Page 1: Technical Data OEF-P – High-Bay Fixture Mount sheet.pdf · OEF-P – High-Bay Fixture Mount Overview The OEF-P sensor controls fluorescent fixtures and can be mounted directly to

Technical Data Effective November 5, 2014

OEF-P – High-Bay Fixture Mount

OverviewThe OEF-P sensor controls fluorescent fixtures and can be mounted directly to the fixtures via a 1/2” knock out. The nipple on the sensor attaches with a lock nut through a 1/2” knockout on the fixture or on a junction box and all wiring passes through the same knockout.

Features Applications up to 40 feet in height Coverage diameter of twice the mounting height (2MH) Built in power supply, relay and light level sensor Zero-Crossing Technology prolongs relay life by switching high-inrush equipment at close to zero power

Compatible with electronic ballasts, incandescent lighting or motor loads

No minimum load required Direct installation to fixture; fits standard 1/2” knockout

Catalog# Prepared by

Project Date

Comments Type

Technical Data

PIRActivated

Page 2: Technical Data OEF-P – High-Bay Fixture Mount sheet.pdf · OEF-P – High-Bay Fixture Mount Overview The OEF-P sensor controls fluorescent fixtures and can be mounted directly to

2

Technical Data November 2014

OEF-P – High-Bay Fixture Mount

www.coopercontrol.com

Specifications

Technology Passive Infrared (PIR)Electrical Ratings

Contacts:800 VA @ 120 VAC Tungsten800 VA @ 120 VAC Ballast1200 VA @ 240-277 VAC Ballast

Input 120/277 VAC +/- 10% 60HzLight Level Sensing

0 to 200 foot-candles

Operating Environment

Temperature: 32°F - 104°F (0°C - 40°C)Relative humidity: Less than 95%, non-condensingFor indoor use only

Housing Durable, injection molded housing. Polycarbonate resin complies with UL 94V-0

Size 3.08"H x 3.08"W x 1.70"D (78.232mm x 78.232mm x 43.180mm)

Standards FCC Compliant UL Listed

Description/OperationThe OEF-P, High-bay sensors are designed to detect motion from a heat-emitting source (such as a person entering a space) within its field-of-view and automatically switch lights ON. Lights will remain ON until no motion is detected and a preset time delay has expired. If no motion is detected during the time delay, the relay is opened, turning the load off. No adjustments are needed at installation. After the installer test, the sensor will automatically set itself to the default 10-minute time delay. At installation, the sensor will scan the coverage area to determine the optimum sensitivity setting.

Applications Warehouses Manufacturing Garages High Ceilings

Page 3: Technical Data OEF-P – High-Bay Fixture Mount sheet.pdf · OEF-P – High-Bay Fixture Mount Overview The OEF-P sensor controls fluorescent fixtures and can be mounted directly to

3

Technical Data November 2014

OEF-P – High-Bay Fixture Mount

www.coopercontrol.com

Wiring Diagrams

LINE

HOT

NEUTRAL

BLACK

WHITE 120-277 VAC**

BLUELOAD

NOTE:120 VAC INCANDESCENT/TUNGSTEN;MAX. LOAD: 6.7 AMPS, 800VA, 60HZ

120 VAC FLUORESCENT/BALLAST;MAX. LOAD: 6.7 AMPS, 800VA, 60HZ

240-277 VAC FLUORESCENT/BALLAST;MAX. LOAD: 4.3 AMPS, 1200VA, 60HZ

Coverage

Mounting

OEF-P-2MH0-MV-S Note:N Sensor needs to be mounted on fix-ture so that fixture does not block sensor field of view.

Page 4: Technical Data OEF-P – High-Bay Fixture Mount sheet.pdf · OEF-P – High-Bay Fixture Mount Overview The OEF-P sensor controls fluorescent fixtures and can be mounted directly to

Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com

Eaton’s Cooper Controls Business203 Cooper CirclePeachtree City, GA 30269coopercontrol.com

© 2014 EatonAll Rights ReservedPrinted in USAPublication No. ACC141017November 5, 2014

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

Technical Data November 2014

OEF-P – High-Bay Fixture Mount

Coverage HoodsComes with each sensor

180 Dtgrtt Aislt CusoNm

Note:N Custom hood sections can be broken off to create custom pattern.

OrderingCatalog # Mounting Photocell Wire Lead Length

OEF-P-2MH0-MV-S Side Yes 36 inces


Recommended