GEA Heat Exchangers / HVAC Systems
GEA CAIRfricostar ®
Swimming pool climate control with integrated heat recovery
GEA Air Handling Units for swimming pools of every type and size
8,000 m3/h
55%
[28°C]
[30°C]
If you want to not only dehumidify your swimming pool or
public baths, but also desire general climate control, then you
can succeed especially comfortably and energy-efficiently with
the central air handling units of the GEA CAIRfricostar range
of models.
Well designed, comfortable, and flexible
With GEA CAIRfricostar, you have the broadest and most exten-
sive spectrum of dehumidifier units for indoor swimming pools
available on the European market. GEA air handling units en-
sure very high efficiency and selective air exchange. The air on
one side of the hall can be evacuated and resupplied on the op-
posite side. The admixing of fresh air according to VDI 2089 im-
proves the air quality. GEA CAIRfricostar equipment is outstand-
ing due to its modular design, and especially flexible because
also suitable for retrofitting due to small entry openings. With
modular technology, an individual unit can be created for eve-
ry application case. The specialists of GEA Air Treatment will be
happy to support you in the tendering, configuration, and selec-
tion of the units you need for your individual requirement.
Multi-stage integrated heat recovery
The integrated heat recovery of GEA CAIRfricostar units ensures
high amortisation. The humidity is at first removed from the air
via heat pump and heat recovery. The resulting condensate is
captured and drained off into the waste water system. The inter-
stage heat exchanger for the dehumidification returns the ther-
mal energy recovered in the exhaust air as well as the drive pow-
er of the compressor to the pool water and/or the dehumidified
air. Well-designed and freely programmable control units ensure
the greatest flexibility, energy-optimised functionality, and
maintenance of all desired air parameters
Customised and energy-efficient
Sustainable swimming pool climate control with integrated heat recovery
Dehumidification and climate control of public
and large pools with the central air handling units
of the GEA CAIRfricostar range of models:
Highly efficient heat recovery with up to 60%
energy savings and high efficiencies of up to 82%
Secure, reliable dehumidification
Certified according to DIN ISO 9001
Furnished with CE and Eurovent seal
Top hygiene standard (also suitable for clinic and
rehabilitation applications) according to VDI 6022
Individual, customised units for every application
case through modular construction
Reliable function for all climatic conditions and
constant performance over the entire temperature
range
Planning support from GEA Air Treatment
2 PR-2009-0061-GB · Subject to modification · Version 02/2009
Suited for every use
You can optimally plan every swimming pool with GEA CAIRfricostar
Comfortable private swimming pools, hotel pools, wellness
and therapy facilities, or public halls and adventure pools:
GEA CAIRfricostar air handling units are optimally suited for
every application and work in recirculated air or mixed air op-
erating mode. Regulated share fraction of fresh air in connec-
tion with various heat recovery systems – with a heat recovery
quantity of up to 82% – keeps your operating costs within
bounds.
Features with or without heat pump
Depending on the application, the units of the GEA CAIRfricos-
tar range of models offer heat recovery with additional heat-
pump circuitry as well as heat recovery without additional heat-
pump circuitry. Units with heat recovery and heat-pump
circuitry represent the synthesis of efficacy and air quality.
Swimming pool exhaust air drying and fresh air pre-warming,
paired with optimised compressor output, lead to low heating
costs and save valuable energy. Units with heat recovery but
without heat-pump circuit are fundamentally employed for small
water surfaces in proportion to a large hall volume. Low main-
tenance costs and a small investment volume are further argu-
ments for this equipment version.
Corrosion protection for long equipment life
The cold-bridge-free design of the GEA CAIRfricostar units pre-
vents water formation by condensation and ensures long equip-
ment life. Furthermore, all units can be delivered in three cor-
rosion protection classes:
Corrosion protection class K: standard version for use in
normal swimming pools
Corrosion protection class H: enhanced version for
increased requirements in chlorine or saline air (sea water
and brine baths up to 3% brine)
Corrosion protection class P: top version for very high
requirements in aggressive environments such as thermal
spas and for salt contents of more than 3%
Broad performance and geometry spectrum
For air volumes of 750 to 45,000 m3/h
Performance ratings available for all pool areas
Variable equipment design permits individual
configuration of empty and filter chambers, doors,
sound absorbers, service openings and the like
Easy cleaning, servicing, and inspection due to
equipment design with completely smooth inner
surfaces and hinges and sash fasteners that lie
outside the airflow
Deliverable in various corrosion protection classes
Cold-bridge-free design with quality components
In addition to our modular units, GEA Fricostar
Micro offers a compact and ready-to-install
swimming pool hall climate-control unit with
smaller dimensions
3PR-2009-0061-GB · Subject to modification · Version 02/2009
Performance diversity
Performance ratings for all pool sizes and air volumes up to 45,000 m3/h
For every individual requirement in swimming pool climate control
GEA CAIRfricostar > Modular, powerful, and energy-efficient
[For pool areas of up to 1,000 m2] [Up to 45,000 m3/h air volume flow] [RLT hygiene according to VDI 6022] [Dehumidification capacity up to 310 kg/ h]
GEA CAIRfricostar units have a performance range of 750 to maximum 45,000 m3/h. Swimming pools with
pool areas up to 1,000 m2 can be dehumidified with a single unit. In the performance model family which
works with air velocities of about 2 m/s in the clearance cross-section, the largest unit can supply up
to 36,000 m3 air per hour, in the standard version even 45,000 m3 at 2.8 m/s.
The units achieve dehumidification capacity of up to 310 kg/h. The hygiene standard of the entire range of
models according to VDI 6022 even conforms to applications in hospitals and rehabilitation centres.
4 PR-2009-0061-GB · Subject to modification · Version 02/2009
Unit distribution according to air volume flow and water surfaces Performance series
Unit distribution according to air volume flow and water surfaces Standard series
Stan
dar
d u
nit
typ
e
Air volume flow (m3 / h)
CAM 320
CAM 290
CAM 250
CAM 230
CAM 200
CAM 170
CAM 150
CAM 130
CAM 110
CAM 100
CAM 083
CAM 055
CAM 045
CAM 037
CAM 030
CAM 020
CAM 015
0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000
40 m2
60 m2
70 m2
85 m2
100 m2
130 m2
195 m2
260 m2
325 m2
380 m2
435 m2
510 m2
590 m2
680 m2
745 m2
850 m2
950 m2
Water surface max. (m2)
Air temperature: 30 °C
Water temperature: 28 °C
Perf
orm
ance
un
it t
ype
Air volume flow (m3 / h)
CAM 360
CAM 320
CAM 290
CAM 250
CAM 230
CAM 200
CAM 170
CAM 150
CAM 130
CAM 110
CAM 100
CAM 083
CAM 055
CAM 045
CAM 037
CAM 030
CAM 020
CAM 015
0 5000 10000 15000 20000 25000 30000 35000 40000
60 m2
70 m2
85 m2
100 m2
130 m2
190 m2
230 m2
250 m2
300 m2
340 m2
400 m2
530 m2
575 m2
830 m2
670 m2
740 m2
460 m2
35 m2
Water surface max. (m2)
Air temperature: 30 °C
Water temperature: 28 °C
5PR-2009-0061-GB · Subject to modification · Version 02/2009
GEA CAIRfricostar and GEA Fricostar Micro
Construction and unit type
Compact construction
GEA Fricostar Micro CAC with heat pump
GEA Fricostar Micro CWC without heat pump
Ready-to-install swimming pool hall climate-control
units of compact design. Owing to smaller dimensions,
they are especially suited for small private and public
swimming pools. The features correspond to the
modular units
Modular construction
GEA CAIRfricostar air handling units with heat pump
Unit types CAU, CAM, CMU, CMP, CPP
Heat recovery with ECOSTAT POWER TUBE
Heat pipe or ECOPLAT 2 POWER PLATE double-plate heat
exchanger and additional heat pump circuit
GEA CAIRfricostar air handling units without heat pump
Unit types CWP, CWR
Heat recovery without additional heat pump
GEA CAIRfricostar GEA Fricostar MicroConstruction Modular CompactUnit type CAU CAM CMU CMP CPP CWP CWR CAC CWC
Heat recovery
Heat pump circuit
Heat pipe technologyECOSTAT POWER TUBE
Double-plate heat exchangerECOPLAT 2 POWER PLATE
Plate heat exchangerECOPLAT POWER PLATE
Method of operation
Recirculated air
Mixed air
Air volume flow
Minimum m3/h 750 750 750 750 750 750 750 750 750
Maximum m3/h 4100 45000 6200 37500 37500 37500 45000 3600 3600
Series
Standard
Performance
Control
All-electronic
DDC control
Main use
Private pools
Pools with partial day operation(private, hotel, therapeutic baths)
Private and public pools withsmall water surfaces and large hall volume
Private and public pools of all kinds
Public pools, swimming sport and recreational facilities
6 PR-2009-0061-GB · Subject to modification · Version 02/2009
Recirculated air dehumidification units with heat pump GEA CAIRfricostar CAU
Standard series 1)
Unit typeCAU_SU 015 015 025 025 030 030 037 037
Unit dimensions
Width mm 760 760 760 760 760 760 760 760
Height mm 1120 1120 1360 1360 1360 1360 1600 1600
Length mm 1680 1680 1800 1800 1800 1880 1720 1800
Air volume flow
Minimum m3/h 750 – 1842 – 2755 – 3354 –
Maximum m3/h – 1842 – 2755 – 3355 – 4129
Rating for dehumidification m3/h 750 1842 1842 2755 2755 3355 3354 4129
Rating for ventilation m3/h 500 1228 1228 1836 1836 2236 2236 2752
Dehumidification capacity
Recirculated-air operation 2) kg/h 3.1 1.4 4.2 3.3 4.3 3.6 4.9 3.9
Thermal capacity
Air condenser without PWC operation kW 7.0 8.0 13.0 13.8 16.2 16.6 19.8 20.1
Air condenser with PWC operation kW 4.6 6.0 10.6 11.3 13.3 13.9 16.3 17.0
Pool water condenser 3) kW 2.3 2.0 2.5 2.1 2.6 2.5 3.3 3.1
After heater 4) kW 5.9 9.4 11.1 14.1 14.1 15.8 18.3 20.5
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use current GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Pool water condenser (PWC) = accessory4) Feed / return temperature = 70°C / 50°C
GEA CAIRfricostar CAU was primarily conceived for private swimming
pools and is deliverable in four sizes as well as for an air volume flow of
750 to 4,100 m³/h. The unit dehumidifies and heats the swimming pool in
recirculated-air operation. It is delivered with an all-electronic control which
automatically regulates the functions of the facility.
In recirculated-air operation without dehumidification, the air in the swim-
ming pool hall is circulated. When the target humidity is exceeded, the mul-
ti-function hygrostat installed in the hall switches the facility into dehu-
midification operation. The fan is then switched to level two and the
refrigeration system for dehumidification is started. The dehumidification
procedure runs until the target humidity is achieved, then the fan switch-
es back to level one and the compressor in the dehumidifying plant stops.
With an optional pool water condenser, a part of the obtained surplus en-
ergy from the heat pump circuit can be transferred to the pool water or an
equivalent cycle.
Advantages of GEA CAIRfricostar CAU:
Small investment expenditure
Compact solution
with small space requirements
Electronic control
Swimming pool operation
with dehumidification requirement
Fan Compressor1 2
1
2
7PR-2009-0061-GB · Subject to modification · Version 02/2009
GEA CAIRfricostar CAM Mixed air dehumidification unit with heat pump
GEA CAIRfricostar CAM was conceived for private and public swimming
pools of all kinds. The range of models is available with air volume flow of
750 to 46,000 m3/h. The unit dehumidifies and heats the swimming pool
hall in mixed air operating mode. Apart from a refrigeration system (heat
pump), this unit type is additionally equipped with an efficient heat recov-
ery (ECOSTAT POWER TUBE heat pipe). It is delivered with a DDC unit
and controls all functions of the plant fully automatically.
Advantages of CAIRfricostar CAM:
Efficient and compact heat recovery
Low investment,
operation and maintenance costs
Individually adaptable
to all structural conditions
Performance ratings for all pool areas
Standard series 1)
Unit typeCAM_SU 015 025 030 037 045 055 083 100 110 130 150 170 200 230 250 320
Unit dimensions
Width mm 760 760 760 760 1080 1080 1080 1400 1720 2000 1720 2000 2320 2640 2320 2920
Height mm 1120 1360 1360 1600 1360 1600 2240 2240 2240 2320 2880 2960 2960 2960 3600 3600
Length mm 3000 3200 3300 3300 3300 3400 4000 4000 4000 4000 4400 4600 4600 4800 5000 5300
Air volume flow
Minimum m3/h 750 1842 2755 3354 4128 5031 6192 9289 12385 15482 18191 20643 24256 28384 32513 40642
Maximum m3/h 1843 2756 3355 4129 5032 6193 9290 12386 15483 18192 20644 24257 28385 32514 35482 45128
Rating for de-humidification m3/h 1000 2000 3000 4000 5000 6000 9000 12000 15000 18000 20000 24000 27000 32500 34000 45000
Rating forventilation m3/h 667 1333 2000 2667 3333 4000 6000 8000 10000 12000 13333 16000 18000 21667 22667 30000
Dehumidification capacity
Swimming pool operation(30% outs. air) kg/h 6 12 16 19 26 31 43 57 72 86 98 117 135 158 169 219
Standby operation(Recirculated air) kg/h 3 5 5 5 9 11 12 17 21 24 31 37 45 48 58 79
VDI 2089 2) kg/h 6 13 19 25 32 38 57 76 95 115 127 153 172 207 216 286
Thermal capacity
Air condenserwithoutPWC operation kW 5.4 9.3 10.7 13.1 17.3 21.3 26.9 35.6 42.4 53.1 62.6 72.9 87.8 99.4 108.1 135.1
Air condenserwithPWC operation kW 3.0 6.7 7.9 10.8 14.5 18.7 22.5 30.7 39.0 45.6 55.7 63.2 77.1 86.6 95.4 118.5
Pool water-condenser 3) kW 2.4 2.8 3.0 2.5 2.6 2.5 4.3 5.2 4.6 6.5 8.2 10.2 10.2 13.5 14.2 15.7
Heatrecovery kW 3.0 5.9 6.9 8.9 12.2 15.0 22.0 30.6 39.3 45.4 50.8 61.8 72.5 85.8 91.6 120.0
After heater 4) kW 9.9 16.3 20.6 28.0 35.9 43.9 66.5 88.8 110.0 135.9 147.3 180.1 188.2 232.4 237.6 327.3
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Pool water condenser (PWC) = accessory4) Feed / return temperature = 70°C / 50°C
8 PR-2009-0061-GB · Subject to modification · Version 02/2009
Mixed air dehumidification unit with heat pump GEA CAIRfricostar CAM
Swimming pool operation
with dehumidification requirement
During swimming pool operation, the outside and exhaust air flap of the
unit opens and the recirculating air flap is closed. The refrigeration system
is started for dehumidification and both fans are switched to level two. A
part of the obtained surplus energy of the refrigeration system can be re-
leased to the pool water with an optional pool water condenser.
Performance series 1)
Unit typeCAM_PU 015 025 030 037 045 055 083 100 110 130 150 170 200 230 250 320
Unit dimensions
Width mm 760 760 760 760 1080 1080 1080 1400 1720 2000 1720 2000 2320 2640 2320 2920
Height mm 1120 1360 1360 1600 1360 1600 2240 2240 2240 2320 2880 2960 2960 2960 3600 3600
Length mm 3000 3200 3300 3300 3300 3400 4000 4000 4000 4000 4400 4600 4600 4800 5000 5300
Air volume flow
Minimum m3/h 750 1500 2500 2994 3685 4492 5529 8293 9952 11058 12994 14745 17325 20274 23223 29029
Maximum m3/h 1500 2500 2995 3686 4493 5530 8294 9953 11059 12995 14746 17326 20275 23224 25344 32256
Rating for de-humidification m3/h 1000 2000 2900 3600 4400 5500 7500 9900 11000 12500 14500 17000 20000 23000 25000 32000
Rating forventilation m3/h 667 1333 1933 2400 2933 3667 5000 6600 7333 8333 9667 11333 13333 15333 16667 21333
Dehumidification capacity
Swimming pool operation(30% outs. air) kg/h 6 11 16 19 25 31 39 53 62 70 82 94 112 130 138 177
Standby operation(recirculated air) kg/h 4 5 6 7 10 12 14 19 25 29 36 37 45 54 49 63
VDI 2089 2) kg/h 6 13 18 23 28 35 48 63 70 80 92 108 127 146 159 204
Thermal capacity
Air condenserwithoutPWC operation kW 5.6 7.4 10.8 12.9 16.8 20.6 23.7 30.9 36.4 43.1 52.3 54.1 67.4 77.3 79.8 101.4
Air condenserwithPWC operation kW 3.5 5.3 7.9 10.1 14.0 17.9 19.6 26.2 31.8 35.8 44.5 46.6 57.6 65.2 66.2 86.4
Pool water-condenser 3) kW 2.3 2.1 3.3 2.9 3.1 3.1 4.4 5.1 4.9 7.5 8.6 9.0 9.6 13.7 12.3 15.6
Heatrecovery kW 3.5 7.0 8.7 10.9 14.1 17.7 24.3 33.5 39.8 45.2 52.1 61.3 73.2 85.6 92.0 118.1
After heater 4) kW 9.5 15.3 20.0 24.7 30.8 38.8 56.3 72.7 86.9 98.6 115.5 132.7 158.9 185.2 199.3 288.2
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Pool water condenser (PWC) = accessory4) Feed / return temperature = 70°C / 50°C
Fans Outside and exhaust air flap Recirculating air flap Mixed air flap1 2 3 4
1
12
3
4
9PR-2009-0061-GB · Subject to modification · Version 02/2009
GEA CAIRfricostar CMU Mixed air dehumidification unit with heat pump
GEA CAIRfricostar CMU was conceived for private and small public swim-
ming pools. The unit is especially suitable for pools in partial daily opera-
tion, i.e., hotels and therapeutic baths, and requires very little space. The
range of models is available in six sizes as well as for an air volume flow of
750 up to 6,200 m³/h. The unit dehumidifies and heats the swimming pool
in a mixed air operating mode. It is delivered with a DDC unit and controls
all functions of the plant fully automatically.
When the swimming pool is in use, the outside and exhaust air flap of the
unit opens and the recirculating air flap is closed. For dehumidification, the
refrigeration system is started and both fans are switched to level two. A
part of the obtained surplus energy from the refrigeration system can be
released to the pool water with an optional pool water condenser
Advantages of GEA CAIRfricostar CMU:
Flexibility in features
Compact solution with small space
requirements
Small dimensions
Variable control, drive and filters
Swimming pool operation
with dehumidification requirement
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Pool water condenser (PWC) = accessory4) Feed / return temperature = 70°C / 50°C
Standard series 1)
Unit typeCMU_SU 015 025 030 037 045 055
Unit dimensions
Width mm 760 760 760 760 1080 1080
Height mm 1120 1360 1360 1600 1360 1600
Length mm 2600 2700 2700 2740 2760 2800
Air volume flow
Minimum m3/h 750 1842 2755 3354 4128 5031
Maximum m3/h 1843 2756 3355 4129 5032 6193
Rating for dehumidification m3/h 1000 2000 3000 4000 5000 6000
Rating for ventilation 2/3 m3/h 667 1333 2000 2667 3333 4000
Dehumidification capacity
Swimming pool operation (30% outs. air) kg/h 5 10 14 18 21 26
Standby operation (recirculated air) kg/h 2 4 4 5 4 6
VDI 2089 2) kg/h 6 13 19 25 32 38
Thermal capacity
Air condenser without PWC operation kW 7.0 13.0 16.6 21.0 24.2 30.0
Air condenser with PWC operation kW 5.6 11.5 14.8 18.1 20.2 26.3
Pool water condenser 3) kW 1.6 1.5 1.6 2.1 2.1 2.6
After heater 4) kW 10.6 11.7 14.8 20.2 36.0 46.4
1
12
3
4
Fans Outside and exhaust air flap Recirculating air flap Mixed air flap1 2 3 4
10 PR-2009-0061-GB · Subject to modification · Version 02/2009
Swimming pool operation
with dehumidification requirement
Mixed air dehumidification unit with heat pump GEA CAIRfricostar CMP
GEA CAIRfricostar CMP was conceived for private and public high-perfor-
mance swimming pools of all kinds. The range of models can be delivered
for an air volume flow of 750 up to 37,500 m³/h. The unit dehumidifies and
heats the swimming pool hall in a mixed air operating mode. Apart from
a heat pump plant, this unit type is additionally equipped with a highly ef-
ficient heat recovery system (efficiency 82%) by means of double-plate heat
exchanger (ECOPLAT 2 POWER PLATE). It is delivered with a DDC unit
and controls all functions of the plant fully automatically.
When the swimming pool is being used, the outside and exhaust air flap of
the unit opens and the recirculating air flap regulates the mixed air share
with the DDC. For dehumidification, the refrigeration system is started and
both fans are switched to level two. A part of the obtained surplus energy
of the refrigeration system can be released to the pool water with an optio-
nal pool water condenser.
Advantages of GEA CAIRfricostar CMP:
Multi-stage high-performance heat
recovery with two high-performance heat
exchangers and heat pump
Low operating costs
Performance ratings for all pool areas
Performance Series 1)
Unit typeCMP_PU 015 025 037 055 083 110 130 150 170 200 250 320
Unit dimensions
Width mm 760 760 760 1080 1080 1720 2000 1720 2000 2320 2320 2920
Height mm 1120 1360 1600 1600 2240 2240 2320 2880 2960 2960 3600 3600
Length mm 4240 4480 4840 4880 5480 5720 5920 6600 6800 7080 7360 8120
Air volume flow
Minimum m3/h 750 1500 2500 3685 5529 8293 11058 12994 14745 17325 20274 29029
Maximum m3/h 1500 2500 3686 5530 8294 11059 12995 14746 17326 20275 25344 32256
Rating for dehumidification m3/h 1000 2000 3400 5000 7500 11000 12500 14000 17000 20000 25000 32000
Rating for ventilation 2/3 m3/h 667 1333 2267 3333 5000 7333 8333 9333 11333 13333 16667 21333
Dehumidification capacity
Swimming pool operation (30% outs. air) kg/h 6 11 18 27 40 58 68 77 94 112 134 175
Standby operation (Recirculated air) kg/h 4 5 8 13 17 25 31 37 46 57 61 84
VDI 2089 2) kg/h 6 13 22 32 48 70 80 90 108 127 159 204
Thermal capacity
Air condenser without PWC operation kW 5.0 6.7 10.7 15.9 22.4 30.7 36.9 42.1 51.5 61.9 75.7 99.4
Air condenser with PWC operation kW 2.6 3.9 7.7 12.1 17.6 25.2 29.0 32.9 39.9 50.0 59.9 75.6
Pool water condenser 3) kW 2.6 2.9 3.2 3.8 5.4 5.6 8.1 8.5 12.2 12.7 16.2 21.9
Heat recovery kW 3.6 6.9 11.3 16.6 25.6 37.5 44.2 51.8 63.0 74.5 84.2 111.4
After heater 4) kW 8.4 13.4 21.2 31.6 48.9 77.8 90.9 98.1 120.7 139.3 180.4 234.6
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Pool water condenser (PWC) = accessory4) Feed / return temperature = 70°C / 50°C
1
2
3
1 4
Fans Outside and exhaust air flap Recirculating air flap Mixed air flap1 2 3 4
11PR-2009-0061-GB · Subject to modification · Version 02/2009
GEA CAIRfricostar CPP Mixed air dehumidification unit with heat pump
GEA CAIRfricostar CPP was conceived for private and public high-perform-
ance swimming pools of all kinds and can be delivered for an air volume
flow of 750 to up to 37,500 m³/h. The unit works in the mixed air operating
mode. A special characteristic is its reversible heat-pump circuit. In the sum-
mer, the cooling cycle of the swimming pool can be reversed for excess tem-
peratures to cool the supply air. The DDC control thus monitors the supply
air temperature in order to regulate the swimming pool temperature to the
pre-set standard value, and selects the most favourable operating state. The
unit is equipped with a highly efficient heat recovery system by means of
double plate heat exchanger (ECOPLAT 2 POWER PLATE).
When the swimming pool is in use, the outside and exhaust air flap of the
unit opens and the recirculating air flap regulates the mixed air share with
the DDC. For dehumidification, the refrigeration system starts and both fans
are switched to level two. A part of the obtained surplus energy of the refrig-
eration system can be released to the pool water with the optional pool wa-
ter condenser.
Advantages of GEA CAIRfricostar CPP:
Multi-stage high-performance heat
recovery with two high-performance heat
exchangers and a heat pump plant with
a reversible cooling cycle and summer
cooling function
Performance ratings for all pool areas
Swimming pool operation
with dehumidification requirement
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Pool water condenser (PWC) = accessory4) Feed / return temperature = 70°C / 50°C
Performance Series 1)
Unit typeCPP_PU 015 025 037 055 083 110 130 150 170 200 250 320
Unit dimensions
Width mm 760 760 760 1080 1080 1720 2000 1720 2000 2320 2320 2920
Height mm 1120 1360 1600 1600 2240 2240 2320 2880 2960 2960 3600 3600
Length mm 4240 4480 4840 4880 5480 5720 5920 6600 6800 7080 7360 8120
Air volume flow
Minimum m3/h 750 1500 2500 3685 5529 8293 11058 12994 14745 17325 20274 29029
Maximum m3/h 1500 2500 3686 5530 8294 11059 12995 14746 17326 20275 25344 32256
Rating for dehumidification m3/h 1000 2000 3400 5000 7500 11000 12500 14000 17000 20000 25000 32000
Rating for ventilation 2/3 m3/h 667 1333 2267 3333 5000 7333 8333 9333 11333 13333 16667 21333
Dehumidification capacity
Swimming pool operation (30% outs. air) kg/h 6 11 18 27 40 58 68 77 94 112 134 175
Standby operation (recirculated air) kg/h 4 5 8 13 17 25 31 37 46 57 61 84
VDI 2089 2) kg/h 6 13 22 32 48 70 80 90 108 127 159 204
Heating / cooling capacity
Air condenser without PWC operation kW 5.0 6.7 10.7 15.9 22.4 30.7 36.9 42.1 51.5 61.9 75.7 99.4
Air condenser with PWC operation kW 2.6 3.9 7.7 12.1 17.6 25.2 29.0 32.9 39.9 50.0 59.9 75.6
Pool water condenser 3) kW 2.6 2.9 3.2 3.8 5.4 5.6 8.1 8.5 12.2 12.7 16.2 21.9
Heat recovery kW 3.6 6.9 11.3 16.6 25.6 37.5 44.2 51.8 63.0 74.5 84.2 111.4
After heater 4) kW 8.4 13.4 21.2 31.6 48.9 77.8 90.9 98.1 120.7 139.3 180.4 234.6
Cooling capacity kW Data not known by copy deadline
1
2
3
1 4
Fans Outside and exhaust air flap Recirculating air flap Mixed air flap1 2 3 4
12 PR-2009-0061-GB · Subject to modification · Version 02/2009
Swimming pool operation
with dehumidification requirement
Mixed air dehumidification unit without heat pump GEA CAIRfricostar CWP
GEA CAIRfricostar CWP was conceived for private and public high-perfor-
mance swimming pools of all kinds. The range of models can be delivered
with an air volume flow from 750 up to 37,500 m³/h. The unit dehumidifies
and heats the swimming pool in a mixed air operating mode and is equipped
with an efficient heat recovery (ECOPLAT 2 POWER PLATE double-plate heat
exchanger) without a heat pump. It is delivered with a DDC unit and controls
all the functions of the plant fully automatically.
When the swimming pool is in use, the outside and exhaust air flap of the
unit opens and the mixed air flap controls the mixed air share according to
the dehumidification requirement via the DDC. Both fans are switched to le-
vel two.
Advantages of GEA CAIRfricostar CWP:
Multi-stage heat recovery with two
high-performance heat exchangers
High efficiency, low energy consumption
Low, internal pressure loss
Performance Series 1)
Unit typeCWP_PU 015 025 037 055 083 110 130 150 170 200 250 320
Unit dimensions
Width mm 760 760 760 1080 1080 1720 2000 1720 2000 2320 2320 2920
Height mm 1120 1360 1600 1600 2240 2240 2320 2880 2960 2960 3600 3600
Length mm 3600 3800 4100 4200 5700 5700 6000 6600 6800 7100 7400 8200
Air volume flow
Minimum m3/h 750 1500 2500 3685 5529 8293 11058 12994 14745 17325 20274 29029
Maximum m3/h 1500 2500 3686 5530 8294 11059 12995 14746 17326 20275 25344 32256
Rating for dehumidification m3/h 1000 2500 3400 5000 7500 11000 12500 14000 17000 20000 25000 32000
Rating for ventilation 2/3 m3/h 667 1667 2267 3333 5000 7333 8333 9333 11333 13333 16667 21333
Dehumidification capacity
According to VDI 2089for rated airflow 2) kg/h 6 16 22 32 48 70 80 89 108 127 159 204
Thermal capacity
Heat recovery kW 2.1 5.1 6.8 10.1 15.3 25.3 26.1 30.0 36.4 42.8 49.9 65.0
After heater 3) kW 8.4 15.4 21.2 31.6 48.9 78.9 90.9 98.1 120.7 139.3 180.4 234.5
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum. Outside air state = 5°C / 85% rel. F.3) Feed / return temperature = 70°C / 50°C
1
2
3
1
Fans Outside and exhaust air flap Recirculating air flap Mixed air flap1 2 3 4
13PR-2009-0061-GB · Subject to modification · Version 02/2009
GEA CAIRfricostar CWR Mixed air dehumidification unit without heat pump
GEA CAIRfricostar CWR was conceived for private and public swimming
pools of all kinds. The range of models is available with 750 to 45,000 m³/h
air volume flow. The unit dehumidifies and heats the swimming pool in a
mixed-air operating mode. This unit type is equipped with an efficient heat
recovery (ECOSTAT POWER TUBE heat pipe) without a heat pump. It is de-
livered with a DDC unit and controls all functions of the plant fully auto-
matically.
Advantages of GEA CAIRfricostar CWR:
Efficient heat recovery
Lower investment costs, since without
heat pump
Low operation and maintenance costs
Individual and customised units according
to requirements
Standard series 1)
Unit typeCWR_SU 015 025 030 037 045 055 083 100 110 130 150 170 200 230 250 320
Unit dimensions
Width mm 760 760 760 760 1080 1080 1080 1400 1720 2000 1720 2000 2320 2640 2320 2920
Height mm 1120 1360 1360 1600 1360 1600 2240 2240 2240 2320 2880 2960 2960 2960 3600 3600
Length mm 2520 2560 2560 2680 2680 2720 3320 3360 3480 3520 3840 3800 3880 3880 4200 4320
Air volume flow
Minimum m3/h 750 2395 2755 3593 4423 5390 6635 9952 13270 16588 19491 22117 25988 30412 34835 43545
Maximum m3/h 2396 2756 3594 4424 5391 6636 9953 13271 16589 19492 22118 25989 30413 34836 38016 48384
Rating for de-humidification m3/h 1500 2500 3000 4000 4800 6000 9000 12000 15000 17500 20000 23500 27000 31500 35000 44000
Rating for venti-lation 2/3 m3/h 1000 1667 2000 2667 3200 4000 6000 8000 10000 11667 13333 15667 18000 21000 23333 29333
Dehumidification capacity
According to VDI 2089for rated airflow 2) kg/h 10 16 19 25 31 38 57 76 95 111 127 150 172 200 223 280
Thermal capacity
Heatrecovery kW 2.6 4.6 5.2 6.9 8.7 10.9 16.6 22.5 28.5 32.9 37.3 44.3 51.5 60.2 66.5 84.3
After heater 3) kW 12.5 19.1 20.6 28.9 34.8 43.9 66.5 88.8 110.0 133.2 147.3 177.4 188.2 227.1 242.6 321.9
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Feed / return temperature = 70°C / 50°C
14 PR-2009-0061-GB · Subject to modification · Version 02/2009
Mixed-air dehumidification unit without heat pump GEA CAIRfricostar CWR
When the swimming pool is in use, the outside and exhaust air flap of the
unit opens and the mixed air flap is closed, and both fans are switched to
level two.
Swimming pool operation
with dehumidification requirement
Fans Outside and exhaust air flap Recirculating air flap1 2 3
1
1
Performance series 1)
Unit typeCWR_PU 015 025 030 037 045 055 083 100 110 130 150 170 200 230 250 320
Unit dimensions
Width mm 760 760 760 760 1080 1080 1080 1400 1720 2000 1720 2000 2320 2640 2320 2920
Height mm 1120 1360 1360 1600 1360 1600 2240 2240 2240 2320 2880 2960 2960 2960 3600 3600
Length mm 2520 2700 2700 2700 2800 2800 3300 3500 3500 3600 3600 3800 4000 4000 4200 4500
Air volume flow
Minimum m3/h 750 1500 2500 2994 3685 4492 5529 8293 9952 11058 12994 14745 17325 20274 23223 29029
Maximum m3/h 1500 2500 2995 3686 4493 5530 8294 9953 11059 12995 14746 17326 20275 23224 25344 32256
Rating for de-humidification m3/h 1500 2500 2800 3300 4200 5000 7500 9900 11000 12800 14500 17000 20000 23000 25000 32000
Rating for venti-lation 2/3 m3/h 1000 1667 1867 2200 2800 3333 5000 6600 7333 8533 9667 11333 13333 15333 16667 21333
Dehumidification capacity
According to VDI 2089for rated airflow 2) kg/h 10 16 18 21 27 32 48 63 70 81 92 108 127 146 159 204
Thermal capacity
Heatrecovery kW 2.9 5.2 5.7 6.8 8.8 8.9 15.8 21.2 23.9 27.8 31.4 37.0 43.6 50.2 54.6 70.1
After heater 3) kW 11.9 18.0 19.5 23.2 29.7 36.0 56.3 72.7 86.9 100.4 115.4 132.7 158.9 185.2 199.3 238.2
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Feed / return temperature = 70°C / 50°C
2
3
15PR-2009-0061-GB · Subject to modification · Version 02/2009
GEA Fricostar Micro CAC Compact climate-control unit with heat pump
GEA Fricostar Micro CAC was developed for small private and public swim-
ming pools, i.e., in hotel and therapeutic baths, and can be delivered in two
model sizes as well as three performance ratings. Owing to its compact di-
mensions and the special positioning of the connection fittings, the unit is
especially suited for installation in small technical rooms. Apart from a heat
pump plant, it is equipped with an efficient heat recovery system (ECOPLAT
POWER PLATE heat exchanger) and an intelligent DDC unit.
When the swimming pool is in use with dehumidification, the warm swim-
ming pool hall exhaust air is cooled down in the plate heat exchanger and
dehumidified in the evaporator. A part of the dried swimming pool hall air
is now supplied to the fresh air with the mixed air flaps, pre-warmed in the
plate exchanger, warmed further in the condenser, and made available to
the swimming pool hall with the fresh air fans. If necessary, the supply air
is warmed to the final temperature with the post-heating register in order
to reach the desired swimming pool temperature.
Advantages of GEA Fricostar Micro CAC:
Compact unit dimensions
Convenient fittings position, simple
connections
Multi-stage heat recovery
Low investment
Plate heat exchanger Evaporator Mixed air flaps Compressor
Fresh air fans Exhaust fan Condenser
1
5 76
2 3 4
Swimming pool operation
with dehumidification requirement
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Pool water condenser (PWC) = accessory4) Feed / return temperature = 70°C / 50°C
Standard series 1)
Unit typeCAC_SU 015 030 037
Unit dimensions
Width mm 760 760 760
Height mm 1480 1800 1800
Length mm 1640 2760 2760
Air volume flow
Minimum m3/h 750 1600 2000
Maximum m3/h 1600 2500 3600
Rating for dehumidification m3/h 1000 2000 3050
Rating for ventilation 2/3 m3/h 743 1320 2013
Dehumidification capacity
Swimming pool operation (30% outs. air) kg/h 5 12 17
Standby operation (recirculated air) kg/h 4 6 7
VDI 2089 2) kg/h 6 13 19
Thermal capacity
Air condenser without PWC operation kW 5.4 10.0 12.1
Air condenser with PWC operation kW 3.3 7.2 10.1
Pool water condenser 3) kW 2.4 3.2 3.0
Heat recovery kW 3.0 5.9 6.9
After heater 4) kW 10.0 16.2 23.2
1 2
4
356
7
16 PR-2009-0061-GB · Subject to modification · Version 02/2009
GEA Fricostar Micro CWC was developed for small private and public swim-
ming pools, i.e., hotel and therapeutic baths, and can be delivered in two
sizes. Owing to its compact dimensions and the special position of the con-
nection fittings, it is especially suitable for small technical rooms. The unit
is equipped with an efficient heat recovery (ECOPLAT POWER PLATE heat
exchanger) and a DDC unit.
When the swimming pool is in use with dehumidification, the warm swim-
ming pool hall exhaust air is cooled down in the plate heat exchanger. A
part of the swimming pool hall air is supplied by the mixed-air flaps to the
fresh air. The fresh air is pre-warmed in the plate exchanger and made avail-
able by the fresh air fans of the swimming pool hall. If necessary, the sup-
ply air is further warmed with the after-heating register in order to reach
the desired swimming pool hall temperature.
Advantages of GEA Fricostar Micro CWC:
Compact unit dimensions
Advantageous fittings position,
simpler connection
Heat recovery
Low investment
Low maintenance costs
Plate heat exchanger heater Fresh air fan exhaust fan1 2 3 4 Swimming pool operation
with dehumidification requirement
Compact climate-control unit without heat pump GEA Fricostar Micro CWC
Standard series 1)
Unit typeCWC_SU 015 037
Unit dimensions
Width mm 760 760
Height mm 1480 1800
Length mm 1640 2760
Air volume flow
Minimum m3/h 750 1500
Maximum m3/h 2000 3600
Rating for dehumidification m3/h 1500 2500
Rating for ventilation 2/3 m3/h 1000 1667
Dehumidification capacity
According to VDI 2089at rated airflow 2) kg/h 9.5 16
Thermal capacity
Heat recovery kW 2.8 4.8
After heater 3) kW 16.0 23.0
All data are rounded values and merely serve for an overview. For exact data of the current configuration, use GEA Air Treatment software.
1) Standard series = max. air velocity approx. 2.8 m/s2) Condition of hall air: 30°C / 54% rel. hum.3) Feed / return temperature = 70°C / 50°C
1
2
34
17PR-2009-0061-GB · Subject to modification · Version 02/2009
Standard equipment and accessories GEA CAIRfricostar and GEA Fricostar Micro
1) The unit types CAM, CMU, and CWR can be furnished with the fan unit LESS ENERGY SYSTEM as well as with the fan unit GEA OPTIVENT.
GEA CAIRfricostar GEA Fricostar MicroConstruction Modular CompactUnit type CAU CAM CMU CMP CPP CWP CWR CAC CWC
Series components
Heat pump for dehumidificationaccording to VDI 6022
Droplet eliminator
Fan unit GEAcentrifugal fanLESS ENERGY SYSTEM1 1)
Fan unitHigh performance fan impellersGEA OPTIVENT 1)
Filter according to DINwith pressure differentialswitch for filter monitoring
Heating sector PWW air heaters, heat exchanger with Cu pipes and pressed-on aluminium laminations with aluminium frame according to VDI 6022, extensible
GEA motor 3-way mixing valve
Air flap valve system for recirculated air/bypass
Heat recovery with heat pipetechnology ECOSTAT POWER TUBE
Heat recovery with double-plateheat exchangerECOPLAT 2 POWER PLATE
Heat recovery with plateheat exchangerECOPLAT POWER PLATE
All-electronic control
DDC control
Corrosion protection Class KStandard protection for normal spas
Optional accessory
Valve-limit switch for the demand-dependent control of theafter-heating pump 9349W20
Pool water pump, self-primingin corrosion resistant designof industrial quality F8ZBP
Corrosion protection Class HProtection for spas with salt content up to 3%
Corrosion protection Class PProtection for spas with salt content up to 3%
18 PR-2009-0061-GB · Subject to modification · Version 02/2009
Corrosion protection class K H P Standard Salt content up to 3% Salt content over 3%
Features
Aluminium components in endangered areas
Anti-corrosion Bumax screw connectors
V4A appliance parts with additional coating inendangered areas
V4A flaps
Protection paintwork for fans
Reinforced protection paintwork for fans
Protection paintwork for cooling cycle and components(section dependent)
Multicoat marine paint ULTRA HIGH SOLID for coolingcycle, flaps and various components
Plastic laminated cooling cycle pipe work(section dependent)
Alodyne coating of the heat exchangerlamellas
S70 immersion-bath coating, heat exchanger
SÄKA-TEC coating, evaporator
PlasTec capillary lines
Coated stainless steel panels
GEA CAIRfricostar and GEA Fricostar Micro Corrosion protection class
Technical information subject to change
19PR-2009-0061-GB · Subject to modification · Version 02/2009
GEA open- and closed-loop control technology
Intelligent control technology for optimal operation
All GEA air handling units for swimming pool hall climate
control and dehumidification possess a uniform and intelli-
gent control for energy-optimised and demand-controlled op-
eration
Simple and rapid commissioning of the software
The software is loaded in the factory and preset as required. On-
site commissioning therefore takes place considerably faster be-
cause only the relevant functions for the respective execution
appear in the display.
All-electronic control for the unit type CAU
The electronic system controls the functions of the plant. The
permissible humidity limit value is transferred to the control
with a hygrostat located in the swimming pool hall with func-
tion displays and switch. If the limit value is exceeded, the de-
humidification is initiated, the fan starts, and the compressor
equipment runs. If the air humidity falls below the preset val-
ue, then the compressor stops again. The surplus heat gained
from the dehumidification procedure can be made available to
the swimming pool hall air and, provided a pool water condens-
er is installed, to the pool water as well. The control automati-
cally monitors the cooling cycle of the system with a security
chain. With the remote control in the swimming pool hall, the
hygrostat can adjust the humidity, a master switch switches the
plant on or off, and LEDs inform on the operating state.
DDC control for all other unit types
Sophisticated DDC control automatically determines the most
favourable method of operation and supports the economical op-
eration of the air handling plant. In intermittent standby oper-
ation, the unit switches on or off in a predetermined cycle in
order to save energy and reduce noise emission. Free night cool-
ing and intermittent standby operation round off the range of
functions. All units can be operated on location, or if required
from a central control station. An optional modem permits re-
mote system checks. Interfaces to all prominent building man-
agement systems present no problem for GEA CAIRfricostar and
GEA Fricostar Micro. Systems such as BACnet, LON, MOD, EIB,
PROFIBUS, OPC, OSPA Blue Control, and Internet or SMS com-
munication can be easily connected.
GEA open- and closed-loop control system
Consisting of a separate switching cabinet for
extensions or separate installation (depending on
unit sizes) with all components necessary for the
monitoring and control of the unit, wired according
to VDE standards
IP55: electrical connections (by screw or terminal
plugs) between switching cabinet and unit by
prepared lines ready-to-install
Electrical installation for the voltage supply for
mixing valve actuation and after-heating pump
If necessary, exit for pool water pump, outdoor
sensor and further options such as external switch
function inputs provided by customer on site
The switching cabinet is delivered freestanding
– including mounting materials – for attachment to
the unit or as a standing cabinet (dependent on the
type of equipment)
All electronic monitoring and control components
are easily exchanged
20 PR-2009-0061-GB · Subject to modification · Version 02/2009
Components GEA open- and closed-loop control technology
Unit type CAU Principal mounting parts of control cabinet
Master switch for all-pole switch-off of the electrical system
Group fuses for fan and compressor– Fuse for pump after-heater circuit 230 V– Control fuse and control voltage power supply 24 V (safety low voltage SELV)– Actuation of the fresh air fans with motor full protection facility with PTC resistor temperature sensor and electronic motor full protection trip mechanism– Actuation compressor motor, with thermal motor protection as well as locking with security chain and control card, anti-icing protection monitoring, low pressure, high pressure– Electronic control card for the compressor control, with minimum running and minimum standby time as timing protection, service reset key, status indicator for time control as well as LED for cooling cycle disruption
Hygrostatic moisture control as remote control for the installation in swimming pool halls– With operation and malfunction light as well as operating switch– Operation with protective low voltage– Setpoint adjustor 30 - 90% relative humidity– Colour: white– Surface-mounted assembly– Dimensions: 145 mm wide x 80 mm high x 30 mm deep– Delivered as stand-alone
Electronic 3-point PI controller for exhaust air temperature control with setpoint value adjustment on the switchingcabinet, including built-in NTC exhaust air temperature sensor
Output 230 V for modulating 3-way valve motor in the after-heater circuit
If necessary, GEA pool water temperature control for actuation of the pool water pump– Consisting of the built-in immersion thermostat– Locking with compressor operation and output for pool water pump 230 V (only control output max. 2 A) as well as positive time control for actual value recording (only in connection with pool water condenser)
Output for common fault notification (zero-voltage change-over contact)
Actuation possibility of an on-site exhaust air fan, two levels, 230 V / max. 150 W
All unit types (apart from CAU) with DDC controllerPrincipal mounting parts for the control cabinet
Master switch for all-pole switch-off of the electrical system as switch disconnector, lockable
Groups fuses for fan and compressor
Fuses for after-heater pump (and possibly pool water condenser pump)– 230 V / N / PE / 50 Hz (unit sizes 015 to 083)– 3 x 400 V / N / PE / 50 Hz (unit sizes 100 to 320), motor protection by the owner if required
Control fuses, control transformer 230 V, and control voltage power supply 24 V DC for digital control
Control automatic circuit breaker and control voltage power supply 24 V AC for actuators
Phase detector (optional)
Interior assembly, frost-free
21PR-2009-0061-GB · Subject to modification · Version 02/2009
All unit types (apart from CAU) with DDC controllerOpen- and closed-loop control functions
– Operation and malfunction messages as plaintext
– Display of all operation and control parameters
– Multi-level access rights with code
– Integrated timer switch
– Automatic summer/winter switchover, week timer, holidays and special days programs
– Malfunction storage with date and time stamp
– Service hour counter, total working time and service intervals
– Data logger function for important parameters, accessible
– Separate supply and exhaust fan motor control
– Air volume flow adjustment and display in m3/h, including monitoring for equipment with frequency converters
– Fan motor monitoring with PTC resistor and motor protection relay
– Filter monitoring
– Compressor control (heat pump) with minimum run/standing times
– Mixing flaps control with selectable minimum outside-air fraction and maximum limitation, automatically regulating depending on the outside and swimming pool hall air state
– Control sequence with heat/cold-recovery system, heating unit, possibly compressor (heat pump), bypass flaps and mixed air flaps system
– Exhaust air temperature cascade control with min/max limitation of the supply air temperature
– Cooling with outside air (night cooling)
– After-heater pump requirements control with stoppage protection function
– Continuous moisture control
– Possible automatic pool water pump requirement control with stoppage protection function
– Automatic swimming pool operation/standby switchover
– Intermittent pre-selectable standby operation
– Several languages selectable in the display
– Initial startup function for dampers
– Inputs: external safety shut-off (i.e., fire-protection damper or chlorine gas warning)
– Motor monitoring for switchable NE pump, with motor protection provided by the owner if necessary
– Motor monitoring for switchable basin water pump, with motor protection provided by the owner if necessary
All unit types (apart from CAU) with DDC controllerDigital control
– Modular automation station incorporated in the control cabinet with secured software modules, as well as digital and analogue inputs and outputs, equipped for all control and monitoring tasks of the swimming pool hall air dehumidification unit
– Comfortable operator terminal with its own intelligent system supporting the display, the operating keys as well as the data transfer incorporated in the control cabinet door
– Aluminium face plate with sealed keyboard
– Keyboard connector with plug connector
– Safety protection class IP65 on the front side
– LCD display with 8 lines of 40 characters each as plaintext display, monochrome
– 6 function keys
– Coloured back lighting, configurable, automatic illumination switching
– LCD contrast adjustment is configurable
– System bus CAN
GEA Control and regulating technology Components
22 PR-2009-0061-GB · Subject to modification · Version 02/2009
All unit types (apart from CAU) with DDC controllerOptional accessories Designation
– Access expansion for on-site control action DEW
– Floating contacts for messages DPK
– Output expansion, 0 -10 V signal, return air humidity and exhaust air temperature DAW
– Input expansion for on-site setpoint value logging, 0 -10 V signal, return air humidity, exhaust air temperature and minimum outside-air fraction DFV
– Fault notification fire protection flap / fire detection facility BSK
– Operating display in separate enclosure as remote control (without cabinet display) DFB
– Additional operator display in separate enclosure as remote control DFD
– Automatic humidity setpoint value logging DFS
– Air stream monitoring for supply and exhaust fan DLW
– Emergency/manual operation for fans, NE valve, pump, damper actuator DNH
– Automatic room temperature setpoint value adaptation (dependent on pool water temperature) DTA
– Interface for GSM modem including operator control software GSM
– Interface for ISDN modem including operator control software ISDN
– Interfaces from GEA to the GFR building services management system DSG
– Interface to OPC - S Bus OPC
– Interface to BACnet Bus BACNET
– Interface to LON Bus LON
– Interface to OSPA Blue Control OSPA
– Interface to MOD Bus MOD
– Creation of data point list for respective BMS systems xxxDP
– Support of the network technician for commissioning the connections of the BMS connections on location (prerequisite is a complete on-site exclusion of units) xxxIB
– Interface for modem DSM
– Comfortable touch operator terminal (LCD Display with 16 colours, graphic resolution 320 x 240 pixel) TBT
– Software WEBVISION light WEV
Accessories GEA open- and closed-loop control technology
Technical information subject to change
You are on this level of our documentation structure. You can order at no charge
from the first 3 levels as printed copies, under: [email protected].
You can download all brochures as PDF files from the following Internet site:
www.gea-airtreatment.com.
Application brochures
Image brochure
Product brochures
Data & Facts and operation manuals (available only as PDF)
23PR-2009-0061-GB · Subject to modification · Version 02/2009
Customer proximity, sales structures
Reachable always and everywhere!
The complete addresses are available on the Internet under: www.gea-air-eco2nomy.com.
www.gea-air-eco2nomy.com
02/2
009
– PR
-200
9-00
61-G
B Su
bjec
t to
mod
ifica
tion
• C
opyr
ight
GEA
GEA Air Treatment
Middle East
UAE-Dubai
Tel. +971 / 4 / 887 3881
GEA Klimatechnik
GmbH & Co KG
A-4673 Gaspoltshofen
Tel. +43 / 7735 / 8000-0
GEA Klimatechnik
GmbH & Co KG
RS-11070 Novi Beograd
Tel. +381 / 11 / 3193955
GEA Happel Belgium N. V.
B-1130 Brussels
Tel. +32 / 2 / 2406161
EVISS Ltd.
BG-7000 Rousse
Tel . +359 / 82 / 81000
GEA Klimatechnik UAB
LT-01141 Vilnius
Tel. +370 / 5 / 2106060
ATC Klimatec Schweiz AG
CH-3065 Bolligen
Tel. +41 / 31 / 9171919
GEA LVZ, a.s.
CZ-46312 Liberec
Tel. +420 / 48 / 5225-111
GEA Klimatizace spol. s r.o.
CZ-46312 Liberec
Tel. +420 / 48 / 5225-303
GEA Happel
Klimatechnik GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-00
GEA Happel
Wieland GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-754
GEA Deichmann
Umwelttechnik GmbH
D-36179 Bebra
Tel. +49 / 6622 / 504-0
GEA Delbag
Lufttechnik GmbH
D-44625 Herne
Tel. +49 / 2325 / 468-700
GEA Delbag-Luftfilter
Vertriebsgesellschaft mbH
D-10709 Berlin
Tel. +49 / 30 / 43592-3
CS Klimateknik ApS
DK-5450 Otterup
Tel . +45 / 38 / 887070
GEA Klimatechnik UAB
LT-01141 Vilnius
Tel. +370 / 5 / 2106060
GEA Air Treatment
Marketing Services Int.
GmbH – oficina España
ES-28028 Madrid
Tel. +34 / 91 / 3837701
OY TEKNOCALOR AB
FIN-01300 Vantaa
Tel. +358 / 10 / 8201100
GEA Delbag
Filtration de l‘air
F-77450 Montry
Tel. +33 / 1 / 60043355
GEA Happel France sarl
F-59436 Roncq Cedex
Tel. +33 / 3 / 20689020
GEA Denco Ltd.
UK-HR4 8DS Hereford
Tel. +44 / 1432 / 277 277
GEA Klima-rashladna
tehnika d.o.o.
HR-10000 Zagreb
Tel. +385 / 1 / 6064900
GEA Klimatechnika Kft
H-1037 Budapest
Tel. +36 / 1 / 4393200
Aspect Environmental Ltd.
Ardee, Co. Louth Ireland
Tel. +353 / 41 / 6858983
Rafn Jensson
IS-110 Reykjavik
Tel. +354 / 56 / 780-30
GEA Klimatechnik UAB
LT-01141 Vilnius
Tel. +370 / 5 / 2106060
GEA Happel Luxembourg
L-4940 Bascharage
Tel. +352 / 26 / 502970
GEA Klimatechnik UAB
LT-01141 Vilnius
Tel. +370 / 5 / 2106060
GEA Klimatechnik
GmbH & Co KG
RS-110 70 Novi Beograd
Tel. +381 / 11 / 3193955
GEA Happel Nederland B.V.
NL-2909 LL
Capelle a/d Ijssel
Tel. +31 / 10 / 2350606
GEA Klimaprodukter AS
N-0484 Oslo
Tel. +47 / 220 / 27990
GEA Klimatyzacja Sp. z o.o.
PL-54610 Wroclaw
Tel. +48 / 71 / 3737952
Nónio, Lda.
P-1269-090 Lisboa
Tel. +351 / 21 / 3826160
GEA Klimatechnik s.r.l.
RO-300222 Timisoara
Tel. +40 / 356 / 423703
GEA Klimatechnik
GmbH & Co KG
RU-105094 Moskva
Tel. +7 / 495 / 9566674
GEA EXOS Ventilation AB
S-74528 Enköping
Tel. +46 / 171 / 85530
GEA Klimatizacijska
Tehnika d.o.o.
SI-1000 Ljubljana
Tel. +386 / 1 / 2573850
GEA Klimatizácia s.r.o.
SK-83104 Bratislava
Tel. +421 / 7 / 44457917
GEA Klimatechnik
GmbH & Co KG
RS-11070 Novi Beograd
Tel. +381 / 11 / 3193955
GEA ISISAN
TR-80700
Balmumcu Istanbul
Tel. +90 / 212 / 2757171
GEA Ukraina t.o.v.
UA-01135 Kyiv
Tel. +38 / 044 / 4619356
AT
BE
BG
BA
BY
CH
CZ
CZ
DE
DE
DE
DE
DE
PT
RO
UA
RU
SE
SK
SI
RS
TR
AE
DK
ES
EE
FR
FI
FR
HU
NL
LV
IE
IS
LU
ME
NO
HR
LT
PLGB