FLOOR CEILING ASSEMBLY
OPEN WEB WOOD TRUSS
RC Channel on RC-1 Boost Isolator
CONSTRUCTION· Ceramic Tile
· Ecore QT4002 2mm Rubber underlayment floated
· 3/4" Light Weight Gypsum Concrete Topping
· 3/4” Plywood
· 18" Open Webb Truss @ 24" oc.
· R-13 Fiberglass Insulation
· RC-1 Boost @ 16" x 24" oc.
· Dietrich RC-1 Pro @ 16" oc.
· 1 Layers 5/8" Fire code “C” Gypsum Board
STC 62
IIC 54
©2020 PAC International, LLC. All Rights Reserved. • (866) 774-2100 RSIC® is a registered Trade Mark
IIC
Test #: ATI-L2271.29
World Leader in
Noise Control
Solutions
Dietrich RC-1 Pro on RC-1 BoostAssembly#: OWTRC1BOOST
UL File Number:
R16638
RC-1 BOOST
PACINTERNATIONAL, LLC
RTTDS-R-AMER-Test-2844© 2017 INTERTEK
TEST DATE07/24/20
ISSUE DATE10/26/20
RECORD RETENTION END 07/24/24
14
REPORT NUMBERL2271.29-113-11-R0
ACOUSTICAL
SCOPE OF WORK
ASTM E90 AND ASTM E492 TESTING ON CERAMIC TILE OVER ECORE QT4002
PERFORMANCE
SPECIMEN TYPE
457 mm Open Web Truss with PAC Boost Resilient Channel Isolators
PAGES
ATI 00629 (03/21/18)DOCUMENT CONTROL
TEST REPORT
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
SECTION 1SCOPE
REPORT ISSUED TOPAC INTERNATIONAL2000 4th Avenue, Suite ACanby, Oregon 97013
STCIICHIIC 55
54
Intertek Building & Construction (B&C) was contracted to perform testing in accordance with
ASTM E90 AND ASTM E492 on Ceramic Tile over ECORE QT4002. This report is a reissue in the
name of PAC International through written authorization from the original report holder.
Results obtained are tested values and were secured by using the designated test method(s).
Testing was conducted in the VT test chambers at Intertek B&C located in York, Pennsylvania.
SECTION 2SUMMARY OF TEST RESULTS
DATA FILE NO. L2271.15
62
This report does not constitute certification of this product nor an opinion or endorsement by
this laboratory.
SERIES/MODEL: Ceramic Tile over ECORE QT4002
Daniel B. MohlerProject Lead - Acoustical
Testing
COMPLETED BY:
TITLE:
SIGNATURE:10/26/20
COMPLETED BY:
TITLE:
SIGNATURE:DATE:DATE:
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek
and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek
assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or
damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this
report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of
the tested material, product or service must first be approved in writing by Intertek. The observations and test
results in this report are relevant only to the sample(s) tested. This report by itself does not imply that the material,
product, or service is or has ever been under an Intertek certification program.
10/26/20
Morgan S. J. KennedyTechnician - Acoustical
Testing
Version: 03/21/18This page alone is not a complete report.
Page 2 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
The full test specimen was assembled on the day of testing by B&C. All materials provided by
the original client were installed on an existing B&C assembly (457 mm Open Web Truss with
PAC Boost Resilient Channel Isolators) utilizing B&C-supplied materials. The assembly was
installed in a steel test frame which was installed into the opening between the source and
receive rooms in the test chamber. The test frame was isolated from the structure with dense
neoprene gasket.
SECTION 3
The specimen was evaluated in accordance with the following:
This report is reissued in the name of PAC International through written authorization from the
original report holder. The original Report No. is L2271.15-113-11.
B&C will service this report for the entire test record retention period. Test records, such as
detailed drawings, datasheets, representative samples of test specimens, or other pertinent
project documentation, will be retained by B&C for the entire test record retention period.
TEST METHODS
The total weight of the floor/ceiling assembly was 985.6 kg. B&C will store samples of the test
specimen for four years. Photographs of the test specimen are included in the report. The
client did not supply drawings of the test specimen.
MATERIAL SOURCE/INSTALLATION
Impact Sound Transmission Through Floor-Ceiling Assemblies Using the Tapping
ASTM E413-16, Classification for Rating Sound Insulation
SECTION 4
ASTM E492-09(2016)e1, Standard Test Method for Laboratory Measurement of
ASTM E90-09 (2016), Standard Test Method for Laboratory Measurement ofAirborne Sound Transmission Loss of Building Partitions
ASTM E989-18, Classification for Determination of Impact Insulation Class (IIC)
ASTM E2235-04 (2020), Standard Test Method for Determination of Decay Rates forUse in Sound Insulation Test Methods
Machine
ASTM E3222-20, Standard Classification for Determination of High-Frequency ImpactSound Ratings
Version: 03/21/18This page alone is not a complete report.
Page 3 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
*
*
*
Intertek B&CDaniel B. Mohler
MANUFACTURER MODEL DESCRIPTION
VT RECEIVE ROOM VOLUME
VT SOURCE ROOM VOLUME
155.77 m³
* The calibration frequency for this equipment is every two years per the manufacturer's recommendation.
INSTRUMENT
SECTION 5EQUIPMENT
190 m³
COMPANYIntertek B&C
NAMEMorgan S. J. Kennedy
LIST OF OFFICIAL OBSERVERSSECTION 6
ASSET # CAL DATE
Data Acquisition Unit National Instruments PXI-4462 Data Acquisition Card 65124 12/18
Data Acquisition Unit National Instruments PXI-4462 Data Acquisition Card 63763-4 09/18
Data Acquisition Unit National Instruments PXI-4462 Data Acquisition Card 63763-1 06/19
Microphone Calibrator Larson Davis CAL250 Acoustical Calibrator 65327 11/19
Receive Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier 65029 03/20
Receive Room Microphone PCB Piezotronics 378B20 Microphone and Preamplifier 63742 03/20
Receive Room Microphone PCB Piezotronics 378B20 Microphone and Preamplifier 63747 08/19
Receive Room Microphone PCB Piezotronics 378B20 Microphone and Preamplifier 63740 04/20
10/19
10/19
Receive Room Microphone PCB Piezotronics 378B20 Microphone and Preamplifier 63739 04/20
Receive Room Environmental
IndicatorComet T7510
Temperature and Humidity
Transmitter
63810
63811
Source Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier 65586 01/20
Source Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier 65969 04/20
Source Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier 64340 10/19
Source Room Microphone PCB Piezotronics 378C20 Microphone and Preamplifier 63746 10/19
Temperature and Humidity
Transmitter63812 10/19
Source Room Microphone PCB Electronics 378C20 Microphone and Preamplifier INT00652 01/20
Tapping Machine Norsonic Nor277 Tapping Machine INT00936 01/20
Source Room Environmental
IndicatorComet T7510
Version: 03/21/18This page alone is not a complete report.
Page 4 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
The microphones were calibrated before conducting the tests. The air temperature and
relative humidity conditions were monitored and recorded during all measurements. The
average temperature and humidity of both the source and received rooms are listed in
Sections 10 and 11. The maximum and minimum temperatures and humidities of the receive
room from the duration of the test are listed in Sections 12 and 13.
The airborne transmission loss test was conducted in accordance with the ASTM E90 test
method using the single direction method. Two background noise sound pressure level and
five sound absorption measurements were conducted at each of five microphone positions.
Two sound pressure level measurements were made simultaneously in both rooms, at each of
five microphone positions.
The impact sound transmission test was conducted in accordance with the ASTM E492 test
method. Two background noise sound pressure level, two sound pressure level measurements
with the tapping machine operating at each position specified by ASTM E492, and five sound
absorption measurements were conducted at each of five microphone positions.
SECTION 8TEST CALCULATIONS
The STC (Sound Transmission Class), IIC (Impact Insulation Class), and HIIC (High-Frequency
Impact Insulation Class) ratings were calculated in accordance with ASTM E413, ASTM E989,
and ASTM E3222, respectively.
Detailed test procedures, data for flanking limit tests, repeatability measurements, and
reference specimen tests are available upon request.
TEST PROCEDURESECTION 7
Version: 03/21/18This page alone is not a complete report.
Page 5 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
Gypsum Panel
1219 by 3023USG SHEETROCK® Brand
FIRECODE® C Core10.98 m² 11.91 kg/m²
Note: Installed on 610 mm centers using JUS414 hanger brackets.
Note: Installed on 406 mm centers perpendicular to the trusses with PAC International RC-1 Boost
Isolators. The measured thickness of the metal was 0.7 mm.
Note: Fastened to the channels on 305 mm centers with 25.4 mm Type S bugle head screws. The
seams of the gypsum panels were sealed with Pecora AC-20 FTR caulk and covered with pressure
sensitive tape.
12.3 ClarkDietrich RC-1 Pro™ 29.01 lin m 0.51 kg/m
Fiberglass
Insulation
520.7 by 3023 88.9 10.98 m² 1.32 kg/m²
SECTION 9
1219 by 2438 18.8 N/A
Note: Installed in the cavity between trusses, tied flush with the subfloor
Johns Manville Faced R-13
11.67 kg/m²
TEST SPECIMEN DESCRIPTION
York PB Truss L/360
Note: Adhered to the floor trusses with Loctite PL 400 Subfloor adhesive. Fastened with 9D nails
on 203 mm centers along perimeter and 305 mm centers along trusses.
10.98 m²
7 trusses 19.05 kg/truss88.9 by 2933.7 457.2
Floor
Underlayment
3022.6 by 3632.2 19.1 USG Levelrock® Brand 2500 10.98 m² 33.15 kg/m²
Note: Poured directly onto the subfloor underlayment, cured a minimum of 14 days. The gypsum
panel had a closed cell foam perimeter isolation. No noticeable shrinkage or cracking was visible
on the specimen.
2.0 ECORE QT4002 10.98 m²
Note: A sheet of 2 mil polyethylene plastic was adhered to the floor slab with Sprayway Fast Tack
85 spray adhesive. The underlayment was adhered to the sheeting with E-GRIP III adhesive, which
was spread using a 0.79 mm by 1.59 mm by 1.98 mm U-notch trowel. Adhesive was allowed to
cure per manufacturer's specifications.
1.86 kg/m²
Resilient Channel
with PAC RC-1
Boost
15.9
Oriented Strand
Board Sheathing
Open Web Truss
Traffic Master8.0298.4 by 298.4
Rubber
Underlayment
1219.2 by 3632
Note: An ANSI A118.7 cementitious grout was placed into the 6.35 mm (0.25") joints between the
ceramic tile and wiped clean. The ceramic tile was placed onto a bed of ANSI A118.4 latex
modified thin-set mortar. The mortar was set using a 6.35 mm by 6.35 mm (0.25" by 0.25")
trowel. Both the grout and mortar were allowed to cure to manufacturer's specifications.
50.8 by 3390.9
DIMENSIONS
(mm)
THICKNESS
(mm)
MANUFACTURER AND
SERIESQUANTITY
AVERAGE
WEIGHT
16.45 kg/m²10.98 m²
Ceramic Tile
MATERIAL
Version: 03/21/18This page alone is not a complete report.
Page 6 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
10.3
11.2
10.7
25
98
98
11.5
12.6
9.6
93
39
0.6
0.6
0.3
0.4
0.4
0.3
103
101
103
103
2.1
2.7
2.1
1.8
0.8
60 3
-
0
1.3
0.6
0.4
0.7
36
34
0.9
0.4
0.4
Notes:
78
81
30
28
102
10000 19.6
6.5
6.8
103
103
8.7
38
75
13
7
16
10.8
1.0
0.67.1
103
14.1
15.1
6.3
17.2
27.3
9.1
27.2
25.7
17.7
9.5
8.8
16.5
500
2000
6300
8.8
STC Rating
1000
1250
1600
630
800
8000
62
12.7
11.3
103
101
20.4
100
125
160
95200
315
400
4000
5000
7.6
2500
3150
6.7
250
17.3
16.4
17.8
100
42
44
97
94
97
103
103
104
49
72
0
68
19.6
14.0
16.0
84
84 -
0.6
0
0
0
55
3
54
58
60
69
3
CONFIDENCE
80
BACKGROUND
-
-
45
44
65
67
1
3
61
62
SPL
(dB)
Receive Temp.
(dB)
96
DATA FILE NO.
CLIENT
SPECIMENRECEIVE
78%Receive Humidity Source Humidity
95%
Source Temp.
TEST DATE
9.4
TL
(dB)
DESCRIPTION
(Hz)
MSJK
SPL
10.98 m²
SOURCE
m² LIMIT(dB)
6232.3 15.5
44 1.1
OF
DEFICIENCIES
2
35
44
36
SPL
-
-
48
2
3
9.7
5
FREQ
Sum of Deficiencies(Sound Transmission Class)
NUMBER
1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
2) Specimen TL levels listed in red are potentially limited by the laboratory flanking limit.
3) Specimen TL levels listed in blue indicate the lower limit of the transmission loss.
4) Specimen TL levels listed in green indicate that there has been a filler wall correction applied
31
L2271.15
PAC International
8.4
60
55
SECTION 10TEST RESULTS - AIRBORNE SOUND TRANSMISSION LOSS
7/24/2020
8 mm Traffic Master Ceramic Tile, 2 mm ECORE QT4002 Rubber Underlayment, 19.1 mm USG
Levelrock® Brand 2500 Floor Underlayment, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm
Johns Manville Faced R-13 Fiberglass Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 12.3
mm ClarkDietrich RC-1 Pro™ Resilient Channel with PAC RC-1 Boost, 15.9 mm USG SHEETROCK®
Brand FIRECODE® C Core Gypsum Panel
SPECIMEN AREA 26.1°C
TECHNICIAN
25.1°C
8.5
ABSORPTION
8.7
8.6
78%
49
50
47
2
4
53
Version: 03/21/18This page alone is not a complete report.
Page 7 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
Source Humidity 78%78%
26.1°C
DATA FILE NO.
SECTION 11
Receive Humidity
10.98 m²SPECIMEN AREA
PAC International
DESCRIPTION
Source Temp.Receive Temp. 25.1°C
TECHNICIAN MSJK
L2271.15
CLIENT
TEST RESULTS - AIRBORNE SOUND TRANSMISSION LOSS GRAPH
TEST DATE 7/24/2020
8 mm Traffic Master Ceramic Tile, 2 mm ECORE QT4002 Rubber Underlayment, 19.1 mm USG
Levelrock® Brand 2500 Floor Underlayment, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm
Johns Manville Faced R-13 Fiberglass Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 12.3
mm ClarkDietrich RC-1 Pro™ Resilient Channel with PAC RC-1 Boost, 15.9 mm USG SHEETROCK®
Brand FIRECODE® C Core Gypsum Panel
0
10
20
30
40
50
60
70
80
90
100
63
125
250
500
1000
2000
4000
8000
Sou
nd
Tra
nsm
issi
on
Lo
ss (
dB
re
: 2
0
Pa
)
Frequency (Hz)
Airborne Sound Transmission Loss
Specimen TL
Contour Curve
Version: 03/21/18This page alone is not a complete report.
Page 8 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
TEST DATE
5000 7.3
25.2°CSPECIMEN AREA
250 20.5
9.7
1250
FREQBACKGROUND
(Hz)
Max. Humidity
(dB)
DATA FILE NO. L2271.15
CLIENT PAC International
DESCRIPTION
TECHNICIAN
NORMALIZED IMPACT SPL
(dB)
SPL
26.8
IIC Rating 54
8 mm Traffic Master Ceramic Tile, 2 mm ECORE QT4002 Rubber Underlayment, 19.1 mm USG
Levelrock® Brand 2500 Floor Underlayment, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm
Johns Manville Faced R-13 Fiberglass Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 12.3
mm ClarkDietrich RC-1 Pro™ Resilient Channel with PAC RC-1 Boost, 15.9 mm USG SHEETROCK®
Brand FIRECODE® C Core Gypsum Panel
SECTION 12TEST RESULTS - IMPACT SOUND TRANSMISSION
500 18.2
400 16.0
7/24/2020
MSJK
9.5
10.98 m² Maximum Temp.
15.9
77%
ABSORPTIONNUMBER
80 32.1
200 22.4
125
160 25.8
100 27.8
1600 19.3
18.9
18.5
1000 18.3
315
800 18.0
4000 8.7
630 20.2
3150 11.2
2500 12.2
2000 16.4
0.3
8000 6.9
6300 7.0 15.9
19.6
OF
m² DEFICIENCIES
79% Min. Humidity
Minimum Temp. 25.1°C
0
9.4 3
-
9.3 6
62
64
57
61
3
10.7 20.5
6
11.2
64
61
60
10.5
258 0.2
9.8 20.359
8.9
8.7 256 0.3
8.6 358 0.3
0
8.9 0
8.5 052 0.4
8.6 49
45
12.5 -
11.6 0
1
10.8 1
45
42
34
-12 0.3
13.9 -20 0.2
-9 0.2
Notes: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
19.610000 7.2
31
8
95%
CONFIDENCE
LIMIT
-
(Impact Insulation Class) Sum of Deficiencies
0.6
0.7
0.8
0.2
0.3
0.2
0.1
0.2
0.228
1.2
1.1
1.1
Version: 03/21/18This page alone is not a complete report.
Page 9 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
L2271.15
SPECIMEN AREA 25.1°C
SECTION 13TEST RESULTS - IMPACT SOUND TRANSMISSION GRAPH
TEST DATE 7/24/2020
DATA FILE NO.
CLIENT PAC International
DESCRIPTION
TECHNICIAN MSJK Max. Humidity Min. Humidity 77%
8 mm Traffic Master Ceramic Tile, 2 mm ECORE QT4002 Rubber Underlayment, 19.1 mm USG
Levelrock® Brand 2500 Floor Underlayment, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm
Johns Manville Faced R-13 Fiberglass Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 12.3
mm ClarkDietrich RC-1 Pro™ Resilient Channel with PAC RC-1 Boost, 15.9 mm USG SHEETROCK®
Brand FIRECODE® C Core Gypsum Panel
10.98 m² Maximum Temp. 25.2°C Minimum Temp.
79%
10
20
30
40
50
60
70
80
90
100
1100
10
20
30
40
50
60
70
80
90
100
63
125
250
500
1000
2000
4000
8000
Imp
act
Insu
lati
on
Cla
ss (
IIC
)
Sou
nd
Pre
ssu
re L
eve
l (d
B r
e: 2
0 P
a)
Frequency (Hz)
Impact Sound Transmission
Normalized Impact SPL
Contour Curve
Version: 03/21/18This page alone is not a complete report.
Page 10 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
SECTION 14TEST RESULTS - HIGH-FREQUENCY IMPACT SOUND TRANSMISSION
TEST DATE 7/24/2020
DATA FILE NO. L2271.15
CLIENT PAC International
DESCRIPTION 8 mm Traffic Master Ceramic Tile, 2 mm ECORE QT4002 Rubber Underlayment, 19.1 mm USG
Levelrock® Brand 2500 Floor Underlayment, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm
Johns Manville Faced R-13 Fiberglass Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 12.3
mm ClarkDietrich RC-1 Pro™ Resilient Channel with PAC RC-1 Boost, 15.9 mm USG SHEETROCK®
Brand FIRECODE® C Core Gypsum Panel
SPECIMEN AREA 10.98 m² Maximum Temp. 25.2°C Minimum Temp. 25.1°C
TECHNICIAN MSJK Max. Humidity 79% Min. Humidity 77%
FREQBACKGROUND
ABSORPTION NORMALIZED IMPACT SPL95% NUMBER
SPL CONFIDENCE OF
(Hz) (dB) m² (dB) LIMIT DEFICIENCIES
400 16.0 9.8 59 0.3 3
500 18.2 8.9 58 0.2 3
630 20.2 8.6 58 0.3 4
800 18.0 8.7 56 0.3 3
1000 18.3 8.5 52 0.4 0
1250 18.5 8.6 49 0.2 0
1600 19.3 8.9 45 0.3 0
10.8 42 0.1 2
2000 16.4 9.7 45 0.2 2
3150 11.2 11.6 34 0.2 0
2500 12.2
HIIC Rating 55 18
Notes: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
(High-Frequency Impact Insulation Class) Sum of Deficiencies
Version: 03/21/18This page alone is not a complete report.
Page 11 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
SECTION 15TEST RESULTS -HIGH-FREQUENCY IMPACT SOUND TRANSMISSION GRAPH
TEST DATE 7/24/2020
DATA FILE NO. L2271.15
DESCRIPTION 8 mm Traffic Master Ceramic Tile, 2 mm ECORE QT4002 Rubber Underlayment, 19.1 mm USG
Levelrock® Brand 2500 Floor Underlayment, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm
Johns Manville Faced R-13 Fiberglass Insulation, 457.2 mm York PB Truss L/360 Open Web Truss, 12.3
mm ClarkDietrich RC-1 Pro™ Resilient Channel with PAC RC-1 Boost, 15.9 mm USG SHEETROCK®
Brand FIRECODE® C Core Gypsum Panel
SPECIMEN AREA 10.98 m² Maximum Temp. 25.2°C Minimum Temp. 25.1°C
TECHNICIAN MSJK Max. Humidity 79% Min. Humidity 77%
CLIENT PAC International
10
20
30
40
50
60
70
80
90
100
1100
10
20
30
40
50
60
70
80
90
100
500
1000
2000
4000
8000
Imp
act
Insu
lati
on
Cla
ss (
IIC
)
Sou
nd
Pre
ssu
re L
eve
l (d
B r
e: 2
0 P
a)
Frequency (Hz)
Impact Sound Transmission
Normalized Impact SPL
Contour Curve
Version: 03/21/18This page alone is not a complete report.
Page 12 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
Photo No. 2
Construction of Test Specimen
SECTION 16
Photo No. 1
Source Room View of Test Specimen Installation
PHOTOGRAPHS
Version: 03/21/18This page alone is not a complete report.
Page 13 of 14 RTTDS-R-AMER-Test-2844
130 Derry Court
Facsimile:
TEST REPORT FOR PAC INTERNATIONALReport No.: L2271.29-113-11-R0
717-764-7700
www.intertek.com/building
Date: 10/26/20
York, PA 17406
Telephone: 717-764-4129
10/26/20
PAGES
N/A
DESCRIPTIONDATEOriginal Report Issue - Reissue of Report No.
L2271.15-113-11 in the name of PAC
International.
SECTION 17REVISION LOG
REVISION #
R0
Version: 03/21/18This page alone is not a complete report.