Special Reinforced Concrete Structural Walls
The requirements of this section apply to special reinforced concrete
structural walls serving as part of the earthquake force-resisting system.
Shear Strength:
Based on ACI 18.10.4.1, nominal shear strength nV of structural walls is not
to exceed
ytcccvn ffAV '
Where c is a coefficient defining the relative contribution of concrete
strength to wall strength, given as follows.
c = 0.80 for 5.1/ ww lh ;
c = 0.53 for 0.2/ ww lh ;
c = 0.53 to 0.80 (linear variation) for ww lh / between 1.5 and 2.0.
cvA = gross area of concrete section bounded by web thickness and length of
section in the direction of shear force considered, cm2.
Shear Reinforcement:
At least two curtains of reinforcement shall be used in a wall if the in-plane
factored shear force assigned to the wall exceeds ccv fA 53.0 or 0.2/ ww lh ,
as specified by ACI 18.10.2.2.
Based on ACI 18.10.2.1, the distributed web reinforcement ratios, l and
t for structural walls shall not be less than 0.0025, except if uV does not
exceed ccv fA 27.0 , l and t shall be permitted to be reduced to the
values required in ACI 11.6. Reinforcement spacing each way in structural
walls shall not exceed 45 cm. reinforcement contributing to uV shall be
continuous and shall be distributed a cross the shear plane.
According to ACI 18.10.4.3, walls are to be reinforced with shear
reinforcement in two orthogonal directions in the plane of the wall.
If 0.2/ ww lh , reinforcement ratio l shall be at least the reinforcement ratio
t .
`
144
Design for Flexure and Axial Loads:
Based on ACI 18.10.5.1, structural walls and portions of such walls subject
to combined flexural and axial loads shall be designed in accordance with
ACI 22.4.
Horizontal Wall Segments:
ACI 2.3 defines a horizontal wall segment, shown in the Figure R18.10.4.5,
as a segment of structural wall, bounded vertically by two openings or by an
opening and an edge. A vertical wall segment is a segment of a structural
wall bounded horizontally by two openings, or by an opening and an edge;
wall piers are vertical wall segments. A vertical wall segment is referred to
as a coupling beam when openings are aligned vertically over the building
height.
Normal shear strength of horizontal wall segments shall be assumed not to
exceedccw fA '65.2 , where cwA is the cross-sectional area of a horizontal
wall segment or coupling beam, as specified in ACI 18.10.4.5.
Wall Piers:
ACI 2.3 defines a wall pier as a vertical wall segment within a structural
wall, bounded horizontally by two openings or by an opening and an edge,
with ratio of horizontal length to wall thickness ( ww bl / ) less than or equal to
6.0, and ratio of clear height to horizontal length ( ww lh / ) greater than or
equal to 2.0
ACI 18.10.4.4 states that normal shear strength of all wall segments sharing
a common lateral force, nV , shall not be taken larger than ccv fA 12.2 , where
`
145
cvA is the total cross-sectional area of concrete bounded by web thickness
and length of section. The normal shear strength of any one of the individual
wall pier, nV , shall not be taken larger than ccw fA '65.2 , where cwA is the
cross-sectional area of the individual vertical wall segment considered.
In ACI 18.10.4.2, the value of ratio ww lh / used for determination of nV for
segments of a wall shall be the larger of the ratios for the entire wall and the
segment of wall considered.
Boundary Elements:
ACI 2.3 defines a boundary element as a portion along wall and diaphragm
edge, including edges of openings, strengthened by longitudinal and
transverse reinforcement.
Two design approaches for evaluating the need of boundary elements at the
edges of structural walls are provided in ACI 18.10.6.2 and explained below.
A- For walls or wall piers with 0.2/ ww lh that are effectively continuous
from the base of the structure to top of wall and designed to have a single
critical section for flexure and axial loads, ACI 18.10.6.2 requires that
compression zones be reinforced with special boundary elements where:
wu
w
h
lc
/5.1600
and c corresponds to the largest neutral axis depth calculated for the factored
axial force and nominal moment strength consistent with the direction of
design displacement u . The ratio wu h/ in the previous equation shall not be
taken less than 0.005.
Special boundary element reinforcement shall extend vertically above and
below the critical section at least the greater of wl and uu VM 4/ , except when
the critical section occurs at wall base, the boundary element transverse
reinforcement at the wall base shall extend into the support at least dl of the
largest longitudinal reinforcement in the special boundary element. Where
the special boundary element terminates on a footing, mat, or pile cap,
special boundary element transverse reinforcement shall extend at least 30
cm into the footing, mat, or pile cap, unless a greater extension is required
by ACI 18.13.2.3.
`
146
The above design approach uses a displacement-based model. In this
method, the wall is displaced an amount equal to 1.5 the expected design
displacement, and boundary elements are required to confine the concrete
when the strain at the extreme compression fiber of the wall exceeds a
critical value.
Boundary Element Requirements (ACI 18.10.6.2)
B- Structural walls not designed to the provisions of ACI 18.10.6.2, shall
have special boundary elements at boundaries and edges around openings of
structural walls where the maximum extreme fiber compressive stress,
corresponding to factored forces including earthquake effect, exceeds cf 2.0 .
The special boundary element shall be permitted to be discontinued where
the calculated compressive stress is less than cf 15.0 , as stated in ACI
18.10.6.3.
Stresses are calculated for the factored forces using a linearly elastic model
and gross section properties, as given here
g
wu
g
u
I
lM
A
Pf
2/
`
147
Boundary Element Requirements (ACI 18.10.6.3)
Boundary Element Dimensions:
As required by ACI 18.10.6.4, boundary elements are to extend horizontally
from the extreme compression fiber a distance not less than the larger of
wlc 1.0 and .2/c
Width of the flexural compression zone, b, over the horizontal distance
calculated above, including flange if present, shall be at least 16/uh , where
uh is equivalent to ul . For walls or wall piers with 0.2/ ww lh and with
8/3/ wlc , width of flexural compression zone shall be greater than or equal
to 30 cm.
Boundary Element Transverse Reinforcement:
The boundary element transverse reinforcement shall satisfy the
requirements of ACI 18.7.5.2(a) through (e) and 18.7.5.3, except the value
of xh in 18.7.5.2 shall not exceed the lesser of 35 cm and two-thirds of the
boundary element thickness, and the transverse reinforcement spacing limit
of 18.7.5.3(a) shall be one-third of the least dimension of the boundary
element.
The amount of transverse reinforcement shall be in accordance with Table
18.10.6.4(f).
The above requirements are summarized below:
`
148
Transverse reinforcement shall be provided by either single or overlapping
hoops. Crossties of the same bar size and spacing as the hoops shall be
permitted. Each end of the crossties shall engage a peripheral long
reinforcing bar. Consecutive crossties shall be alternated end for end and
along the longitudinal reinforcement. Spacing of crossties or legs of
rectangular hoops, xh within a cross section of the member shall not exceed
35 cm on center.
where:
shA total cross-sectional area of transverse reinforcement, including
crossties, within spacing s and perpendicular to dimension cb , cm2.
gA gross area of concrete section, cm2.
chA cross-sectional area of a member measured to the outside edges of
transverse reinforcement, cm2.
s = spacing of transverse reinforcement measured along the longitudinal
axis of the structural member, center-to-center.
cb = cross-sectional dimension of member core measured to the outside
edges of the transverse reinforcement composing area shA , cm.
xs = maximum center-to-center spacing of longitudinal bars supported by
corners of crossties or hoop legs around the perimeter of the boundary
element.
ytf = specified yield strength of transverse reinforcement.
cf = specified compressive strength of concrete.
`
149
Based on ACI 18.7.5.3, spacing of transverse reinforcement shall not exceed
the smallest of (a) through (c):
(a) one-third of the minimum member dimension (as modified by ACI
18.10.6.4(e)),
(b) six times the diameter of the smallest longitudinal bar
(c) s as calculated by:
3
h3510s x
The value of s shall not exceed 15 cm and need not be taken less than 10
cm.
In ACI 18.10.6.5, where special boundary elements are not required by ACI
18.10.6.2 or 18.10.6.3, (a) and (b) shall be satisfied.
(a) If the longitudinal reinforcement ratio at the wall boundary is
greater than yf/28 , boundary transverse reinforcement shall
satisfy 18.7.5.2(a) through (e) over the distance calculated in
accordance with 18.10.6.4(a). The maximum longitudinal spacing
of transverse reinforcement in the boundary shall not exceed the
lesser of 20 cm and bd8 ;
(b) Except when uV in the plane of the wall is less than
ccv fA 265.0 , horizontal reinforcement terminating at the edges
of structural walls without boundary elements shall have a standard
hook engaging the edge reinforcement or the edge reinforcement
shall be enclosed in U-stirrups having the same size and spacing as
and spliced to the horizontal displacement.
`
150
Reinforcement Details for Boundary Elements
Anchorage and Splicing of Reinforcement:
In ACI 18.8.5.1, the development length dhl for a bar with a standard 90
degree hook shall not be less than the largest of bd8 , 15 cm, and the length
required by the following equation, which is applicable to bar diameters
ranging from 10 mm to 36 mm.
c
yb
dhf
fdl
'17
The 90-degree hook shall be located within the confined core of a boundary
element.
`
151
In ACI 18.8.5.3, for bar diameters 10 mm through 36 mm, the development
length dl , in tension, for a straight bar shall not be less than (a) and (b):
(a) 2.5 times the length required by the above-mentioned equation if
the depth of the concrete cast in one lift beneath the bar does not
exceed 30 cm, and
(b) 3.25 times the length provided by the same equation if the depth of
the concrete cast in one lift beneath the bar exceeds 30 cm.
In ACI 18.8.5.4, straight bars terminated at a joint shall pass through the
confined core of a boundary element. Any portion of dl not within the
confined core shall be increased by a factor of 1.6.
The next figures show boundary element requirements for special shear
walls.
`
152
`
153
Example (7):
Redesign shear wall 'A' in example (6) as a special shear wall using ACI
318-14 for reinforced concrete design.
Use 22 /4200 and /300 cmkgfcmkgf yc .
Solution:
Design for shear: -1
At least two curtains of reinforcement shall be used in a wall if the in-plane
factored shear force exceeds ccv 'fA53.0 or 0.2/ ww lh .
tonsfAV ccvn 08.551000/3003002053.053.0
21.2075.0
16.15
uV> 55.08 tons
Since 83
24/ ww lh , two curtains of reinforcement are required.
1-1 Horizontal shear reinforcement:
0025.0t
cm45S max,2
cm/cm05.0S
A and 200025.0h0025.0
S
A 2
2
t
2
t
For two curtains of reinforcement and trying 10 mm bars
max,22
2
Scm4.31S ,05.0S
785.02 . Use 10 mm bars @ 30cm.
tons374.17tons06.281000/3003002027.0'fA27.0 ccv
Thus t and l may be reduced based according to ACI 11.6. Nevertheless,
it will not be reduced in this example.
`
154
1-2 Vertical shear reinforcement:
cm45S max,1
For two curtains of reinforcement, and trying 10 mm bars
11
l
S
0.7852 200025.0h0025.0
S
A
and max,11 Scm40.31S . Use 10mm bars @ 30cm.
Check for shear reinforcement capacity
tonsVn 21.2075.0/16.15
ytcccvn f'fAV
83
24/ ww lh ,i.e.
53.0c
KOtonstons
ffAV ytcccvn
.21.2008.1181000/42000025.030053.030020
max,
2- Design for flexure and axial loads:
Boundary elements are required where the maximum fiber compression
stress > c'f2.0 , calculated from the following equation:
g
wu
g
u
I
2/lM
A
Pf
The boundary elements may be disconnected where the compressive stress
< c'f15.0
wys
uwysu
l
c1
fA
P1lfA5.0M
where:
1w 85.02l
c
,
'fhl
fA
cw
ys and
'fhl
p
cw
u
For the vertical shear reinforcement of 10 mm
@30cm, 2s cm28.17A 836.0280300
70
05.085.0 ,
04032.030020300
420028.17
'fhl
fA
cw
ys
`
155
, u
u
cw
u P00055.030020300
1000P
'fhl
p ,
79124.0
P00055.004032.0
836.085.004032.02
P00055.004032.0
l
c uu
w
Load combinations are
EDS QDS 2.02.1
EDS QDS 2.09.0
For first storey:
tonsPu 92.435.22432.022.1
3002.0/81.9512/30020
2/30010000047.265
30020
100092.43 2
3 cmkgf
i.e., special boundary elements are required at wall ends.
Flexural capacity at section of maximum moment:
08094.0
79124.0
92.4300055.004032.0
wl
c
cmc 28.2430008094.0 , and length of boundary element is not less than the
larger of wl1.0c and cmc 14.122/
mtMu .54.144 and
mtM u .93.12054.14447.265' For a boundary element 35 cm in length, additional reinforcement in each of
the two boundaries is given as follows
2
, 40.15785.0426142009.0
10000093.120cmA additionals
Use 8 16 mm bars in each of the two boundary elements.
Boundary element transverse reinforcement:
The larger of:
yt
ccsh
f
bsfA
09.0
yt
c
ch
g
shf
f
A
AA
130.0
`
156
cms
cm
cm
ofsmallesttheS
22.173
33.133510
6.96.16
67.63/20
max
where xh is the lesser of 35 cm and (20x2/3)
and
maxS is taken as 5 cm.
For the longer direction of boundary, cmbc 1242201
For the shorter direction of boundary, cmbc 314352
239.04200
30012509.0cmAsh
213.14200
3001
3112
203551230.0 cmAsh
Use 2-legged mm10 ties @ 5 cm
Anchorage of horizontal shear reinforcement:
For 10 mm bars hooked at 180 degree,
cm
f
dfA
c
by
sh 26.1430017
14200
17
For straight bars
cmld 91.4926.145.3 , taken as 50 cm, N.O.K
For second storey: tonsPu 43.385.22132.022.1
`
157
3002.0/74.7912/30020
2/30010000099.219
30020
100043.38 2
3 cmkgf
i.e., special boundary elements are required at wall ends.
Flexural capacity at section of maximum moment:
0771.0
79124.0
43.3800055.004032.0
wl
c
cmc 13.233000771.0 , and length of boundary element is not less than the
larger of wl1.0c and cmc 57.112/
mtMu .3.138 and
mtM u .69.8130.13899.219' For a boundary element 35 cm in length, additional reinforcement in each of
the two boundaries is given as follows
2
, 42.11785.0426142009.0
10000069.81cmA additionals
Use 8 14 mm bars in each of the two boundary elements.
Boundary element transverse reinforcement:
The larger of:
yt
ccsh
f
bsfA
09.0
yt
c
ch
g
shf
f
A
AA
130.0
cms
cm
cm
ofsmallesttheS
22.173
33.133510
6.96.16
67.63/20
max
where xh is the lesser of 35 cm and (20x2/3)
and
maxS is taken as 5 cm.
For the longer direction of boundary, cmbc 1242201
`
158
For the shorter direction of boundary, cmbc 314352
239.04200
30012509.0cmAsh
213.14200
3001
3112
203551230.0 cmAsh
Use 2-legged mm10 ties @ 5 cm
Anchorage of horizontal shear reinforcement:
For 10 mm bars hooked at 180 degree,
cm
f
dfA
c
by
sh 26.1430017
14200
17
For straight bars
cmld 91.4926.145.3 , taken as 50 cm, N.O.K
For third storey:
tonsPu 94.325.21832.022.1
3002.0/96.6312/30020
2/30010000041.175
30020
100094.32 2
3 cmkgf
i.e., special boundary elements are required at wall ends.
Flexural capacity at section of maximum moment:
0733.0
79124.0
94.3200055.004032.0
wl
c
cmc 223000733.0 , and length of boundary element is not less than the
larger of wl1.0c and cmc 112/
mtMu .0.132 and
mtM u .41.430.13241.175' For a boundary element 35 cm in length, additional reinforcement in each of
the two boundaries is given as follows
`
159
2
, 54.7785.0426142009.0
10000041.43cmA additionals
Use 6 14 mm bars in each of the two boundary elements.
Boundary element transverse reinforcement:
The larger of:
The larger of:
yt
ccsh
f
bsfA
09.0
yt
c
ch
g
shf
f
A
AA
130.0
cms
cm
cm
ofsmallesttheS
22.173
33.133510
6.96.16
67.63/20
max
where xh is the lesser of 35 cm and (20x2/3)
and
maxS is taken as 5 cm.
For the longer direction of boundary, cmbc 1242201
For the shorter direction of boundary, cmbc 314352
239.04200
30012509.0cmAsh
213.14200
3001
3112
203551230.0 cmAsh
Use 2-legged mm10 ties @ 5 cm
Anchorage of horizontal shear reinforcement:
For 10 mm bars hooked at 180 degree,
cm
f
dfA
c
by
sh 26.1430017
14200
17
`
160
For straight bars
cmld 91.4926.145.3 , taken as 50 cm, N.O.K
For fourth storey:
tonsPu 45.275.21532.022.1
3002.0/88.4812/30020
2/30010000090.132
30020
100045.27 2
3 cmkgf
i.e., special boundary elements are required at wall ends, and will be
discontinued when 30015.0f . Nevertheless, the boundary will be used
throughout the entire fourth floor.
Flexural capacity at section of maximum moment:
06950.0
79124.0
45.2700055.004032.0
wl
c
cmc 85.203000695.0 , and length of boundary element is not less than the
larger of wl1.0c and cmc 43.102/
mtMu .65.125 and
mtM u .25.765.12590.132' For a boundary element 35 cm in length, additional reinforcement in each of
the two boundaries is given as follows
2
, 87.3785.0426142009.0
10000025.7cmA additionals
Use 6 10 mm bars in each of the two boundary elements.
Boundary element transverse reinforcement:
The larger of:
yt
ccsh
f
bsfA
09.0
yt
c
ch
g
shf
f
A
AA
130.0
`
161
cms
cm
cm
ofsmallesttheS
22.173
33.133510
6.96.16
67.63/20
max
where xh is the lesser of 35 cm and (20x2/3)
and
maxS is taken as 5 cm.
For the longer direction of boundary, cmbc 1242201
For the shorter direction of boundary, cmbc 314352
239.04200
30012509.0cmAsh
213.14200
3001
3112
203551230.0 cmAsh
Use 2-legged mm10 ties @ 5 cm
Anchorage of horizontal shear reinforcement:
For 10 mm bars hooked at 180 degree,
cm
f
dfA
c
by
sh 26.1430017
14200
17
For straight bars
cmld 91.4926.145.3 , taken as 50 cm, N.O.K
For fifth storey:
tonsPu 96.215.21232.022.1
3002.0/92.3412/30020
2/30010000078.93
30020
100096.21 2
3 cmkgf
`
162
and < 0.15 (300)
i.e., special boundary elements are no longer required at wall ends.
Flexural capacity at section of maximum moment:
0657.0
79124.0
96.2100055.004032.0
wl
c
mtmtMu .78.93.24.119
Thus, no additional reinforcement is required at wall ends.
For sixth, seventh and eighth storeys
No additional reinforcement is required.