8/16/2019 TIE ROD Calculation
http://slidepdf.com/reader/full/tie-rod-calculation 1/1
TITLE CALCULATION FOR TIE-ROD IS TENSION Document # 120141200‐09‐101
FIFTH INDUSTRIAL SQUARE UPGRADING PROJECT, SHARJAH: REV. 1PS10B STORMWATER PUMPING STATION & RISING MAIN Date 11.05.16
By SVChkd RKAppd SS
CALCULATION FOR TIE‐ROD IS TENSION
1.80 m
2.54 m2
4.50 bar g
350.00 kN/m2
M52
0.001758 m2
4.00
222.66 kN
75.00 ksi517106.25 kN/m2
2.00
454.54 kN
Bolt size considered
Internal pressure
PROJECT
CLIENT
BOLT SIZE SELECTED IS SAFE SINCE TOTAL LOAD ON ONE BOLT IS LESS THAN ALLOWABLE TENSILE LOAD
Tensile Strength for SA‐276 SS316 bar
Safety factor
ALLOWABLE TENSILE LOAD (Tensile Strength x Bolt Stress Area / Safety factor)
UNITED ARAB EMIRATESMINISTRY OF PUBLIC WORKS
Internal pressure
Pipe area
Diameter of pipe
Tensile Strength
for
SA
‐276
SS316
bar
TOTAL LOAD ON ONE BOLT (Internal pressure x Pipe area / no of bolts)
No of bolts
Bolt Stress area
C:\Users\Sleiman.Shokr\Desktop\TIE ROD
Calculati