC voltage input low SC Output short circuit AH AC input voltage high TH Main radiator

temperature is high BL Battery voltage is low TV Main radiator

temperature BLL Battery voltage is too

low FF Fan failure

HV DC output voltage is

too high    

 

 

 

4.2.2   RS-485 version ZXD800 15A switching regulator

Real-time data is displayed as shown in Figure 4-4.

  53.5V 14.3A T = 26 FLOAT A

Figure 4-4 Real-time data display

For RS-485 version ZXD800 15A switching regulator, in fact, when the

data shown in Figure 4-4. Under normal conditions, the first row shows

three messages: a first voltage to the rectifier (53.5V); the second

rectifier current (14.3A); temperature value of the third main radiator (

C). The second line shows the two information: the first one for the

battery charging method ("FLOAT" said float; case of "EQUAL", it means

that both charge); second of alarm information (if "A" flashes, an alarm

Page 21: ZX D800 15A Switching Rectifier

is generated; If "A" is not flashing, it means that no alarm). If there is

an alarm, then press the "Enter", the alarm message will be displayed in

Figure 4-5:

 

  ON ON FF

Figure 4-5 alarms

Displayed on the first line of the display status information rectifier,

there are two: the first one is the output state ("ON" indicates that the

output of normal; "OFF" indicates that the output off); second AC switch

status ( "ON" said AC switch is turned on; "OFF" said AC switch off) the

alarm information on the second line of the display include: AC voltage

is too high (AH) or too low (AL), the main heat sink temperature is high

(TH) or too high (TV), direct current high voltage (HV) or short circuit

(SC), fan failure (FF). Figure 4-5 The second line shows the system fan

failure (FF) alarms.

4.3   Keyboard and control menu There are four buttons on the keyboard rectifier, used to modify the

working parameters and alarm protection rectifier, the specific

meaning and function of each key as shown in Table 4-2.

 

 

Table 4-2 Keys and Function Table

Button Description Esc Return to the previous menu, cancel the ongoing changes Forward, move the cursor up, numbers increase Next, move the cursor down, numbers reduced Enter Into the digital modify, amend confirmation.

Page 22: ZX D800 15A Switching Rectifier

In normal display mode, press "" key to enter the control menu.

Control menu of eight, with the "" button to cycle between

various menus, use the "" key to enter the menu, press the "Enter Esc"

key to exit the menu.

Modify method parameters and status: The "" key to move the

cursor to the item you want to modify the cursor in the back-digit ,

press "Enter" to enter the changes, then the cursor at the bottom of the

modified figures . With "" key to increase or decrease numbers.

Modification is completed, press "Enter" key to confirm the changes,

press the "Esc" key to discard changes. For example, to modify the

current limit, while pressing the "", then press the or

can be set menu selection, press the key in the event CURRENT LIMIT

"Enter", the cursor will move to "15A", and press the or

current limit can be set, such as double-click limiting point into

13A, and then press the "Enter", the new 13A current limit will Save to

SCM system, if you press the "ESC", the new setting will be canceled

and returned to their original values. Finally, press the "ESC" back to

the previous menu.

The specific meaning of the menu below.

1.               TEMP LIMIT

Fan control and overheating protection temperature threshold

setting. A total of four, namely: the temperature of the fan half

turn, full turn the fan temperature derating protection

temperature shutdown protection temperature, the unit is ℃.

Fan control and overheating protection rectifier will be adjusted

according to these thresholds. For RS-232 version ZXD800 15A

switching regulator, the default value: 30,407,080; For RS-485

version ZXD800 15A switching regulator, the default value is:

35506575.

2.               DCOU T LIMIT

DC output voltage overvoltage protection threshold. DC output

voltage exceeds this value, the rectifier will shutdown protection.

Page 23: ZX D800 15A Switching Rectifier

For RS-232 version ZXD800 15A switching regulator, it defaults to

60 .0 V; For RS-485 version ZXD800 15A switching regulator, it

defaults to 5 8 .0 V.

3.               OUT VOLTAGE

DC float, are charging output voltage setting for output voltage

regulation, a total of two, namely: floating output voltage, output

voltage are charging.

For RS-232 version ZXD800 15A switching regulator, it defaults to

53.50V 56 5 0V;. For RS-485 version ZXD800 15A switching regulator,

it defaults to 53.50V 56.40V.

4.               CURRENT LIMIT

The output current limit value is set, is used to set the DC output

current limit, shown in Figure 4-6.

 

. 4 CURRENT LIMIT: 15A

Figure 4-6 Set Limit

For RS-232 version ZXD800 15A switching regulator, it defaults to

15A; For RS-485 version ZXD800 15A switching regulator, it defaults

to 5A.

5.               CHARGE CTRL

Charging control. Used to set the output state rectifier. FLOAT:

float; EQUAL: BC.

The default is: FLOA T. Power cycle is set to floating state.

6.               SMR NUMBER

Rectifier number, when used in the various components of the

system are numbered rectifiers. In one system, the number used

to identify each rectifier rectifier centralized control. This

parameter need to be adjusted when the component systems.

Page 24: ZX D800 15A Switching Rectifier

7.               SMR CONTROL

Single switch control, ON is open monomer, OFF is off monomer.

8.               BAT CONTROL (only RS-232 communication interface ZXD800 15A

switch rectifier has this feature).

Battery relay switch control, ON is a closed cell relay, OFF to

disconnect the battery relay.

 

1  

Page 25: ZX D800 15A Switching Rectifier

Chapter 5    Installation and Use

5.1   Installation ZXD80015A switch rectifier general access network with ZTE's products

used together, if used alone, can be placed on a shelf or on a shelf with

a porous, rectifiers and wall spacing of not less than 30 cm.

5.2   Input and output The rectifier input and output are on the rear panel is complete, shown

in Figure 5-1.

Figure 5-1 after the rectifier panel Figure

5.2.1   AC input

Input lines can use the standard single-phase three-wire power cord,

its diameter should be greater than 1 mm 2 .

5.2.2   DC output

Output lines using a dedicated four-wire power cord, which should be

greater than 3 mm 2 diameter . Respectively, then the battery positive

and negative, positive and negative loads. In connection should be

wired according to a sign on the rear panel.

5.2.3   Communication Interface

After the panel has a 9-pin socket provides a standard RS-232 or RS-485

interface, and a combination of power system monitoring backstage

Page 26: ZX D800 15A Switching Rectifier

access network to communicate with the operation or maintenance of

station communication.

5.2.4   Current sharing bus interface

When two or more switches 15A rectifiers in parallel, should have flow

on either end of the bus between two shorted. Short wiring using

ordinary signal cable.

5.3   The installation process The installation process is as follows (charged directly installed):

1.               The rectifier AC input into shutdown (OFF) state;

2.               The rectifier rectifier module is installed into the rack position;

3.               The rectifier is inserted in the end even slow;

4.               Check the AC input, serial cable, all flow lines, the DC output

jack is properly connected;

5.               Tighten the four captive screws on the panel and the rack;

6.               Close the AC input switch;

7.               Subject rectifier start to steady state (about 3 ~ 8s), observe the

output voltage, current and temperature LCD is normal, if there is an

alarm message, if not normal, you need to check the specific methods

refer to the manual, "Troubleshooting" section .

When the step rectifier failure or other reasons may need to replace

rectifier, rectifier demolition follows (System Power Off):

8.               AC input rectifier switch in the Off (OFF) state;

9.               Unplug the AC input rectifier;

10.               Unplug the DC output rectifier;

11.               If all flow lines, serial line should be removed;

12.               The panel of four fastening screws rectifier unloading;

13.               The rectifier uniform slowly withdrawn.

 

Page 27: ZX D800 15A Switching Rectifier

1  

Page 28: ZX D800 15A Switching Rectifier

Chapter 5   Installation and Use

Page 29: ZX D800 15A Switching Rectifier

Chapter 6    Maintenance and repair

6.1   Daily use This equipment should be used in a clean, airy room.

When used with multiple power should maximize the positive power

shelf space, where conditions permit, it is best to install air

conditioning or exhaust fans and other equipment.

Each rectifier during system installation parameters have been

adjusted, generally without further adjustment.

Need to prepare to run the daily operation of the rectifier records once

a year to maintain the need for testing.

Rectifier failure can not run, the processing method, see the manual

"Troubleshooting" section.

6.2   Troubleshooting The output current limit is a working state, not a failure, usually

without treatment.

And LCD display panel lights when not lit, check the AC power is

normal, the input switch is closed, if the normal AC input, the input

switch is closed, there is still no indication and LCD indicator, the

rectifier is faulty. If the indicator with LCD correctly, you can make the

appropriate treatment of the liquid crystal display according to the

message. Treatment as shown in Table 6-1.

Table 6-1 Troubleshooting Table

Alarm Code Fault information Treatment AL AC input low Check the AC input, AC input is abnormal if indeed, there was no

AH AC input high To be treated, wait AC input is normal, the load is powered by

the battery HV Output voltage is

high Unplug the DC output plug, reboot, if still alarms, rectifiers need

repair. SC Output short Unplug the DC output plug, reboot, if normal, you need to check

Page 30: ZX D800 15A Switching Rectifier

circuit the load, if still alarms, rectifier needs repair CL Output current

limit Check the output voltage, if the voltage at 46V or more, do not

deal with. But need to check whether caused by abnormal load

limit, if the output voltage is too low, you should reduce the load

to protect the rectifier and load. TH Main radiator

temperature is

high

Internal automatic limit protection

TV Main radiator

temperature Internal automatic shutdown

FF Fan failure Check whether the fan has stalled, missed, if the fan is damaged,

replace the fan BL Battery voltage is

low Check the battery voltage and battery and battery fuse breaker

BLL Battery voltage is

too low Check the battery voltage and battery and battery fuse breaker

When determining rectifier failure, immediately turn off the AC input

rectifier switch, unplug the DC output plug, if the backup rectifiers,

rectifier put back up, and notify the nearest maintenance center ZTE

ZTE engineering department or be dealt with, not on their own

disassemble, otherwise ZTE will not be responsible.

 

1  

Page 31: ZX D800 15A Switching Rectifier

Appendix A    Packaging, transportation and storage

A.1   Package

The device uses carton packaging, there are shockproof and

moisture-proof foam plastic bags.

A.2   Transport

Product transportation should be conducted in the packaging intact,

handling process may not violent vibration and impact, to prevent

moisture and rain.

A.3   Store

Product should be stored at -40 ℃ ~ 70 ℃, relative humidity less than

75%, non-corrosive gases, indoor air circulation, storage period of 24

months.

A.4   Random packing accessories

Product User Manual: 1

Product certification: a

25A Fuse: 1


Recommended