A complete range of automatic and remotely operated transfer switches from 40 to 160 A
The ATyS M range:safe and reliable solutions
RTSE(Remotely operated)
ATSE(Automatic)
Mains/mains and mains/gensetTripping function, programmable parameters and communication
ATyS p MAutomatic Transfer
Switching Equipment
Dual power supply
ATyS d MMotorised Transfer
Switching Equipment
Automatic controller to manage mains/mains applications
ATyS t MAutomatic Transfer
Switching Equipment
Automatic controller to manage mains/genset applications
ATyS g MAutomatic Transfer
Switching Equipment
416 General Catalogue 2017-2018
Order at 訂貨熱線:
香港批發 /分銷 T (852) 2781 2855
澳門批發 /分銷 T (853) 2822 2751
工程 /商業項目 T (852) 2691 9166E [email protected]
Secure operationElectrical and mechanical interlocking for optimum safety.Positive break indication with two mechanical switch position indicators for clear and secure use.Padlocking in the 0 position enables the lockout function on each product.Padlocking in 3 positions can also be configured prior to installation.Permanent indication of product availability thanks to the Watchdog relay, which constantly monitors the product operating conditions (ATyS g M and ATyS p M).
Highperformance
On-load making and isolation for using a single product with any load type, including inductive loads (AC-33).Immunity to control voltage fluctuations thanks to stable positions and power supply only required during switching.Excellent dynamic withstand for improved safety when closing on a short-circuit.Extremely low electrical blackout time
the electromagnetic actuator technology used with rotary self-cleaning contacts.
A fully compact solutionAll-in-one solution, with minimum risk of incorrect mounting or wiring.Highly reliable thanks to the compliance
transfer switching equipment.Simplified ordering process: a single reference for the complete solution.
Intuitiveuse
Manual emergency control:The product can be operated quickly and safely using an emergency handle.Simple selection of operating mode (Auto/Manual) using an integrated selector.
Rapidcommissioning
ATyS d M: No configuration required.ATyS t M and ATyS g M: Configuration in just a few minutes using a screwdriver.ATyS p M: Simplified configuration
on the device).
Easy to installTwo switching devices mounted side-by-side for easy access to cabling with installation in a standard 18 module enclosure (product has a very low depth).Quick and easy mounting on a DIN rail or back plate.Simplified wiring thanks to the cage clamp terminals and dedicated bridging bars that allows a common outgoing connection whilst retaining the cage terminal connections.
The advantages
> Study, definition, advice, implementation, maintenance and training…
> Our Expert Services team offers customised support to make your project a success.
Expert Services
The ATyS M range:safe and reliable solutions
IEC 60947-6-1 / GB 14048-11> AC 32B - up to 160 A> AC 33B - up to 125 A> AC 33iB - up to 160 A
IEC 60947-3> AC 23B - up to 160 A
Performance
417General Catalogue 2017-2018
Tran
sfer
sw
itche
sATyS d MRemotely operated Transfer Switching Equipmentfrom 40 to 160 A
Function
Advantages
ATyS d M devices are 2 pole or 4 pole transfer switches that are remotely controlled using volt-free contacts from an external controller. They are modular products with positive break indication. They are intended for use in low voltage power supply systems where a brief interruption of the load supply is acceptable during transfer.
SecureATyS M have both electrical and mechanical interlocks for optimum security. They also feature a positive break indicator, confirming switch position with dual mechanical indicators for increased safety.
High-speed transferATyS d M devices are based on a coil solution with rotating contacts, therefore ensuring an extremely short black-out duration (< 90ms).
Superior electrical performanceATyS M devices are compliant with
transfer switches. Their AC-33B properties of up to 125 A mean you can use the same product for resistive and inductive loads.
Immune to voltage fluctuationsThe power supply of the ATyS d M is only active during transfer. As the product is based on stable positions, it is not affected by network voltage fluctuations.
> Applications with a normal/emergency external controller
> Building Management System (BMS)
The solution for
> Secure> Superior electrical
performance> High-speed transfer> Immune to voltage
fluctuations
Strong points
Operating modes
Padlocking facilityManual emergency operation
ATyS
m_0
16_c
_1_c
at
ATyS
m_0
15_c
_1_c
at
> IEC 60947-6,-1> IEC 60947-3> GB 14048.11
Conformity to standards
Approvals and certifications
Easy selection of AUT/MAN mode
ATyS
m_0
14_c
ATyS d M I-0-II 4P
atys
-dm
_002
_b_1
_cat
418 General Catalogue 2017-2018
ATyS d MRemotely operated Transfer Switching Equipment
from 40 to 160 A
ATyS
m_0
42_b
_1_g
b_ca
t
Electrical controlThe positions are controlled by dry contacts on any external automated system (e.g. ATyS C30). These positions are stable even in case of loss of input supply.
Control logicTwo types of control logic are offered:
Pulse logic- A switching command of at
least 60 ms is necessary to initiate operation.
- Commands I and II have priority over command 0.
- The first command received (I or II) has priority as long as it remains present.
Contactor logic- Command 0 must be
maintained.- If command I or II disappears,
the device returns to position 0, so long as the power supply is available.
ATyS
m_0
29_c
Three-phase interface
ATyS
m_2
02_b
Single-phase interface
Power supply
These two supplies can be connected individually; one to switch I and the other to switch II:- Power supply 101-102 must be available to reach position I- Power supply 201-202 must be available to reach position II.The use of a dual power supply (DPS) or an external supply module secures the command of the 3 positions irrespective of the power supply source.In this case, both the supply inputs must be connected in parallel.
ReferencesATyS d M
Rating (A) No. of poles ATyS d M Bridging barsVoltage sensing and
power supply tap Terminal shrouds Auxiliary contact block
40 A2 P 9323 2004
2 P1309 2006
4 P1309 4006 2 pieces1399 4006
2 pieces2294 4016(1)
1st unitincluded
2nd unitSeparate common points
1309 0001(2)
Linked common points1309 0011(2)
4 P 9323 4004
63 A2 P 9323 20064 P 9323 40062 P 9323 20084 P 9323 4008
100 A2 P 9323 20104 P 9323 4010
125 A2 P 9323 20124 P 9323 4012
160 A2 P 9323 2016 1309 20164 P 9323 4016 1309 4016
(1) For the three-phase version, for complete upstream and downstream protection, please order 2x; for the single-phase version please order the part just 1x.(2) 1 NO/NC contact block for positions I, 0 and II.
What you need to know
order I
Impulse logic
Imp. ≥60ms maintained
Contactor logic
order O
order II
position I
position O
position II
102 101 201202
POWER POWER
102 101 201202
DPS
POWER POWER
ON ON
ON ON ON ON
ON ON
ON ONON ON
OR OR OR OR
419General Catalogue 2017-2018
Tran
sfer
sw
itche
sATyS t M - ATyS g MAutomatic Transfer Switching Equipmentfrom 40 to 160 A
ATyS g M I-0-II 2P
atys
-gm
_001
_b_1
_cat
ATyS t M I-0-II 4P at
ys-tm
_001
_b_1
_cat
> High-rise buildings> Data centers> Healthcare buildings
The solution for
> Fast commissioning> ATyS d M with an integrated
controller for dedicated mains/mains or mains/genset functions
> Secure programming
Strong points
> IEC 60947-6,-1> IEC 60947-3> GB 14048.11
Conformity to standards
Approvals and certifications(1)
(1) Product references on request.
Function
Advantages
ATyS t M and ATyS g M are modular automatic transfer switches with positive break indication. ATyS t M are 4 pole (three-phase) devices and ATyS g M are 2 or 4 pole (single or three-phase) devices.They have all the functions of the ATyS d M together with an integrated controller, giving them automatic features dedicated to mains/mains (ATyS t M) and mains/genset (ATyS g M) applications. They are intended for use in low voltage power supply systems where a brief interruption of the load supply is acceptable during transfer.
Quick startATyS t M and g M transfer switches offer significant time saving during commissioning (the process takes 2 to 3 minutes). Thanks to the design that allows commissioning through just one potentiometer (4 on the ATyS g M) and four DIP switches, a screwdriver is all that is required to configure the parameters.
ATyS g M: dedicated to mains/genset applicationsIn addition to its single-phase and three-phase voltage & frequency monitoring for both incoming sources, the product’s integrated controller also features functions that are specific to mains/genset applications (genset control, test on load, etc.).
ATyS t M: dedicated to three-phase mains/mains applicationsThe ATyS t M integrated controller has been designed to provide all the functions necessary for these applications (operation with or without priority, preferred source selection) together with the monitoring of the voltage and frequency of both sources for three-phase networks.
Secure programmingTo ensure that the correct configuration is maintained an optional sealable cover can be fitted in order to avoid any unintentional modifications to the programming.
420 General Catalogue 2017-2018
ATyS t M - ATyS g MAutomatic Transfer Switching Equipment
from 40 to 160 A
ReferencesATyS t M
Rating (A) No. of poles Network (VAC) ATyS t MBridging
bars
Voltage sensing and power supply tap
Terminal shrouds
Auxiliary contact block
Sealablecover
40 A 4 P 230/400 9344 4004
4 P1309 4006 2 pieces
1399 40062 pieces
2294 4016(1)
1 unitSeparate common points
1309 0001(2)Linked common points
1309 0011(2)
1359 0000
63 A 4 P 230/400 9344 400680 A 4 P 230/400 9344 4008100 A 4 P 230/400 9344 4010125 A 4 P 230/400 9344 4012160 A 4 P 230/400 9344 4016 1309 4016
(1) For complete upstream and downstream protection please order quantity 2.(2) 1 NO/NC contact block for positions I, 0 and II.
ATyS g M
Rating (A) No. of poles Network (VAC)(3) ATyS g MBridging
bars
Voltage sensing and power supply tap
Terminal shrouds
Auxiliary contact block
Sealablecover
40 A2 P 230 9353 2004
2 P1309 2006
4 P1309 4006 2 pieces1399 4006
2 pieces2294 4016(1)
1 unitSeparate common
points1309 0001(2)
Linked common points
1309 0011(2)
2 P1359 2000
4 P1359 0000
4 P 230/400 9354 4004
63 A2 P 230 9353 20064 P 230/400 9354 4006
80 A2 P 230 9353 20084 P 230/400 9354 4008
100 A2 P 230 9353 20104 P 230/400 9354 4010
125 A2 P 230 9353 20124 P 230/400 9354 4012
160 A2 P 230 9353 2016 1309 20164 P 230/400 9354 4016 1309 4016
(1) 4 pole version - for complete upstream and downstream protection please order quantity 2; for 2 pole version order quantity 1.(2) 1 NO/NC contact block for positions I, 0 and II.(3) For 127/230VAC networks, please contact your supplier.
What you need to knowThe ATyS t M and ATyS g M are automatic transfer switching equipment that include a fully integrated ATS controller. These products are self powered from incoming supplies: 230 VAC (176-288 VAC), 50/60 Hz (45/65Hz).
421General Catalogue 2017-2018
Tran
sfer
sw
itche
sATyS p MAutomatic Transfer Switching Equipmentfrom 40 to 160 A
atyy
s-pm
_001
_b_1
_cat
ATyS p M I-0-II 4P
> High-rise buildings> Data centres> Healthcare buildings> Banks and insurance
companies> Transport (airports, tunnels, etc.)
The solution for
> Flexible programming > Trip function> Communication and
configuration> Remote control interface
Strong points
> IEC 60947-6,-1> IEC 60947-3> GB 14048.11
Conformity to standards
Approvals and certifications
Function
Advantages
ATyS p M are single-phase or three-phase modular automatic transfer switches with positive break indication.Functions include ATyS t M and ATyS g M capability, with additional programmable parameters and a tripping function. A product model with communication is available. They are intended for use in low voltage power supply systems where a brief interruption of the load supply is acceptable during transfer.
Flexible programmingATyS p M time delays and inputs/outputs are completely configurable, hence enabling the easy monitoring of specific applications (load shedding, test…) and the definition of an operating cycle specifically adapted to your application.
Trip functionATyS p M features a function for returning to the 0 position in case of the loss of both power supply sources (tripping). This protects the load from issues due to source instability.
Communication and configuration A specific version of ATyS p M is available with integrated Modbus communication. This gives acces to most product data (status, voltages, frequencies…). A user friendly configuration software is also available free (Easyconfig) to configure, view and save all the parameters in the ATyS p M.
Remote control interfaceSpecifically designed for installations where the product is enclosed, the remote interface displays product status on the front panel (D10) or displays and controls with access to programming (D20).
422 General Catalogue 2017-2018
ATyS p MAutomatic Transfer Switching Equipment
from 40 to 160 A
ATyS p M
Rating (A)No. of poles
Network(VAC) (3) ATyS p M
ATyS p M+ com Bridging bars
Voltage sensing and power supply tap Terminal shrouds
Auxiliary contact block Remote interface
40 A 4 P 230/400 9364 4004 9384 4004
4 P1309 4006 2 pieces
1399 40062 pieces
2294 4016(1)
1 pieceSeparate common
points1309 0001(2)
Linked common points1309 0011(2)
D109599 2010
D209599 2020
63 A 4 P 230/400 9364 4006 9384 400680 A 4 P 230/400 9364 4008 9384 4008100 A 4 P 230/400 9364 4010 9384 4010125 A 4 P 230/400 9364 4012 9384 4012160 A 4 P 230/400 9364 4016 9384 4016 1309 4016
(1) For complete upstream and downstream protection please order quantity 2.(2) 1 NO/NC contact block for positions I, 0 and II.(3) For 127/230VAC networks, please contact us.
What you need to know
Easyconfig
The ATyS p M are automatic transfer switching equipment that include a fully integrated ATS controller. These products are self powered from incoming supplies: 230 VAC (160-305 VAC), 50/60 Hz (45/65Hz). Automatic products are all equipped with a sequence logic. Here is an example of the sequence logic in case of loss and return of the preferred source.
Source failure
Automatic mode (AUT)
End “t” source 1 failure
Source availability
Generator stop(1)
Source availability
End “t” source 2 availability
End “t” stop to position 0End “t” source 1 availability
End “t” stop to position 0
End “t” cool down timer before generator
2
1
1
Switch to position 0
Switch to position II
Switch to position I
Switch to position 0
Generator start(1)
Source 1 : priority power sourceSource 2 : backup power source “t” : timer
Example (generator application):
(1) Only for mains/genset applications.
atys
_028
_h_1
_gb_
cat
atys
_849
_b_g
b
Easyconfig software is the ideal solution to save time and simplify complex configuration.
You can configure the following parameters:application type,voltage and frequency thresholds,timers,inputs/outputs…
423General Catalogue 2017-2018
Tran
sfer
sw
itche
s
Bridging bars
atys
m_0
25_a
UseUsed to bridge the outgoing common connection between switch I and switch II. The bridging bar does not reduce the connection capacity of the cage terminals.
Rating (A) No. of poles Reference40 … 125 2 P 1309 2006160 2 P 1309 201640 … 125 4 P 1309 4006160 4 P 1309 4016
Accessories
Terminal shrouds
atys
m_0
27_a
UseProtection against direct contact with terminals or connecting parts.Advantages of the terminal shroudsPerforations allow remote thermographic inspection without the need to remove the shrouds. Possibility of sealing.
MountingFor complete upstream and downstream protection of 4 pole products, please order quantity 2; for 2 pole products please order quantity 1.
Rating (A) Position Reference40 … 160 top / bottom 2294 4016(1)
(1) Reference composed of 2 pieces.
Voltage sensing and power supply tap
atys
m_0
26_a
Use
voltage sensing or power cables.The single-pole voltage sensing tap can be mounted in any of the terminals (incoming) without reducing their connecting capacity.
Rating (A) Pack Reference40 … 160 2 pieces 1399 4006
Sealable cover
atys
m_3
13_a
UsePrevents access to the ATyS t M and ATyS g M configuration panels.Rating (A) No. of poles Reference40 … 160 2 P 1359 200040 … 160 4 P 1359 0000
Auxiliary contactUseA maximum of two auxiliary contact blocks can be fitted to each product. Each auxiliary contact block integrates 3 NO/NC auxiliary contacts (I, 0, II).The ATyS d M is delivered as standard with
Characteristics:250 VAC / 5 A maximum. 24 VDC / 2 A maximum.
Rating (A) Type Reference40 … 160 Separate common points 1309 000140 … 160 Linked common points 1309 0011
acce
ss_3
98_a
acce
ss_3
53_a
ATyS M rangeATyS d M, ATyS t M, ATyS g M, ATyS p Mfrom 40 to 160 A
424 General Catalogue 2017-2018
ATyS M rangeATyS d M, ATyS t M, ATyS g M, ATyS p M
from 40 to 160 A
Polycarbonate enclosure
atys
m_0
36_b
_1_c
at
UseDedicated to the installation of a three-phase ATyS M, it enables easy integration of a compact transfer switch solution.
Rating (A) H x W x D (mm) Reference40 … 160 385 x 385 x 193 1309 9006
Extension unit
atys
m_0
39_a
_1_x
_cat
UseCombined with the polycarbonate enclosure, the extension unit provides
Rating (A) Reference40 … 160 1309 9007
Residential enclosure
atys
m_1
96_a
_1_c
at
UseDedicated to the implementation of a single-phase ATyS M, the plastic enclosure provides a compact IP41 transfer switch solution with easy integration.
Rating (A) H x W x D (mm) Reference40 … 160 410 x 305 x 150 1309 9056
Double power supply - DPS
atys
_612
_a_2
_cat
3
21atys
_616
_a_1
_cat
1 and 2. Inputs3. Output
UseAllows an ATyS d M to be supplied by two 230 VAC 50/60 Hz networks.Input
The input is considered as “active” from 200 VAC.
2.
Description of accessories ReferenceDPS 1599 4001
Input 1 Input 2 Output230 VAC 0 VAC 230 VAC (input 1)0 VAC 230 VAC 230 VAC (input 2)230 VAC 230 VAC 230 VAC (input 1)0 VAC 0 VAC 0 VAC
425General Catalogue 2017-2018
ATyS M rangeATyS d M, ATyS t M, ATyS g M, ATyS p Mfrom 40 to 160 A
Remote interfaces for ATyS p M
atys
_564
_c_1
_cat
atys
_565
_c_1
_cat
atys
_597
_a_1
_cat
RJ45 to connect to ATyS p M
Ø 22.5
4036
20
= =
96 x 96
atys
_161
_a_1
_x_c
at
Drillings
UseTo remotely display source availability and position indication on the front of a panel when the ATyS M is enclosed.The remote interface is powered directly from the ATyS M via the RJ45 connection cable.
D10To display source availability and position indication on the front panel of an enclosure.
D20In addition to the functions of the D10, the D20 displays measurements and enables control and configuration from the front of the display panel.
Door mounting2 holes Ø 22.5.ATyS M connection via RJ45 cable, not isolated.Cable not provided.
Description of accessories ReferenceD10 9599 2010D20 9599 2020
Connecting cable for remote interfaces
Type Length ReferenceRJ45 cable 3 m 1599 2009
acce
s_20
9_a_
2_ca
tUseTo connect between a remote interface (type D10 or D20) and a control product (ATyS p M).
Characteristics:RJ45 8 wire straight-through, non isolated cable. Length 3 m.
Cage-terminal interfaceUseThe power connection terminals allow conversion of the cage clamp terminals into bolt-on
cable. Compatible with aluminium terminals. Each power connection terminal is provided with separation screens.
Rating (A) Reference40 … 160 1399 4017(1)
(1) For complete conversion, order quantity 3.
Accessories (continued)
acce
s_25
2_a_
1_ca
t
Auto-transformerUseFor use with ATyS M in 400 VAC three-phase applications that have no distributed neutral.The ATyS M includes integrated sensing and power supply circuits, therefore a neutral connection is required for 400 VAC three-phase applications. When no neutral connection is available this autotransformer (400/230 VAC, 400 VA) provides the 230 VAC required for the ATyS to function. Rating (A) Reference40 … 160 1599 4121
trafo
_165
_b_1
426 General Catalogue 2017-2018
ATyS M rangeATyS d M, ATyS t M, ATyS g M, ATyS p M
from 40 to 160 A
Polycarbonate enclosed solution
From 40 to 160 A.
Flame resistant to 650°C.
General characteristics
ReferencesATyS d M single-phase model (2 P)
ATyS g M single-phase model (2 P)
Rating (A) Reference40 1823 200463 1823 200680 1823 2008100 1823 2010125 1823 2012160 1823 2016
Rating (A) Reference40 1854 200463 1854 200680 1854 2008100 1854 2010125 1854 2012160 1854 2016
atys
m_2
51_a
_1_c
at
Accessories
For model ATyS d M onlyDescription ReferenceATyS C30 relay driver 1599 3030ATyS C40 relay driver 1599 3040Dual power supply 1599 4001
Dimensions305
410
150
atys
m_2
08_a
_1_x
_cat
2 according to rating 2).
Customer fitDescription ReferenceAuxiliary contact 1309 0001Voltage sensing and power supply tap (2 per reference) 1399 4006
427General Catalogue 2017-2018
ATyS M rangeATyS d M, ATyS t M, ATyS g M, ATyS p Mfrom 40 to 160 A
Solutions with steel enclosure
Adapted to mechanical risk and dust hazard.Integrated bridging bar.
General characteristics
References
Rating (A) No. of polesIP 3X
ReferenceIP 54
Reference40 4 P 1823 4004 1823 400563 4 P 1823 4006 1823 400780 4 P 1823 4008 1823 4009100 4 P 1823 4010 1823 4011125 4 P 1823 4012 1823 4013160 4 P 1823 4016 1823 4017
AccessoriesCustomer fitDescription ReferenceSolid neutral 1309 9008IP54 kit 1399 4016
ATyS p M + COM RS485 modelsRating (A) No. of poles IP 3XReference
IP 54Reference
40 4 P 1884 4004 1884 400563 4 P 1884 4006 1884 400780 4 P 1884 4008 1884 4009100 4 P 1884 4010 1884 4011125 4 P 1884 4012 1884 4013160 4 P 1884 4016 1884 4017
ATyS g M models
Rating (A) No. of poles IP 3XReferenceIP 54
Reference40 4 P 1854 4004 1854 400563 4 P 1854 4006 1854 400780 4 P 1854 4008 1854 4009100 4 P 1854 4010 1854 4011125 4 P 1854 4012 1854 4013160 4 P 1854 4016 1854 4017
Dimensions
1612.5 200400
560
600
450
atys
m_2
10_a
_1_x
_cat
coff_
366_
b
428 General Catalogue 2017-2018
ATyS M rangeATyS d M, ATyS t M, ATyS g M, ATyS p M
from 40 to 160 A
ATyS M 40 to 160 AThree-phase ATyS M
1
34017610452
324
116
245
131.
5
45143
350
2613
73.55346
186 x M6
Three-phase ATyS M - door cut-out326
47
atys
m_0
08_b
_1_x
_cat
atys
m_0
34_a
_1_x
_cat
1. Auxiliary contact (2 max).
Dimensions
Single-phase ATyS M
1
235
17652
222
116
245
131.
5
45143
350
2613
73.55346
18atys
m_2
04_a
_1_x
_cat
Single-phase ATyS M - door cut-out224
47
atys
m_2
07_a
_1_x
_cat
1. Auxiliary contact (2 max).
101102201202313314315317
A
BB
3
4
6 6
21 C
7
5
atys
m_2
05_a
_1_x
_cat
position I, 0, II (factory fitted)
Single-phase ATyS d M
101102201202313314315317
A
BBBB
3
5
4
6 6 6 6
21 C
7
atys
m_0
40_e
_1_x
_cat
Three-phase ATyS d MTerminals and connections
429General Catalogue 2017-2018
ATyS M rangeATyS d M, ATyS t M, ATyS g M, ATyS p Mfrom 40 to 160 A
Terminals and connections (continued)Three-phase ATyS t M
atys
m_2
12_a
_1_x
_cat
Three-phase ATyS g M
A
1 2
B
210209208207 7473646331
2
6
atys
-tm_0
02_a
_1_x
_cat
A
1 2
B
210209208207 74736463
312
76
atys
m_2
06_a
_1_x
_cat
Single-phase ATyS g M
1 primary source2 backup source
per position I, 0, II (accessory)
1 primary source (network)2 backup source (network)
per position I, 0, II (accessory)
Three-phase ATyS p M
atys
m_2
11_a
_1_x
_cat
1 primary source2 backup source
430 General Catalogue 2017-2018
ATyS M rangeATyS d M, ATyS t M, ATyS g M, ATyS p M
from 40 to 160 A
Characteristics according to IEC 60947-3 and IEC 60947-6-140 to 160 A
Thermal current Ith at 40°C 40 A 63 A 80 A 100 A 125 A 160 ARated insulation voltage Ui (V) (power circuit) 800 800 800 800 800 800Rated impulse withstand voltage Uimp (kV) (power circuit) 6 6 6 6 6 6Rated insulation voltage Ui (V) (control circuit) 300 300 300 300 300 300Rated impulse withstand voltage U imp (kV) (control circuit) - ATyS d M 4 4 4 4 4 4Rated impulse withstand voltage U imp (kV) (control circuit) - ATyS t M, g M and p M 2.5 2.5 2.5 2.5 2.5 2.5
Rated operational currents Ie (A) according to IEC 60947-6-1Rated voltage Utilisation category A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1)415 VAC AC-31 A / AC-31 B 40/40 63/63 80/80 100/100 100/125 100/160415 VAC AC-32 A / AC-32 B 40/40 63/63 80/80 100/100 100/125 100/160415 VAC AC-33 A / AC-33 B -/40 -/63 -/80 -/100 -/125 -/125
Rated operational currents Ie (A) according to IEC 60947-3Rated voltage Utilisation category A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1)415 VAC AC-20 A / AC-20 B 40/40 63/63 80/80 100/100 125/125 160/160415 VAC AC-21 A / AC-21 B 40/40 63/63 80/80 100/100 125/125 160/160415 VAC AC-22 A / AC-22 B 40/40 63/63 80/80 100/100 125/125 160/160415 VAC AC-23 A / AC-23 B 40/40 63/63 80/80 100/100 125/125 125/160690 VAC AC-21 A / AC-21 B 40/40 63/63 80/80 100/100 125/125 160/160690 VAC AC-22 A / AC-22 B 40/40 63/63 80/80 80/80 100/125 100/125690 VAC AC-23 A / AC-23 B 40/40 63/63 63/63 80/80 80/80 80/80
Current rated as conditional short-circuit with fuse gG DINConditional short-circuit current (kA rms) 50 50 50 50 50 40Associated fuse rating (A) 40 63 80 100 125 160
Current rated as conditional short-circuit with any brand of circuit breaker that ensures tripping in less than 0.3s (4)Current rated as short-time withstand Icw 0.3s (kA rms) 7 7 7 7 7 7
Short-circuit operation (switch only) Current rated as short-time withstand Icw 1s (kA rms)(2) 4 4 4 4 4 4Rated peak withstand current (kA peak)(2) 17 17 17 17 17 17
ConnectionMin. connection cross-section 10 10 10 10 10 10Minimum Cu cable cross-section (mm2) 70 70 70 70 70 70Tightening torque (Nm) 5 5 5 5 5 5
Switching time(5)I - 0 or II - 0, following a command (ms) 45 45 45 45 45 45Transfer time I - II or II - I, following a command (ms) 180 180 180 180 180 180I-0 or II-0, after outage (s) 1.2 1.2 1.2 1.2 1.2 1.2I-II or II-I transfer time, after outage (s) 1.4 1.4 1.4 1.4 1.4 1.4Contact transfer time (“black-out”) I-II min. (ms) (3) 150 150 150 150 150 150
Power supplyMin./max. supply (VAC) (ATyS d M, t M and g M) 176/288 176/288 176/288 176/288 176/288 176/288Min./max. supply (VAC) (ATyS p M) 160/305 160/305 160/305 160/305 160/305 160/305
Control supply power demandRated power (VA) 6 6 6 6 6 6Max. intensity at 230 VAC (A) - ATyS d M, t M and g M 30 30 30 30 30 30Max. intensity at 230 VAC (A) - ATyS p M 20 20 20 20 20 20
Mechanical specificationsDurability (number of operating cycles) 10,000 10,000 10,000 10,000 10,000 10,000Weight of single-phase models - non-packaged (kg) 2.8 2.8 2.8 2.8 2.8 2.8Weight of single-phase models - including packaging (kg) 3.5 3.5 3.5 3.5 3.5 3.5Weight of three-phase models - non-packaged (kg) 3.5 3.5 3.5 3.5 3.5 3.5Weight of three-phase models - including packaging (kg) 4.2 4.2 4.2 4.2 4.2 4.2
(1) Category with index A = frequent operation / Category with index B = infrequent operation.(2) For a rated operational voltage Ue = 400 VAC.(3) 5% tolerance.
(4) Value for coordination with any circuit breaker that ensures tripping in less than 0.3s. For coordination with specific circuit-breaker references, higher short-circuit current values are available. Please contact us.
(5) At rated voltage - excluding time delays, where applicable.