INFRARED INSPECTION SURVEY REPORT
SAMPLE CUSTOMER
MCC SURVEY
DATA COLLECTED: 4/9/2018
REPORT DATE
EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY
PAGE #
03/29/18 107L126 APCU Heater Power Panel
Line #2 connection on this power panel has an elevated thermal pattern that indicates a loose connection in early stages.
During scheduled outage, inspect and tighten connections. MODERATE 3
03/29/18 Bottom FuseMain Cooling Tower Cell 3
Fan
The bottom fuse has a comparatively elevated thermal pattern. This could be due to a worn or incorrect fuse, or may be load related.
Verify correct fuse and verify load is balanced. MODERATE 4
03/29/18Steam Turbine
Generator Enclosure
Steam Turbine This unit has a loose connection During scheduled outage, inspect and tighten connections. MODERATE 5
03/29/18 Enclosure Vent Fan 1 CTG2 This connection has a comparatively elevated thermal
pattern that indicates a loose connection. During scheduled outage, inspect and tighten connections. MINOR 6
03/29/18 EN1700 Industrial Control Panel
Connection #21 has a comparatively elevated thermal pattern that indicates a loose connection.
During scheduled outage, inspect and tighten connections. MINOR 7
1- CRITICAL
2- DEFECTS ARE IN MODERATE STAGES
3 - DEFECTS MAY BE PRESENT
4 - LEVELS ARE ABOVE NORMAL
5 - NORMAL
2 of 7
68 °F137 °F95.7 °F41.3 °F69 °F0.95
INSPECTED / REPAIRED BY: DATE:
DEFECT RISE ABOVE AMBIENTEMISSIVITY
AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP
RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.
Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MODERATE
OBSERVATIONS: Line #2 connection on this power panel has an elevated thermal pattern that indicates a loose connection in early stages. Temperatures are elevated but not excessive at this time.
Facility location: Equipment Name: 107L126Data Collected: Image Filename: IR000010
INFRARED EXCEPTION ANALYSIS REPORT
Company: Location Description: APCU Heater Power Panel
www.conditionmonitoringservices.com
3 of 7
68 °F162.2 °F97.4 °F64.8 °F94.2 °F0.95
INSPECTED / REPAIRED BY: DATE:
DEFECT RISE ABOVE AMBIENTEMISSIVITY
AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP
RECOMMENDATIONS: Verify correct fuse and verify load is balanced.
Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MODERATE
OBSERVATIONS: The bottom fuse has a comparatively elevated thermal pattern. This could be due to a worn or incorrect fuse, or may be load related.
Facility location: Equipment Name: FusesData Collected: Image Filename: IR000060
INFRARED EXCEPTION ANALYSIS REPORT
Company: Location Description: Main Cooling Tower Cell 3 Fan
www.conditionmonitoringservices.com
4 of 7
68 °F113.2 °F73.8 °F39.4 °F45.2 °F0.95
INSPECTED / REPAIRED BY: DATE:
DEFECT RISE ABOVE AMBIENTEMISSIVITY
AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP
RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.
Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MODERATE
OBSERVATIONS: This unit has a loose connection at the location marked below.
Facility location: Equipment Name: Steam Turbine Data Collected: Image Filename: IR000061
INFRARED EXCEPTION ANALYSIS REPORT
Company: Location Description: Steam Turbine Generator Enc.
www.conditionmonitoringservices.com
5 of 7
68 °F106.7 °F84.6 °F22.1 °F38.7 °F0.95
INSPECTED / REPAIRED BY: DATE:
DEFECT RISE ABOVE AMBIENTEMISSIVITY
AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP
RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.
Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MINOR
OBSERVATIONS: This connection has a comparatively elevated thermal pattern that indicates a loose connection. Temperatures are elevated but not excessive at this time.
Facility location: Equipment Name: Enclosure Vent Fan 1Data Collected: Image Filename: IR000059
INFRARED EXCEPTION ANALYSIS REPORT
Company: Location Description: CTG2
www.conditionmonitoringservices.com
6 of 7
68 °F97 °F87.7 °F9.3 °F29 °F0.95
INSPECTED / REPAIRED BY: DATE:
DEFECT RISE ABOVE AMBIENTEMISSIVITY
AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP
RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.
Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MINOR
OBSERVATIONS: Connection #21 has a comparatively elevated thermal pattern that indicates a loose connection. Temperatures are comparatively elevated but minor at this time.
Facility location: Equipment Name: EN1700Data Collected: Image Filename: IR000062
INFRARED EXCEPTION ANALYSIS REPORT
Company: Location Description: Industrial Control Panel
www.conditionmonitoringservices.com
7 of 7