Page 1: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

-- SHADED AREA FIXTURE ON EMERGENCY CIRCUIT

BOX.CEILING MOUNTED LIGHTING FIXTURE AND OUTLET

--

LIGHTINGDESCRIPTIONSYMBOL

-- SHADED AREA FIXTURE ON EMERGENCY CIRCUIT

WALL MOUNTED LIGHTING FIXTURE AND OUTLET

--

BOX.

CEILING/WALL EXIT LIGHT AND OUTLET BOX,LED TYPE, SELF CONTAINED, WITH BATTERY PACK:- SHADED AREA INDICATES ILLUMINATED FACE(S)- ARROW INDICATES DIRECTION

EMERGENCY UNIT EQUIPMENT, 90 MINUTEBATTERY PACK, CHARGER AND TEST SWITCH.

NOTE: SEE LIGHT FIXTURE SCHEDULE AND SPECIFICATIONSFOR COMPLETE FIXTURE DESCRIPTION.

DESCRIPTIONSYMBOL

WIRING DEVICES

LINE VOLTAGE SWITCH- LOWER CASE LETTER DENOTES SWITCHING ZONES- 'T' DENOTES SWITCH TYPE:MC - MOMENTARY CONTACTD - DIMMERWP - WEATHER PROOF

LOW VOLTAGE SWITCH

OCCUPANCY SENSOR, CEILING MOUNTED

ABBREVIATIONSDESCRIPTIONSYMBOL

L

LTG

C

A, AMP AMPERE

AMPS INTERRUPTING CAPACITYAIC

AC ALTERNATING CURRENT

ABOVE FINISHED FLOORAFF

ATC AUTOMATIC TEMPERATURE CONTROL

AUTOMATIC TRANSFER SWITCHATS

BAS BUILDING AUTOMATION SYSTEM

BUILDING MANAGEMENT SYSTEMBMS

BFG BELOW FINISHED GRADEC, CDT CONDUIT

CIRCUIT BREAKERCB

CABINET HEIGHTCH

CKT CIRCUIT

CONDUIT ONLYC.O., CO

CONFIG. CONFIGURATION

CENTERLINE

CONVENIENCECONV

CM CONSTRUCTION MANAGER

DIGITAL DATA CONTROLDDC

DWG DRAWING

ELECTRICAL CONTRACTORE.C.

ELEC ELECTRICAL

EMERGENCYEM

EMT ELECTRICAL METALLIC TUBING

ELECTRICALLY OPERATED 'ON-OFF'E.O.

EQUALEQ

EWC ELECTRIC WATER COOLER

FIRE ALARMFAFAI FURNISH AND INSTALL

FS FIRE SHUTTER/DOOR

FULL LOAD AMPSFLA

FSD FIRE SMOKE DAMPER

GROUNDG, GND

GEN GENERATOR

GROUND FAULT CIRCUIT INTERRUPTERGFCI

HC HUNG CEILING

HIGH INTENSITY DISCHARGEHID

HAND-OFF-AUTOMATICHOA

HORSE POWERHP

INSTALLED BY ELECTRICAL CONTRACTORIBEC

FURNISHED BY OTHERSFBO

ISOLATED GROUNDIGJB,J JUNCTION BOX

KILO VOLT- AMPEREKVA

KW KILO WATT

KILO WATT HOURKWH

LC

LCP

LOCK & COVER

LIGHTING CONTROL PANEL

LIGHTING

LOW VOLTAGELV

LVR LOW VOLTAGE RELAY

MOTOR CONTROL CENTERMCC

MOTOR CONTROL PANELMCP

MER MECHANICAL EQUIPMENT ROOM

MANUFACTURERMFRR

MIN MINIMUM

MAIN LUGS ONLYMLO

MSB MAIN SWITCHBOARD

MOUNTEDMTD

N NEUTRAL

NOT APPLICABLENA, N/A

NEMA NATIONAL ELECTRICAL MANUFACTURERSASSOCIATION

N.C. NORMALLY CLOSED

NOT IN CONTRACTNIC

# NUMBER

NORMALLY OPENN.O.

NTS NOT TO SCALE

ON CENTEROC

POLESP

PB PULL BOX

POWER FACTOR CORRECTIONPFC

PH, ø PHASE

PANELPNL

PVC POLYVINYL CHLORIDE

POWERPWR

RC REHEAT COIL

RECEPTACLERECPT, REC

RM ROOM

SIGNAGESG

SHT SHEET

SPECIFICATIONSSPEC

SPDT SINGLE POLE DOUBLE THROW

SINGLE POLE SINGLE THROW

SWITCH

SPST

SW

SWBD

SWGR

SWITCHBOARD

SWITCHGEAR

TIME CLOCKTC

TYP TYPICAL

UNDERGROUNDUG

UON, U.O.N. UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLYUPS

UNF UNFUSED

VOLTV

VA VOLT-AMPERES

VACUUM PRESSURE IMPREGNATIONVPI

VAPOR TIGHTVT

W WATT

WEATHER PROOFWP

XFMR TRANSFORMER

POWERDESCRIPTIONSYMBOL

SAFETY DISCONNECT SWITCH, 3 POLE UONA: 30A UNFUSED AF: 30A FUSEDB: 60A UNFUSED BF: 60A FUSEDC: 100A UNFUSED CF: 100A FUSEDD: 200A UNFUSED DF: 200A FUSEDE: 400A UNFUSED EF: 400A FUSED- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

TRANSFORMER, SEE SCHEDULE FOR RATING

RELAY - NUMERAL DENOTES NUMBER OF POLES

SURFACE MOUNTED PANELBOARD

FLOOR MOUNTED DISTRIBUTION/SWITCHBOARD

CONDUIT AND WIRE HOMERUN. CONTINUOUS RUN TOMCC, PANELBOARD, SWITCHBOARD OR EQUIPMENTCABINET.

CONDUIT AND WIRE RUN IN WALL OR CEILING SPACE,OR RUN EXPOSED IN UNFINISHED SPACE.

FUSED DISCONNECT SWITCH- NUMERICAL DENOTES TRIP SIZE- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

AUTOMATIC TRANSFER SWITCH, SEE RISERDIAGRAM FOR RATING

FLUSH MOUNTED PANELBOARD

PULLBOX

R

HOSPITALDESCRIPTIONSYMBOL

NURSE CALL SYSTEM PATIENT STATION WALLMOUNTED OR ON PATIENT HEADWALL UNIT

NURSE CALL SYSTEM EMERGENCY STATION, WALLMOUNTED AT +48" UON.

NURSE CALL SYSTEM TOILET STATION, WALLMOUNTED AT +30" UON. WITH PULL CORD

NURSE CALL SYSTEM SHOWER STATION, WALLMOUNTED AT +60" UON. WITH PULL CORD

NURSE CALL SYSTEM DUTY STATION, WALLMOUNTED AT +48" UON.

NURSE CALL SYSTEM STAFF STATION, WALLMOUNTED AT +48" UON.

NURSE CALL CODE BLUSE STATION, WALL MOUNTAT +48" OR MOUNT ON PATIENT HEADWALL UON.

NURSE CALL SYSTEM DOME LIGHT, WALL MOUNTED(SEE ARCH. ELEVATORS FOR EXACT LOCATION)

NURSE CALL SYSTEM DOME LIGHT, CEILING MOUNT

NURSE CALL SYSTEM CONTROL PANEL

R 6

ATS

4x AF

J

J

J

T4

a,b

Ta,b

XP - EXPLOSION PROOF

O

OCCUPANCY SENSOR, WALL MOUNTEDO

PHOTOCELL CONTROLLER, CEILING MOUNTED

PHOTOCELL CONTROLLER, WALL MOUNTED

LIGHTING CONTACTOR

TIME CLOCK

PUSH BUTTON

REMOTE CONTROL SWITCHRC

TC

LC

SURGE SUPPRESSIONSS

XP EXPLOSION PROOF

SIMPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON

QUAD RECEPTACLE WALL MOUNTED, +18" AFF, UON

SPECIAL RECEPTACLE WALL MOUNTED, +18" AFF, UON

SIMPLEX RECEPTACLE CEILING MOUNTED

DUPLEX RECEPTACLE CEILING MOUNTED

QUAD RECEPTACLE CEILING MOUNTED

SPECIAL RECEPTACLE CEILING MOUNTED

SIMPLEX RECEPTACLE FLUSH FLOOR MOUNTED

DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED

QUAD RECEPTACLE FLUSH FLOOR MOUNTED

SPECIAL RECEPTACLE FLUSH FLOOR MOUNTED

JUNCTION BOX RECESSED WALL MOUNTED

JUNCTION BOX RECESSED CEILING MOUNTED

JUNCTION BOX RECESSED FLUSH FLOOR MOUNTED

LIGHTNING PROTECTION& GROUNDING

DESCRIPTIONSYMBOL- 'L' DENOTES LIGHTNING PROTECTION MAINCONDUCTOR

LIGHTING PROTECTION AIR TERMINAL

GROUND ELECTRODE CONNECTION TO EQUIPMENT

THRU ROOF PENETRATION CABLE IN CONDUIT

TRIANGULAR GROUND GRID - THREE 3/4" x10'-0" RODS SPACED 30'-0" MINIMUM APARTINTERCONNECTED WITH 4/0 COPPER CONDUCTOR.

THRU ROOF PENETRATION TO STEEL

FULL DOWNLEAD TO GROUND

STEEL COLUMN BOND TO GROUND

EXPOSED DOWNLEAD TO GROUND

2"x1/4" COPPER GROUND BUS BAR, LENGTH ASINDICATED ON PLANS.

- 'G' DENOTES COUNTERPOISE/GROUND CABLE

GROUND PLATE CONNECTION SOLID COPPER,24"x24"x20 GA.

GROUND ELECTRODE 3/4" COPPER ROD, 10'-0"DEEP - "TW" INDICATES TEST WELL

G

TW

L

PS

ES

TS

SH

DS

SS

NURSE CALL SYSTEM MASTER ANNUCIATOR STAT

CB

NCCP

MA

MISCELLANEOUSDESCRIPTIONSYMBOL

FEEDER SIZE, SEE FEEDER SCHEDULE

REFERENCE NOTE

DETAIL REFERENCE:- DETAIL DESIGNATION- SHEET NUMBER REFERENCE

EQUIPMENT REFERENCE. COORDINATE EQUIPMENTWITH MECHANICAL/PLUMBING TRADES. SEEMECHANICAL/PLUMBING DRAWINGS FOR LOCATIONS.

EF1

#

P380D

SINGLE LINE DIAGRAMDESCRIPTIONSYMBOL

PANELBOARD, SEE PANEL SCHEDULE FOR RATING.

MOLDED CASE CIRCUIT BREAKER:- 'TEXT' DENOTES CB ACCESSORIES

LOW VOLTAGE DRAW OUT CIRCUIT BREAKER:

MEDIUM VOLTAGE DRAW OUT CIRCUIT BREAKER

AUTOMATIC TRANSFER SWITCH

GENERATOR

UTILITY METER

DIGITAL MULTIFUNCTION METER WITHCURRENT/POTENTIAL TRANSFORMER AS REQUIRED

ST, ET. GFP, EO, LSI TRIP FUNCTIONS- NUMERICAL DENOTES TRIP SIZE

- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE

WITH INTEGRAL TRIP UNIT

LOW VOLTAGE FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES

ST, GFR, EO, LO, LOCK OUT PROVISIONS- NUMERICAL DENOTES FUSE SIZE

MEDIUM VOLTAGE DRAWOUT FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES FUSE SIZE

ENCLOSED CIRCUIT BREAKER- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE

ENCLOSED SAFETY DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE

ENCLOSED FUSED DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE

INTERMEDIATE CLASS MOV SURGE ARRESTER- NUMERICAL DENOTES ARRESTER RATING

MOTOR

AUTOMATIC TRANSFER SWITCHW/BYPASS ISOLATION

KEY INTERLOCK

RELAY NUMERICAL INDICATES TYPE

CURRENT TRANSFORMER:- '200/5' DENOTES CT RATIO IF INDICATED

POTENTIAL TRANSFORMER:- NUMERICAL DENOTES QUANTITY OF FUSES

INVERTER

RECTIFIER

BATTERY

TRANSFORMER WITH PRIMARY ANDSECONDARY CONNECTIONSAS INDICATED ON RISER DIAGRAM.

M

A

FEEDER

BUSWAY

PANEL

1

51

BW

200/5

KI

GFPTRIP

N E

L

LSITRIP

STTRIP

STTRIP

GFP

FUSE

M VA

52

GFP

FUSE

G

M

SA

12KV

ATS-#CONNAMPS

ATS-#CONNAMPS

DIGITAL ENERGY METERM

DUPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON

X

LETTER DESIGNATION ON RECEPTACLES:A = ARC FAULT CIRCUIT INTERRUPTERG = GROUND FAULT CIRCUIT INTERRUPTERIG = ISOLATED GROUNDWP = WEATHER PROOF WITH 'GFCI'S = SAFETYCT = ABOVE COUNTERCR = CRITICALEQ = EQUIPMENTLS = LIFE SAFETY+X" = INDICATES MOUNTING HEIGHTSHADING = INDICATES RECEPTACLE ON EMERGENCY

CONDUIT AND WIRE RUN EXPOSED ON WALL ORCEILING IN FINISHED SPACE.

CONDUIT AND WIRE RUN CONCEALED IN SLAB, UNDERSLAB OR UNDERGROUND

GROUND CONNECTION

MOTOR CONTROL EQUIPMENT AND CONNECTION TOCONTROLLED MOTOR(S). CONTROLLER IS MOUNTEDAGAINST AN ADJACENT WALL OR OTHERWISEREMOTE FROM THE MOTOR. SEE MOTOR EQUIPMENTSCHEDULE(S) FOR CIRCUITING, TYPE OF CONTROLEQUIPMENT, QUANTITY OF MOTORS CONNECTED TOCONTROLLER, AND OTHER DETAILS. CONDUCTOR SIZEBETWEEN CONTROLLER AND MOTOR SHALL MATCHTHE UPSTREAM OF THE CONTROLLER UNLESS NOTEDOTHERWISE ON THE SCHEDULE.MOTOR CONTROL EQUIPMENT AND CONNECTION TOCONTROLLED MOTOR(S). CONTROLLER IS EITHERINTEGRAL TO THE EQUIPMENT OR MOUNTEDDIRECTLY ONTO THE EQUIPMENT. SEE MOTOREQUIPMENT SCHEDULE(S) FOR CIRCUITING, TYPE OFCONTROL EQUIPMENT, QUANTITY OF MOTORSCONNECTED TO CONTROLLER, AND OTHER DETAILS.CONDUCTOR SIZE BETWEEN CONTROLLER ANDMOTOR SHALL MATCH THE UPSTREAM OF THECONTROLLER UNLESS NOTED OTHERWISE ON THESCHEDULE.

CB4x 225

+X"

ACCESS FLOOR BOX WITH OUTLETS AS SPECIFIED

POKE THROUGH FLOOR BOX WITH OUTLETS ASSPECIFIED

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT CAPPED

ARC FAULT CIRCUIT INTERRUPTERAFCI

RACEWAYS

FLEXIBLE CONNECTION

CONDUIT AND WIRE, HASH MARKS INDICATE NUMBEROF WIRES. # HASH MARKS INDICATES 3#12+1#10N+1#12G IN 3/4" CONDUIT UON.

P

P

E-3A

DESCRIPTION

FIRE ALARM SYMBOLSSYMBOL

FIRE SERVICE OR EMERGENCY TELEPHONEJ - JACKFTS - FIRE FIGHTER’s TELEPHONE SYSTEM

MANUAL PULL STATION

MANUAL STATIONHL - HALON

CO2 - CARBON DIOXIDE

FO - FOAMWM - WATER MISTDL - DELUGE SPRINKLERPRE - PREACTION SYSTEM

ABORT SWITCHHL - HALON

CO2 - CARBON DIOXIDECA - CLEAN AGENT

DL - DELUGE SPRINKLERPRE - PREACTION SYSTEMEPO - EMERGENCY POWER OFF

HEAT DETECTORR/F - RATE OF RISE AND FIXED TEMPERATURER/C - RATE COMPENSATIONF - FIXED TEMPERATURER - RATE OF RISE ONLY

SMOKE DETECTORP - PHOTOELECTRICBR - BEAM RECEIVERBT - BEAM TRANSMITTER

SMOKE DETECTOR FOR DUCT

SMOKE/HEAT DETECTOR

HEAT LINE-TYPE DETECTOR(HEAT SENSITIVE CABLE)

GAS DETECTOR

FLAME DETECTORF - FLAMEUV - ULTRAVIOLETUV/IR - COMBINATION ULTRAVIOLET/INFRAREDVR - VISIBLE RADIATION

ADDRESSABLE MODULEAIM - INPUTAOM - OUTPUT

FLOW DETECTOR/SWITCH

PRESSURE DETECTOR/SWITCHW - WATERLA - LOW AIRHA - HIGH AIR

LEVEL DETECTOR/SWITCH

TAMPER DETECTOR/SWITCH

VALVE TAMPER DETECTOR/SWITCH

OUTPUT RELAY

TEMPERATURE SWITCHHT - HIGH TEMPERATURELT - LOW TEMPERATURE

AUDIO DEVICE (WALL MOUNTED)H - HORNS - SPEAKER

C - CHIMEM - MINI

AUDIO DEVICE (CEILING MOUNTED)H - HORNS - SPEAKER

C - CHIME

STROBE (WALL MOUNTED)

STROBE (CEILING MOUNTED)

AUDIO/VISUAL COMBINATION (WALL MOUNTED)H - HORNS - SPEAKER

C - CHIME

AUDIO/VISUAL COMBINATION (CEILING MOUNTED)H - HORNS - SPEAKER

C - CHIME

ROTATED BEACON

BELL (WALL MOUNTED)V - VIBRATING

VS - VIBRATING/STROBEGS - GONG/STROBE

DOOR HOLDER FLOOR/DOOR

FIRE ALARM CONTROL PANEL

FIRE SYSTEM ANNUNCIATOR ALARM

AIR SAMPLING CONTROL DETECTOR PANEL

ELEVATOR STATUS/RECALL

FIRE ALARM COMMUNICATOR

HVAC CONTROL PANEL

VOICE EVACUATION PANEL

FIRE ALARM TERMINAL CABINET

FIRE ALARM TRANSPONDER

DATA GATHERING PANEL

FIRE COMMAND SYSTEM

SPRINKLER ALARM PANEL

RELAY ALARM PANEL

PURGE PANEL

FIRE ALARM CONTROL UNIT

BATTERY PACK AND CHARGER

AMPLIFIER RACK

FIRE SYSTEM CONTROL PANELHL - HALON

CO2 - CARBON DIOXIDE

DC - DRY CHEMICALWC - WET CHEMICALDL - DELUGE SPRINKLER

REMOTE TEST SWITCH

DC - DRY CHEMICALWC - WET CHEMICALCA - CLEAN AGENT

DC - DRY CHEMICALFO - FOAM WC - WET CHEMICAL

WM - WATER MIST

P - PHONE

I - IONIZATIONASD - AIR SAMPLING

IR - INFRARED

G - GONG

FO - FOAMWM - WATER MIST

T - TROUBLE

CA - CLEAN AGENT

HL

AIM

AMP

ASFP

H

H

H

H

BATT

GS

DGP

J

ESR

EVAC

FAC

FACP

FACU

FATC

FCS

F

FSA

FSCPHL

FTR

HVA

P

HL

R

PP

LA

RTS

RP

SAP

FIRE SYSTEM ANNUNCIATOR PANELFSAP

P

R

HT

F

A - ACCESSIBLE

PB

PLAN NORTH

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

12" = 1'-0"

ELECTRICAL -SYMBOLS,ABBREVIATIONS, ANDDRAWING LIST

WT-1-E.0.01

PACKAGE 1

ELECTRICAL DRAWING LISTDRG NO. DRAWING TITLE SCALE

WT-1-E.0.01 ELECTRICAL - SYMBOLS, ABBREVIATIONS, AND DRAWING LIST NTSWT-1-E.2.30 ELECTRICAL - SEGMENT THREE - BASEMENT - POWER PLAN 1/8" = 1'-0"WT-1-E.4.00.1 ELECTRICAL - SINGLE LINE DIAGRAM - SHEET 1 NTSWT-1-E.4.00.2 ELECTRICAL - SINGLE LINE DIAGRAM - SHEET 2 NTSWT-1-E.7.00.1 ELECTRICAL - BASEMENT - PARTIAL PLANS 1/4" = 1'-0"

No. Date Description

Page 2: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

BB AA ABCEFJLNOPQRS.TU.VXYZ DGHKMW

28

27

26

24

22

21

20

19

18

17

16

15

14

13

12

11

10

8

7

6

5

4

3

2

1

9

23

25

USS-BA

USS-BB

BLB

BLL

BEHC

BETC

BELC

BLC

BHC

BDPC

BLK

BLH

BLG

BLA

BHA

BLJ

PC-3

PC-2

PC-1

BEHABETA

BELA

BDPA

PLAN NORTH

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

1/8" = 1'-0"

ELECTRICAL -SEGMENT THREE -BASEMENT - POWERPLAN

WT-1-E.2.30

PACKAGE 1

No. Date Description

1/8" = 1'-0"1 BASEMENT - SEGMENT THREE

Page 3: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

1500KVA4160/208V

USS-BA-TX

BASEMENT

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4

LEVEL 5

LEVEL 6

LEVEL 7

ROOF

200A

APS2100A MLO208/120VWPA - CULLEN

225A MLO208/120V

PC460kVA

APL2225A MLO208/120V

PC560kVA

UP2A100A MLO208/120V

4#600MCMIN 3 1/2"

BULLSWITCH

BROWN #1208V

UPS2100A

208/120V

UPS1200A

208/120V

UPL1225A

208/120V

4#600MCMIN 3 1/2"

BULLSWITCH

CULLEN #1208V

BULLSWITCH

CULLEN #2208V

UPL2A-LT225A MLO208/120V

UPL2A-RT225A MLO208/120V

WPB - CULLEN225A MLO208/120V

WPA - BROWN225A MLO208/120V

WPB - BROWN225A MLO208/120V

UPL1A225A

208/120V

RENTALSOUNDSWITCH

208V

RENTALSOUNDSWITCH

208V

UPL2225A

208/120V

CULLEN STAGE BROWN STAGE

BULLSWITCH

BROWN #2208V

BULLSWITCH

BROWN #3208V

BULLSWITCH

BROWN #4208V

RENTALSOUNDSWITCH

208V

USS-BA4000A MCB, 208/120V 3PH., 4W, 100KAIC

200A 200A 200A 200A 150A 100A150A 400A200A 100A 200A 400A 400A 200A400A 400A 200A 200A 200A 200A 60A 200A100A 2 X 400APROVISION

4 X 100APROVISION

LSIG4000A

M VA

2 X 225APROVISION

NOT IN THE SCOPE OF THIS BID

SPD 250kA

MSB, 4160V

P380

D

P380

D

P200

D

P200

D

P150

DP1

50D

P150

DP1

50DP2

00D

P70D

P110

D

P200

D

P200

D

P200

D

P200

D

P200

D

P200

D

P110

D

P380

D

P380

D

P380

D

P380

D

P200

D

P70D

P200

D

PLAN NORTH

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

12" = 1'-0"

ELECTRICAL - SINGLELINE DIAGRAM -SHEET 1

WT-1-E.4.00.1

PACKAGE 1

No. Date Description

Page 4: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

MSB, 4160V

BASEMENT

LEVEL 1

LEVEL 2

LEVEL 3

LEVEL 4

LEVEL 5

LEVEL 6

LEVEL 7

ROOF

USS-BB4000A MCB, 208/120V 3PH., 4W, 100KAIC

1500KVA4160/208V

USS-BB-TX400A

ASS1

2LA100 MLO208/120V

1LA100 MLO208/120V

PC760kVA

D6

EMERGENCYCIRCUITS

FROM 3ELA

3LA100 MLO208/120V

APS1 APL1

PC140kVA

PC240kVA

ASL1

PC340kVA

UPL3 UPS3

P85D

P200

D

P150

D

P55D

P110

D

P110

D

P110

D

P110

D

P110

D

P150

D

P110

D

P200

D

D5

EMERGENCYCIRCUITS FEDFROM BELBREHERSAL

STORAGE NEARTO ELEC (2.B.39)E2.20

P110

D

P70D

P110

D

WAGONLIFT208V

M VA

100A 150A 150A100A 60A 50A 200A 200A 100A 200A 100A

FUTURE400A MLO208/120V

P380

D

400A

FUTURE400A MLO208/120V

P380

D

400A

FUTURE225A MLO208/120V

P230

D

225A

FUTURE225A MLO208/120V

P230

D

225A

FUTURE225A MLO208/120V

P230

D

225A

FUTURE225A MLO208/120V

P230

D

225A

FUTURE225A MLO208/120V

P230

D

225A 2 X 400APROVISION

4 X 100APROVISION

2 X 225APROVISION

P200

D

200A

P200

D

200A

LOADINGDOCK

(KLIEGL)208V

LOADINGDOCK

(KLIEGL)208V

NOT IN THE SCOPE OF THIS BID

SPD

LSIG4000A

250kA

PLAN NORTH

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

12" = 1'-0"

ELECTRICAL - SINGLELINE DIAGRAM -SHEET 2

WT-1-E.4.00.2

PACKAGE 1

No. Date Description

Page 5: WT-1-E.0 - Houston First | Houston First Corporation · PDF file · 2018-01-12cb circuit breaker ch cabinet height ckt circuit c.o., co conduit only ... vpi vacuum pressure impregnation

V

X

Y

Z

W

24 22 21 20 19 18 172325

USS-BA

USS-BB

BELA

BEHA

PC-1 PC-2 PC-3

BLJ

BHA

BLA

BLG

(SUSPENDED)

2' - 0"

2' - 0

"

2' - 0

"

2' - 0"

REMOVABLE FLOOR SECTION.

22' - 11"

5' - 6

"9'

- 0"

2' - 0

"

TOP VIEW

FRONT VIEW

SECONDARYDISTRIBUTION SECTION120/208V 3PH., 4W.

TRANSFORMER SECTION4160V 3PH., 3W - 120/208V4PH., 4W

INCOMING SECTION4160V 3PH. 3W

TOP HAT SECTION

*NOTE: DIMENSIONS ARE PROVIDED AS MAXIMUMS FOR A FRONT ACCESS ONLY UNIT SUBSTATION.REFER TO SINGLE LINE DIAGAMS FOR ADDITIONAL INFORMATION.

Project Team

WORTHAMTHEATERREHABILITATION501 Texas AveHouston, TX 77002

Scale:

© Copyright 2018All information, drawn, written, or implied, appearing in thisdocument constitutes the original and unpublished work ofHarrisonKornberg Architects, LLC. and may not beduplicated, distributed, or disclosed by any means withoutthe prior written consent of HarrisonKornberg Architects,LLC. This is an instrument of services and sole property ofthe author. The use of this document shall be revoked if anyof the design intent or the construction methods shownherein are not adhered to, or the terms of the contractualagreement for its use is violated.Written dimensions on these drawings shall haveprecedence over scale dimensions. Contractors shall beresponsible for all dimensions and conditions on the job.HarrisonKornberg Architects, LLC must be notified of anyvariation from the dimension and conditions shown bythese drawings.

3800 Buffalo Speedway, Suite 550Houston, Texas 77098tel (713) 229-0688fax (713) 229-0692

ARCHITECTHarrisonKornbergContact: David Kaczynskit: 713.229.0688

A

B

C

D

E

F

G

H

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

Date:Project Name: HFR 12/27/2017

Issue for Bid

701 Avenida de las AmericasHouston, TX 77010

CIVIL ENGINEERMartinez MooreContact: TBDt: TBD

MEP ENGINEERArupContact: Tom Smitht: 713.343.1472

PARKING CONSULTANTWalker ParkingContact: Jeremy Rochat: TBD

ACOUSTICS / AV / ITJaffe HoldenContact: Garth Hemphillt: TBD

Key Plan

Revisions

01-12-2018

As indicated

ELECTRICAL -BASEMENT - PARTIALPLANS

WT-1-E.7.00.1

PACKAGE 1

1/4" = 1'-0"1 Enlarged Electrical Room B80

2 Electrical Room B80 Isometric

1/8" = 1'-0"3TYPICAL UNIT SUBSTATION ELEVATIONDETAIL

No. Date Description


Recommended