G O D S H A L L K A N E O ’ R O U R K E A R C H I T E C T S , L L C
KEVIN R. GODSHALL, AIA · DAMON ROYAL KANE, AIA EMERITAS · P. MICHAEL O’ROURKE, AIA
300 BROOKSIDE AVENUE BUILDING 18, SUITE 150 AMBLER YARDS AMBLER, PA 19002 T: 215.646.2003 www.gkoarchitects.com
Shop Drawing/ Submittal Review
Project Name: Villa Joseph Marie High School
Auditorium Addition
GKO Project #: 2339
Submittal For: 23 74 35 1750-01 Aaon RTUs Date Submitted: 2/22/18
Corrections or comments made during this review does not
relieve the Contractor from compliance with requirements of
the drawings and specifications. This check is only for review
of general conformance with the design concept of the project
and general compliance with the information given in the
contract documents. The contractor is responsible for;
confirming and correlating all quantities and dimensions;
selecting fabrication processes and techniques of construction;
coordination of his work with that of all other trades; and
performing his work in a safe and satisfactory manner.
Reviewed By: Jason Mulligan, GKO
Date Returned: 3/20/18
Comments:
☒ No Exceptions Taken
☐ Furnish As Corrected
☐ Revise and Resubmit
☐ Rejected/ Resubmit
Corrections or comments made on the shop drawings during this review do not relieve contractor from compliance with requirements of the drawings and specifications. This check is only for review of general conformance with the design concept of the project and general compliance with the information given in the contract documents. The contractor is responsible for: confirming and correlating all quantities and dimensions; selecting fabrication processes and techniques of construction; coordinating his work with that of all other trades; and performing his work in a safe and satisfactory manner.
Submittal Review Cover Sheet
Project Name: Villa Joseph Marie High School - Auditorium Addition
Client: GKO Architects
Submittal #: 23 74 35 - 1
Submittal Name: Rooftop AC Units
Reviewed By: Gene Hoffman
Date: 03.12.2018
☒ No Exceptions Taken ☐ Revise & Resubmit
☐ Rejected/Resubmit ☐ Furnish as Corrected
☐ Furnish as Corrected and Resubmit
Engineer’s Review Comments:
Villa Joseph Marie High School
Auditorium
NBRI Project No: 1750
Villa Joseph Marie High School
1180 Holland Road
Holland, PA 18966
Twining Construction Company
1801 2nd St. Pike
Richboro, PA 18954
Aaon
H.C. Nye Company, Inc.
2999 Revere Street
Harrisburg, PA 17111
237435 Rooftop Air Conditioning Units
APPROVED: X APPROVED AS NOTED:
BY: Date:
Justin Rogers No.
Project Manager
Date: 2/19/2018
311 County Line Road, Suite 31, Gilbertsville, PA 19525
Project:
Specification Section:
SUBMITTAL COVER SHEET
CONTRACTORʹS REVIEW
Owner:
General Contractor:
Manufacturer:
Subcontractor / Supplier:
1
H.C. Nye Company, Inc. Environmental Solutions
2999 Revere Street; Harrisburg, PA 17111 (717) 561-2500; Fax: (717) 561-2577
SUBMITTAL DATA
DATE: February 7, 2018
JOB NAME: Villa Joseph Marie HS – Auditorium Addition
CONTRACTOR: NB Rogers, Inc.
EQUIPMENT: Packaged Rooftop Units (Tag: RTU-1 thru 6)
MANUFACTURER: Aaon, Inc.
SALESMAN: Tim Wenrich
SUBMITTAL NOTES:
2
H.C. Nye Company, Inc. Environmental Solutions
2999 Revere Street; Harrisburg, PA 17111 (717) 561-2500; Fax: (717) 561-2577
Submittal Notes: (6) Aaon Packaged Rooftop Units (Tag: RTU-1 thru 6) To Include the following:
- 2” Double Wall Construction w/R13 Spray Foam Insulation - RTU-1, 2, 3 shall have horizontal supply and bottom return without use of a plenum curb - RTU-4, 5, 6 shall have bottom supply and return - Voltage 460v-3ph-60hz - Single Point Power Connection - R410A Refrigerant - Copeland digital scroll compressors, capable of modulating to 10% of rated capacity - Fully modulating economizer with enthalpy control - Factory installed power exhaust fans with VFD's - Modulating Hot Gas Reheat Coil - factory installed - Stainless steel natural gas fired heat exchanger with modulating control valve (except RTU-6) - Factory installed hot water heating coil - RTU-6 only - 2" Pleated pre-filter - 30% Eff with 4" thick - 85% efficient filters - 115v Convenience Outlet (Factory Wired) - Supply Fan w/VFD - Non-fused Disconnect Switch - Phase and brown out protection - Stainless Steel Drain Pan - Factory Installed DDC Controller with required sensors - Terminal block for connection to field supplied smoke detectors - 1-Year Unit Parts Only Warranty (Labor Not Included) - 5-Year Compressor Parts Only Warranty (Labor Not Included) - 25-year non-pro rated warranty on the SS heat exchanger - parts only - Factory authorized start up - 18" high roof curb with duct kits with 1" spring isolation rails, curb installed on flat roof
***ITEMS NOT INCLUDED***
- Rigging, hauling, installation - Air Flow Stations - Smoke detectors - Labor warranty - Seismic ratings for roof curb
* Factory start up requires a minimum of 3 weeks notice prior to schedule.
*Pre-start up checklists must be submitted with request to schedule a date.
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1 2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D
7
8
9A
9B
9C
9D
R N A - 0 1 6 - C - 0 - 3 - D A A 0 A - D B 1 K 0 : 0 1 - D Q 0 J - G 0 0 - 0 0 0 0 - C L B G - Q C - C B 0 0 - 0 0 - E 0 - 0 - A N 0 - E B - B K 0 B - 0 0 - 0 0 0 - A A 0 A 0 0 - E 0 0 0 0 0 - 0 0 0 0 0 0 X
10A
10B
11A
11B
12
13A
13B
13C
14
15
16A
16B
16C
16D
17A
17B
18A
18B
18C
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tag: RTU #1, 2
(Values do not account for changes described in SPA)
Job Information Unit Information **WEIGHT AND PERFORMANCE DO NOT INCLUDE SPA
Job Name: Approx. Op./Ship Weights: Job Number: Supply CFM/ESP: Site Altitude: Pre-Filter FV / Qty: Refrigerant Coil Filter FV / Qty:
Exhaust CFM/ESP/TSP: Outside CFM: Ambient Temperature: Return Temperature:
Villa Joseph Marie 3606 / 3606 lbs. (±5%)Job #14238 5000 / 1 in. wg.0 ft 240.00 fpm / 6R-410A 240.00 fpm / 6
5000 / 0.50 / 0.75 in. wg.170092 ºF DB / 74 ºF WB75 ºF DB / 62 ºF WB
Static Pressure External: Economizer: Evaporator: Heating: Coil Filters Clean: Cabinet: Dirt Allowance Re-Heat Coil: Total:
1.00 in. wg. 0.09 in wg0.15 in wg 0.20 in wg0.21 in wg 0.08 in. wg.0.35 in. wg. 0.03 in wg
2.11 in wg
Cooling Section Heating SectionGross Net
Total Capacity: Sensible Capacity: Latent Capacity: Mixed Air Temp: Entering Air Temp: Lv Air Temp (Coil): Lv Air Temp (Unit) Digital Comp. Capacity Ratio: Supply Air Fan: SA Fan RPM / Width: Exhaust Air Fan: EA Fan RPM / Width:
Evaporator Coil: Evaporator Face Velocity:
188.93 180.89 MBH139.41 131.37 MBH49.52 MBH80.78 ºF DB 66.44 ºF WB80.78 ºF DB 66.44 ºF WB54.40 ºF DB 53.44 ºF WB55.87 ºF DB 54.04 ºF WB100%1 x 270 @ 2.83 BHP993 / 4.965"1 x RM220A @ 1.38 BHP1197 / 4.920"
19.9 ft² / 3 Rows / 14 FPI251.7 fpm
PreHeat Type: Std (No Preheat)
Heating Type: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Input: Heater Qty: Consumption: Total Turndown Ratio:
Nat. Gas Heat5000218.7 MBH0.0 ºF DB / -1.0 ºF WB75.0 ºF DB / 62.0 ºF WB49.5 ºF DB / 46.6 ºF WB90.0 ºF DB / 62.9 ºF WB270.0 MBH1270.0 MBH3:1
Re-Heat Coil: Capacity: 84 MBH LA DB / WB: 70.00 ºF / 59.53 ºF RH: 54%
Rating Information
Listing Model: RN-016-3-H-BAAY-V0-21-000-A
Cooling Capacity (MBH): 184.0 Cooling EER: 11.8 Cooling IEER: 13.8 Rated in accordance with AHRI 340/360
Application EER @ Op. Conditions: 10.7
Electrical Data Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:
460V/3Ø/60Hz 4036 50
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 12.6 Compressor 2: 1 460 3 12.2 Condenser Fans: 2 0.75 460 3 1080 1.8 Supply Fan: 1 5.00 460 3 1170 8.1 Exhaust Fan: 1 2.00 460 3 1760 3.4 Combustion: 1 0.25 460 1 3210 0.9
Cabinet Sound Power Levels*
Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 83 83 87 83 79 80 76 72
Unit Rating
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:06:56 AM
Return LW(dB): 85 84 81 72 71 70 65 59 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.
Unit Rating
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:06:56 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: Width%: Date: Tip Speed:
Inertia:
Villa Joseph Marie 1,800RTU #1, 2 27.4 in. x 1
8102/07/2018 7,123 FPM
16 WR²
OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Plenum DP: Nominal RPM: Inlet Grill DP: VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:
5,000 CFM 5 / No2.11 in. Wg. 215T0.00 in. Wg. 11700.00 in. Wg. 460V/3Ø/60Hz2.11 in. Wg. Premium / 0.8950.00 Ft ODP2.11 in. Wg. 117 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 83 / 88 dB
Max Duct SP with Blocked Airway: 2.3 in. Wg. @ 993 rpm
9932.8358.7% 79 78 76 74 76 76 75 741305/1366 FPM 81 81 85 84 82 83 80 7683 FPM
RPMBHPSYSTEMEfficiencySP SurgeCFM Min
Supply Fan Model: 270 @ 993 RPM and 81% WidthDesign Conditions: 5000 CFM @ 2.11" SP
CFM x 100087654321
SP
2
1
0
BH
P
7
6
5
4
3
2
1
0
40%
20%
0%
RPM: 993
BHP: 2.83
EFFICIENCY: 58.67
27.0" STAR Plenum
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:06:56 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:
Inertia:
Villa Joseph Marie 2,200RTU #1, 2 22.0 in. x 1
500002/07/2018 6,894 FPM
5 WR²
OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:
VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:
5,000 CFM 2 / No0.50 in. Wg. 145T0.25 in. Wg. 1760
460V/3Ø/60Hz0.75 in. Wg. Premium / 0.8650.00 Ft ODP0.75 in. Wg. 27 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 85 / 85 dB
11971.3843.0% 85 85 85 80 74 72 67 611529/1684 FPM 85 85 85 80 74 72 67 6183 FPM
RPMBHPSYSTEMEfficiencySP SurgeCFM Min
Exhaust Fan Model: RM220A @ 1197 RPM and 100% WidthDesign Conditions: 5000 CFM @ 0.75" SP
CFM x 100054321
SP
2
1
0
BH
P
5
4
3
2
1
0
60%
40%
20%
0%
RPM: 1197
BHP: 1.38
EFFICIENCY: 43.03
22.0" STAR Plenum
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:06:56 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1 2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D
7
8
9A
9B
9C
9D
R N A - 0 1 6 - C - 0 - 3 - D A A 0 A - D B 1 K 0 : 0 1 - D Q 0 J - G 0 0 - 0 0 0 0 - C L B G - Q C - C B 0 0 - 0 0 - E 0 - 0 - A N 0 - E B - B K 0 B - 0 0 - 0 0 0 - A A 0 A 0 0 - E 0 0 0 0 0 - 0 0 0 0 0 0 X
10A
10B
11A
11B
12
13A
13B
13C
14
15
16A
16B
16C
16D
17A
17B
18A
18B
18C
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tag: RTU #1, 2 Job Name: Villa Joseph Marie Unit Submittal For: Job Number: Job #14238 Unit Submittal Date: February 07, 2018
Base Option Description
RN Generation RN Series
A Major Revision Major Revision A
016 Unit Size Sixteen
C Series C Series
0 Minor Revision Minor Revision 0
3 Voltage 460V/3Ø/60Hz
D Compressor Style R-410A Variable Capacity Scroll Compressor
A Condenser Style Microchannel Air-Cooled Condenser
A Indoor Coil Configuration Standard Evaporator
0 Cooling Heat Exchanger Construction Standard
A Cooling Staging 1 Variable Capacity Comp + 1 On/Off Comp
D Heat Type Natural Gas
B Heat Construction Stainless Steel Heat Exchanger
1 Heat Designation 270 MBH
K Heat Staging Modulating Gas Heat - Temperature Control
0 Heat Pump Auxiliary Heating No Heat Pump
Feature Option Description
0 1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles
1 2. Supply & Return Locations Horizontal Configuration - End Supply--End Return
D 3A. Supply Fan Configuration 1 Fan + Factory Installed VFD
Q 3B. Supply Fan Size 27" Direct Drive Backward Curved Plenum - 100% Width Aluminum
0 3C. Supply Fan Motor Type High Efficiency Motor (1,200 nominal rpm)
J 3D. Supply Fan Motor Size 5 hp
G 4A. Outside Air Section Economizer + Power Exhaust
0 4B. Energy Recovery Type No Energy Recovery
0 4C. Energy Recovery Size No Energy Recovery
0 5A. Return Fan Configuration Standard
0 5B. Return Fan Size Standard
0 5C. Return Fan Motor Type Standard
0 5D. Return Fan Motor Size Standard
C 6A. Exhaust Fan Configuration 1 Fan + Factory Installed VFD
L 6B. Exhaust Fan Size 22" Backward Curved Plenum Fan - 100% Width Aluminum
B 6C. Exhaust Fan Motor Type High Efficiency Motor (1,800 nominal rpm)
G 6D. Exhaust Fan Motor Size 2 hp
Q 7. Outside Air Control CO2 Override + Fully Mod. Act. - Enthalpy Limit
C 8.Return and Exhaust Air Options Standard Barometric Relief EA Dampers
C 9A. Unit Filter Type 2" Pleated MERV 8 + 4" Pleated MERV 13
B 9B. Unit Filter Size & Location High Efficiency Filters in Standard Position
0 9C. Final Filter Type No Final Filters
0 9D. Filter Options None
Unit Submittal
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:06:56 AM
Feature Option Description
0 10A. Refrigeration Control A None
0 10B. Blank Standard
E 11A. Refrigeration Options A Modulating Hot Gas Reheat
0 11B. Blank Standard
0 12. Refrigeration Accessories None
A 13A. Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch
N 13B. Disconnect 1 Size 100 Amps
0 13C. Blank Standard
E 14. Safety Options Remote Safety Shutdown Terminals
B 15. Electrical Accessories Phase & Brown Out Protection
B 16A. Control Sequence Single Zone VAV Unit Controller - VAV Cool + CAV Heat
K 16B. Control Supplier WattMaster VCC-X
0 16C. Control Supplier Options None
B 16D. BMS Connection & Diagnostics BACnet MSTP
0 17A. Preheat Configuration Standard - None
0 17B. Preheat Sizing Standard - None
0 18A. Option Box Location None
0 18B. Option Box Size None
0 18C. Option Box Accessories None
A 19. Outside Air Accessories Outside Air Hood
A 20. Cabinet Options Base Insulation
0 21. Blank Standard
A 22. Maintenance Accessories Factory Wired 115V Convenience Outlet
0 23. Code Options Standard - ETL U.S.A. Listing
0 24. Shipping Splits Standard
E 25.Air-Cooled Condenser Accessories VFD Condenser Fan Head Pressure Control
0 26. Blank Standard
0 27.Water-Cooled Condenser Accessories None
0 28. Energy Recovery Accessories None
0 29. VFD Options Standard
0 30. Miscellaneous Options Standard
0 31. Blank Standard
0 32. Blank Standard
0 33. Blank Standard
0 34. Blank Standard
0 35. Warranty Standard Warranty
0 36. Cabinet Material Galvanized Cabinet - Double Wall + R-13 Foam Insulation
X 37. Specials & Paint SPA + Premium AAON Gray Paint Exterior Paint
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1 2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D
7
8
9A
9B
9C
9D
R N A - 0 1 6 - C - 0 - 3 - D A A 0 A - D B 1 K 0 : 0 1 - D Q 0 J - G 0 0 - 0 0 0 0 - C L B G - Q C - C B 0 0 - 0 0 - E 0 - 0 - A N 0 - E B - B K 0 B - 0 0 - 0 0 0 - A A 0 A 0 0 - E 0 0 0 0 0 - 0 0 0 0 0 0 X
10A
10B
11A
11B
12
13A
13B
13C
14
15
16A
16B
16C
16D
17A
17B
18A
18B
18C
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tag: RTU #1, 2 Job Name: Villa Joseph Marie Unit Submittal For: Job Number: Job #14238 Unit Submittal Date: February 07, 2018
Unit Submittal
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:06:57 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1 2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D
7
8
9A
9B
9C
9D
R N A - 0 1 6 - C - 0 - 3 - D A A 0 A - D B 1 K 0 : 0 1 - D Q 0 J - G 0 0 - 0 0 0 0 - C L B G - Q C - C B 0 0 - 0 0 - E 0 - 0 - A N 0 - E B - B K 0 B - 0 0 - 0 0 0 - A A 0 A 0 0 - E 0 0 0 0 0 - 0 0 0 0 0 0 X
10A
10B
11A
11B
12
13A
13B
13C
14
15
16A
16B
16C
16D
17A
17B
18A
18B
18C
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tag: RTU #1, 2 Job Name: Villa Joseph Marie VCCX For: Job Number: Job #14238 VCCX Date: February 07, 2018
Hardware Included For VCCX Controller
Part # Included Parts Assigned Channel BACnet PointV87900 VCCX CONTROLLERV13050 OSA Temp/Hum Sensor EBUS2 communicating sensor AI:16,AI:17,AI:18,AI:19V09300 Space Digital Temp/Hum Sensor EBUS3 communicating sensor AI:12,AI:13R82890 Supply Temp Sensor - Field Installed VCCX control point AI 3 AI:9V09320 Duct Mount C02 EBUS4 communicating sensor AI:29R37030 Building Pressure Sensor VCCX control point AI 5 AI:23
Supply Fan Control Signal 0-10VDC VCCX control point AO 1 AI:22Economizer VCCX control point AO 2 AI:30Building Pressure Control Signal VCCX control point AO 4 AI:24
R62330 Proof of Air Flow VCCX control point BI 1 BI:6Safety Shut Down VCCX control point BI 8 BI:26Supply Fan Configured Relay point BI:63Exhaust Fan Configured Relay Point BI:64
V61520 DIGITAL REFRIGERATION MODULER57800 Comp Discharge Temp A RSMD point TEMP1 AI:56R57800 Comp Discharge Temp B RSMD point TEMP2 AI:57V38391 Suction Pressure Sensor B RSMD point AI3 AI:54V38391 Suction Pressure Sensor A RSMD point AI1 AI:48V38410 Discharge Pressure Sensor A RSMD point HP-1 AI:50V38410 Discharge Pressure Sensor B RSMD point HP-2 AI:55
Modulated Condenser Signal B RSMD point AO2 AI:44Modulated Condenser Signal A RSMD point AO1 BI:Comp Status Input A RSMD point BIN1Comp Status Input B RSMD point BIN2 BI:79Emergency Shutdown RSMD point BIN4 BI:81,82Condenser Enable AB RSMD Fixed Relay point BI:78,BI:85Comp Enable A RSMD Fixed Relay point AI:46Comp Enable B RSMD Fixed Relay point BI:77,BI:84Condenser Enable B RSMD Fixed Relay point BI:86
V12100 MODULATING HOT GAS REHEAT MODULEReheat HGR Valve MHGRV-X AI:42
V12090 MODULATING GAS MODULEModGas Gas Valve Signal MODGAS-XModGas High Speed Enable MODGAS-X AI:43ModGas Low Speed Enable MODGAS-X
VCCX Components
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:06:57 AM
CLEARANCES
LOCATION
OUTSIDE AIR
20*
(BACK)
SUPPLY AIR
(FRONT)
LEFT SIDE
RIGHT SIDE
TOP UNOBSTRUCTED
6
60
6
*CLEARANCE IS MEASURED FROM
THE END OF THE OUTSIDE AIR
RAIN HOOD
FRONT VIEW
RIGHT SIDE VIEW
BACK VIEW
TOP VIEW
DETAIL A DETAIL B
SPECIAL RN SERIESC- CABINET HORIZONTAL AIR COOLED
ECONOMIZER WITH POWER EXHAUST ANDBOTTOM RETURN
MATERIAL:
TOLERANCES
FRAC.:
DEC.
ANG.
UNLESSOTHERWISESPECIFIED
+/- 1/32 < 48 INCHES+/- 1/16 > 48 INCHES
+/- 0.03 < 48 INCHES+/- 0.06 > 48 INCHES
+/- 1°
_
_
DWG BY:
CKD BY:
APPD BY:
DATE REV
REV BY ECN NUMBER DATE
DRAWING NUMBER
AAON INC.2425 S. YUKON TULSA, OKLAHOMA
SHEET /SQUARE FT. :
11
A
N/A
01/16/18 AN/A DT002868-001
kce-ac
catalog corner weight villa joseph marie 16t rnc
138.162
C OF G
838 LBS. 862 LBS.
919 LBS.946 LBS.
TOTAL WEIGHT = 3565 LBS.
RIGHT SIDE VIEW
TOP VIEW
RN SERIESC- CABINET KNOCKDOWN CURB HORIZONTAL
AIR COOLED~ 16 - 30 TON
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1 2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D
7
8
9A
9B
9C
9D
R N A - 0 1 3 - C - 0 - 3 - D A A 0 A - D B 1 K 0 : 0 1 - D Q 0 J - G 0 0 - 0 0 0 0 - C L B G - Q C - C B 0 0 - 0 0 - E 0 - 0 - A N 0 - E B - B K 0 B - 0 0 - 0 0 0 - A A 0 A 0 0 - E 0 0 0 0 0 - 0 0 0 0 0 0 X
10A
10B
11A
11B
12
13A
13B
13C
14
15
16A
16B
16C
16D
17A
17B
18A
18B
18C
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tag: RTU #3
(Values do not account for changes described in SPA)
Job Information Unit Information **WEIGHT AND PERFORMANCE DO NOT INCLUDE SPA
Job Name: Approx. Op./Ship Weights: Job Number: Supply CFM/ESP: Site Altitude: Pre-Filter FV / Qty: Refrigerant Coil Filter FV / Qty:
Exhaust CFM/ESP/TSP: Outside CFM: Ambient Temperature: Return Temperature:
Villa Joseph Marie 3608 / 3608 lbs. (±5%)Job #14238 4000 / 1 in. wg.0 ft 192.00 fpm / 6R-410A 192.00 fpm / 6
4000 / 0.50 / 0.70 in. wg.110092 ºF DB / 74 ºF WB75 ºF DB / 62 ºF WB
Static Pressure External: Economizer: Evaporator: Heating: Coil Filters Clean: Cabinet: Dirt Allowance Re-Heat Coil: Total:
1.00 in. wg. 0.07 in wg0.24 in wg 0.14 in wg0.15 in wg 0.05 in. wg.0.35 in. wg. 0.04 in wg
2.04 in wg
Cooling Section Heating SectionGross Net
Total Capacity: Sensible Capacity: Latent Capacity: Mixed Air Temp: Entering Air Temp: Lv Air Temp (Coil): Lv Air Temp (Unit) Digital Comp. Capacity Ratio: Supply Air Fan: SA Fan RPM / Width: Exhaust Air Fan: EA Fan RPM / Width:
Evaporator Coil: Evaporator Face Velocity:
152.52 145.61 MBH113.98 107.07 MBH38.54 MBH79.68 ºF DB 65.62 ºF WB79.68 ºF DB 65.62 ºF WB52.77 ºF DB 52.26 ºF WB54.35 ºF DB 52.92 ºF WB100%1 x 270 @ 2.43 BHP977 / 4.352"1 x RM220A @ 0.85 BHP1006 / 4.920"
14.6 ft² / 4 Rows / 14 FPI274.3 fpm
PreHeat Type: Std (No Preheat)
Heating Type: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Input: Heater Qty: Consumption: Total Turndown Ratio:
Nat. Gas Heat4000218.7 MBH0.0 ºF DB / -1.0 ºF WB75.0 ºF DB / 62.0 ºF WB54.4 ºF DB / 49.9 ºF WB105.0 ºF DB / 68.5 ºF WB270.0 MBH1270.0 MBH3:1
Re-Heat Coil: Capacity: 74 MBH LA DB / WB: 70.00 ºF / 59.09 ºF RH: 53%
Rating Information
Listing Model: RN-013-3-H-BAAY-V0-21-000-A
Cooling Capacity (MBH): 144.0 Cooling EER: 12 Cooling IEER: 14.3 Rated in accordance with AHRI 340/360
Application EER @ Op. Conditions: 11.0
Electrical Data Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:
460V/3Ø/60Hz 3532 45
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 9.7 Compressor 2: 1 460 3 10.6 Condenser Fans: 2 0.75 460 3 1080 1.8 Supply Fan: 1 5.00 460 3 1170 8.1 Exhaust Fan: 1 2.00 460 3 1760 3.4 Combustion: 1 0.25 460 1 3210 0.9
Cabinet Sound Power Levels*
Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 82 82 84 81 77 79 75 71
Unit Rating
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:07:24 AM
Return LW(dB): 80 81 76 66 68 67 61 55 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.
Unit Rating
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:07:24 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: Width%: Date: Tip Speed:
Inertia:
Villa Joseph Marie 1,800RTU #3 27.4 in. x 1
7102/07/2018 7,008 FPM
16 WR²
OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Plenum DP: Nominal RPM: Inlet Grill DP: VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:
4,000 CFM 5 / No2.04 in. Wg. 215T0.00 in. Wg. 11700.00 in. Wg. 460V/3Ø/60Hz2.04 in. Wg. Premium / 0.8950.00 Ft ODP2.04 in. Wg. 117 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 82 / 87 dB
Max Duct SP with Blocked Airway: 2.2 in. Wg. @ 977 rpm
9772.4353.0% 79 76 75 74 74 74 73 721044/1093 FPM 81 81 83 82 80 82 79 7567 FPM
RPMBHPSYSTEMEfficiencySP SurgeCFM Min
Supply Fan Model: 270 @ 977 RPM and 71% WidthDesign Conditions: 4000 CFM @ 2.04" SP
CFM x 1000654321
SP
2
1
0
BH
P
5
4
3
2
1
0
40%
20%
0%
RPM: 977
BHP: 2.43
EFFICIENCY: 52.96
27.0" STAR Plenum
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:07:24 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:
Inertia:
Villa Joseph Marie 2,200RTU #3 22.0 in. x 1
400002/07/2018 5,794 FPM
5 WR²
OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:
VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:
4,000 CFM 2 / No0.50 in. Wg. 145T0.20 in. Wg. 1760
460V/3Ø/60Hz0.70 in. Wg. Premium / 0.8650.00 Ft ODP0.70 in. Wg. 27 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 80 / 80 dB
10060.8552.0% 80 82 80 74 70 68 62 551223/1347 FPM 80 82 80 74 70 68 62 5567 FPM
RPMBHPSYSTEMEfficiencySP SurgeCFM Min
Exhaust Fan Model: RM220A @ 1006 RPM and 100% WidthDesign Conditions: 4000 CFM @ 0.70" SP
CFM x 10004321
SP
1
0
BH
P
2
1
0
60%
40%
20%
0%
RPM: 1006
BHP: 0.85
EFFICIENCY: 52.02
22.0" STAR Plenum
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:07:24 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1 2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D
7
8
9A
9B
9C
9D
R N A - 0 1 3 - C - 0 - 3 - D A A 0 A - D B 1 K 0 : 0 1 - D Q 0 J - G 0 0 - 0 0 0 0 - C L B G - Q C - C B 0 0 - 0 0 - E 0 - 0 - A N 0 - E B - B K 0 B - 0 0 - 0 0 0 - A A 0 A 0 0 - E 0 0 0 0 0 - 0 0 0 0 0 0 X
10A
10B
11A
11B
12
13A
13B
13C
14
15
16A
16B
16C
16D
17A
17B
18A
18B
18C
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tag: RTU #3 Job Name: Villa Joseph Marie Unit Submittal For: Job Number: Job #14238 Unit Submittal Date: February 07, 2018
Base Option Description
RN Generation RN Series
A Major Revision Major Revision A
013 Unit Size Thirteen
C Series C Series
0 Minor Revision Minor Revision 0
3 Voltage 460V/3Ø/60Hz
D Compressor Style R-410A Variable Capacity Scroll Compressor
A Condenser Style Microchannel Air-Cooled Condenser
A Indoor Coil Configuration Standard Evaporator
0 Cooling Heat Exchanger Construction Standard
A Cooling Staging 1 Variable Capacity Comp + 1 On/Off Comp
D Heat Type Natural Gas
B Heat Construction Stainless Steel Heat Exchanger
1 Heat Designation 270 MBH
K Heat Staging Modulating Gas Heat - Temperature Control
0 Heat Pump Auxiliary Heating No Heat Pump
Feature Option Description
0 1. Unit Orientation Standard Access - Hinged Access Doors with Lockable Handles
1 2. Supply & Return Locations Horizontal Configuration - End Supply--End Return
D 3A. Supply Fan Configuration 1 Fan + Factory Installed VFD
Q 3B. Supply Fan Size 27" Direct Drive Backward Curved Plenum - 100% Width Aluminum
0 3C. Supply Fan Motor Type High Efficiency Motor (1,200 nominal rpm)
J 3D. Supply Fan Motor Size 5 hp
G 4A. Outside Air Section Economizer + Power Exhaust
0 4B. Energy Recovery Type No Energy Recovery
0 4C. Energy Recovery Size No Energy Recovery
0 5A. Return Fan Configuration Standard
0 5B. Return Fan Size Standard
0 5C. Return Fan Motor Type Standard
0 5D. Return Fan Motor Size Standard
C 6A. Exhaust Fan Configuration 1 Fan + Factory Installed VFD
L 6B. Exhaust Fan Size 22" Backward Curved Plenum Fan - 100% Width Aluminum
B 6C. Exhaust Fan Motor Type High Efficiency Motor (1,800 nominal rpm)
G 6D. Exhaust Fan Motor Size 2 hp
Q 7. Outside Air Control CO2 Override + Fully Mod. Act. - Enthalpy Limit
C 8.Return and Exhaust Air Options Standard Barometric Relief EA Dampers
C 9A. Unit Filter Type 2" Pleated MERV 8 + 4" Pleated MERV 13
B 9B. Unit Filter Size & Location High Efficiency Filters in Standard Position
0 9C. Final Filter Type No Final Filters
0 9D. Filter Options None
Unit Submittal
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:07:24 AM
Feature Option Description
0 10A. Refrigeration Control A None
0 10B. Blank Standard
E 11A. Refrigeration Options A Modulating Hot Gas Reheat
0 11B. Blank Standard
0 12. Refrigeration Accessories None
A 13A. Unit Disconnect Type Single Point Power - Non-fused Disconnect Power Switch
N 13B. Disconnect 1 Size 100 Amps
0 13C. Blank Standard
E 14. Safety Options Remote Safety Shutdown Terminals
B 15. Electrical Accessories Phase & Brown Out Protection
B 16A. Control Sequence Single Zone VAV Unit Controller - VAV Cool + CAV Heat
K 16B. Control Supplier WattMaster VCC-X
0 16C. Control Supplier Options None
B 16D. BMS Connection & Diagnostics BACnet MSTP
0 17A. Preheat Configuration Standard - None
0 17B. Preheat Sizing Standard - None
0 18A. Option Box Location None
0 18B. Option Box Size None
0 18C. Option Box Accessories None
A 19. Outside Air Accessories Outside Air Hood
A 20. Cabinet Options Base Insulation
0 21. Blank Standard
A 22. Maintenance Accessories Factory Wired 115V Convenience Outlet
0 23. Code Options Standard - ETL U.S.A. Listing
0 24. Shipping Splits Standard
E 25.Air-Cooled Condenser Accessories VFD Condenser Fan Head Pressure Control
0 26. Blank Standard
0 27.Water-Cooled Condenser Accessories None
0 28. Energy Recovery Accessories None
0 29. VFD Options Standard
0 30. Miscellaneous Options Standard
0 31. Blank Standard
0 32. Blank Standard
0 33. Blank Standard
0 34. Blank Standard
0 35. Warranty Standard Warranty
0 36. Cabinet Material Galvanized Cabinet - Double Wall + R-13 Foam Insulation
X 37. Specials & Paint SPA + Premium AAON Gray Paint Exterior Paint
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1 2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D
7
8
9A
9B
9C
9D
R N A - 0 1 3 - C - 0 - 3 - D A A 0 A - D B 1 K 0 : 0 1 - D Q 0 J - G 0 0 - 0 0 0 0 - C L B G - Q C - C B 0 0 - 0 0 - E 0 - 0 - A N 0 - E B - B K 0 B - 0 0 - 0 0 0 - A A 0 A 0 0 - E 0 0 0 0 0 - 0 0 0 0 0 0 X
10A
10B
11A
11B
12
13A
13B
13C
14
15
16A
16B
16C
16D
17A
17B
18A
18B
18C
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tag: RTU #3 Job Name: Villa Joseph Marie Unit Submittal For: Job Number: Job #14238 Unit Submittal Date: February 07, 2018
Unit Submittal
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:07:25 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1 2 3A
3B
3C
3D 4A
4B
4C 5A
5B
5C
5D 6A
6B
6C
6D
7
8
9A
9B
9C
9D
R N A - 0 1 3 - C - 0 - 3 - D A A 0 A - D B 1 K 0 : 0 1 - D Q 0 J - G 0 0 - 0 0 0 0 - C L B G - Q C - C B 0 0 - 0 0 - E 0 - 0 - A N 0 - E B - B K 0 B - 0 0 - 0 0 0 - A A 0 A 0 0 - E 0 0 0 0 0 - 0 0 0 0 0 0 X
10A
10B
11A
11B
12
13A
13B
13C
14
15
16A
16B
16C
16D
17A
17B
18A
18B
18C
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Tag: RTU #3 Job Name: Villa Joseph Marie VCCX For: Job Number: Job #14238 VCCX Date: February 07, 2018
Hardware Included For VCCX Controller
Part # Included Parts Assigned Channel BACnet PointV87900 VCCX CONTROLLERV13050 OSA Temp/Hum Sensor EBUS2 communicating sensor AI:16,AI:17,AI:18,AI:19V09300 Space Digital Temp/Hum Sensor EBUS3 communicating sensor AI:12,AI:13R82890 Supply Temp Sensor - Field Installed VCCX control point AI 3 AI:9V09320 Duct Mount C02 EBUS4 communicating sensor AI:29R37030 Building Pressure Sensor VCCX control point AI 5 AI:23
Supply Fan Control Signal 0-10VDC VCCX control point AO 1 AI:22Economizer VCCX control point AO 2 AI:30Building Pressure Control Signal VCCX control point AO 4 AI:24
R62330 Proof of Air Flow VCCX control point BI 1 BI:6Safety Shut Down VCCX control point BI 8 BI:26Supply Fan Configured Relay point BI:63Exhaust Fan Configured Relay Point BI:64
V61520 DIGITAL REFRIGERATION MODULER57800 Comp Discharge Temp A RSMD point TEMP1 AI:56R57800 Comp Discharge Temp B RSMD point TEMP2 AI:57V38391 Suction Pressure Sensor B RSMD point AI3 AI:54V38391 Suction Pressure Sensor A RSMD point AI1 AI:48V38410 Discharge Pressure Sensor A RSMD point HP-1 AI:50V38410 Discharge Pressure Sensor B RSMD point HP-2 AI:55
Modulated Condenser Signal B RSMD point AO2 AI:44Modulated Condenser Signal A RSMD point AO1 BI:Comp Status Input A RSMD point BIN1Comp Status Input B RSMD point BIN2 BI:79Emergency Shutdown RSMD point BIN4 BI:81,82Condenser Enable AB RSMD Fixed Relay point BI:78,BI:85Comp Enable A RSMD Fixed Relay point AI:46Comp Enable B RSMD Fixed Relay point BI:77,BI:84Condenser Enable B RSMD Fixed Relay point BI:86
V12100 MODULATING HOT GAS REHEAT MODULEReheat HGR Valve MHGRV-X AI:42
V12090 MODULATING GAS MODULEModGas Gas Valve Signal MODGAS-XModGas High Speed Enable MODGAS-X AI:43ModGas Low Speed Enable MODGAS-X
VCCX Components
Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456) Date Printed: 2/7/2018 11:07:25 AM
CLEARANCES
LOCATION
OUTSIDE AIR
20*
(BACK)
SUPPLY AIR
(FRONT)
LEFT SIDE
RIGHT SIDE
TOP UNOBSTRUCTED
6
60
6
*CLEARANCE IS MEASURED FROM
THE END OF THE OUTSIDE AIR
RAIN HOOD
FRONT VIEW
RIGHT SIDE VIEW
BACK VIEW
TOP VIEW
DETAIL A DETAIL B
SPECIAL RN SERIESC- CABINET HORIZONTAL AIR COOLED
ECONOMIZER WITH POWER EXHAUST ANDBOTTOM RETURN
MATERIAL:
TOLERANCES
FRAC.:
DEC.
ANG.
UNLESSOTHERWISESPECIFIED
+/- 1/32 < 48 INCHES+/- 1/16 > 48 INCHES
+/- 0.03 < 48 INCHES+/- 0.06 > 48 INCHES
+/- 1°
_
_
DWG BY:
CKD BY:
APPD BY:
DATE REV
REV BY ECN NUMBER DATE
DRAWING NUMBER
AAON INC.2425 S. YUKON TULSA, OKLAHOMA
SHEET /SQUARE FT. :
11
A
N/A
01/16/18 AN/A DT002869-001
kce-ac
catalog corner weight villa joseph marie 13t rnc
138.162
TOTAL WEIGHT = 3565 LBS.
C OF G
919 LBS.946 LBS.
838 LBS.862 LBS.
RIGHT SIDE VIEW
TOP VIEW
RN SERIESC- CABINET KNOCKDOWN CURB HORIZONTAL
AIR COOLED~ 16 - 30 TON
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RN-011-3-0-EB09-3F9:A000-Q0B-DCE-AG0-0DEAHB2-00-0JB0000VB Tag: RTU# 4
Job Information Unit Information
Job Name: Approx. Op./Ship Weights: Job Number: Supply CFM/ESP: Site Altitude: Pre-Filter FV / Qty: Refrigerant Final Filter FV / Qty:
Outside CFM: Ambient Temperature: Return Temperature:
Villa Joseph Marie 1853 / 1853 lbs. (±5%)Job #14238 3600 / 1.5 in. wg.0 ft 259.20 fpm / 4R-410A 259.20 fpm / 4
100092 ºF DB / 74 ºF WB75 ºF DB / 62 ºF WB
Static Pressure External: Economizer: Evaporator: Heating: Filters Clean: Cabinet: Dirt Allowance Re-Heat Coil: Total:
1.50 in. wg. 0.14 in. wg.0.23 in. wg. 0.03 in. wg.0.23 in. wg. 0.09 in. wg.0.35 in. wg. 0.03 in. wg.
2.60 in. wg.
Cooling Section Heating SectionGross Net
Total Capacity: Sensible Capacity: Latent Capacity: Mixed Air Temp: Entering Air Temp: Lv Air Temp (Coil): Lv Air Temp (Unit) Digital Comp. Capacity Ratio: Supply Air Fan: SA Fan RPM / Width:
Evaporator Coil: Evaporator Face Velocity:
130.86 124.13 MBH101.28 94.55 MBH29.58 MBH79.72 ºF DB 65.66 ºF WB79.72 ºF DB 65.66 ºF WB53.16 ºF DB 53.00 ºF WB54.87 ºF DB 53.71 ºF WB100%1 x RN185 @ 2.37 BHP1736 / 4.099"
14.6 ft² / 6 Rows / 12 FPI246.9 fpm
PreHeat Type: Std (No Preheat)
Heating Type: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Input: Heater Qty: Consumption: Total Turndown Ratio:
Nat. Gas Heat3600156.0 MBH0.0 ºF DB / -1.0 ºF WB75.0 ºF DB / 62.0 ºF WB54.2 ºF DB / 49.8 ºF WB94.3 ºF DB / 65.1 ºF WB195.0 MBH1195.0 MBH3:1
Re-Heat Coil: Capacity: 65 MBH LA DB / WB: 70.00 ºF / 59.60 ºF RH: 55%
Rating Information
Cooling Capacity (MBH): 128.0 Cooling EER: 12.7 Cooling IEER: 15.4 Rated in accordance with AHRI 340/360
Application EER @ Op. Conditions: 11.0
Electrical Data Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:
460/3/60 2826 35
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 8.1 Compressor 2: 1 460 3 7.8 Condenser Fans: 2 0.333 460 1 1110 2.8 Supply Fan: 1 3.00 460 3 1760 4.8 Combustion: 1 0.09 460 1 3010 0.7
Cabinet Sound Power Levels*
Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 87 84 89 84 76 73 71 65 Return LW(dB): 78 73 76 68 63 58 48 36 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.
Unit Rating
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:30:02 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:
Inertia:
Villa Joseph Marie 2,200RTU# 4 18.5 in. x 1
360002/07/2018 8,408 FPM
3 WR²
OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:
VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:
3,600 CFM 3 / No2.60 in. Wg. 182T0.00 in. Wg. 1760
460/3/602.60 in. Wg. Premium / 0.8950.00 Ft ODP2.60 in. Wg. 29 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 88 / 88 dB
Max Duct SP with Blocked Airway: 3.2 in. Wg. @ 1736 rpm
17362.3762.3% 87 84 89 86 79 77 75 692057/2156 FPM 87 84 89 86 79 77 75 6960 FPM
RPMBHPSYSTEMEfficiencySP SurgeCFM Min
Supply Fan Model: RN185 @ 1736 RPM and 99% WidthDesign Conditions: 3600 CFM @ 2.60" SP
CFM x 100054321
SP
3
2
1
0
BH
P
5
4
3
2
1
0
60%
40%
20%
RPM: 1736
BHP: 2.37
EFFICIENCY: 62.30
18.5" STAR Plenum
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:30:02 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RN-011-3-0-EB09-3F9:A000-Q0B-DCE-AG0-0DEAHB2-00-0JB0000VB Tag: RTU# 4
Job Name: Villa Joseph Marie Unit Submittal For: Job Number: Job #14238 Unit Submittal Date: February 07, 2018
Base Option Description
R Series Roof Top Unit
N Generation Ninth Generation
011 Unit Size Eleven
3 Voltage 460V/3Ø/60Hz
0 Interior Protection Standard
E Refrigerant Style R-410A VCC - High Efficiency
B Unit Configuration Air-Cooled Cond. + 6 Row Evap. Coil
0 Coil Coating Standard
9 Cooling/Heat Pump Staging Modulating - 1 VCC + 1 On/Off Comp.
3 Heating Type Natural Gas Stainless Steel
F Heating Designation Heat F - 195 MBtuh
9 Heating Staging Modulating Gas - Temperature Control
Feature Option Description
A 1A. RA/OA Section Economizer
0 1B. RA/EA Blower Configuration Standard - None
0 1C. RA/EA Blower Standard - None
0 1D. RA/EA Blower Motor Standard - None
Q 2. OA Control CO2 Override + Fully Modulating Actuator - Enthalpy Limit
0 3. Heat Options Standard
B 4. Maintenance Options 115V Convenience Outlet - Factory Wired
D 5A. SA Blower Configuration 1 Blower + Premium Efficiency Motor + 1 VFD
C 5B. SA Blower 18.5'' Direct Drive Backward Curved Plenum
E 5C. SA Motor 3.0 hp - 1760 rpm
A 6A. Pre Filter Type 2" Pleated Pre Filter - 30% Eff
G 6B. Unit Filter Type 4" Pleated - 85% Eff - MERV 13
0 6C. Filter Options Standard
0 7. Refrigeration Control Standard - Adj Comp. Cooling Lock Out Through Unit Controls
D 8. Refrigeration Options Modulating Hot Gas Reheat
E 9. Refrigeration Accessories ECM Condenser Fan - Head Pressure Control
A 10. Power Options Non-fused Disconnect Power Switch - 100 Amps
H 11. Safety Options Remote Safety Shutdown Terminals
B 12. Controls Phase & Brown Out Protection
2 13. Special Controls VAV Single Zone Unit Controller - VAV Cool + CAV Heat
0 14A. Preheat Configuration Standard - None
0 14B. Preheat Sizing Standard - None
0 15. Glycol Percent Water or No WSHP
J 16. Interior Cabinet Options Compressor Sound Blankets
B 17. Exterior Cabinet Options Burglar Bars
0 18. Customer Code Standard
0 19. Code Options Standard - ETL U.S.A. Listing
0 20. Crating Standard
0 21. Water-Cooled Cond. Standard - None
V 22. Control Vendors WattMaster VCC-X Controls + Integrated BACnet MSTP
B 23. Type Standard - Includes AAON Gray Paint
Unit Submittal
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:30:02 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RN-011-3-0-EB09-3F9:A000-Q0B-DCE-AG0-0DEAHB2-00-0JB0000VB Tag: RTU# 4 Job Name: Villa Joseph Marie VCCX For: Job Number: Job #14238 VCCX Date: February 07, 2018
Hardware Included For VCCX Controller
Part # Included Parts Assigned Channel BACnet PointV87900 VCCX CONTROLLERV13050 OSA Temp/Hum Sensor EBUS2 communicating sensor AI:16,AI:17,AI:18,AI:19V09300 Space Digital Temp/Hum Sensor EBUS3 communicating sensor AI:12,AI:13R82890 Supply Temp Sensor - Field Installed VCCX control point AI 3 AI:9V09320 Duct Mount C02 EBUS4 communicating sensor AI:29
Supply Fan Control Signal 0-10VDC VCCX control point AO 1 AI:22Economizer VCCX control point AO 2 AI:30
R62330 Proof of Air Flow VCCX control point BI 1 BI:6Safety Shut Down VCCX control point BI 8 BI:26Supply Fan Configured Relay point BI:63
V61520 DIGITAL REFRIGERATION MODULER57800 Comp Discharge Temp A RSMD point TEMP1 AI:56V38391 Suction Pressure Sensor A RSMD point AI1 AI:48V38410 Discharge Pressure Sensor A RSMD point HP-1 AI:50V38410 Discharge Pressure Sensor B RSMD point HP-2 AI:55R63950 Modulated Condenser Signal B RSMD point AO2 AI:44R63950 Modulated Condenser Signal A RSMD point AO1 BI:
Comp Status Input A RSMD point BIN1Comp Status Input B RSMD point BIN2 BI:79Emergency Shutdown RSMD point BIN4 BI:81,82Condenser Enable AB RSMD Fixed Relay point BI:78,BI:85Comp Enable A RSMD Fixed Relay point AI:46Comp Enable B RSMD Fixed Relay point BI:77,BI:84Condenser Enable B RSMD Fixed Relay point BI:86
V12100 MODULATING HOT GAS REHEAT MODULEReheat HGR Valve MHGRV-X AI:42
V12090 MODULATING GAS MODULEModGas Gas Valve Signal MODGAS-XModGas High Speed Enable MODGAS-X AI:43ModGas Low Speed Enable MODGAS-X
VCCX Components
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:30:02 AM
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:30:02 AM
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:30:02 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RQ-003-3-V-EA09-319:A000-D0B-QKC-AG0-0DEA002-00-0JA0000VB Tag: RTU# 5
Job Information Unit Information
Job Name: Approx. Op./Ship Weights: Job Number: Supply CFM/ESP: Site Altitude: Pre-Filter FV / Qty: Refrigerant Final Filter FV / Qty:
Outside CFM: Ambient Temperature: Return Temperature:
Villa Joseph Marie 866 / 866 lbs. (±5%)Job #14238 1000 / 1.05 in. wg.0 ft 180.00 fpm / 2R-410A 180.00 fpm / 2
25095 ºF DB / 75 ºF WB75 ºF DB / 62 ºF WB
Static Pressure External: Economizer: Evaporator: Heating: Filters Clean: Cabinet: Dirt Allowance Total:
1.05 in. wg. 0.08 in. wg.0.09 in. wg. 0.12 in. wg.0.14 in. wg. 0.02 in. wg.0.35 in. wg. 1.87 in. wg.
Cooling Section Heating SectionGross Net
Total Capacity: Sensible Capacity: Latent Capacity: Mixed Air Temp: Entering Air Temp: Lv Air Temp (Coil): Lv Air Temp (Unit) Digital Comp. Capacity Ratio: Supply Air Fan: SA Fan RPM / Width:
Evaporator Coil: Evaporator Face Velocity:
39.14 37.23 MBH29.05 27.14 MBH10.09 MBH80.00 ºF DB 65.61 ºF WB80.00 ºF DB 65.61 ºF WB52.55 ºF DB 51.88 ºF WB54.30 ºF DB 52.62 ºF WB100%1 x RQ185D60-VFD @ 0.59 BHP1506 / 1.750"
5.3 ft² / 3 Rows / 14 FPI190.5 fpm
PreHeat Type: Std (No Preheat)
Heating Type: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Input: Heater Qty (Hi/Low): Consumption: Operation: Total Turndown Ratio:
Nat. Gas Heat100048.6 MBH0.0 DB / -1.0ºF WB75.0 ºF DB / 62.0 ºF WB56.3 ºF DB / 51.1 ºF WB101.2 ºF DB / 67.6 ºF WB60.0 MBH160.0 MBHN/A3.3:1
Re-Heat Coil: Capacity: 19 MBH LA DB / WB: 70.00 ºF / 58.84 ºF RH: 52%
Rating Information
Cooling Capacity (MBH): 40.5 Cooling SEER: 15.7 Cooling EER: 13.55 Rated in accordance with AHRI 210/240
Application EER @ Op. Conditions: 10.9
Electrical Data Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:
460/3/60 1110 15
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 6.2 Condenser Fans: 1 0.333 230 1 1110 2.8 Supply Fan: 1 1.00 460 3 1760 2.1 Combustion: 1 0.09 460 1 3000 0.7
Cabinet Sound Power Levels*
Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 80 79 81 75 69 67 63 58 Return LW(dB): 77 76 72 64 62 58 49 42 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.
Unit Rating
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.261 (OSN# 0123456) Date Printed: 2/7/2018 10:30:31 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:
Inertia:
Villa Joseph Marie 2,200RTU# 5 18.5 in. x 1
100002/07/2018 7,294 FPM02/07/2018 7,294 FPM
OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:
VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:
1,000 CFM 1 / No1.87 in. Wg. 480.00 in. Wg. 1760
460/3/601.87 in. Wg. Standard / 0.7850.00 Ft ODP1.87 in. Wg. 15 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 82 / 82 dB
Max Duct SP with Blocked Airway: 2.5 in. Wg. @ 1506 rpm
15060.5950.0% 80 79 81 77 72 70 67 62/ FPM 80 79 81 77 72 70 67 6217 FPM
RPMBHPSYSTEMEfficiencySP SurgeCFM Min
Supply Fan Model: RQ185D60-VFD @ 1506 RPM and 100% WidthDesign Conditions: 1000 CFM @ 1.87" SP
CFM x 100010
SP
2
1
0
BH
P
2
1
0
40%
20%
0%
RPM: 1506
BHP: 0.59
EFFICIENCY: 49.98
18.5" STAR Plenum
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.261 (OSN# 0123456) Date Printed: 2/7/2018 10:30:31 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RQ-003-3-V-EA09-319:A000-D0B-QKC-AG0-0DEA002-00-0JA0000VB Tag: RTU# 5
Job Name: Villa Joseph Marie Unit Submittal For: Job Number: Job #14238 Unit Submittal Date: February 07, 2018
Base Option Description
R Series Roof Top Unit
Q Generation Tenth Generation
003 Unit Size Three
3 Voltage 460V/3Ø/60Hz
V Interior Protection Vertical Discharge and Return
E Refrigerant Style R-410A Variable Capacity Scroll Compressor (VCC) - High Efficiency
A Unit Configuration Air-Cooled Cond. + Std Evap. Coil
0 Coil Coating Standard
9 Cooling/Heat Pump Staging Modulating - 1 Variable Capacity Compressor
3 Heating Type Natural Gas Stainless Steel
1 Heating Designation Heat 1 - 60 MBtuh
9 Heating Staging Modulating Gas - Temperature Control
Feature Option Description
A 1A. RA/OA Section Economizer
0 1B. RA/EA Blower Configuration Standard - None
0 1C. RA/EA Blower Standard - None
0 1D. RA/EA Blower Motor Standard - None
D 2. OA Control Fully Modulating Actuator - Enthalpy Limit
0 3. Heat Options Standard
B 4. Maintenance Options 115V Convenience Outlet - Factory Wired
Q 5A. SA Blower Configuration 1 Blower + Inverter Rated 3 Phase Motor + VFD
K 5B. SA Blower 19" Direct Drive Backward Curved Plenum - 60% Width
C 5C. SA Motor 1 HP 1750 rpm
A 6A. Pre Filter Type 2" Pleated Pre Filter - 30% Eff
G 6B. Unit Filter Type 4" Pleated - 85% Eff - MERV 13
0 6C. Filter Options Standard
0 7. Refrigeration Control Standard - Adj Comp. Cooling Lock Out Through Unit Controls
D 8. Refrigeration Options Modulating Hot Gas Reheat
E 9. Refrigeration Accessories ECM Condenser Fan - Head Pressure Control
A 10. Power Options Non-fused Disconnect Power Switch - 100 Amps
0 11. Safety Options Standard
0 12. Controls Standard
2 13. Special Controls VAV Single Zone Unit Controller - VAV Cool + CAV Heat
0 14A. Preheat Configuration Standard - None
0 14B. Preheat Sizing Standard - None
0 15. Glycol Percent Water or No WSHP
J 16. Interior Cabinet Options Compressor Sound Blankets
A 17. Exterior Cabinet Options Base Insulation
0 18. Customer Code Standard
0 19. Code Options Standard - ETL U.S.A. Listing
0 20. Crating Standard
0 21. Water-Cooled Cond. Standard - None
V 22. Control Vendors VCCX w/ BACnet MSTP
B 23. Type Standard - Includes AAON Gray Paint
Unit Submittal
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.261 (OSN# 0123456) Date Printed: 2/7/2018 10:30:31 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RQ-003-3-V-EA09-319:A000-D0B-QKC-AG0-0DEA002-00-0JA0000VB Tag: RTU# 5 Job Name: Villa Joseph Marie VCCX For: Job Number: Job #14238 VCCX Date: February 07, 2018
Hardware Included For VCCX Controller
Part # Included Parts Assigned Channel BACnet PointV87900 VCCX CONTROLLERV13050 OSA Temp/Hum Sensor EBUS2 communicating sensor AI:16,AI:17,AI:18,AI:19V09300 Space Digital Temp/Hum Sensor EBUS3 communicating sensor AI:12,AI:13R82890 Supply Temp Sensor - Field Installed VCCX control point AI 3 AI:9
Supply Fan Control Signal 0-10VDC VCCX control point AO 1 AI:22Economizer VCCX control point AO 2 AI:30
R62330 Proof of Air Flow VCCX control point BI 1 BI:6Safety Shut Down VCCX control point BI 8 BI:26Supply Fan Configured Relay point BI:63
V61520 DIGITAL REFRIGERATION MODULER57800 Comp Discharge Temp A RSMD point TEMP1 AI:56V38391 Suction Pressure Sensor A RSMD point AI1 AI:48V38410 Discharge Pressure Sensor A RSMD point HP-1 AI:50R63950 Modulated Condenser Signal A RSMD point AO1 BI:
Comp Status Input A RSMD point BIN1Emergency Shutdown RSMD point BIN4 BI:81,82Condenser Enable AB RSMD Fixed Relay point BI:78,BI:85Comp Enable A RSMD Fixed Relay point AI:46
V12100 MODULATING HOT GAS REHEAT MODULEReheat HGR Valve MHGRV-X AI:42
VCCX Components
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.261 (OSN# 0123456) Date Printed: 2/7/2018 10:30:31 AM
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.261 (OSN# 0123456) Date Printed: 2/7/2018 10:30:31 AM
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.261 (OSN# 0123456) Date Printed: 2/7/2018 10:30:31 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RN-009-3-0-EB09-EHJ:A000-D0B-DCE-AG0-0D0AHBD-00-0JA0000VB Tag: RTU# 6
Job Information Unit Information
Job Name: Approx. Op./Ship Weights: Job Number: Supply CFM/ESP: Site Altitude: Pre-Filter FV / Qty: Refrigerant Final Filter FV / Qty:
Outside CFM: Ambient Temperature: Return Temperature:
Villa Joseph Marie 1773 / 1773 lbs. (±5%)Job #14238 3200 / 1.5 in. wg.0 ft 230.40 fpm / 4R-410A 230.40 fpm / 4
32092 ºF DB / 74 ºF WB75 ºF DB / 62 ºF WB
Static Pressure External: Economizer: Evaporator: Heating: Filters Clean: Cabinet: Dirt Allowance Re-Heat Coil: Total:
1.50 in. wg. 0.12 in. wg.0.18 in. wg. 0.09 in. wg.0.20 in. wg. 0.07 in. wg.0.35 in. wg. 0.02 in. wg.
2.53 in. wg.
Cooling Section Heating SectionGross Net
Total Capacity: Sensible Capacity: Latent Capacity: Mixed Air Temp: Entering Air Temp: Lv Air Temp (Coil): Lv Air Temp (Unit) Digital Comp. Capacity Ratio: Supply Air Fan: SA Fan RPM / Width:
Evaporator Coil: Evaporator Face Velocity:
103.17 97.39 MBH84.43 78.64 MBH18.74 MBH76.70 ºF DB 63.35 ºF WB76.70 ºF DB 63.35 ºF WB51.94 ºF DB 51.78 ºF WB53.59 ºF DB 52.48 ºF WB100%1 x RN185 @ 2.03 BHP1653 / 4.099"
14.6 ft² / 6 Rows / 12 FPI219.4 fpm
PreHeat Type: Std (No Preheat)
Heating Type: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Entering Water: Leaving Water: GPM / Head: Water Velocity: FA / RD / FPI / FV:
Hot Water Heat320073.8 MBH0.0 ºF DB / -1.0 ºF WB70.0 ºF DB / 58.0 ºF WB63.0 ºF DB / 54.0 ºF WB84.1 ºF DB / 61.8 ºF WB180.0 ºF154.7 ºF6 / 0.6 ft1.04 fps5.83 ft² / 1 / 8 / 548.6
Re-Heat Coil: Capacity: 62 MBH LA DB / WB: 69.84 ºF / 58.93 ºF RH: 52%
Rating Information
Cooling Capacity (MBH): 106.0 Cooling EER: 13.8 Cooling IEER: 16.8 Rated in accordance with AHRI 340/360
Application EER @ Op. Conditions: 11.2
Electrical Data Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:
460/3/60 2321 30
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 460 3 7.8 Compressor 2: 1 460 3 6.2 Condenser Fans: 2 0.33 460 1 1080 1.1 Supply Fan: 1 3.00 460 3 1760 4.8
Cabinet Sound Power Levels*
Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 85 83 87 82 74 72 69 63 Return LW(dB): 76 72 74 67 61 57 46 34 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.
Unit Rating
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:31:20 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:
Inertia:
Villa Joseph Marie 2,200RTU# 6 18.5 in. x 1
320002/07/2018 8,006 FPM
3 WR²
OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:
VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:
3,200 CFM 3 / No2.53 in. Wg. 182T0.00 in. Wg. 1760
460/3/602.53 in. Wg. Premium / 0.8950.00 Ft ODP2.53 in. Wg. 29 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 86 / 86 dB
Max Duct SP with Blocked Airway: 2.9 in. Wg. @ 1653 rpm
16532.0362.7% 85 83 87 84 77 76 73 671829/1916 FPM 85 83 87 84 77 76 73 6753 FPM
RPMBHPSYSTEMEfficiencySP SurgeCFM Min
Supply Fan Model: RN185 @ 1653 RPM and 99% WidthDesign Conditions: 3200 CFM @ 2.53" SP
CFM x 100054321
SP
2
1
0
BH
P
5
4
3
2
1
0
60%
40%
20%
RPM: 1653
BHP: 2.03
EFFICIENCY: 62.70
18.5" STAR Plenum
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:31:20 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RN-009-3-0-EB09-EHJ:A000-D0B-DCE-AG0-0D0AHBD-00-0JA0000VB Tag: RTU# 6 Job Name: Villa Joseph Marie Unit Submittal For: Job Number: Job #14238 Unit Submittal Date: February 07, 2018
Base Option Description
R Series Roof Top UnitN Generation Ninth Generation
009 Unit Size Nine3 Voltage 460V/3Ø/60Hz0 Interior Protection StandardE Refrigerant Style R-410A VCC - High EfficiencyB Unit Configuration Air-Cooled Cond. + 6 Row Evap. Coil0 Coil Coating Standard
9Cooling/Heat Pump Staging Modulating - 1 VCC + 1 On/Off Comp.
E Heating Type Hot Water Standard CoilH Heating Designation 1 Row CoilJ Heating Staging Half Serpentine 8 FPI
Feature Option Description
A 1A. RA/OA Section Economizer
0 1B.
RA/EA Blower Configuration Standard - None
0 1C. RA/EA Blower Standard - None0 1D. RA/EA Blower Motor Standard - NoneD 2. OA Control Fully Modulating Actuator - Enthalpy Limit0 3. Heat Options Standard
B 4.
Maintenance Options 115V Convenience Outlet - Factory Wired
D 5A.
SA Blower Configuration 1 Blower + Premium Efficiency Motor + 1 VFD
C 5B. SA Blower 18.5'' Direct Drive Backward Curved PlenumE 5C. SA Motor 3.0 hp - 1760 rpmA 6A. Pre Filter Type 2" Pleated Pre Filter - 30% EffG 6B. Unit Filter Type 4" Pleated - 85% Eff - MERV 130 6C. Filter Options Standard
0 7.
Refrigeration Control Standard - Adj Comp. Cooling Lock Out Through Unit Controls
D 8.
Refrigeration Options Modulating Hot Gas Reheat
A 9.
Refrigeration Accessories Non-fused Disconnect Power Switch - 100 Amps
H 10. Power Options Remote Safety Shutdown TerminalsB 11. Safety Options Phase & Brown Out ProtectionD 12. Controls VAV Unit Controller - VAV Cool + CV Heat0 13. Special Controls Standard - None
0 14A.
Preheat Configuration Standard - None
0 14B. Preheat Sizing Water or No WSHPJ 15. Glycol Percent Compressor Sound Blankets
A 16.
Interior Cabinet Options Base Insulation
0 17.
Exterior Cabinet Options Standard
Unit Submittal
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:31:20 AM
0 18. Customer Code Standard - ETL U.S.A. Listing0 19. Code Options Standard0 20. Crating Standard - NoneV 21. Water-Cooled Cond. WattMaster VCC-X Controls + Integrated BACnet MSTPB 22. Control Vendors Standard - Includes AAON Gray PaintB 22. Control Vendors Standard - Includes AAON Gray Paint
Unit Submittal
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:31:20 AM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
RN-009-3-0-EB09-EHJ:A000-D0B-DCE-AG0-0D0AHBD-00-0JA0000VB Tag: RTU# 6 Job Name: Villa Joseph Marie VCCX For: Job Number: Job #14238 VCCX Date: February 07, 2018
Hardware Included For VCCX Controller
Part # Included Parts Assigned Channel BACnet PointV87900 VCCX CONTROLLERV13050 OSA Temp/Hum Sensor EBUS2 communicating sensor AI:16,AI:17,AI:18,AI:19V09300 Space Digital Temp/Hum Sensor EBUS3 communicating sensor AI:12,AI:13R82890 Supply Temp Sensor - Field Installed VCCX control point AI 3 AI:9R82890 Return Temp Sensor VCCX control point AI 4 AI:14P87100 Duct Static Pressure Sensor VCCX control point AI 8 AI:21
Supply Fan Control Signal 0-10VDC VCCX control point AO 1 AI:22Economizer VCCX control point AO 2 AI:30Modulated Heating (0-10VDC) VCCX control point AO 3 AI:35
R62330 Proof of Air Flow VCCX control point BI 1 BI:6Safety Shut Down VCCX control point BI 8 BI:26Supply Fan Configured Relay point BI:63Morning Warm-Up Configured Relay Point BI:64
V61520 DIGITAL REFRIGERATION MODULER57800 Comp Discharge Temp A RSMD point TEMP1 AI:56V38391 Suction Pressure Sensor A RSMD point AI1 AI:48
Comp Status Input A RSMD point BIN1Comp Status Input B RSMD point BIN2 BI:79Emergency Shutdown RSMD point BIN4 BI:81,82Comp Enable A RSMD Fixed Relay point AI:46Comp Enable B RSMD Fixed Relay point BI:77,BI:84
V12100 MODULATING HOT GAS REHEAT MODULEReheat HGR Valve MHGRV-X AI:42
VCCX Components
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:31:20 AM
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:31:20 AM
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:31:20 AM
Date Created/Modified: 2/7/2018 10:29:54 AM Using Ver 4.264 (OSN# 0123456) Date Printed: 2/7/2018 10:31:20 AM
UNIT
SPECIFICATIONS
Specifications - RN Series Rooftop Units
Packaged Rooftop Units Tag: RTU-1, 2, 3, 4, 6
Part 1 - General
1.02 General Description
A. This section includes the design, controls and installation requirements for packaged rooftop units / outdoor air handling units.
1.03 Quality Assurance
A. Packaged air-cooled condenser units shall be certified in accordance with ANSI/AHRI Standard 340/360 performance rating of commercial and industrial unitary air-conditioning and heat pump equipment.
B. Unit shall be certified in accordance with UL Standard 1995/CSA C22.2 No. 236, Safety Standard for Heating and Cooling Equipment.
C. Unit and refrigeration system shall comply with ASHRAE 15, Safety Standard for Mechanical Refrigeration.
D. Unit shall be certified in accordance with ANSI Z21.47b/CSA 2.3b and ANSI Z83.8/CSA 2.6, Safety Standard Gas-Fired Furnaces.
E. Unit Energy Efficiency Ratio (EER) shall be equal to or greater that prescribed by ASHRAE 90.1, Energy Efficient Design of New Buildings except Low-Rise Residential Buildings.
F. Unit shall be safety certified by ETL and ETL US listed. Unit nameplate shall include the ETL/ETL Canada label.
G. Unit shall be approved for use in and outside High Velocity Hurricane Zones (HVHZ) by the Florida Building Code (FL# 15031), when using the required steel rooftop curb and attachment methods. Maximum allowable lateral wind pressure is +100psf/-100psf. Maximum allowable uplift is +50psf/-50psf. Positive and negative required design pressures calculated for use with this system shall be determined by others on a job specific basis, in accordance with the governing code. Site specific pressures shall be less than or equal to the listed positive or negative allowable lateral wind design pressure and allowable uplift values for the product.
1.04 Submittals
A. Product Data: Literature shall be provided that indicates dimensions, operating and shipping weights, capacities, ratings, fan performance, filter information, factory supplied accessories, electrical characteristics and connection requirements. Installation, Operation, and Maintenance manual with startup requirements shall be
provided.
B. Shop Drawings: Unit drawings shall be provided that indicate assembly, unit dimensions, construction details, clearances and connection details. Computer generated fan curves for each fan shall be submitted with specificdesign operation point noted. Wiring diagram shall be provided with details for both power and control systems and differentiate between factory installed and field installed wiring.
1.05 Delivery, Storage, and Handling
A. Unit shall be shipped with doors screwed shut and outside air hood closed to prevent damage during transport and thereafter while in storage awaiting installation.
B. Follow Installation, Operation, and Maintenance manual instructions for rigging, moving, and unloading the unit at its final location.
C. Unit shall be stored in a clean, dry place protected from construction traffic in accordance with the Installation, Operation, and Maintenance manual.
1.06 Warranty
A. Manufacturer shall provide a limited “parts only” warranty for a period of 12 months from the date of equipment startup or 18 months from the date of original equipment shipment from the factory, whichever is less. Warranty shall cover material and workmanship that prove defective, within the specified warranty period, provided manufacturer’s written instructions for Installation, Operation, and maintenance have been followed. Warranty excludes parts associated with routine maintenance, such as belts and filters.
Part 2 - Products
2.02 Rooftop Units
A. General Description
1. Packaged rooftop unit shall include compressors, evaporator coils, filters, supply fans, dampers, air-cooled condenser coils, condenser fans, reheat coil, gas heaters, hot water coils, exhaust fans, and unit controls.
2. Unit shall be factory assembled and tested including leak testing of the DX coils, leak testing of the hot water coils, pressure testing of the refrigeration circuit, and run testing of the completed unit. Run test report shall be supplied with the unit in the service compartment’s literature pocket.
3. Unit shall have decals and tags to indicate lifting and rigging, service areas and caution areas for safety and to assist service personnel.
4. Unit components shall be labeled, including pipe stub outs, refrigeration system components and electrical and controls components.
5. Estimated sound power levels (dB) shall be shown on the unit ratings sheet.
6. Installation, Operation, and Maintenance manual shall be supplied within the unit.
7. Laminated color-coded wiring diagram shall match factory installed wiring and shall be affixed to the interior of the control compartment’s hinged access door.
8. Unit nameplate shall be provided in two locations on the unit, affixed to the exterior of the unit and affixed to the interior of the control compartment’s hinged access door.
B. Construction
1. All cabinet walls, access doors, and roof shall be fabricated of double wall, impact resistant, rigid polyurethane foam panels.
2. Unit insulation shall have a minimum thermal resistance R-value of 13. Foam insulation shall have a minimum density of 2 pounds/cubic foot and shall be tested in accordance with ASTM D1929-11 for a minimum flash ignition temperature of 610°F.
3. Unit construction shall be double wall with G90 galvanized steel on both sides and a thermal break. Double wall construction with a thermal break prevents moisture accumulation on the insulation, provides a cleanable interior, prevents heat transfer through the panel, and prevents exterior condensation on the panel.
4. Unit shall be designed to reduce air leakage and infiltration through the cabinet. Cabinet leakage shall not exceed 1% of total airflow when tested at 3 times the minimum external static pressure provided in AHRI Standard 340/360. Panel deflection shall not exceed L/240 ratio at 125% of design static pressure, at a maximum 8 inches of positive or negative static pressure, to reduce air leakage. Deflection shall be measured at the midpoint of the panel height and width. Continuous sealing shall be included between panels and between access doors and openings to reduce air leakage. Piping and electrical conduit through cabinet panels shall include sealing to reduce air leakage.
5. Roof of the air tunnel shall be sloped to provide complete drainage. Cabinet shall have rain break overhangs above access doors.
6. Access to filters, dampers, cooling coils, reheat coil, heaters, exhaust fans, compressors, and electrical and controls components shall be through hinged access doors with quarter turn, zinc cast, lockable handles. Full length stainless steel piano hinges shall be included on the doors.
7. Exterior paint finish shall be capable of withstanding at least 2,500 hours, with no visible corrosive effects, when tested in a salt spray and fog atmosphere in accordance with ASTM B 117-95 test procedure.
8. Units with cooling coils shall include double sloped 304 stainless steel drain pans.
9. Unit shall be provided with base discharge and return air openings. All openings through the base pan of the unit shall have upturned flanges of at least 1/2 inch in
height around the opening. – RTU-4, 6 only
10. Unit shall be provided with horizontal discharge and vertical base return air openings. All openings through the base pan of the unit shall have upturned flanges of at least 1/2 inch in height around the opening. RTU-1, 2, 3 only
11. Unit shall include lifting lugs on the top of the unit.
12. Unit base pan shall be provided with 1/2 inch thick foam insulation.
C. Electrical
1. Unit shall be provided with factory installed and factory wired, non-fused disconnect switch.
2. Unit shall be provided with a factory installed and factory wired 115V, 12 amp GFI outlet disconnect switch in the unit control panel.
3. Unit shall be provided with phase and brown out protection which shuts down all motors in the unit if the electrical phases are more than 10% out of balance on voltage, the voltage is more than 10% under design voltage or on phase reversal.
D. Supply Fans
1. Unit shall include direct drive, unhoused, backward curved, plenum supply fans.
2. Blowers and motors shall be dynamically balance and mounted on rubber isolators.
3. Motors shall be premium efficiency ODP with ball bearings rated for 200,000 hours service with external lubrication points.
4. Variable frequency drives shall be factory wired and mounted in the unit. Fan motors shall be premium efficiency.
E. Exhaust Fans – RTU-1, 2, 3 only
1. Exhaust dampers shall be sized for 100% relief.
2. Fans and motors shall be dynamically balanced.
3. Motors shall be premium efficiency ODP with ball bearings rated for 200,000 hours service with external lubrication points.
4. Access to exhaust fans shall be through double wall, hinged access doors with quarter turn lockable handles.
5. Unit shall include belt driven, unhoused, backward curved, plenum exhaust fans.
6. Variable frequency drives shall be factory wired and mounted in the unit. Fan motors shall be premium efficiency.
F. Cooling Coils
1. Evaporator Coils
a. Coils shall be designed for use with R-410A refrigerant and constructed of copper tubes with aluminum fins mechanically bonded to the tubes and galvanized steel end casings. Fin design shall be sine wave rippled.
b. Coils shall have interlaced circuitry and shall be standard capacity.
c. Coils shall have interlaced circuitry and shall be 6 row high capacity.
d. Coils shall be hydrogen or helium leak tested.
e. Coils shall be furnished with factory installed expansion valves.
G. Refrigeration System
1. Unit shall be factory charged with R-410A refrigerant.
2. Compressors shall be scroll type with thermal overload protection and carry a 5 year non-prorated warranty, from the date of original equipment shipment from the factory.
3. Compressors shall be mounted in an isolated service compartment which can be accessed without affecting unit operation. Lockable hinged compressor access doors shall be fabricated of double wall, rigid polyurethane foam injected panels to prevent the transmission of noise outside the cabinet.
4. Compressors shall be isolated from the base pan with the compressor manufacturer’s recommended rubber vibration isolators, to reduce any transmission of noise from the compressors into the building area.
5. Each refrigeration circuit shall be equipped with expansion valve type refrigerant flow control.
6. Each refrigeration circuit shall be equipped with automatic reset low pressure and manual reset high pressure refrigerant safety controls, Schrader type service fittings on both the high pressure and low pressure sides and a factory installed replaceable core liquid line filter driers.
7. Unit shall include a variable capacity scroll compressor on the lead refrigeration circuit which shall be capable of modulation from 10-100% of its capacity.
8. Unit shall include factory provided and installed compressor sound jackets on all compressors.
9. Lead refrigeration circuit shall be provided with hot gas reheat coil, modulating valves, electronic controller, supply air temperature sensor and a control signal terminal which allow the unit to have a dehumidification mode of operation, which includes supply air temperature control to prevent supply air temperature swings
and overcooling of the space.
H. Condensers
1. Air-Cooled Condenser
a. Condenser fans shall be a vertical discharge, axial flow, direct drive fans.
b. Coils shall be designed for use with R-410A refrigerant. Coils shall be multi-pass and fabricated from aluminum microchannel tubes.
c. Coils shall be designed for a minimum of 10°F of refrigerant sub-cooling.
d. Coils shall be hydrogen or helium leak tested.
e. Condenser fans shall be high efficiency electrically commutated motor driven with factory installed head pressure control module. Condenser airflow shall continuously modulate based on head pressure and cooling operation shall be allowed down to 35°F with adjustable compressor lockout.
f. Condenser fans shall be VFD driven variable speed for condenser head pressure control. Factory provided and factory programmed VFDs shall continuously modulate the fan air flow to maintain head pressure at acceptable levels. Cooling operation shall be allowed down to 35°F with adjustable compressor lockout.
I. Gas Heating
1. Stainless steel heat exchanger furnace shall carry a 25 year non-prorated warranty, from the date of original equipment shipment from the factory.
2. Gas furnace shall consist of stainless steel heat exchangers with multiple concavities, an induced draft blower and an electronic pressure switch to lockout the gas valve until the combustion chamber is purged and combustion airflow is established.
3. Furnace shall include a gas ignition system consisting of an electronic igniter to a pilot system, which will be continuous when the heater is operating, but will shut off the pilot when heating is not required.
4. Unit shall include a single gas connection and have gas supply piping entrances in the unit base for through-the-curb gas piping and in the outside cabinet wall for across the roof gas piping.
5. Modulating Natural Gas Furnace shall be equipped with modulating gas valves, adjustable speed combustion blowers, stainless steel tubular heat exchangers, and electronic controller. Combustion blowers and gas valves shall be capable of modulation. Electronic controller includes a factory wired, field installed supply air temperature sensor. Sensor shall be field installed in the supply air ductwork. Supply air temperature setpoint shall be adjustable on the electronic controller within the controls. Gas heater shall be capable of capacity turndown ratio as
shown on the unit rating sheet.
J. Heating Coils – RTU-6 only
1. Hot Water Heating Coils
a. Coils shall be certified in accordance with AHRI Standard 410 and be hydrogen or helium leak tested.
b. Coils shall be constructed of copper tubes with aluminum fins mechanically bonded to the tubes and galvanized steel end casings. Fin design shall be sine wave rippled.
c. Coils shall be one row, half serpentine circuitry, and 8 fins per inch.
d. Coils shall be located in the reheat position downstream of the cooling coil.
e. Control valves shall be field supplied and field installed.
K. Filters
1. Unit shall include 4 inch thick, pleated panel filters with an ASHRAE MERV rating of 13, upstream of the cooling coil. Unit shall also include 2 inch thick, pleated panel pre filters with an ASHRAE MERV rating of 8, upstream of the 4 inch standard filters.
L. Outside Air/Economizer
1. Unit shall include 0-100% economizer consisting of a motor operated outside air damper and return air damper assembly constructed of extruded aluminum, hollow core, airfoil blades with rubber edge seals and aluminum end seals. Damper blades shall be gear driven and designed to have no more than 20 cfm of leakage per sq ft. at 4 in. w.g. air pressure differential across the damper. Low leakage dampers shall be Class 2 AMCA certified, in accordance with AMCA Standard 511. Damper assembly shall be controlled by spring return enthalpy activated fully modulating actuator. Unit shall include outside air opening bird screen, outside air hood, and barometric relief dampers.
2. Economizer shall be furnished with return air CO2 override. – RTU-1, 2, 3, 4
M. Controls
1. Factory Installed and Factory Provided Controller
a. Unit controller shall be capable of controlling all features and options of the unit. Controller shall be factory installed in the unit controls compartment and factory tested. Controller shall be capable of stand alone operation with unit configuration, setpoint adjustment, sensor status viewing, unit alarm viewing, and occupancy scheduling available without dependence on a building management system.
b. Controller shall have an onboard clock and calendar functions that allow for occupancy scheduling.
c. Controller shall include non-volatile memory to retain all programmed values without the use of a battery, in the event of a power failure.
d. Variable Air Volume Controller – RTU-6 only
1. Unit shall utilize a variable capacity compressor system and a variable speed supply fan system to modulate cooling and airflow as required to meet space temperature cooling loads and to save operating energy. Supply fan speed shall modulate based on supply air duct static pressure. Cooling capacity shall modulate based on supply air temperature.
2. With modulating hot gas reheat, unit shall modulate cooling and hot gas reheat as efficiently as possible, to meet space humidity loads and prevent supply air temperature swings and overcooling of the space.
3. Unit shall modulate heating with constant airflow to meet space temperature heating loads. Modulating heating capacity shall modulate based on supply air temperature.
e. Single Zone VAV Controller – RTU-1, 2, 3, 4
1. Unit shall utilize a variable capacity compressor system and a variable speed fan system to modulate the cooling and airflow as required in meeting the space temperature needs and to save unit operating energy. Unit fan speed shall modulate based on space temperature, not supply air pressure.
2. Units ordered with modulating gas, shall be capable of modulating fan speed in both the heating and cooling mode.
3. With modulating hot gas reheat, unit shall modulate cooling and hot gas reheat as efficiently as possible, to meet space humidity loads and prevent supply air temperature swings and overcooling of the space.
4. Unit shall be provided with supply air temperature control. Mixing boxes and bypass ducts shall not be required for operation as a single zone VAV system.
f. Unit configuration, setpoint adjustment, sensor status viewing, unit alarm viewing, and occupancy scheduling shall be accomplished with connection to interface module with LCD screen and input keypad, interface module with touch screen, or with connection to PC with free configuration software. Controller shall be capable of connection with other factory installed and factory provided unit controllers with individual unit configuration, setpoint adjustment, sensor status viewing, and occupancy scheduling available from a single unit. Connection between unit controllers shall be with a modular cable. Controller
shall be capable of communicating and integrating with a LonWorks or BACnet network.
N. Accessories
1. Unit shall be provided with a safety shutdown terminal block for field installation of a smoke detector which shuts off the unit's control circuit.
2.03 Curbs
A. Curbs shall to be fully gasketed between the curb top and unit bottom with the curb providing full perimeter support, cross structure support and air seal for the unit. Curb gasket shall be furnished within the control compartment of the rooftop unit to be mounted on the curb immediately before mounting of the rooftop unit.
B. Roof curb shall be 14” high with duct support rails shall be factory furnished in one piece with 1” spring isolation rails installed on the curb. Curb shall ship in one piece.
Specifications - RQ Series Rooftop Unit
Packaged Rooftop Unit Tag: RTU-5 Part 1 - General
1.02 General Description
A. This section includes the design, controls and installation requirements for packaged rooftop units/heat pumps/outdoor air handling units.
1.03 Quality Assurance A. Packaged air-cooled condenser units shall be certified in accordance with
ANSI/AHRI Standard 340/360 performance rating of commercial and industrial unitary air-conditioning and heat pump equipment.
B. Unit shall be certified in accordance with UL Standard 1995/CSA C22.2 No. 236, Safety Standard for Heating and Cooling Equipment.
C. Unit and refrigeration system shall comply with ASHRAE 15, Safety Standard for Mechanical Refrigeration.
D. Unit shall be certified in accordance with ANSI Z21.47b/CSA 2.3b and ANSI Z83.8/CSA 2.6, Safety Standard Gas-Fired Furnaces.
E. Unit Seasonal Energy Efficiency Ratio (SEER) shall be equal to or greater that prescribed by ASHRAE 90.1, Energy Efficient Design of New Buildings except Low-Rise Residential Buildings.
F. Unit shall be safety certified by ETL and ETL US listed. Unit nameplate shall include the ETL/ETL Canada label.
G. Unit shall be approved for use in and outside High Velocity Hurricane Zones (HVHZ) by the Florida Building Code (FL# 15031), when using the required steel rooftop curb and attachment methods. Maximum allowable lateral wind pressure is +100psf/-100psf. Maximum allowable uplift is +50psf/-50psf. Positive and negative required design pressures calculated for use with this system shall be determined by others on a job specific basis, in accordance with the governing code. Site specific pressures shall be less than or equal to the listed positive or negative allowable lateral wind design pressure and allowable uplift values for the product.
1.04 Submittals A. Product Data: Literature shall be provided that indicates dimensions, operating and
shipping weights, capacities, ratings, fan performance, filter information, factory supplied accessories, electrical characteristics and connection requirements. Installation, Operation and Maintenance manual with startup requirements shall be provided.
B. Shop Drawings: Unit drawings shall be provided that indicate assembly, unit
dimensions, construction details, clearances and connection details. Computer generated fan curves for each fan shall be submitted with specific design operation point noted. Wiring diagram shall be provided with details for both power and control systems and differentiate between factory installed and field installed wiring.
1.05 Delivery, Storage, and Handling A. Unit shall be shipped with doors bolted shut and outside air hood closed to prevent
damage during transport and thereafter while in storage awaiting installation.
B. Follow Installation, Operation and Maintenance manual instructions for rigging, moving, and unloading the unit at its final location.
C. Unit shall be stored in a clean, dry place protected from construction traffic in accordance with the Installation, Operation and Maintenance manual.
1.06 Warranty A. Manufacturer shall provide a limited “parts only” warranty for a period of 24 months
from the date of original equipment shipment from the factory. Warranty shall cover material and workmanship that prove defective, within the specified warranty period, provided manufacturer’s written instructions for installation, operation and maintenance have been followed. Warranty excludes parts associated with routine maintenance, such as belts and air filters.
1.07 Startup Repair Program A. Manufacturer shall provide startup repair for a period of 12 months from the date of
original equipment shipment from the factory. Program shall cover labor for materials and workmanship that prove defective, within the specified warranty period, provided manufacturer’s written instructions for installation, operation and maintenance have been followed. Program excludes labor associated with routine maintenance, such as belt and air filter replacement.
Part 2 – Products
2.02 Rooftop Units A. General Description
1. Packaged rooftop unit shall include compressor, evaporator coil, filters, supply fan, dampers, air-cooled condenser coils, condenser fan, reheat coil, gas heater, and unit controls.
2. Unit shall be factory assembled and tested including leak testing of the DX coils, pressure testing of the refrigeration circuit, and run testing of the completed unit. Run test report shall be supplied with the unit in the service compartment’s literature pocket.
3. Unit shall have decals and tags to indicate lifting and rigging, service areas and caution areas for safety and to assist service personnel.
4. Unit components shall be labeled, including refrigeration system components and
electrical and controls components.
5. Estimated sound power levels (dB) shall be shown on the unit ratings sheet.
6. Installation, Operation and Maintenance manual shall be supplied within the unit.
7. Laminated color-coded wiring diagram shall match factory installed wiring and shall be affixed to the interior of the control compartment’s hinged access door.
8. Unit nameplate shall be provided in two locations on the unit, affixed to the exterior of the unit and affixed to the interior of the control compartment’s hinged access door.
B. Construction
1. All cabinet walls, access doors, and roof shall be fabricated of double wall, impact resistant, rigid polyurethane foam panels.
2. Unit insulation shall have a minimum thermal resistance R-value of 13. Foam insulation shall have a minimum density of 2 pounds/cubic foot and shall be tested in accordance with ASTM D-1929 for a minimum flash ignition temperature of 610°F.
3. Unit construction shall be double wall with G90 galvanized steel on both sides and a thermal break. Double wall construction with a thermal break prevents moisture accumulation on the insulation, provides a cleanable interior, prevents heat transfer through the panel, and prevents exterior condensation on the panel.
4. [RTU# 5] Unit shall be designed to reduce air leakage and infiltration through the cabinet. Cabinet leakage shall not exceed 1% of total airflow when tested at 3 times the minimum external static pressure provided in AHRI Standard 210/240.Panel deflection shall not exceed L/240 ratio at 125% of design static pressure, at a maximum 8 inches of positive or negative static pressure, to reduce air leakage. Deflection shall be measured at the midpoint of the panel height and width. Continuous sealing shall be included between panels and between access doors and openings to reduce air leakage. Piping and electrical conduit through cabinet panels shall include sealing to reduce air leakage.
5. Roof of the air tunnel shall be sloped to provide complete drainage. Cabinet shall have rain break overhangs above access doors.
6. Access to filters, dampers, cooling coil, reheat coil, heater, compressor, and electrical and controls components shall be through hinged access doors with quarter turn, lockable handles. Full length stainless steel piano hinges shall be included on the doors.
7. Exterior paint finish shall be capable of withstanding at least 2,500 hours, with no visible corrosive effects, when tested in a salt spray and fog atmosphere in accordance with ASTM B 117-95 test procedure.
8. Units shall include double sloped 304 stainless steel drain pans.
9. Unit shall be provided with through the base vertical discharge and return air openings. All openings through the unit shall have upturned flanges of at least 1/2 inch around the opening.
10. Unit shall include lifting lugs on the top of the unit.
11. Unit base pan shall be provided with 1/2 inch thick foam insulation.
C. Electrical
1. Unit shall be provided with factory installed and factory wired, non-fused disconnect switch.
2. Unit shall be provided with a factory installed and factory wired 115V, 12 amp GFI outlet disconnect switch in the unit control panel.
D. Supply Fans
1. Unit shall include direct drive, unhoused, backward curved, plenum supply fans.
2. Blowers and motors shall be dynamically balanced.
3. Motor shall be inverter rated efficiency ODP with ball bearings rated for 200,000 hours service with external lubrication points.
4. Variable frequency drive shall be factory wired and mounted in the unit. Fan motor shall be inverter rated efficiency.
E. Cooling Coils
1. Evaporator Coils
a. Coils shall be designed for use with R-410A refrigerant and constructed of copper tubes with aluminum fins mechanically bonded to the tubes and aluminum end casings. Fin design shall be sine wave rippled.
b. Coil shall be standard capacity
c. Coils shall be helium hydrogen or helium leak tested.
d. Coils shall be furnished with factory installed electronic expansion valves.
F. Refrigeration System
1. Unit shall be factory charged with R-410A refrigerant.
2. Compressors shall be scroll type with thermal overload protection and carry a 5 year non-prorated warranty, from the date of original equipment shipment from the factory.
3. Compressors shall be mounted in an isolated service compartment which can be accessed without affecting unit operation. Lockable hinged compressor access doors shall be fabricated of double wall, rigid polyurethane foam injected panels to prevent the transmission of noise outside the cabinet.
4. Compressors shall be isolated from the base pan with the compressor manufacturer’s recommended rubber vibration isolators, to reduce any transmission of noise from the compressors into the building area.
5. Each refrigeration circuit shall be equipped with thermostatic expansion valve type refrigerant flow control.
6. Each refrigeration circuit shall be equipped with automatic reset low pressure and manual reset high pressure refrigerant safety controls, Schrader type service fittings on both the high pressure and low pressure sides and a factory installed replaceable core liquid line filter driers.
7. Unit shall include a variable capacity scroll compressor on the refrigeration circuit which shall be capable of modulation from 10-100% of its capacity.
8. Unit shall include factory provided and installed compressor sound jackets on all compressors.
9. Refrigeration circuit shall be provided with hot gas reheat coil, modulating valves, electronic controller, supply air temperature sensor and a control signal terminal which allow the unit to have a dehumidification mode of operation, which includes supply air temperature control to prevent supply air temperature swings and overcooling of the space.
G. Condensers
1. Air-Cooled Condenser
a. Condenser fans shall be a vertical discharge, axial flow, direct drive fans.
b. Coils shall be designed for use with R-410A refrigerant.
c. Condenser coils shall be multi-pass and fabricated from aluminum microchannel tubes.
d. Coils shall be designed for a minimum of 10°F of refrigerant sub-cooling.
e. Coils shall be hydrogen or helium leak tested.
f. Condenser fans shall be high efficiency electrically commutated motor driven with factory installed head pressure control module. Condenser airflow shall continuously modulate based on head pressure and cooling operation shall be allowed down to 35°F with adjustable compressor lockout.
H. Gas Heating
1. Stainless steel heat exchanger furnace shall carry a 25 year non-prorated warranty, from the date of original equipment shipment from the factory.
2. Gas furnace shall consist of stainless steel heat exchangers with multiple concavities, an induced draft blower and an electronic pressure switch to lockout the gas valve until the combustion chamber is purged and combustion airflow is established.
3. Furnace shall include a gas ignition system consisting of an electronic igniter to a pilot system, which will be continuous when the heater is operating, but will shut off the pilot when heating is not required.
4. Unit shall include a single gas connection and have gas supply piping entrances in the unit base for through-the-curb gas piping and in the outside cabinet wall for across the roof gas piping.
5. Modulating Natural Gas Furnace shall be equipped with modulating gas valves, adjustable speed combustion blowers, stainless steel tubular heat exchangers, and electronic controller. Combustion blowers and gas valves shall be capable of modulation. Electronic controller includes a factory wired, field installed supply air temperature sensor. Sensor shall be field installed in the supply air ductwork. Supply air temperature setpoint shall be adjustable on the electronic controller within the controls. Gas heater shall be capable of capacity turndown ratio as shown on the unit rating sheet.
I. Filters
1. Unit shall include 4 inch thick, pleated panel filters with an ASHRAE MERV rating of 13, upstream of the cooling coil. Unit shall also include 2 inch thick, pleated panel pre filters with an ASHRAE MERV rating of 8, upstream of the 4 inch standard filters.
J. Outside Air/Economizer
1. Unit shall include 0-100% economizer consisting of a motor operated outside air damper and return air damper assembly constructed of extruded aluminum, hollow core, airfoil blades with rubber edge seals and aluminum end seals. Damper blades shall be gear driven and designed to have no more than 15 CFM of leakage per sq. ft. of damper area when subjected to 2 inches w.g. air pressure differential across the damper. Unit shall include outside air opening bird screen, outside air hood with rain lip and barometric relief dampers.
2. Damper assembly shall be controlled by spring return enthalpy activated fully modulating actuator.
K. Controls
1. Factory Installed and Factory Provided Controller
a. Unit controller shall be capable of controlling all features and options of the
unit. Controller shall be factory installed in the unit controls compartment and factory tested.
b. Controller shall be capable of stand alone operation with unit configuration, setpoint adjustment, sensor status viewing, unit alarm viewing, and occupancy scheduling available without dependence on a building management system.
c. Controller shall have an onboard clock and calendar functions that allow for occupancy scheduling.
d. Controller shall include non-volatile memory to retain all programmed values without the use of a battery, in the event of a power failure.
e. Single Zone VAV Controller
1. Unit shall utilize a variable capacity compressor system and a variable speed fan system to modulate the cooling and airflow as required in meeting the space temperature needs and to save unit operating energy. Unit fan speed shall modulate based on space temperature, not supply air pressure.
2. Units ordered with modulating gas, shall be capable of modulating fan speed in both the heating and cooling mode.
3. With modulating hot gas reheat, unit shall modulate cooling and hot gas reheat as efficiently as possible, to meet space humidity loads and prevent supply air temperature swings and overcooling of the space.
4. Unit shall be provided with supply air temperature control. Mixing boxes and bypass ducts shall not be required for operation as a single zone VAV system.
f. Unit configuration, setpoint adjustment, sensor status viewing, unit alarm viewing, and occupancy scheduling shall be accomplished with connection to interface module with LCD screen and input keypad, interface module with touch screen, or with connection to PC with free configuration software. Controller shall be capable of connection with other factory installed and factory provided unit controllers with individual unit configuration, setpoint adjustment, sensor status viewing, and occupancy scheduling available from a single unit. Connection between unit controllers shall be with a modular cable. Controller shall be capable of communicating and integrating with a LonWorks or BACnet network.
2.03 Curbs A. Curbs shall to be fully gasketed between the curb top and unit bottom with the curb
providing full perimeter support, cross structure support and air seal for the unit. Curb gasket shall be furnished within the control compartment of the rooftop unit to be mounted on the curb immediately before mounting of the rooftop unit.
B. Roof curb shall be 14” high with duct support rails shall be factory furnished. Curb shall ship in one piece with 1” spring vibration rails installed.
UNIT
CONTROLS
Form: AAON-OE338-26B-VCCX2 -1A.doc Page 1 of 1
Description The VCCX2 Controller (Orion Part No. OE338-26B-VCCX2; AAON Part No. V87900) is designed with 8 analog inputs, 4 analog outputs, 8 binary inputs, and 8 relay outputs.
The VCCX2 Controller has an on-board BACnet® port for connection to a BACnet® MS/TP network. There are also 2 E-BUS Expansion Ports which allow the connection of communi-cating sensors and future E-BUS Modules via modular cable assemblies. The VCCX2 Controller contains a 2 x 8 LCD character display and 4 buttons that allow for status and alarm display as well as BACnet® configuration.
The VCCX2 Controller provides for Constant Volume, VAV, Make-Up Air, and Single Zone VAV applications. Single Zone VAV applications can be configured for VAV Cooling and either CAV or VAV Heating.
Mounting The VCCX2 Controller is housed in a plastic enclosure. It is designed to be mounted by using the 3 mounting holes in the enclosure base. The VCCX2 Controller needs to be installed in an environment which can maintain a temperature range between -30°F and 150°F not to exceed 90% RH levels (Non-Condensing). It is important to mount the controller in a location that is free from extreme high or low temperatures, moisture, dust, and dirt. Be careful not to damage the electronic components when mounting the controller.
Technical Data OE338-26B-VCCX2 VCCX2 Controller
Operating Power 24 VAC Power Consumption 15 VA MaximumOperating Temp -30F to 150F Operating Humidity 90% RH Non-Condensing
Communications WattMaster Communications E-BUS
BACnet MS/TP
Weight 1 lb.
Inputs 8 Analog Inputs8 Binary Inputs
Outputs 4 Analog Outputs8 Relay Outputs
Three Year Warranty WattMaster reserves the right to change specifications without notice
M
ENTER
UP
DOWN
ALARM
MENU
RELAY CONTACTRATING IS 1 AMPMAX @ 24 VAC
RS-485 COMMLOOP. WIRE“R” TO “R”,“T” TO “T”“SHLD” TO “SHLD”
24 VAC POWER
ONLY
WARNING!
POLARITY
MUST BE
OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
www.aaon.com www.orioncontrols.com
VCCX2 CONTROLLER
Orion No.: OE338-26B-VCCX2AAON No.: V87900
BINARY INPUTS
BI1 = PROOF OF AIRFLOWBI2
BI3
BI5
BI6
AI1
AI2
AI3
AI4
AI5
A 6
= DIRTY FILTER= HOOD ON/OFF= REMOTE OCCUPIED= REMOTE COOLING= REMOTE HEATING= REMOTE DEHUMIDIFICATION= EMERGENCY SHUTDOWN
= SPACE TEMPERATURE= SPACE SLIDE OFFSET= SUPPLY AIR TEMPERATURE= RETURN AIR TEMPERATURE= BUILDING PRESSURE= SUPPLY AIR TEMP RESET= OUTDOOR AIR TEMPERATURE= NOT CONNECTED USE DUCT
STATIC CONNECTOR
BI4
BI7
BI8
I
AI7
AI8
ANALOG INPUTS
WattMasterOverlay
#S 000079Rev.: 1AW
DUALE-BUS
+2
4V
AC
GN
D
MAIN FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
RELAY 7
RELAY 8
RELAYCOMMON
MAIN SUPPLY FAN VFD =ECONOMIZER ACTUATOR =
MODULATING HEATING =EXHAUST FAN VFD =
AO1
AO2
AO3
AO4
BACNET –
BACNET SHIELD
BACNET +
= T
= SH
= R
DUCTSTATIC
7.958.388.38
0.2130. 2.752.75
6.046
4.104.10
0.700.701.50
8.38
OE338-26B-VCCX2 VCCX2 Controller
Form: AAON-OE370-26-RSMD-1F.doc Page 1 of 1
Description The OE370-26-RSMD Refrigerant System Module for Digital Compressors (RSMD) can monitor and control up to two com-pressors and condensers. The compres-sors can be in either a tandem or non-tandem configuration. The module is de-signed for R410-A refrigerant. The RSMD Module is connected to the VCC-X Controller (Orion Part No. OE338-26B-VCCX; AAON Part No. V42430) or VCCX2 Controller (Orion Part No. OE338-26B-VCCX2; AAON Part No. V87900). Up to 2 RSMD Modules can be connect-ed, depending on the size of the system.
Features The RSMD Module provides the following features:
• Modulates the Compressors to satisfy the Suction Coil (Saturated) Temperature. The Suction Coil (Saturated) Tem-perature Setpoint is reset by the VCC-X/VCCX2 Controller to maintain the Supply Air Temperature during Cooling mode. During Dehumidification mode, it controls the Compressors to the Suction (Saturation) Temperature Setpoint.
• In Heating mode, the RSMD modulates and stages the compressors to maintain a given Supply Air Temperature Setpoint.
• Modulates the Condenser Fan or Valve to maintain the Head Pressure Setpoint.
• Provides alarms and safeties for the Compressor and Condenser operation.
• Allows connection of the Modular Service Tool SD to the module when required communication wire is run to the VCC-X/VCCX2 Controller.
• Provides a 2 x 8 LCD character display and 4 buttons that allow for status of system operation, system setpoints, system configurations, sensors, and alarms, and to change the module’s address, if necessary.
Mounting The RSMD Module is housed in a plastic enclosure. It is designed to be mounted by using the 3 mounting holes in the enclosure base. It is important to mount the module in a location that is free from extreme high or low temperatures, moisture, dust, and dirt. Be careful not to damage the electronic components when mounting the module.
10A250V
AC
~5A
30VD
C
SA
VD
E
G5Q
-1A4
OM
RO
N
DC
12V
CH
INA
Technical Data OE370-26-RSMD Refrigerant System Module for Digital Compressors
Operating Power 24 VAC Power Consumption 18 VA MaximumOperating Temp -30F to 150F Operating Humidity 90% RH Non-Condensing
Communications E-BUS Weight 8 oz.
Three Year Warranty WattMaster reserves the right to change specifications without notice
OE370-26-RSMDRefrigerant System Module
Form: AAON-OE377-26-00059-MHGRV-X-1A.doc
Description The OE377-26-00059 MHGRV-X Con-troller (AAON part number V12100) is designed to control a Modulating Hot Gas Reheat Valve to maintain a de-sired Supply Air Temperature during Dehumidification. The controller can be used as a stand-alone controller or it can be connected to and used in conjunction with the AAON Factory Packaged HVAC unit controller. The MHGRV-X controller is connected to the HVAC unit controller via a modular expansion cable and corresponding connectors on the controllers.
Features The MHGRV-X provides the following features.
Can Be Operated as a Stand-Alone Controller or Integrated with the HVAC Unit Controller
Provides for Supply Air Tem-
perature Setpoint Reset When Required
Second Stage Reheat Capabil-
ity When Using 2 Hot Gas Re-heat Valves
Control of Reheat Solenoid
Valve to Provide Coil Flushing for Positive Refrigerant Oil Return
Contains a 2 x 8 LCD character display and 4 buttons that allow for status display, setpoint changes, and
configuration changes.
Mounting It is important to mount the controller in a location that is free from extreme high or low temperatures, moisture, dust and dirt. The MHGRV-X Controller is housed in a plastic enclosure. It is designed to be mounted by using the 3 mounting holes in the enclosure base. It is important to mount the module in a location that is free from extreme high or low temperatures, moisture, dust, and dirt. Be careful not to damage the electronic components when mounting the module.
Technical Data OE377-26-00059 MHGRV-X ControllerOperating Power 24 VAC Power Consumption 12 VA MaximumOperating Temp -30F to 150F Operating Humidity 90% RH Non-Condensing
Communications E-BUS Weight 1 lb.Three Year Warranty WattMaster reserves the right to change specifications without notice
REHEAT EN
HEAT OVRD
COOL OVRD
STATUSALARMCOMMPOWER
SERIAL #
MADE IN USA
YS102466 REV 1WATTMASTER CONTROLS
FAN
COMP
VALVE
AUXRESET IN
AUX IN
SAT
GND
GND
CONDENSOR DRIVE
REHEAT DRIVE
OPENING
GREEN
WHITE
BLACK
GREEN
RED
SAT OPTIONSNORMALMODGASMODGASx
TB1
P1
C23
C1
D8
LC
P2
R2
TB2
TB3
TB4
10uF
18221002
R1
WHITE
BLACK
RED
OPENING
COMMON
J3
.01uF
5.00
0.20
5.63
5.87
5.44
2.72
2.050.67
4.10
1.49" DEPTH
OE377-26-00059 MHGRV-X Controller
Form: AAON-OE377-26-00058-MODGASX-1A.doc Page 1 of 1
Description The OE377-26-00058 MODGAS-X Controller (AAON Part No. V12090) is designed to modulate up to (2) gas valves to maintain a desired Discharge Air Temperature. It also controls the speed of the induced draft fan to maintain proper com-bustion in the heat exchanger. The controller can be used as a stand-alone unit or be connected to the AAON HVAC unit controller as an expansion board.
Features The MODGAS-X Controller pro-vides the following features.
Supply Air Temperature Sensor Input
HEAT EN Input (24VAC)
Discharge Air Temperature Reset Signal Input (0-10VDC)
Fan Enable (Relay Output) Auxiliary Output (Relay Output)
Low Speed Fan Control (Relay Output)
Gas Valve Analog Output (0-20 VDC)
Contains a 2 x 8 LCD character display and 4 buttons that allow for status display, setpoint changes, and configuration changes.
When used in a stand-alone application (not connected to an AAON HVAC unit controller board), the MODGAS-X Controller will modulate the gas valve to maintain the DISCHARGE setpoint set in the LCD display. The MODGAS-X Controller is activated by a 24VAC signal to the HEAT EN input. Mounting It is important to mount the controller in a location that is free from extreme high or low temperatures, moisture, dust and dirt. The MODGAS-X Controller is housed in a plastic enclosure. It is designed to be mounted by using the 3 mounting holes in the enclosure base. The Heat Sink must be fastened with sheet metal screws to a sheet metal surface. It is important to mount the module in a location that is free from extreme high or low tempera-tures, moisture, dust, and dirt. Be careful not to damage the electronic components when mounting the module.
COMMON
VALV
E
GND
VOUT
GAS
CONTROLS
MADE IN USA
YS102378 REV 1WATTMASTER
SE
RIA
L#
POWER
COMM
ALARM
STATUS
HEAT EN
RLY1
RLY2
RLY3
RLY4
AUX BIN
GND
RESET IN
SAT
AUX AIN
GND
GND
OPTIONS12
R42
R39
J3
U1
D1
C18
D12
D14
R5
R19
R22
R26
R30
TB5
TB1V1
R7
R2C2
TB2
TB4
U210D210
C211
C210
R210
R
RR
C212L210
R
.1uF
.01uF
1962
2803
1212
6042
1502
10201002
2211
.47uF
22uF
3.3uF
2211
2211
2211
5.73
2.62
2.05
4.100.57
0.20
5.00 5.63
5.24
1.68
1.20
0.2505
1.49" DEPTH
Technical Data OE377-26-00058 MODGAS-X ControllerOperating Power 24 VAC Power Consumption 18 VA MaximumOperating Temp -30F to 150F Operating Humidity 90% RH Non-Condensing
Communications E-BUS Weight 1 lb.Three Year Warranty WattMaster reserves the right to change specifications without notice
OE377-26-00058 MODGAS-X Controller
Form: ORION-OE217-02-03-EBUS-DRS-1B.doc Page 1 of 1
Description The OE217 series of Touch Screen E-BUS Digital Room Sensors are used to sense Space Temperature only or Space Temperature & Space Humidity. The OE217-02 model is the Space Temperature Sensor only model and can be used with the VCCX2 Controller, VCC-X Controller or VCB-X Controller and the VAV/Zone Controller. The OE217-03 is a combination Space Temperature & Space Humidity Sensor model and can only be used with the VCCX2, VCC-X or VCB-X Controller. Besides sensing Temperature & Humidity, the E-BUS Digital Room Sensors also provide these other useful features:
• User Friendly Graphical LCD Display with LED Backlight
• Display the Current Space and Outdoor Air Temperature
• Display the Current Space Humidity and Outdoor Air Relative Humidity (OE217-03 Model Only)
• Display the current Zone Setpoint Temperature
• Equipped With Push Buttons for Changing the Zone Setpoint Temperature
• Equipped With an Override Button for Forcing the VAV/Zone Controller or VCB-X Controller into Occupied Operation from Unoccupied Operation
• Provides graphics to indicate the mode of operation
• Provides LEDs to indicate Schedule Override, Button Push, and Alarms
Both sensors connect to the controllers using E-BUS cables of multiple lengths connected between the controller and the sensor. The E-BUS cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads.
Mounting The Digital Room Sensor is designed to be mounted to a vertical, 2” x 4” electrical box recessed in the wall. If the wall cannot be penetrated, a plastic surface mount box such as those made by WiremoldTM, may be used to mount the sensor to the wall surface. The Sensor is mounted by removing the front cover and fastening the housing base to the electrical box using the supplied (2) 6/32” x 1” machine screws. The E-BUS cable is then plugged into the E-BUS connector located on the circuit board that is mounted on the cover. The cover is then placed onto the housing base and the Allen Screw on the bottom of the base is adjusted to hold the cover in place. An additional cover plate is provided in case the sheet rock cut-out is too large to be covered by the regular back plate.
Technical Data OE217-02 & OE217-03 E-BUS Digital Room Sensor
Sensor Element Type III Thermistor 10k ohm@ 77 F Digital Sensing Device
Display 112 x 64 Monochrome Graphical LCD w/LED Backlight
Sensor Reading Range
40F to 120FRH = 0-100%
Connection E-BUS
Ambient Temperature Limits
-40F to 180F Weight 3.2 oz.
Accuracy RH +/-2%, Temp +/- .5F
Three Year Warranty WattMaster reserves the right to change specifications without notice
OE217-02 & OE217-03 E-BUS Digital Room Sensors
FILENAME
DATE: B. CREWS
DESCRIPTION:PAGE
DRAWN BY:
Duct Temperature Sensor1
JOB NAME
07/13/15
G-DUCSENS1.CDR
OE230 & OE231
Duct Temperature Sensors
OE230 (6" Probe) & OE231 (12" Probe)
Mounting Plate
Gasket
Adhesive Backed Drill GuideMounting Template
11-1/2" (OE231)
5-1/2" (OE230) Mounting Plate
4.0"
3/4"
1/4" Hex Head Sheet Metal Screws
ThreadTogether
Duct Work
Drill 3/8” Hole In Ductwork For Probe
Leads Are Non-polarized.Butt Splice Leads To 24 GaugeWire Minimum. Connect LeadsTo "Analog In" And "Ground"At Controller.
Notes:
1.)All Wiring To Be In Accordance WithLocal And National Electrical CodesAnd Specifications.
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
F Ohms @ Input*-10.............93333........4.620-5...............80531........4.5500...............69822........4.4745...............60552........4.390
10..............52500........4.29715..............45902........4.20020..............40147........4.09525..............35165........3.98230..............30805........3.86235..............27140........3.73740..............23874........3.605
�
Temp Resistance* Voltage
F Ohms @ Input*�
45..............21094........3.47050..............18655........3.33052..............17799........3.27554..............16956........3.21756..............16164........3.16058..............15385........3.10060..............14681........3.04262..............14014........2.98564..............13382........2.92766..............12758........2.86768..............12191........2.810
Temp Resistance* Voltage
F Ohms @ Input*�
69..............11906 ........2.78070..............11652 ........2.75271..............11379 ........2.72272..............11136 ........2.69573..............10878........2.66574..............10625........2.63575..............10398........2.60776..............10158........2.57078..............9711 ..........2.52080..............9302..........2.46582..............8893..........2.407
Temp Resistance* Voltage
F Ohms @ Input*84..............8514..........2.35286..............8153..........2.29788..............7805..........2.24290..............7472..........2.18795..............6716..........2.055100............6047..........1.927105............5453..........1.805110 ............4923..........1.687115 ............4449..........1.575120............4030..........1.469
�
125............3656..........1.369
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts.Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltageis above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
The Duct Sensor Is Used For Sensing SupplyOr Return Air Temperatures. Location Of TheSensors Is Very Important In Order To ObtainAccurate Temperature Readings. TheFollowing Recommendations Should BeFollowed:
When Used As A Supply Air Sensor TheSensor Should Be Mounted In The Supply AirDuct As Close To The HVAC Unit As PossibleAnd Upstream Of The Bypass Damper (IfUsed) For Best Results. For Best Accuracy,Apply Insulation On The Outside Of TheDuctwork Over The Sensor. This Will HelpThermal Gradients From Affecting The Sensor.
Supply Air
Return Air
When Used As A Return Air Sensor TheSensor Should Be Mounted In The Return AirDuct As Close To The HVAC Unit As PossibleAnd Upstream Of The Bypass Damper (IfUsed) For Best Results. For Best Accuracy,Apply Insulation On The Outside Of TheDuctwork Over The Sensor. This Will HelpThermal Gradients From Affecting The Sensor.
See The Systems Installation And OperationManual For Other Design Considerations AndRecommendations Regarding DuctTemperature Sensor Location.
Caution!
Technical Specifications
Sensor Element: Type III Thermistor 10k ohm @ 77ºF
Accuracy: � 0.4º F between 40º F to 95º F
Range: -30º F to 150º F
Form: Orion-OE265-15-EBUS-Horiz-OA-RH-Sensor-01B Page 1 of 1
Description The OE265-15 E-BUS Horizontal Outdoor Air Temperature and Humidity is a combination Outdoor Air Temperature and Outdoor Air Humidity sensor that connects to the VCC-X or VCB-X Controller using an EBC E-BUS modular cable. This sensor is used when both Outdoor Air Temperature and Humidity are needed for the VCC-X or VCB-X Controller to do Wetbulb or Dewpoint Economizer Control. It is also used if the VCC-X or VCB-X Controller is used in a Make Up Air application to initiate dehumidification based on an Outdoor Air Dewpoint Setpoint.
Mounting A 10 foot EBC E-BUS cable (provided) plugs into the E-BUS Outdoor Air Temperature and Humidity Sensor's attached 3 foot cable and then attaches to an E-BUS Expansion port on the VCC-X or VCB-X Controller or into another available E-BUS Expansion port. The sensor should be mounted in the upright position as shown in an area that is protected from the elements and direct sunlight. CAUTION: Be sure to mount the E-BUS Outdoor Air Temperature & Humidity Sensor in an area that is not exposed to direct sunlight. The shaded area under the HVAC unit rain hood is normally a good location. Unused conduit opening(s) must have closure plugs installed and must be coated with sealing compound to provide a rain-tight seal. Water can damage the sensor.
43213M
4.91
2.34
4.18
2.82
2.35 3.29
36.00 APPROX.
E-BUS CONNECTORFEMALE END
SENSING TUBE
FILTER
HINGED COVER
EBC-10F "WATTMASTER EBUS" "WATTMASTER EBUS" EBC-10F
43
21
3M
43
21
3M
120.00 APPROX.
E-BUS CONNECTOR EXTENSION CABLE WITH MALE ENDS PROVIDED WITH SENSOR
Technical Data OE265-15 E-BUS Horizontal Outdoor Air Temperature and Humidity Sensor
Sensor Element Digital Capacitive Sensing Device
Accuracy RH +/-2%, Temp +/- .5F
Sensor Reading Range
-40F to 185FRH = 0-100%
Connection E-BUS
Ambient Tempera-ture Limits
-40F to 185F Weight 2.3 oz.
Three Year Warranty WattMaster reserves the right to change specifications without notice
OE265-15 – E-BUS Horizontal Outdoor Air Temperature and Humidity Sensor
Form: ORION-OE258-6-BuildingPressureSensor-1B.doc Page 1 of 1
DescriptionThe OE258 Building Static Pressure Sen-sor is used to sense building pressure inapplications where monitoring of thebuilding static pressure is required to in-sure the building maintains the proper airpressurization.
The OE258 Building Pressure Sensorcase is molded from fire retardant glassfilled polyester. The sensor utilizes a ten-sioned stainless steel diaphragm and in-sulated stainless steel electrode. Thisarrangement allows up to 10 PSI over-pressure without damage to the unit. Thesensor provides a 0.0 to 5.0 VDC outputin response to a –0.25 to +0.25 inch WCpressure differential. Accuracy is ± 1% offull scale of the sensor.
For easy wiring the OE258 Building StaticPressure Sensor has (3) 6-32 screw ter-minal wiring connectors. The sensor has(2) ¼” barbed fittings provided for theconnection of tubing to the high and lowpressure ports.
The OE258 Static Pressure Sensor isdesigned to be mounted to a flat surfaceby means of the (2) 0.156 diameter holesprovided in the sensor casing. For accu-rate readings the sensor must bemounted in a vertical position.
Technical Data OE258 - Building StaticPressure Sensor
Operating PressureRange
-0.25” WC to +0.25” WCPressure Differential
Power InputSignal Output
9-30 VDC0 to 5 VDC
Operating Temp 0°F to 150°F Hysteresis ± 0.1% of full scaleCircuit 3 Wire Non-repeatability ± 0.05% of full scaleAccuracy ± 1% of full scale Weight 3 ounces
Three Year Warranty WattMaster reserves the right to change specifications without notice
HIGH
MODEL 265
LOW
- + +
+
1.89
0.95
3.162.74 setra
0.95
1.64
0.156 DIA. HOLETYP. 2 PL.
����������� ������������ ���
Form: AAON-OE256-07-EBUS-DUCT-CO2-1B.doc Page 1 of 1
Description The E-BUS Duct Mounted E-BUS CO2 Sensor with Remote Pickup (Orion Part No. OE256-07; AAON Part No. V09320) is used in conjunction with the VCB-X Controller (Orion Part No. OE335-23-VCB-X; AAON Part No. V04740) to monitor and control Return Air CO2 levels in the building environment. Some typical applications are:
Demand Control Ventilation
Controlling ventilation in a building where the occupancy varies frequently
Controlling ventilation based on CO2 levels to ensure excess outdoor air is not causing energy waste
To ensure good air distribution throughout building zones
The OE256-07 is used for monitoring duct CO2 levels and is designed for permanent mounting in the Return Air duct. It utilizes an aspiration box to accurately capture CO2 levels in the duct. It con-nects to the VCB-X by using an E-BUS cable with E-BUS connectors.
The OE256-07 CO2 Sensor uses non-dispersive infrared (NDIR) technology and has a measure-ment range of 0-2000 ppm.
Mounting The OE256-07 CO2 Sensor is housed in an aspira-tion box. A conduit clamp is provided to help seal the opening where the sensor cabling penetrates the aspiration box housing. The sensor has a Jack E-BUS connector for connecting it to the provided EBC E-BUS cable. The EBC E-BUS Cable con-nects to the VCB-X Controller or E-BUS Hub or Adapter Board and then to the VCB-X Controller. The sensor and aspiration box assembly is mounted and secured to the ductwork with the (2) supplied sheet metal screws. The remote pickup tube assembly is mounted separately to the duct-work by first cutting a 11/4” diameter hole in the ductwork wall. The remote pickup tube is then in-serted into the hole. The remote pickup tube is then secured to the ductwork by inserting (2) supplied sheet metal screws through the (2) mounting holes in the remote pickup tube mounting plate and securing the remote pickup tube assembly by screwing it to the ductwork using a manual or powered screw driver to tighten the screws. Using the supplied 10 ft. long tub-ing, connect the remote pickup tube to the aspiration box assembly, cutting the tubing to fit.
43213M
E-BUS CONNECTORFEMALE END
SENSOR HOUSING
HINGED COVER
BRASS BARBFITTINGS FOR0.170 I.D. TUBING
BRASS BARBFITTINGS FOR0.170 I.D. TUBING
EBC-10F "WATTMASTER EBUS" "WATTMASTER EBUS" EBC-10F
43
21
3M
43
21
3M
120.00” APPROX.
120.00” APPROX.
E-BUS CONNECTOR EXTENSION CABLE WITH MALE ENDS (PROVIDED WITH SENSOR)
0.170 I.D. TUBING (PROVIDED WITH SENSOR)FIRE RATED
CO2 PICKUP TUBE (PROVIDED WITH SENSOR)
CO2 SENSOR, HOUSING AND CABLE ASSEMBLY
5.00
"
3.31"
4.12"
2.55”
13.0
0"A
PP
RO
X.
8.25"0.55”
4.06
"
2.81”
Technical Data OE256-07 E-BUS Duct Mounted CO2 Sensor with Remote Pickup
Input Power 12-34 VDC Power Consumption 30 mW Maximum Average1.25 W Peak Power
Operating Temperature 14 to 122F Operating Humidity 5-95% RH Non-CondensingSample Method Flow-Through
50-100 ml/minMeasurement Range 0 to 2000 ppm
Sensitivity <20 ppm Resolution 1 ppmAccuracy 50 ppm @ 1000 ppm or
2% measured valueCommunications E-BUS
One Year Warranty WattMaster reserves the right to change specifications without notice
OE256-07 E-BUS Duct Mounted CO2 Sensor with Remote Pickup
Form: ORION-OE391-12-ModularServiceToolSD-1C.doc Page 1 of 1
Description The OE391-12 Modular Service Tool SD is a system interface that provides a direct link to enable the system operator to view the status, configure, and adjust the setpoints of the following Orion controllers:
VCC-X Controller VCM-X Series Controller VCM-X E-BUS Series Controller VCB-X Controller RNE Controller SA E-BUS Controller VCM Controller VAV/CAV Controller MUA II Controller VAV/Zone Controller MiniLink PD
The OE391-12 Modular Service Tool SD is housed in a black plastic enclosure. The display area is covered with a clear plastic bezel for protection of the display screen. The Modular Service Tool SD has a four line by 20 character display panel with adjustable contrast control and a 27 key membrane keypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu-driven programming allows for easy setup and operation without the need for specialized training. The OE391-12 Modular Service Tool SD is supplied with a programmable 4 Gigabyte SD memory card, with (4) AA 1.5 V batteries, a wall mount a DC power supply, a mini-Din communication cable, and an E-BUS communication cable. The mini-Din cable allows you to connect the Modular Service Tool to any Orion controller which has a mini-Din connector socket for programming, monitoring, and troubleshooting purposes. The Modular Service Tool is also equipped with an EBC E-BUS port and an RS-485 three conductor terminal block port. The E-BUS port and included E-BUS cable are used for updating E-BUS Module software. The RS-485 port is used for hard-wiring to older controllers that do not have a mini-DIN connector socket. The Modular Service Tool SD is designed to be carried by the system installer or service technician. Its rugged plastic housing provides superior protection for the electronic components housed inside. The Modular Service Tool SD is a top quality service tool that will stand up to the demands of the typical job site for many years.
Technical Data OE391-12 Modular Service Tool SDPower (4) AA (1.5V) Batteries
Supplied Display 4 Line by 20 Character
Power Switch Membrane Switch Network Connection RS-485Operating Temp 10F to 149F Protocol HSI Open Protocol Token PassingOperating Humidity
90% RH Non-Condensing Color Black
Keypad 27 Key Membrane Style Communications RS-485 9600 or 57,600 BaudSD Memory Card Programmable 4 Gigabyte Connections RS-485 and EBC E-BUS Ports3 Year Warranty WattMaster reserves the right to change specifications without notice
OE391-12 Modular Service Tool SD