Substrate Viking SuperStrandor F11 Roofing ply
Viking CertainTeed Underlayrefer CT17 and CT18 for
requirements
Truss or Rafter
Viking CertainTeed ShinglesNail fixed to Plywood or SuperStrand sarking
Refer to Viking CertainTeed specification for fixing details in required wind-zone
Step Flashingrefer CT09
Barge detailrefer CT06
Vented ridgerefer CT02
Drip-edgerefer CT01
Valley detailsrefer CT07 and CT08
Pipe penetrationrefer CT15
Viking CertainTeed ShinglesGeneral Roof details Details
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Metal drip-edge flashing
CertainTeed Shingles
Viking Underlay
Plywood or SuperStrand sarkingSubstrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Timber nog required to support bottom edge of substratenot to restrict airflow for ventilation
Airflow gap 10mm above top of Fascia
Air flow for vented intake
30mm
10mm
Viking CertainTeed ShinglesVented Drip-edge Detail CT01 CT01
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
AirflowAirflow
Air gap20mm
minimum
Air gapmin. 20mm
AirflowAirflow
Viking CertainTeedLow Profile Ridge Vent 16mm depth
Viking CertainTeed Shingles
Viking CertainTeed Underlay
Viking CertainTeed Ridge Vent 25mm depthwith ridge Cap installed
Plywood orSuperstrandsarking
Viking CertainTeed ShinglesRidge Vent Detail CT02 CT02
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Min. 20mm unrestricted Air flow
min. 20mm
Refer Table 7 E2/AS1
Viking CertainTeed Shingles
Viking CertainTeed Underlay
Truss or Rafter
Nog to support edgeof substrate
Nail vent to Plywood@ 600mm centres
Viking CertainTeed Ridge Vent DDE265divided in half
NOTE: Min. shingle roof pitch is 9°
Viking CertainTeed ShinglesMonopitch Ridge Vent Detail CT03 CT03
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Airflow uninhibited Roof Cavity (min 25mm)
Viking CertainTeed Shingles
Viking CertainTeed Underlay
Viking Shingle Nails32 x 3.2mm S/S 10mm round Flathead
Viking Waterproof MembraneDiscuss with Viking Roofspecbest option to secure to metal flashing
Optional Dress Shingle if required for astheticsadhered with Viking Pitched Roofing Sealant SES013Ø20mm @ 100mm centres
Metal Flashing with hemmed edgefor added strength to hold firm over vent
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
* Alternative ventilationconsider venting through the membrane roof area if roof structure allows good unrestricted airflow.Allow additional cavity vent for every 50m2 pitched roof area
Air gap20mm Min.
*Viking CertainTeed RidgeVent DDE265 divided in half
Viking CertainTeed ShinglesMansard Vented edge Detail CT04 CT04
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Airflow Roof Cavity (min 25mm)
Nail to Substrate @ 600mm centres
Viking Skirt Vent DDE200
Viking CertainTeed Shingles
Viking CertainTeed Underlay
150mm
20mm
Viking CertainTeed ShinglesLower Vented Roof Detail CT05 CT05
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
refer Table 7 E2/AS1
15mm overhang
70mm
Viking CertainTeed Shingles
Barge Flashing
Viking Pitched Roofing Sealant SES013
Viking CertainTeed Underlay
Viking CertainTeed ShinglesBarge edge Detail CT06 CT06
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
250mm450mm
50mmNOTE: Valley Detail
refer also detail CT08iso
Viking CertainTeed Shingles
Viking Shingle Nails32 x 3.2mm S/S 10mm round Flathead
Viking CertainTeed Hip Cap Shingle
Viking CertainTeed Underlay
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Apply a full width (900mm) of VikingUnderlay vertical to Plywood Roofing
Substrate Valley
Viking Underlay applied over firstshingle layer. Minimum 50mmoverlap over Shingle required.
Viking CertainTeed UnderlayMinimum 150mm overlap
Pitched Roofing Sealantno nails within 150mm of Valley center line
Viking CertainTeed ShinglesHip & Valley Detail CT07 CT07
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
DO NOT nail within 150mm of valley CentrelineViking Underlay Laps
Embed each shingle in 2 beads of
Viking Roofing Sealant SES013CUT (50mm) diagonally off upper corner
of trimmed shingle and removeREMOVEtrimmed shingle
cL
Line Valley by centering (914mm wide)
Viking Peel & Stick Underlay
NoteLay Shingles on smaller roof area,
across valley and onto adjoining
roof area at least 300mm
Viking CertainTeed ShinglesIsometric Valley Detail CT08iso CT08iso
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
100mm Apron Flashing
10mm Gap for water runoff
Step-Flashing under every individual Shingle. withmin.100mm overlap between flashings.Flashings to be placed just above shingle sealant line
Viking CertainTeed Shingles
No nailing through step flashinguse 20mm compressed spots of sealant
Corner lap to be securedwith Viking 76mm Lap Tape
Viking Butylclad Waterproofing MembraneStep Flashing 150mm wide
Viking CertainTeed Shingles
Viking CertainTeed Underlay
Pitched Roofing Sealant SES013no nails through Step Flashings
150m
m150mm
Min. 100mm
150mm
150mm
Viking CertainTeed ShinglesUpstand with Step Flashing Detail CT09 CT09
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
300mm wide Strip Butylclad Step-flashingminimum cover 150mm each on the upstand and shingle
Viking Kickout Flashing
Spouting
Viking CertainTeed ShinglesViking CertainTeed Underlay
Drip Edge Flashing
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Viking CertainTeed ShinglesDrip-edge with Diverter Detail CT10 CT10
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Viking CertainTeed selected Shingle
150m
m Ve
rtical
Heigh
t
150mm
Viking Waterproofing Membrane
Viking Waterproofing membrane detailover barge upstand
Dormer Roof
Viking CertainTeed ShinglesDormer to shingle junction Detail CT11 CT11
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Viking CertainTeed Shingles
Diverter Chased Apron Flashing by builder
Corner lap to be securedwith Viking 76mm Lap Tape
No nailing through step flashinguse 20mm compressed spots of CertainTeed sealant SES013 to secure
Step Flashing under ShinglesMinimum:100mm cover between flashings150mm upstand and 150mm on roof deck
Viking CertainTeed ShinglesChimney and Chase Flashing Detail CT12 CT12
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Viking CertainTeed Shingles
Chased Apron Flashing by builder
Corner lap to be securedwith Viking 76mm Lap Tape
No nailing through step flashinguse 20mm compressed spots of CertainTeed sealant SES013 to secure
Step Flashing under ShinglesMinimum:100mm cover between flashings150mm upstand and 150mm on roof deck
Diverter
Viking CertainTeed ShinglesAlternative Chimney Diverter CT12b CT12b
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Butylclad or metal Flashingrefer CT09 for side flashing
Viking CertainTeed Underlay
Viking CertainTeed Shingles
Aesthetic Tile adhered with 20mm spots ofSES013 CertainTeed Sealant
Generic skylight with proprietary cover flashings
min. 110mmupstand
Viking CertainTeed ShinglesSkylight Detail CT13 CT13
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Solar Panel fixing Bracket withsealed fasteners under Shingles
Solar Panel or similar
Viking CertainTeed Shinglesto cover brackets and fasteners
Structural support for fixing brackets
Viking CertainTeed ShinglesSolar Panel Fixings CT14 CT14
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Viking Pipe Boot placed over pipe and set inViking Roof sealant SES013
Upper and Side Shingles overlap flange andare set in Viking Roof sealant SES013
Plumber to overflash pipe boot
Lower Part of Flange overlaps lower ShinglesSpot seal with 20mm of pitched roofing sealant at 100mm centres
Step 1 Step 2
Viking CertainTeed ShinglesPipe Penetration Detail CT15 CT15
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Viking CertainTeed Shingles Viking CertainTeed Underlay
Truss or Rafter
Substrate as per Viking membrane specification
Viking GM torch-on2 Layer waterproofing System
50mm 200mm
upstandverticalheight
Viking CertainTeed Starter Shingle
Viking CertainTeed ShinglesMembrane roof to Pitched roof CT16 CT16
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Viking CertainTeed Shingles
Truss or Rafter
Viking CertainTeed Underlay
Viking Peel & Stickwaterproofing membrane 400mm minimum
Min. 200mm
Min. 20
0mm
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Viking Peel & StickNot to be placed over Shingle sealant line
*Min. 9° pitch fo
r shingle roofs
* Roof pitch 9°- 12° use only Viking Peel & Stick underlay.Roof Pitch 12°- 18°use either Viking Peel & Stick or double layer of Viking Synthetic UnderlayRoof Pitch 18° + single layer of Viking Synthetic Underlay is suitable
Viking CertainTeed ShinglesShingle Change in Pitch Detail CT17 CT17
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Viking CertainTeed underlay
Aesthetic Tile adhered with 20mm spots ofSES013 CertainTeed Sealant
0.55mm Colour Steel Flashing with Birdsbeakor 1mm Butyl rubber flashingrefer Table 7 E2/AS1 for coverage
Viking CertainTeed Shingles
*Min. 9° Pitch
* Roof pitch 9°- 12° use only Viking Peel & Stick underlay.Roof Pitch 12°- 18°use either Viking Peel & Stick or double layer of Viking Synthetic UnderlayRoof Pitch 18° + single layer of Viking Synthetic Underlay is suitable
Viking CertainTeed ShinglesNon-Vented Mansard / Change in Pitch CT18 CT18
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
Viking CertainTeed Shingles
Metal Valley Flashing
Viking CertainTeed Underlay
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Structural framing
Valley Nogging
250mm
Viking CertainTeed ShinglesAlternative Open Valley Detail CT19 CT19
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
MIN. 100mm Cover over membrane
Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz
Viking Waterproofing Membrane
Min fall in gutter 1:100 to external spoutingor specified Viking Proprietary outlet
Viking Membrane to provide150mm of vertical height
Note: No fixings through membrane below 150mm
Viking CertainTeed ShinglesMi
n. 15
0mm
upsta
nd
Viking CertainTeed ShinglesInternal Gutter CT20 CT20
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA
NOTE:This detail is to show a methodology forSaddle-flashings and kick-out diverters atjunctions.These Saddle-flashings are not supplied byViking Roofspec as they are fabricated forspecific junctions by others to fit variousjunctions and cladding needs.
Stage 1 Flexible Flashing tape adheredto wall underlay at rear of cavityminimum 50mm to all surfaces
Step 3Fabricated Saddle-flashing fitted over flexible
flashing tape behind the cavity.Size & depth of diverter to suit specified
cladding preventing water ingress enteringbehind cladding and cavity
150m
m
Min.
50mm
Cavity Battens and cladding overflashings.Note: NO nails through the flashings
NOTE: 2Refer Viking Typical details for vented apron details etc.
Barge Board
Barge Flashing
ExampleSaddle-flashing
refer table 7 of E2/AS1 for coverage
Viking CertainTeed ShinglesSaddle-flashing Methodology CT21 CT21
17/11/2016
DRAWING STATUS
ISSUEDetail Ref:DATE
DRAWN
Not to Scale
DRAWING TITLE NOTES:
Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz
INFORMATION ONLY
Viking
Substrate Indicative OnlyA